Installation Instructions
Catalog Number 2094-SEPM-FUSE
The Kinetix® 6000M Integrated Drive-Motor (IDM) system has a pair of internal fuses for short-circuit protection of the DC bus in the IDM Power Interface Module (IPIM).
The fuse replacement kit contains six Bussmann FWP-50A14Fa fuses.
IMPORTANT |
Replace both fuses in the fuse holder at the same time. The power surge that opens one fuse |
|
may have stressed and weakened the second fuse. |
|
|
IPIM Fuse Location
Reverse View of
Fuse Holder
Phillips Screw (2x) |
Mounting Screw |
0.5…0.7 N•m |
2.26 N•m |
4…6 lb•in |
20 lb•in |
Follow these steps to replace the fuse pair in an IPIM module.
ATTENTION: Capacitors on the DC bus retain hazardous voltages after input power has been removed. Before working on the IDM system, measure the DC bus voltage to verify it has reached a safe level or wait the full time interval as indicated in the warning on the front panel of the IPIM module.
Failure to observe this precaution could result in severe bodily injury or loss of life.
1.Remove all control and input power supplied to the Kinetix 6000M system.
2.Wait the full time interval specified in the warning on the front panel of the IPIM module before proceeding with the next step.