User Manual
Catalog Number 20-COMM-ER
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Important: Identifies information that is critical for successful application and understanding of the product.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
Burn Hazard labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be at dangerous temperatures.
Allen-Bradley, Rockwell Software, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
2 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013 |
|
Table of Contents |
|
Preface |
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
7 |
|
Conventions Used in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
7 |
|
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
8 |
|
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
8 |
|
Chapter 1 |
|
Getting Started |
Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
11 |
|
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
12 |
|
Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
|
Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
|
Equipment Shipped with the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
|
User-Supplied Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
13 |
|
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
15 |
|
Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
16 |
|
Chapter 2 |
|
Installing the Adapter |
EMC Conformance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
17 |
|
Preparing for an Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
18 |
|
Setting the Web Pages Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
19 |
|
Connecting the Adapter to the Drive or SMC . . . . . . . . . . . . . . . . . . . . . . |
20 |
|
Connecting the Adapter to the Network . . . . . . . . . . . . . . . . . . . . . . . . . . . |
23 |
|
Applying Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
24 |
|
Start-Up Status Indications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
24 |
|
Configuring and Verifying Key Drive Parameters. . . . . . . . . . . . . . . . |
26 |
|
Commissioning the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
26 |
|
Chapter 3 |
|
Configuring the Adapter |
Configuration Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
27 |
|
Using the PowerFlex 7-Class HIM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
28 |
|
Using an LED HIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
28 |
|
Using an LCD HIM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
28 |
|
Using BOOTP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
29 |
|
Configure the Adapter Using a BOOTP Server . . . . . . . . . . . . . . . . . |
29 |
|
Setting the IP Address, Subnet Mask, and Gateway Address. . . . . . . . . . |
32 |
|
Disable the BOOTP Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
32 |
|
Set an IP Address Using Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
32 |
|
Set a Subnet Mask Using Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . |
33 |
|
Set a Gateway Address Using Parameters . . . . . . . . . . . . . . . . . . . . . . . |
33 |
|
Setting the Data Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
34 |
|
Setting the I/O Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
35 |
|
Selecting Master-Slave or Peer-to-Peer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
36 |
|
Setting a Master-Slave Hierarchy 36 |
|
|
Setting the Adapter to Transmit Peer-to-Peer Data . . . . . . . . . . . . . |
37 |
|
Setting the Adapter to Receive Peer-to-Peer Data. . . . . . . . . . . . . . . . |
38 |
|
Setting the Reference Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
41 |
|
Setting a Fault Action. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
41 |
Rockwell Automation Publication 20COMM-UM015B-EN-P – June 2013 |
3 |
Table of Contents
|
Changing the Fault Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
42 |
|
Setting the Fault Configuration Parameters. . . . . . . . . . . . . . . . . . . . . |
42 |
|
Setting Web Access Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
42 |
|
Resetting the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
43 |
|
Viewing the Adapter Status Using Parameters . . . . . . . . . . . . . . . . . . . . . . |
44 |
|
Updating the Adapter Firmware. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
44 |
|
Chapter 4 |
|
Configuring the I/O |
Using RSLinx Classic Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
47 |
|
ControlLogix Controller Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
48 |
|
Adding the Bridge to the I/O Configuration. . . . . . . . . . . . . . . . . . . . |
49 |
|
Using RSLogix 5000 Device Add-on Profiles, Version 16.00 or Later |
|
|
51 |
|
|
Using the RSLogix 5000 Classic Profile, Versions 13.00…15.00. . . |
60 |
|
Using the RSLogix 5000 Generic Profile, All Versions . . . . . . . . . . . |
62 |
|
Limitations Using a MicroLogix 1100/1400 Controller . . . . . . . . . . . . . |
68 |
|
MicroLogix 1100/1400 Controller Example. . . . . . . . . . . . . . . . . . . . . . . . |
68 |
|
Configuring Parameters for Network I/O . . . . . . . . . . . . . . . . . . . . . . |
69 |
|
Creating RSLogix 500 Project, Version 7.00 or Later . . . . . . . . . . . . |
70 |
|
Chapter 5 |
|
Using the I/O |
About I/O Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
79 |
|
Understanding the I/O Image . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
80 |
|
ControlLogix Controller Image. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
80 |
|
MicroLogix 1100/1400 Controller Image . . . . . . . . . . . . . . . . . . . . . . |
82 |
|
Using Logic Command/Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
84 |
|
Using Reference/Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
84 |
|
PowerFlex 7-Class Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
85 |
|
Using Datalinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
86 |
|
Rules for Using Datalinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
86 |
|
Using 16-Bit Datalinks to Read/Write 32-Bit Parameters . . . . . . . . |
86 |
|
Example Ladder Logic Program Information . . . . . . . . . . . . . . . . . . . . . . . |
87 |
|
Functions of the Example Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
87 |
|
Logic Command/Status Words. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
88 |
|
ControlLogix Controller Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
88 |
|
Creating Ladder Logic Using the RSLogix 5000 Device Add-on |
|
|
Profiles, Version 16.00 or Later . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
88 |
|
Creating Ladder Logic Using the RSLogix 5000 Classic Profile, |
|
|
Versions 1300…15.00 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
89 |
|
Creating Ladder Logic Using the RSLogix 5000 Generic Profile, All |
|
|
Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
90 |
|
MicroLogix 1100/1400 Controller Example. . . . . . . . . . . . . . . . . . . . . . . . |
96 |
|
Drive and Adapter Parameter Settings. . . . . . . . . . . . . . . . . . . . . . . . . . |
96 |
|
Understanding Controller Data Table Addresses. . . . . . . . . . . . . . . . |
97 |
Chapter 6
4 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013 |
|
Table of Contents |
|
Using Explicit Messaging |
About Explicit Messaging . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
106 |
|
Performing Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
106 |
|
ControlLogix Controller Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
108 |
|
Explicit Messaging Using RSLogix 5000 Software, Version 15.00 or |
|
|
Later . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
108 |
|
Explicit Messaging Using RSLogix 5000 Software, All Versions. . |
121 |
|
MicroLogix 1100/1400 Controller Examples . . . . . . . . . . . . . . . . . . . . . . |
124 |
|
MicroLogix 1100/1400 Controller Explicit Messaging Using the |
|
|
Read/Write Parameter Service. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
125 |
|
MicroLogix 1100/1400 Controller Explicit Messaging Using the |
|
|
Generic Get/Set Attribute Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
130 |
|
Chapter 7 |
|
Troubleshooting |
Understanding the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
143 |
|
Port Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
144 |
|
Network Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
145 |
|
Link (LS1, LS2) Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
145 |
|
NET A Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
145 |
|
Hardware Reset via Node Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
146 |
|
Viewing Adapter Diagnostic Items. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
146 |
|
Viewing and Clearing Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
149 |
|
Chapter 8 |
|
Viewing the Adapter Web Pages |
Accessing the Adapter Web Home Page. . . . . . . . . . . . . . . . . . . . . . . . . . . |
153 |
|
Viewing the Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
153 |
|
Title Bar on Adapter Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
154 |
|
Navigation Pane on Adapter Web Pages . . . . . . . . . . . . . . . . . . . . . . . |
155 |
|
Process Display Home Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
156 |
|
Browse DPI Device Folder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
156 |
|
Diagnostics Web Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
157 |
|
Diagnostic Overview link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
157 |
|
Network Setting Link. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
158 |
|
EtherNet/IP Statistics Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
159 |
|
Ring Statistics link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
159 |
|
Crash Display Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
160 |
|
Heap Statistics Display link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
160 |
|
Administrative Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
160 |
|
Device Identity Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
161 |
|
Network Configuration Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
161 |
|
Email Configuration Link. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
162 |
|
Password Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
165 |
|
Chapter 9 |
|
Using the Adapter in a DPI External |
Installing the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
167 |
Comms Kit (20-XCOMM-DC-BASE) |
|
|
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013 |
5 |
Table of Contents |
|
|
|
Appendix A |
|
Specifications |
Communications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
169 |
|
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
169 |
|
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
170 |
|
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
170 |
|
Regulatory Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
170 |
|
Appendix B |
|
Adapter Parameters |
About Parameter Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
171 |
|
Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
171 |
|
Appendix C |
|
EtherNet/IP Objects |
Supported Data Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
182 |
|
Identity Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
182 |
|
Assembly Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
183 |
|
Register Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
184 |
|
Parameter Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
185 |
|
Parameter Group Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
188 |
|
Device Level Ring Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
189 |
|
Quality of Service Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
190 |
|
PCCC Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
190 |
|
DPI Device Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
196 |
|
DPI Parameter Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
198 |
|
DPI Fault Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
204 |
|
DPI Alarm Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
206 |
|
DPI Diagnostic Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
207 |
|
DPI Time Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
209 |
|
TCP/IP Interface Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
211 |
|
Ethernet Link Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
213 |
|
Appendix D |
|
Logic Command/Status Words |
PowerFlex 70/70EC, PowerFlex 700/700VC, and PowerFlex 700H |
|
|
Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
215 |
|
Logic Command Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
215 |
|
Logic Status Word. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
216 |
|
PowerFlex 700S Drives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
217 |
|
Logic Command Word (Phase II Control) . . . . . . . . . . . . . . . . . . . . |
217 |
|
Logic Status Word (Phase II Control) . . . . . . . . . . . . . . . . . . . . . . . . |
218 |
|
SMC Flex Controllers /SMC-50 Controllers . . . . . . . . . . . . . . . . . . . . . . |
219 |
|
Logic Status Word. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
219 |
|
Logic Command Word (Control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
220 |
|
Glossary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
221 |
|
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . |
231 |
6 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013 |
Conventions Used in This
Manual
Rockwell Automation
Support
Topic |
Page |
|
|
Conventions Used in This Manual |
7 |
|
|
Rockwell Automation Support |
7 |
|
|
Additional Resources |
8 |
|
|
This manual provides information about the adapter and using it with PowerFlex 7-Class (Architecture-Class) drives or Bulletin 150 SMC Soft Starters. The adapter can be used with other products that support a DPI™ adapter, such as the DPI External Comms Kit (20-XCOMM-DC-BASE). See the documentation for your product for specific information about how it works with the adapter.
The following conventions are used throughout this manual:
•Parameter names are shown in the format Parameter xx - [*]. The xx represents the parameter number. The * represents the parameter name— for example Parameter 01 - [DPI Port].
•Menu commands are shown in bold type face and follow the format Menu > Command. For example, if you read ‘Select File > Open’, you should click the File menu and then click the Open command.
•The firmware revision number (FRN) is displayed as FRN X.xxx, where ‘X’ is the major revision number and ‘xxx’ is the minor revision number.
•The screen images in this manual resulted from using the following software:
–RSLinx® Classic software, version 2.51
–RSLogix 5000 software, version 16
Different versions of the software may have screens that vary in appearance, and differences in procedures.
Rockwell Automation offers support services worldwide, with over 75 sales and support offices, over 500 authorized distributors, and over 250 authorized systems integrators located through the United States alone. In addition, Rockwell Automation representatives are in every major country in the world.
Contact your local Rockwell Automation representative for the following:
•Sales and order support
•Product technical training
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013 |
7 |
Preface
• Warranty support
• Support service agreements
For technical assistance, please review the information in Chapter 7, Troubleshooting, first. If you still have problems, then access the Allen-Bradley Technical Support website at www.ab.com/support/abdrives or contact Rockwell Automation.
These documents contain additional information concerning related products from Rockwell Automation.
Resource |
Description |
|
|
Industrial Automation wiring and grounding guidelines, publication 1770-4.1 |
Provides general guidelines for installing a Rockwell |
|
Automation industrial system. |
|
|
Product certifications website, http://www.ab.com |
Provides declarations of conformity, certificates, and |
|
other certification details. |
|
|
Industrial Security Best Practices, publication SECUR-AT001 |
Provides further information and guidelines on product |
|
and system security. |
|
|
PowerFlex 7-Class DPI (Drive Peripheral Interface) Network Communication Adapter Installation |
Information on the installation of PowerFlex® |
Instructions, publication 20COMM-IN004 |
20-COMM-x Network Communication Adapters. |
|
|
EtherNet/IP Media Planning and Installation Manual, ODVA publication 148 (1) |
Information on the planning, installation, and techniques |
|
used to implement an EtherNet/IP network. |
EtherNet/IP Network Infrastructure Guidelines, ODVA publication 35 (1) |
|
Ethernet Design Considerations Reference Manual, publication ENET-RM002 |
|
|
|
Connected Components Workbench website |
Information on the Connected Components |
http://www.ab.com/support/abdrives/webupdate/software.html, and online help |
Workbench™ software tool—and includes a link for free |
|
software download. |
|
|
PowerFlex 20-HIM-A3/-A5/-C3S/-C5S HIM Quick Reference, publication 20HIM-QR001 |
Information on the use of the PowerFlex 20-HIM-A3, 20- |
|
HIM-A5, 20-HIM-C3S, and 20-HIM-C5S HIMs. |
|
|
PowerFlex 20-HIM-A6/-C6S HIM (Human Interface Module) User Manual, publication 20HIM- |
Information on the installation and use of the PowerFlex |
UM001 |
20-HIM-A6 and 20-HIM-C6S HIMs. |
|
|
PowerFlex 70 User Manual, publication 20A-UM001 |
Information on installing, programming, and technical |
PowerFlex 70/700 Reference Manual, publication PFLEX-RM001 |
data of PowerFlex 70 and PowerFlex 70EC drives. |
PowerFlex 70EC/700VC Reference Manual, publication PFLEX-RM004 |
|
|
|
PowerFlex 700 Series A User Manual, publication 20B-UM001 |
Information on installing, programming, and technical |
PowerFlex 700 Series B User Manual, publication 20B-UM002 |
data of PowerFlex 700/700VC Series A and PowerFlex |
PowerFlex 70/700 Reference Manual, publication PFLEX-RM001 |
700VC Series B drives. |
PowerFlex 70EC/700VC Reference Manual, publication PFLEX-RM004 |
|
|
|
PowerFlex 700H Installation Instructions, publication PFLEX-IN006 |
Information on installing, programming, and technical |
PowerFlex 700H Programming Manual, publication 20C-PM001 |
data of PowerFlex 700H drives. |
|
|
8 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013 |
|
|
Preface |
|
|
|
|
|
|
|
Resource |
Description |
|
|
|
|
PowerFlex 700S w/Phase I Control Installation Manual (Frames 1…6), publication 20D-IN024 |
Information on installing, programming, and technical |
|
PowerFlex 700S w/Phase I Control Installation Manual (Frames 9 and 10), publication PFLEX- |
data of PowerFlex 700S drives. |
|
IN006 |
|
|
PowerFlex 700S w/Phase I Control User Manual (All Frame Sizes), publication 20D-UM001 |
|
|
PowerFlex 700S w/Phase I Control Reference Manual, publication PFLEX-RM002 |
|
|
PowerFlex 700S w/Phase II Control Installation Manual (Frames 1…6), publication 20D-IN024 |
|
|
PowerFlex 700S w/Phase II Control Installation Manual (Frames 9…14), publication PFLEX- |
|
|
IN006 |
|
|
PowerFlex 700S w/Phase II Control Programming Manual (All Frame Sizes), publication 20D- |
|
|
PM001 |
|
|
PowerFlex 700S w/Phase II Control Reference Manual, publication PFLEX-RM003 |
|
|
|
|
|
PowerFlex 700L User Manual, publication 20L-UM001 |
Information on installing, programming, and technical |
|
|
data of PowerFlex 700L Liquid-Cooled AC drives. |
|
|
|
|
SMC Flex Smart Motor Controller User Manual, publication 150-UM008 |
Information on installing, programming, and technical |
|
|
data of SMC Flex State Smart Motor Controller. |
|
|
|
|
SMC-50 Solid-State Smart Motor Controller User Manual, publication 150-UM011 |
Information on installing, programming, and technical |
|
|
data of SMC-50 Solid-State Smart Motor Controller. |
|
|
|
|
PowerFlex Digital DC Drive User Manual, publication 20P-UM001 |
Information on installing, programming, and technical |
|
|
data of PowerFlex Digital DC drives. |
|
|
|
|
Getting Results with RSLinx Guide, publication LINX-GR001and online help (1) |
Information on using RSLinx Classic software. |
|
RSLogix Emulate 5/500 Getting Results Guide, publication EMULAT-GR002 and online help |
Information on how to install and navigate the RSLogix |
|
|
Emulate software for ladder logic programming with |
|
|
Allen-Bradley® PLC-5® and SLC™ 500 processors. |
|
RSLogix 500 Getting Results Guide, publication LG500-GR002 and online help (1) |
Information on using RSLogix 500 software tool. |
|
RSLogix 5000 PIDE Autotuner Getting Results Guide, publication PIDE-GR001 and online help |
Information on using RSLogix 5000 software tool. |
|
(1) |
|
|
|
|
|
EtherNet/IP Modules in Logix5000 Control Systems User Manual, publication ENET-UM001 |
Information on using the ControlLogix® 1756-ENBT or |
|
|
1756-EN2T EtherNet/IP communication modules with |
|
|
your Logix5000 controller and communicating with |
|
|
various devices on the EtherNet/IP network. |
|
|
|
|
Enhanced and Ethernet PLC-5 Programmable Controllers User Manual, publication 1785- |
Information to help design, operate and maintain an |
|
UM012 |
Enhanced and Ethernet PLC-5 programmable controller |
|
|
system. |
|
|
|
|
MicroLogix 1100 Programmable Controllers User Manual, publication 1763-UM001 |
Information to install, wire, and troubleshoot the |
|
MicroLogix 1400 Programmable Controllers User Manual, publication 1766-UM001 |
MicroLogix™ 1100 and MicroLogix 1400 controllers |
|
|
respectively. |
|
|
|
|
Web Updates http://www.ab.com/support/abdrives/webupdate/ |
Flash Update Files, Product Help Files, Control Bar |
|
|
Files, GSD Files, EDS File links, DriveTools SP / Drive |
|
|
AOP Database Files, and other downloads to keep your |
|
|
Allen-Bradley brand drive products up to date |
|
|
|
(1)Use this link to the ODVA EtherNet/IP library: http://odva.org/Home/ODVATECHNOLOGIES/EtherNetIP/EtherNetIPLibrary/tabid/76/Default.aspx
Documentation can be obtained online at http:// literature.rockwellautomation.com. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
To find your local Rockwell Automation distributor or sales representative, visit
http://www.rockwellautomation.com/locations.
For information such as firmware updates or answers to drive-related questions, go to the Drives Service & Support web site at http://www.ab.com/support/ abdrives and click on the Downloads or Knowledgebase link.
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013 |
9 |
Preface
Notes:
10 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - June 2013 |
Chapter 1
The adapter is intended for installation in a PowerFlex 7-Class drive or Bulletin 150 SMC soft starter and is used for network communication.
Topic |
Page |
|
|
Components |
11 |
|
|
Features |
12 |
|
|
Compatible Products |
13 |
|
|
Required Equipment |
13 |
|
|
Safety Precautions |
15 |
|
|
Quick Start |
16 |
|
|
|
|
|
|
|
|
|
|
Item |
Part |
Description |
|
|
Status Indicators |
Four status indicators that indicate the status of the DPI, the |
|
|
|
adapter, and network connection. See Chapter 7, Troubleshooting. |
|
|
DPI Connector |
A 20-pin, single-row shrouded male header. An Internal Interface |
|
|
|
cable is connected to this connector and a connector on the drive. |
|
|
Ethernet Connector |
RJ-45 connector for the Ethernet network cable. The connector is |
|
|
|
CAT-5 compliant to ensure reliable data transfer on 100Base-TX |
|
|
|
Ethernet connections. |
|
|
Web Pages Switch |
Enables or disables the adapter web pages. See Setting the Web |
|
|
(SW4) |
Pages Switch on page 19. |
|
|
Address/mode |
Set IP address or DHCP/BootP mode. |
|
|
switches |
|
|
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
11 |
Chapter 1 |
Getting Started |
|
|
The features of the adapter include the following:
•Typical mounting in a PowerFlex 7-Class drive or SMC soft starter.
•Captive screws to secure and ground the adapter to the drive.
•Compatibility with various configuration tools to configure the adapter and connected host drive, including the following tools:
–PowerFlex HIM (Human Interface Module) on the drive or SMC, if available
–Connected Components Workbench software, version 1.02 or later
–DriveExplorer software, version 2.01 or later
–DriveExecutive software, version 3.01 or later
–RSLogix5000 version16 and later with Drives Add-on Profile version 4.05 and later
Additionally, you can use a BOOTP/DHCP server to configure the network address for the adapter.
•Status indicators that report the status of the drive communications, the adapter, and network. They are visible when the drive cover is open or closed.
•Parameter-configured I/O (Logic Command/Reference and up to four pairs of Datalinks) to accommodate application requirements.
•Explicit Messaging support.
•Master-Slave or Peer-to-Peer hierarchy that can be configured to transmit data to and from either a controller or another PowerFlex drive or SMC on the network.
•User-defined fault actions to determine how the adapter and connected PowerFlex drive respond to the following:
–I/O messaging communication disruptions (Comm Flt Action)
–Controllers in idle mode (Idle Flt Action)
•Web pages, viewed by using a web browser, that show information about the adapter, its connected host drive, and DPI devices connected to the drive.
•Configurable e-mail messaging to desired addresses when selected drive faults occur and/or are cleared, and/or when the adapter takes a communication or idle fault action.
•Access to any PowerFlex drive or SMC and its connected peripherals on the network to which the adapter is connected.
•Device Level Ring (DLR) or Star Topology support with Quality of Service (QoS) support.
12 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
Getting Started |
Chapter 1 |
|
|
At the time of publication, the adapter is compatible with the following products:
• |
PowerFlex 70/70EC drives |
• |
PowerFlex 700L drives |
• |
PowerFlex 700/700VC drives |
• PowerFlex Digital DC drives |
|
• |
PowerFlex 700H drives |
• DPI External Comms Kit |
|
• |
PowerFlex 700S drives |
• |
SMC™-50 |
• |
PowerFlex 7000/7000-2 drives |
• |
SMC™ Flex |
Note: The adapter is not compatible with PowerFlex 750 series drives.
Some of the equipment that is required for use with the adapter is shipped with the adapter, but some you must supply yourself.
When you unpack the adapter, verify that the package includes the following:
One 20-COMM-ER EtherNet/IP adapter
One 2.54 cm (1 in.) long and one 15.24 cm (6 in.) long Internal Interface cable (only one cable is needed to connect the adapter to the drive; for which cable to use, see Figure 3 - on page 2-21)
One PowerFlex 7-Class DPI (Drive Peripheral Interface) Network Communication Adapter Installation Instructions, publication 20COMMIN004
One LED Identification Label for use with Bulletin 150 SMC Flex and Bulletin 700 PowerFlex drives
To install and configure the adapter, you must supply the following:
A small flathead screwdriver
Ethernet cable (for details, see the EtherNet/IP Media Planning and Installation Manual, ODVA publication 148 available on the ODVA website at http://odva.org/Home/ODVATECHNOLOGIES/ EtherNetIP/EtherNetIPLibrary/tabid/76/Default.aspx)
Ethernet switch (for details, see the Ethernet Design Considerations Reference Manual, publication ENET-RM002)
Configuration tool, such as the following:
– PowerFlex 20-HIM-xx HIM
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
13 |
Chapter 1 |
Getting Started |
|
|
–Connected Components Workbench software, version 1.02 or later
Connected Components Workbench is the recommended stand-alone software tool for use with PowerFlex drives. You can obtain a free copy by:
•Internet download at http://www.ab.com/support/abdrives/webupdate/software.html
•Requesting a DVD at http://www.ab.com/onecontact/controllers/micro800/
Your local distributor may also have copies of the DVD available.
Connected Components Workbench software cannot be used to configure SCANport-based drives or Bulletin 160 drives.
–DriveExplorer software, version 2.01 or later
This software tool has been discontinued and is now available as freeware at http://www.ab.com/support/abdrives/webupdate/software.html. There are no plans to provide future updates to this tool and the download is being provided ‘as-is’ for users that lost their DriveExplorer CD, or need to configure legacy products not supported by Connected Components Workbench software.
–DriveExecutive software, version 3.01 or later
A Lite version of DriveExecutive software ships with RSLogix 5000, RSNetWorx MD, FactoryTalk AssetCentre, and ItelliCENTER software. All other versions are purchasable items:
•9303-4DTE01ENE Drive Executive software
•9303-4DTS01ENE DriveTools SP Suite (includes DriveExecutive and DriveObserver software)
•9303-4DTE2S01ENE DriveExecutive software upgrade to DriveTools SP Suite (adds DriveObserver software)
DriveExecutive software updates (patches, and so forth) can be obtained at http://www.ab.com/support/abdrives/webupdate/software.html. It is highly recommended that you periodically check for and install the latest update.
– BOOTP server, version 2.1 or higher, for network setup only
Controller configuration software, such as RSLogix 5/500/5000
A computer connection to the EtherNet/IP network
14 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
Getting Started |
Chapter 1 |
|
|
Please read the following safety precautions carefully.
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove all power from the PowerFlex drive or SMC, and then verify power has been discharged before installing or removing an adapter.
ATTENTION: Risk of injury or equipment damage exists. Only personnel familiar with drive and power products and the associated machinery should plan or implement the installation, start up, configuration, and subsequent maintenance of the product using an adapter. Failure to comply may result in injury and/or equipment damage.
ATTENTION: Risk of equipment damage exists. The adapter contains electrostatic discharge (ESD) sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the adapter. If you are unfamiliar with static control procedures, see Guarding Against Electrostatic Damage, publication 8000- 4.5.2.
ATTENTION: Risk of injury or equipment damage exists. If the adapter is transmitting control I/O to the drive, the drive may fault when you reset the adapter. Determine how your drive will respond before resetting an adapter.
ATTENTION: Risk of injury or equipment damage exists. Parameters 21 - [Comm Flt Action], 24 - [Idle Flt Action], and 43 - [Peer Flt Action] let you determine the action of the adapter and connected drive if communication is disrupted or the controller is idle. By default, these parameters fault the drive. You may configure these parameters so that the drive continues to run, however, precautions should be taken to ensure that the settings of these parameters do not create a risk of injury or equipment damage. When commissioning the drive, verify that your system responds correctly to various situations (for example, a disconnected cable or a controller in idle state).
ATTENTION: Risk of injury or equipment damage exists. When a system is configured for the first time, there may be unintended or incorrect machine motion. Disconnect the motor from the machine or process during initial system testing.
ATTENTION: Risk of injury or equipment damage exists. The examples in this publication are intended solely for purposes of example. There are many variables and requirements with any application. Rockwell Automation, Inc. does not assume responsibility or liability (to include intellectual property liability) for actual use of the examples shown in this publication.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
15 |
Chapter 1 |
Getting Started |
|
|
This section is provided to help experienced users quickly start using the adapter. If you are unsure how to complete a step, refer to the referenced chapter.
Step |
Action |
See |
|
|
|
|
|
1 |
Review the safety precautions for the drive or SMC |
Drive or SMC User |
|
|
|
|
Manual |
|
|
|
|
2 |
Review the safety precautions for the adapter |
Throughout this manual |
|
|
|
|
|
3 |
Verify that the power control device is properly installed. |
Drive or SMC User |
|
|
|
|
Manual |
|
|
|
|
4 |
Install the adapter. |
PowerFlex 7-Class DPI |
|
|
a. Verify that the power control device is not powered. |
Network Communication |
|
|
Adapter Installation |
||
|
b. Connect the adapter to the device with the Internal Interface |
||
|
Instructions, publication |
||
|
|
cable. |
20COMM-IN004, and |
|
c. Use the captive screws to secure and ground the adapter to |
Chapter 2, |
|
|
|
the device. |
Installing the Adapter |
|
d. Connect the adapter to the network with an Ethernet cable. |
|
|
|
NOTE: When installing the adapter in the DPI External Comms |
|
|
|
Kit—see the 20-XCOMM-DC-BASE Installation Instructions, |
|
|
|
publication 20COMM-IN001, supplied with the kit. |
|
|
|
|
|
|
5 |
Apply power to the adapter. |
Chapter 2, |
|
|
a. Verify that the adapter is installed correctly. |
Installing the Adapter |
|
|
|
||
|
b. The adapter receives power from the drive or SMC. Apply |
|
|
|
|
power to the device. |
|
|
|
The status indicators should be green. If they flash red, there |
|
|
|
is a problem. See Chapter 7, Troubleshooting. |
|
|
c. Configure and verify key drive or SMC parameters. |
|
|
|
|
|
|
6 |
Configure the adapter for your application. |
Chapter 3, |
|
|
Set adapter parameters for the following functions as required by |
Configuring the Adapter |
|
|
|
||
|
your application: |
|
|
|
• IP address, subnet mask, and gateway address |
|
|
|
• |
Data rate |
|
|
• |
I/O configuration |
|
|
• Master-Slave or Peer-to-Peer hierarchy |
|
|
|
• |
Fault actions |
|
|
|
|
|
7 |
Configure the controller to communicate with the adapter. |
Chapter 4, |
|
|
Use a controller configuration tool, such as RSLogix software, to |
Configuring the I/O |
|
|
|
||
|
configure the master on the network to recognize the adapter and |
|
|
|
drive or SMC. |
|
|
|
|
|
|
8 |
Create a ladder logic program. |
Chapter 5, |
|
|
Use a controller configuration tool, such as RSLogix software, to |
Using the I/O |
|
|
|
||
|
create a ladder logic program that enables you to do the |
Chapter 6, |
|
|
following: |
Using Explicit |
|
|
• Control the connected device, via the adapter, by using I/O. |
Messaging |
|
|
• Monitor or configure the device or SMC by using explicit |
|
|
|
|
messages. |
|
|
|
|
|
16 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
Chapter 2
Installing the Adapter
This chapter provides instructions for installing the adapter in a PowerFlex 7- Class drive.
Topic |
Page |
|
|
Preparing for an Installation |
18 |
|
|
Setting the Web Pages Switch |
19 |
|
|
Connecting the Adapter to the Drive or SMC |
20 |
|
|
Connecting the Adapter to the Network |
23 |
|
|
Applying Power |
24 |
|
|
Commissioning the Adapter |
26 |
|
|
For all PowerFlex 70 and 700 drive installations that require CE conformance per EN61800-3, a ferrite core must be installed on each EtherNet/IP cable connected to the drive.
These ferrites are not required for installation on SMC products.
A ferrite core such as FAIR-RITE part number 2643803802 needs to be installed according to the following diagram.
Note: the cable is wrapped 4 times around each core.
Figure 1 - Ferrite Core Installation
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
17 |
Chapter 2 Installing the Adapter
Before installing the adapter, do the following:
•Make sure the Ethernet switch is the correct type. A ‘managed’ switch that supports IGMP snooping is usually recommended. An ‘unmanaged’ switch can be used instead if RSLogix 5000 software, version 18.00 or later, is used and all devices on the network are configured for ‘unicast’ I/O. For more details, see the following documents:
–EtherNet/IP Media Planning and Installation Manual, ODVA publication 148
–EtherNet/IP Network Infrastructure Guidelines, ODVA publication 35
–Ethernet Design Considerations Reference Manual, publication ENET-RM002
•Understand IGMP Snooping/Ethernet Switches
The 20-COMM-ER adapter is a multicast device. In most situations, an IGMP snooping (managed) switch is required. If more than one or two 20-COMM-ER adapters are connected to the switch, a managed switch is required—otherwise the drive may fault on a DPI Port x network loss. The 20-COMM-ER, RSLogix 5000 software, version 18.00 or later, and a ControlLogix or CompactLogix controller will support unicast. Unicast setup is required when adding the drive to the I/O. When all adapters are set up as unicast devices, then an IGMP snooping (managed) switch is not needed.
Much of EtherNet/IP implicit (I/O) messaging uses IP multicast to distribute I/O control data, which is consistent with the CIP producer/ consumer model. Historically, most switches have treated multicast packets the same as broadcast packets. That is, all multicast packets are retransmitted to all ports.
IGMP snooping constrains the flooding of multicast traffic by dynamically configuring switch ports so that multicast traffic is forwarded only to ports associated with a particular IP multicast group.
Switches that support IGMP snooping (managed switches) ‘learn’ which ports have devices that are part of a particular multicast group and only forward the multicast packets to the ports that are part of the multicast group.
Be careful as to what level of support a switch has of IGMP snooping. Some layer 2 switches that support IGMP snooping require a router (which could be a layer 3 switch) to send out IGMP polls to learn what devices are part of the multicast group. Some layer 2 switches can use IGMP snooping without a router sending polls. If your control system is a standalone network or is required to continue performing if the router is out of service, make sure the switch you are using supports IGMP snooping without a router being present.
18 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
Installing the Adapter |
Chapter 2 |
|
|
Setting the Web Pages
Switch
•See Appendix A for the number of CIP connections supported by the 20- COMM-ER adapter.
•Verify that you have all required equipment. See Required Equipment on page 13.
To use the adapter web pages, the Web Pages Switch must be set to its ‘Enable Web’ position. For information to enable or disable web pages for an adapter, see Setting Web Access Control on page 42.
ATTENTION: Risk of equipment damage exists. The adapter contains electrostatic discharge (ESD) sensitive parts that can be damaged if you do not follow ESD control procedures. Static control precautions are required when handling the adapter. If you are unfamiliar with static control procedures, see Guarding Against Electrostatic Damage, publication 8000- 4.5.2.
Important: A new switch setting is recognized only when power is applied to the adapter, or the adapter is reset. If you change a switch setting, cycle power or reset the adapter to apply the change.
Set the Web Pages Switch (SW4 in Figure 2) to enable or disable the adapter web pages. By default, the adapter web pages are disabled. For complete details on adapter web pages, see Viewing the Adapter Web Pages on page 153.
Figure 2 - Setting Web Pages Switch (only Series B Adapter)
|
|
|
Web Pages |
|
|
|
Switch |
|
O |
1 |
UpPosition= |
|
Disable |
||
|
N |
|
|
|
Down Position = |
||
|
Enable |
|
|
Setting |
Description |
|
|
Down (OFF) position |
Web server enabled |
|
|
Up (ON) position |
Web server disabled (as shipped) |
|
|
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
19 |
Chapter 2 Installing the Adapter
ATTENTION: Risk of injury or death exists. The PowerFlex drive or SMC may contain high voltages that can cause injury or death. Remove ALL power from the drive or SMC, and then verify power has been discharged before installing or removing the adapter.
1.Remove ALL power from the drive or SMC.
2.Use static control precautions.
3.Remove the drive or SMC cover or open the drive door.
4.Connect the Internal Interface cable to the DPI port on the drive and then to the DPI connector on the adapter (see Figure 3).
5.Secure and ground the adapter to the drive or SMC (see Figure 4) by doing the following:
–On a PowerFlex 70 drive, fold the Internal Interface cable behind the adapter and mount the adapter on the drive using the four captive screws.
–On an SMC Flex, put the wire lug between the mounting screw and 20-COMM-ER board
Important: Tighten all screws to properly ground the adapter. Recommended torque is 0.9 N•m (8.0 lb•in).
20 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
Installing the Adapter |
Chapter 2 |
|
|
Figure 3 - DPI Ports and Internal Interface Cables |
|
20-COMM-ER Adapter |
|
|
|
|
|
|
|
PowerFlex 70 - All Frames |
SMC-50 |
PowerFlex 700 Frames 0 and 1 |
PowerFlex 700 Frames 2 and Larger |
SMC Flex |
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||||||
PowerFlex 700S Frames 0 and 1 |
PowerFlex 700S Frames 2 through 6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
HIM panel opens to |
|
|
allow access to DPI |
X2 |
|
interface. To open panel, |
||
X1 |
||
remove screws on left |
||
|
||
side of HIM panel and |
|
|
swing open. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|||||
|
PowerFlex 700H Frames 9 and Larger |
||||||||||||
|
|
|
|
||||||||||
|
|
Item |
Description |
||||||||||
|
|
|
|
||||||||||
|
|
|
15.24 cm (6 in.) Internal Interface cable |
||||||||||
|
|
|
|
||||||||||
|
|
|
DPI Connector |
||||||||||
|
|
|
|
||||||||||
|
|
|
Ethernet cable |
||||||||||
|
|
|
|
||||||||||
|
|
|
2.54 cm (1 in.) Internal Interface cable |
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Place ground wire tab between mounting screw and circuit board
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
21 |
Chapter 2 Installing the Adapter
Figure 4 - Mounting and Grounding the Adapter
0.9 N•m (8.0 lb•in) 4 Places
Drive
Adapter
Internal Interface Cable folded behind the adapter and in front of the drive.
PowerFlex 70 - All Frame Sizes (Adapter mounts in drive.)
0.9 N•m
(8.0 lb•in)
PowerFlex 700 Frames 0 and 1 PowerFlex 700S Frames 0 and 1 (Adapter mounts on door.)
Ground Tab Detail
Verify metal ground tab is bent 90° and is under the adapter before tightening screw. After tightening the screw, verify continuity exists between the head of the screw and drive ground.
PowerFlex 700 Frames 2 and Larger PowerFlex 700S Frames 2 through 6 (Adapter mounts in drive.)
Ground Tab Detail
X2
0.9 N•m
(8.0 lb•in)
4 Places
PowerFlex 700H Frames 9 and Larger PowerFlex 700S Frames 9 and Larger (Adapter mounts behind HIM panel.)
Verify metal ground tab is bent 90° and is under the adapter before tightening screw. After tightening the screw, verify continuity exists between the head of the screw and drive ground.
22 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
Installing the Adapter |
Chapter 2 |
|
|
ATTENTION: Risk of injury or death exists. The PowerFlex drive may contain high voltages that can cause injury or death. Remove power from the drive, and then verify power has been discharged before installing or removing the adapter.
1.Remove power from the drive.
2.Use static control precautions.
3.Connect one end of an Ethernet cable to the network. See Figure 5 for an example of wiring to an EtherNet/IP network.
Figure 5 - Connecting the Ethernet Cable in a Linear Topology Network
Controller |
Drive or SMC(1) |
(with 20-COMM-ER Option Modules) |
|
(ControlLogix controller |
|
shown with 1756-EN2TR Bridge) |
|
To other |
|
EtherNet/IP |
|
networks |
|
Computer with
Ethernet Connection
Ethernet
Switch
(1) The option module’s ENET1 and ENET2 network ports are used.
Figure 6 - Connecting the Ethernet Cable in a DLR Topology Network
To other |
Drive or SMC(1) |
|
(with 20-COMM-ER Option Modules) |
||
EtherNet/IP |
||
|
||
networks |
Controller |
|
|
(ControlLogix controller |
|
|
shown with 1756-EN2TR Bridge) |
|
1783-ETAP |
|
1783-ETAP |
Computer with |
Ethernet Connection |
(1) The option module’s ENET1 and ENET2 network ports are used.
4.For Linear or DLR Network Topology, route the other end of the Ethernet cable from the network through the bottom of the first drive, and insert its cable plug into the option module ENET1 network port.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
23 |
Chapter 2 Installing the Adapter
To connect to the second drive, attach another Ethernet cable between the first drive’s option module ENET2 network port and the second drive’s option module ENET1 network port.
To connect additional drives, repeat these daisy-chain connections in the same way.
5.Route the other end of the Ethernet cable through the bottom of the PowerFlex drive (Figure 4) and insert its Ethernet cable plug into the mating adapter receptacle.
ATTENTION: Risk of equipment damage, injury, or death exists. Unpredictable operation may occur if you fail to verify that parameter settings are compatible with your application. Verify that settings are compatible with your application before applying power to the drive.
Install the device cover or close the drive door, and apply power to the device. The adapter receives its power from the connected device. When you apply power to the adapter for the first time, its topmost PORT status indicator should be steady green or flashing green after an initialization. If it is red, there is a problem. See Chapter 7, Troubleshooting.
After power has been applied, the status indicators for the device and communications adapter can be viewed on the front of the device (Figure 7). Possible start-up status indications are shown in Table 1.
Figure 7 - Drive and Adapter Status Indicators (location will vary by device)
PS
NS
LS1
LS2
STS
24 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
Installing the Adapter Chapter 2
|
|
|
Table 1 - Drive and Adapter Start-Up Status Indications |
|
|
|
|
|
|
Item |
Name |
Color |
State |
Description |
|
|
|
|
|
|
|
|
|
Drive STS Indicator |
|
|
|
|
|
|
STS (Status) |
Green |
Flashing |
Device ready but not running, and no faults are present. |
|
refer to drive |
|
|
|
|
|
Steady |
Device running, no faults are present. |
|
|
or SMC |
|
||
|
|
|
|
|
|
manual for |
Yellow |
Flashing, |
An inhibit condition exists – the drive cannot be started. Check device Parameter 214 - [Start |
|
status |
|
device stopped |
Inhibits]. |
|
indication |
|
|
|
|
|
Flashing, |
An intermittent type 1 alarm condition is occurring. Check device Parameter 211 - [Drive Alarm 1]. |
|
|
information) |
|
||
|
|
device running |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Steady, |
A continuous type 1 alarm condition exists. Check device Parameter 211 - [Drive Alarm 1]. |
|
|
|
device running |
|
|
|
|
|
|
|
|
Red |
Flashing |
A fault has occurred. |
|
|
|
|
|
|
|
|
Steady |
A non-resettable fault has occurred. |
|
|
|
|
|
|
|
|
|
Adapter Status Indicators |
|
|
|
|
|
|
PS |
Off |
Steady |
No power |
|
|
|
|
|
|
|
Orange |
Flashing |
Requesting DPI I/O Connections |
|
|
|
|
|
|
|
|
Steady |
Peripheral is Connected to an incompatible product or no DPI ping events are detected. |
|
|
|
|
|
|
|
Green |
Flashing |
Normal Operation (DPI connected) - No I/O, or PLC in Program |
|
|
|
|
|
|
|
|
Steady |
Normal Operation (DPI connected) - I/O Operational |
|
|
|
|
|
|
|
Red |
Flashing |
DPI Problem, Bad CRC of Adapter Parameters or Flash Program |
|
|
|
|
|
|
|
|
Steady |
DPI Failure or Failed power-on diagnostic test (hardware failure) |
|
|
|
|
|
|
|
Green/ |
Flashing |
Flash update in progress |
|
|
Red |
|
|
|
|
|
|
|
|
NS |
Off |
Steady |
No power OR no IP Address |
|
|
|
|
|
|
|
Green |
Flashing |
An IP address is configured, but no CIP connections are established, and an Exclusive Owner |
|
|
|
|
connection has not timed out |
|
|
|
|
|
|
|
|
Steady |
At least one CIP connection (any transport class) is established, and an Exclusive Owner |
|
|
|
|
connection has not timed out |
|
|
|
|
|
|
|
Red |
Flashing |
Connection has timed out see the “The EtherNet Adaptation of CIP” Specification sections 9-4.4 |
|
|
|
|
for detailed behavior description |
|
|
|
|
|
|
|
|
Steady |
Duplicate IP Address detected |
|
|
|
|
|
|
|
Orange |
Steady |
Adapter Failure (used in conjunction with PS orange) |
|
|
|
|
|
|
|
Green/ |
Flashing |
Self-test on power up |
|
|
Red |
|
|
|
|
|
|
|
|
LS1 |
Off |
Steady |
No Network Activity |
|
|
|
|
|
|
|
Green |
Flashing |
Network activity at 100 Mbps |
|
|
|
|
|
|
|
Yellow |
Flashing |
Network activity at 10 Mbps |
|
|
|
|
|
|
LS2 |
Off |
Steady |
No Network Activity |
|
|
|
|
|
|
|
Green |
Flashing |
Network activity at 100 Mbps |
|
|
|
|
|
|
|
Yellow |
Flashing |
Network activity at 10 Mbps |
|
|
|
|
|
After verifying correct operation, close or install the drive cover. For more details on status indicator operation, see page 144 and page 145.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
25 |
Chapter 2 Installing the Adapter
The PowerFlex 7-Class drive can be separately configured for the control and Reference functions in various combinations. For example, you could set the drive to have its control come from a peripheral or terminal block with the Reference coming from the network. Or you could set the drive to have its control come from the network with the Reference coming from another peripheral or terminal block. Or you could set the drive to have both its control and Reference come from the network.
The following steps in this section assume that the drive will receive the Logic
Command and Reference from the network.
1.Use drive Parameter 090 - [Speed Ref A Sel] to set the drive speed Reference to ‘22’ (DPI Port 5).
2.If hard-wired discrete digital inputs are not used to control the drive, verify that unused digital input drive Parameters 361 - [Dig In1 Sel] and 362 - [Dig In2 Sel] are set to ‘0’ (Not Used).
3.Verify that drive Parameter 213 - [Speed Ref Source] is reporting that the source of the Reference to the drive is ‘22’ (DPI Port 5).
This ensures that any Reference commanded from the network can be monitored by using drive Parameter 002 - [Commanded Speed]. If a problem occurs, this verification step provides the diagnostic capability to determine whether the drive/adapter or the network is the cause.
using a BOOTP/DHCP server or adapter parameters. See Setting the IP Address, Subnet Mask, and Gateway Address on page 32 for details.
By default, the adapter is configured so that you must set the IP address using a BOOTP/DHCP server or by setting the adapter to a valid address, 1-254, via the rotary switches on the adapter. An invalid address 0 or >254 will cause the module to defer to the addressing mode selected by parameter 3 [BOOTP/ DHCP]. If disabled, the adapter will use the address information stored in the adapters database. If that address is invalid, the adapter will try to contact a DHCP server on the network. To use adapter parameters, you must disable the BOOTP feature. For details, see Disable the BOOTP Feature on page 32.
Important: New settings for some adapter parameters (for example,
Parameters 04 - [IP Addr Cfg 1] through 07 - [IP Addr Cfg 4]) are recognized only when power is applied to the adapter or it is reset. After you change parameter settings, cycle power or reset the adapter.
26 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
Chapter 3
Configuring the Adapter
This chapter provides instructions and information for setting the parameters in the adapter.
Topic |
Page |
|
|
Configuration Tools |
27 |
|
|
Using the PowerFlex 7-Class HIM |
28 |
|
|
Using BOOTP |
29 |
|
|
Setting the IP Address, Subnet Mask, and Gateway Address |
32 |
|
|
Setting the Data Rate |
34 |
|
|
Setting the I/O Configuration |
35 |
|
|
Selecting Master-Slave or Peer-to-Peer |
36 |
|
|
Setting the Reference Adjustment |
41 |
|
|
Setting a Fault Action |
41 |
|
|
Setting Web Access Control |
42 |
|
|
Resetting the Adapter |
43 |
|
|
Viewing the Adapter Status Using Parameters |
44 |
|
|
Updating the Adapter Firmware |
44 |
|
|
For a list of parameters, see Appendix B, Adapter Parameters. For definitions of terms in this chapter, see the .
The adapter stores parameters and other information in its own nonvolatile storage (NVS) memory. You must, therefore, access the adapter to view and edit its parameters. The following tools can be used to access the adapter parameters.
Tool |
See |
|
|
PowerFlex 7-Class HIM |
page 28 |
|
|
BOOTP/DHCP server |
page 29 |
|
|
Connected Components Workbench |
http://www.ab.com/support/abdrives/webupdate/ |
software, version 1.02 or later |
software.html, or online help (installed with the software) |
|
|
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
27 |
Chapter 3 Configuring the Adapter
Using the PowerFlex 7-
Class HIM
If your drive has either an LED or LCD HIM (Human Interface Module), it can be used to access parameters in the adapter as shown below. It is recommended that you read through the steps for your HIM before performing the sequence. For additional information, see the drive documentation or the PowerFlex 7- Class HIM Quick Reference, publication 20HIM-QR001.
Step |
Example Screens |
|
|
1. Press the ALT key and then the Device Sel |
(Sel) key to |
display the Device Screen. |
|
2. Press the or key to scroll to the adapter. Letters represent files in the drive, and numbers represent ports. The adapter is usually connected to port 5.
3.Press the (Enter) key to enter your selection. A parameter database is constructed, and then the first parameter is displayed.
4.Edit the parameters using the same techniques that you use to edit drive parameters.
Step |
|
|
|
|
|
Example Screens |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
||
1. |
In the main menu, press the |
or |
key to scroll to |
|
|
|
|
|
|
|||
|
Device Select. |
|
|
|
|
F-> |
Stopped |
|
Auto |
|
||
2. |
Press the |
|
(Enter) key to enter your selection. |
|
|
0.00 |
Hz |
|
||||
|
|
|
|
|
|
|
||||||
|
|
Main Menu: |
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
|
|
||
3. |
Press the |
|
or |
key to scroll to the adapter (20- |
|
Diagnostics |
|
|
|
|||
|
COMM-ER). |
|
|
|
|
|
|
Parameter |
|
|
|
|
4. |
Press the |
|
(Enter) key to select the adapter. |
|
Device Select |
|
|
|
||||
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
||||||
|
A parameter database is constructed, and then the main |
|
Port 5 Device |
|
|
|
||||||
|
menu for the adapter is displayed. |
|
|
20-COMM-ER |
|
|
|
Main Menu:
5. Edit the parameters using the same techniques that you use to Diagnostics edit drive parameters.
Parameter
Device Select
NOTE: All configuration procedures throughout this chapter use the PowerFlex 7-Class LCD HIM to access parameters in the adapter and show example LCD HIM screens.
TIP When using a PowerFlex 20-HIM-A6 or 20-HIM-C6S HIM, see its User Manual, publication 20-HIM-UM001.
SMC Flex controllers require an external HIM (A3 or A6) to program the adapter. The internal Human Interface of the SMC Flex does not allow programming of the Adapter.
28 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
Configuring the Adapter |
Chapter 3 |
|
|
The IP address, subnet mask and gateway address can be configured multiple ways depending on the setting of the three rotary switches on the adapter. The switches are read on power up or reset.
1.If the switches are set to an address from 1…254, that value will be used as the LSB of the IP address 192.168.1.xxx
2.If the switches are set to an invalid number (000 or a value greater than 254), the unit will check if DHCP is enabled. If DHCP is enabled, the unit requests an address from a DHCP server.
If DHCP is not enabled and switches are set to an illegal value, the adapter will use the IP address (along with other TCP configurable parameters) stored in nonvolatile memory. If the unit finds that the stored IP configuration is not usable (set to 0), then the unit will revert to the out-of- box behavior of DHCP being enabled.
3.Any other switch setting will cause the adapter to use the IP address data set in the adapter's database parameters.
By default, the adapter is configured so that you can set its IP address, subnet mask, and gateway address by using a BOOTP or a DHCP server. There is a variety of BOOTP servers available. The following instructions use Rockwell Automation’s BOOTP Server, version 2.3 or later, a free standalone program that incorporates the functionality of standard BOOTP utilities with a graphical interface. It is available from http://www.software.rockwell.com/support/ download/detail.cfm?ID=3390. See the Readme file and online Help for directions and more information.
TIP If desired, you can disable BOOTP and configure the IP address, subnet mask, and gateway address with adapter parameters. For details, see Setting the IP Address, Subnet Mask, and Gateway Address on page 32.
1.On the adapter label, note the adapter’s hardware Ethernet Address (MAC), which will be used in step 6.
2.On a computer connected to the EtherNet/IP network, start the BOOTP software.
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |
29 |
Chapter 3 Configuring the Adapter
The BOOTP Server window appears.
3. Select Tools > Network Settings to display the Network Settings window.
To properly configure devices on your EtherNet/IP network, you must configure settings in the BOOTP software to match the network.
4. Edit the following:
Box |
Type |
|
|
Subnet Mask (1) |
The subnet mask for the adapter’s network. |
Gateway (1) |
The IP address of the gateway device on the adapter’s network. |
Primary DNS |
The address of the primary DNS server to be used on the local end of |
|
the link for negotiating with remote devices. |
|
|
Secondary DNS |
Optional — the address of the secondary DNS server to be used on the |
|
local end of the link for negotiating with remote devices when the primary |
|
DNS server is unavailable. |
|
|
Domain Name |
The text name corresponding to the numeric IP address that was |
|
assigned to the server that controls the network. |
|
|
(1)For definitions of these terms, refer to the .
5.Click OK to apply the settings.
Devices on the network issuing BOOTP requests appear in the BOOTP Request History list.
30 |
Rockwell Automation Publication 20COMM-UM015B-EN-P - July 2013 |