Rockwell Automation 294E User Manual

0 (0)
Rockwell Automation 294E User Manual

User Manual

ArmorStart® LT Distributed Motor Controller

Catalog Numbers 290E, 291E, 294E

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.

The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Rockwell Automation does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

General Precautions

In addition to the precautions listed throughout this manual, the following statements, which are general to the system, must be read and understood.

ATTENTION: This manual is intended for qualified service personnel responsible for setting up and servicing these devices. The user must have previous experience with and a basic understanding of electrical terminology, configuration procedures, required equipment, and safety precautions.

WARNING: The National Electrical Code (NEC), NFPA79, and any other governing regional or local code will overrule the information in this manual. Rockwell Automation cannot assume responsibility for the compliance or proper installation of the ArmorStart LT or associated equipment. A hazard of personal injury and/or equipment damage exists if codes are ignored during installation.

ATTENTION: The controller contains ESD (electrostatic discharge) sensitive parts and assemblies. Static control precautions are required when installing, testing, servicing, or repairing the assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, refer to Publication 8000-4.5.2, Guarding against Electrostatic Discharge, or any other applicable ESD protection handbooks.

ATTENTION: Only personnel familiar with the controller and associated machinery should plan or implement the installation, startup, and subsequent maintenance of the system. Failure to do this may result in personal injury and/or equipment damage.

Precautions for Bulletin 294E Applications

ATTENTION: Only qualified personnel familiar with adjustable frequency AC drives and associated machinery should plan or implement the installation, startup, and subsequent maintenance of the system. Failure to do this may result in personal injury and/or equipment damage.

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

3

Software Requirements

The table lists the versions of software that are required.

Software

Version

 

 

RSLinx Classic

2.56 or later

 

 

RSLogix 5000

17.01 or later

 

Download the most current version of the Add-On Profile from

 

http://www.rockwellautomation.com/support/downloads.html.

BOOTP/DHCP

Version 2.3 or later

 

 

Additional Resources

These documents and websites contain additional information concerning related Rockwell Automation products.

You can view or download publications at http:/www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative.

Table 1 - Rockwell Automation Industrial Network Resources

Resource

Description

 

 

http://ab.rockwellautomation.com/Networks-and-Communications

Rockwell Automation networks and communication website

 

 

http://ab.rockwellautomation.com/Networks-and-Communications/Ethernet-IP-

Rockwell Automation EtherNet/IP website

Network

 

 

 

http://www.rockwellautomation.com/services/networks/

Rockwell Automation network and security services websites

http://www.rockwellautomation.com/services/security/

 

 

 

http://www.ab.com/networks/architectures.html

Education series webcasts for IT and controls professionals

 

 

EtherNet/IP Embedded Switch Technology Application Guide, Publication ENET-AP005

Describes how to install, configure, and maintain linear and device-level Ring (DLR)

 

networks using Rockwell Automation EtherNet/IP devices with embedded switch

 

technology.

 

 

EtherNet/IP Network Configuration User Manual, Publication ENET-UM001

Describes how to configure and use EtherNet/IP communication modules with a

 

Logix5000 controller and communicate with various devices on the Ethernet network.

 

 

EtherNet Design Consideration, Publication ENET-RM002A-EN-P

Provides details on ethernet design and infrastructure.

 

 

EtherNet/IP Modules in Logix5000 Control Systems User Manual, Publication ENET-UM001

Provides details about how to configure your module.

 

 

EtherNet/IP Embedded Switch Technology Application Guide, Publication ENET-AP005

Provides information about using products with embedded switch technology to

 

construct networks with linear and ring topologies.

 

 

EtherNet/IP Industrial Protocol White Paper, Publication ENET-WP001

Describes how to implement services and data objects on a TCP/UDP/IP based Ethernet

 

network.

 

 

Industrial Automation Wiring and Grounding Guidelines, Publication 1770-4.1

Provides general guidelines for installing a Rockwell Automation industrial system.

 

 

Wiring and Grounding Guidelines, (PWM) AC Drives, Publication DRIVES-IN001

Describes wiring and grounding guidelines for Pulse Width Modulated (PWM) AC Drives

 

 

Product Certifications website,

Provides declarations of conformity, certificates, and other certification details.

http://www.rockwellautomation.com/products/certification/

 

 

 

4

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Table 2 - ODVA Resources

Resource

Description

 

 

http://www.odva.org/

Open DeviceNet Vendors Association (ODVA) website

 

 

http://www.odva.org/default.aspx?tabid=54

The CIP Advantage website

 

CIP features and benefits

 

How to get started

 

 

Ethernet Media Planning and Installation Manual, ODVA publication

Describes the required media components and how to plan for, install, verify,

http://www.odva.org/Portals/0/Library/Publications_Numbered/

troubleshoot, and certify an Ethernet network.

PUB00148R0_EtherNetIP_Media_Planning_and_Installation_Manual.pdf

 

 

 

Network Infrastructure for EtherNet/IP: Introduction and Considerations, ODVA publication

Provides an overview of the technologies used in EtherNet/IP networks and provides

http://www.odva.org/Portals/0/Library/Publications_Numbered/

guidelines for deploying infrastructure devices in EtherNet/IP networks.

PUB00035R0_Infrastructure_Guide.pdf

 

 

 

Table 3 - Product Selection Resources

Resource

Description

 

 

Industrial Controls catalog website,

Industrial Controls catalog website

http://www.ab.com/catalogs/

 

 

 

ArmorStart LT Distributed Motor Controller Selection Guide, Publication 290-SG001

Product selection guide

 

 

Table 4 - Cisco and Rockwell Automation Alliance Resources

Resource

Description

 

 

http://www.ab.com/networks/architectures.html

Rockwell Automation and Cisco Systems reference architecture website

 

 

Converged Plantwide Ethernet (CPwE) Design and Implementation Guide, Publication

Represents a collaborative development effort from Rockwell Automation and Cisco

ENET-TD001

Systems. The design guide is built on, and adds to, design guidelines from the Cisco

 

Ethernet-to-the-Factory (EttF) solution and the Rockwell Automation Integrated

 

Architecture. The design guide focuses on the manufacturing industry.

 

 

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

Installation Assistance

If you experience a problem within the first 24 hours of installation, contact Customer Support.

United States or Canada

1.440.646.3434

 

 

Outside United States or

Use the Worldwide Locator at http://www.rockwellautomation.com/support/

Canada

americas/phone_en.html, or contact your local Rockwell Automation representative.

 

 

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

5

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

United States

Contact your distributor. You must provide a Customer Support case number (call the

 

phone number above to obtain one) to your distributor to complete the return process.

 

 

Outside United States

Please contact your local Rockwell Automation representative for the return

 

procedure.

 

 

6

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Summary of Changes

New and Updated

Information

This table contains the changes made to this revision.

Topic

Page

 

 

Added source brake and IPS specifications

Various

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

7

Summary of Changes

Notes:

8

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Preface

European Communities (EC)

Directive Compliance

Low Voltage and EMC

Directives

If this product has the CE mark it is approved for installation within the European Union and European Economic Area (EEA). It has been designed and tested to meet the following directives.

This product is tested to meet the European Union (EU) Council 2006/95/EC Low Voltage Directive and the EU Council 2004/108/EC Electromagnetic Compatibility (EMC) Directive by applying the following standard(s):

Bulletin 290E_/291E_: EN 60947-4-1 — Low-voltage switchgear and controlgear — Part 4-1: Contactors and motor-starters — Electromechanical contactors and motor-starters.

Bulletin 294E_: EN 61800-3 — Adjustable speed electronic power drive systems — Part 3: EMC product standard including specific test methods EN 61800-5-1:2003 — Adjustable speed electrical power drive systems — Part 5-1: Safety requirements — Electrical, thermal and energy.

This product is intended for use in an industrial environment.

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

9

Preface

Introduction

The ArmorStart LT is an integrated, pre-engineered, motor starting solution designed for use in material handling applications. ArmorStart LT is the latest addition to the ArmorStart portfolio. ArmorStart LT is a leader in the market place given its compact size and high performance features in network, I/O, and motor control. This manual will guide you through the features and functionality when installing the product. Thank you for choosing ArmorStart LT for your distributed motor control needs. If you have any questions please refer to the “Support Section” for contact information.

10

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

 

Table of Contents

 

Important User Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2

 

General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 3

 

Software Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 4

 

Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 4

 

Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 5

 

Installation Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 5

 

New Product Satisfaction Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 6

 

Summary of Changes

 

 

New and Updated Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 7

 

Preface

 

 

European Communities (EC) Directive Compliance . . . . . . . . . . . . . . . . .

9

 

Low Voltage and EMC Directives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

 

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

10

 

Chapter 1

 

Product Overview

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

17

 

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

18

 

Feature Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

19

 

Standard Features Across Product Familly . . . . . . . . . . . . . . . . . . . . . .

19

 

Network Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

20

 

Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

22

 

ArmorStart LT Characteristics Bulletin 290E/291E . . . . . . . . . . . . . . . .

23

 

Catalog Number Explanation Bulletin 290E/291E. . . . . . . . . . . . . . . . . .

24

 

ArmorStart LT Characteristics Bulletin 294E . . . . . . . . . . . . . . . . . . . . . .

25

 

Catalog Number Explanation Bulletin 294E. . . . . . . . . . . . . . . . . . . . . . . . .

26

 

Basic Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

27

 

Group Motor Installations for USA and Canada Markets . . . . . . . . .

27

 

Control Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

27

 

Motor Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

29

 

Local I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

29

 

Overload Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

30

 

Mode of Operation Bulletin 290E/291E . . . . . . . . . . . . . . . . . . . . . . . . . . . .

30

 

Full-Voltage Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

30

 

Mode of Operation Bulletin 294E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

31

 

Sensorless Vector Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

31

 

Status LEDs and Reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

32

 

Electronic Data Sheet (EDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

33

 

Fault Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

34

 

Protection Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

34

 

Optional HOA Selector Keypad. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

35

 

Keypad Local Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

35

 

Optional HOA Keypad Configuration (Bulletin 290E/291E only). . . .

35

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

11

Table of Contents

 

 

 

Optional HOA Selector Keypad

 

 

with Jog Function(Bulletin 294E only). . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

37

 

Keypad Local Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

37

 

Keypad and HOA Disable Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . .

38

 

Source Brake Contactor and Connector (Bulletin 294E only). . . . . . . . .

38

 

Chapter 2

 

Installation and Wiring

Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

39

 

Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

39

 

Inspecting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

39

 

Storing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

39

 

Installation Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

40

 

Precautions for Bulletin 290E/291E Applications. . . . . . . . . . . . . . . . . . . .

40

 

Precautions for Bulletin 294E Applications. . . . . . . . . . . . . . . . . . . . . . . . . .

40

 

Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

40

 

Bulletin 290E/291E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

41

 

Bulletin 294E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

42

 

ArmorStart LT Gland Plate Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

43

 

Connection Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

43

 

Internal Power, Control, and Ground Locations . . . . . . . . . . . . . . . . .

43

 

Gland Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

44

 

Wiring Terminal Detail. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

45

 

Branch Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

46

 

Simple System Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

47

 

ArmorConnect Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

48

 

ArmorConnect Cable Ratings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

49

 

Branch Circuit Protection Requirements for ArmorConnect

 

 

Three-Phase Power Media. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

49

 

Electrical Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

50

 

Group Motor Installations for USA and Canada Markets . . . . . . . . . . . .

55

 

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

55

 

Cable Workmanship Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

55

 

Service Space . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

56

 

Hand Operation (HOA) Considerations. . . . . . . . . . . . . . . . . . . . . . . .

56

 

General Wiring Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

56

 

Grounding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

57

 

Grounding Safety Grounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

57

 

Grounding PE or Ground . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

57

 

Grounding Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

57

 

Power Distribution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

58

 

Delta/Wye with Grounded Wye Neutral . . . . . . . . . . . . . . . . . . . . . . . .

58

 

AC Line Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

58

 

Line Reactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

58

 

Bulletin 294E Motor Cable Considerations . . . . . . . . . . . . . . . . . . . . . . . . .

59

 

Unshielded Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

59

 

Shielded Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

60

 

Recommended Cable Connectors/Glands . . . . . . . . . . . . . . . . . . . . . . .

60

12

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Table of Contents

Product Commissioning

Bulletin 290E/291E/294E Programmable Parameters

Recommended Cord Grips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61

Shield Terminating Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61

Electromagnetic Compatibility (EMC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62

General Notes (Bulletin 294E only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62

Ethernet, DeviceNet, and I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . .63

ArmorConnect Power Media Receptacles . . . . . . . . . . . . . . . . . . . . . . . . . . .64

Optional Locking Clip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65

Chapter 3

IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67 Gateway Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67

Subnet Mask . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67

Configuring EtherNet/IP Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68 Manually Configure the Network Address Switches . . . . . . . . . . . . . .68

Static Address Alternative . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69 Using the Rockwell Automation BootP/DHCP Utility . . . . . . . . . . . . . .69 Save the Relation List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72

Embedded Web Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .74

Network Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75 Parameter Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76

E-mail Notification Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76

How to Add a New Module Using the Add-On Profile. . . . . . . . . . . . . . .78 Electronic Keying. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80

Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81

Configured By . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81 HOA Keypad Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82

Source Brake Electro-Mehanical Brake Option. . . . . . . . . . . . . . . . . . .82

User Configurable I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .82 RSLogix 5000 Add-On Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83

Auto-Generated Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85

Chapter 4

Electronic Data Sheet (EDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99

Basic Setup Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99

Parameter Groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100

ArmorStart LT EtherNet/IP Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . .102

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102

Parameter Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102

Bulletin 290E/291E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102

Basic Status Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102

Trip Status Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107

Basic Configuration Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .111

Starter Protection Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112

User I/O Configuration Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115

Miscellaneous Configuration Group . . . . . . . . . . . . . . . . . . . . . . . . . . .119

Advanced Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .121

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

13

Table of Contents

 

 

 

Bulletin 294E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

124

 

Basic Status Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

124

 

Trip Status Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

129

 

Motor and Control Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

133

 

Speed Control Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

135

 

Starter Protection Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

138

 

User I/O Configuration Group. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

140

 

Miscellaneous Configuration Group . . . . . . . . . . . . . . . . . . . . . . . . . . .

145

 

Advanced Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

146

 

Chapter 5

 

Diagnostics

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

157

 

Status LEDs and Reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

157

 

Fault Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

158

 

Protection Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

158

 

Quick Reference Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

160

 

Fault LED Indications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

161

 

Bulletin 290E/291E Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

161

 

Bulletin 294E Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

163

 

Chapter 6

 

Specifications

Bulletin 290E/291E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

165

 

Motor Overload Trip Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

170

 

Bulletin 100-K/104-K Life-Load Curves . . . . . . . . . . . . . . . . . . . . . . . . . . .

171

 

Bulletin 294E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

172

 

Motor Overload Trip Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

178

Appplying More Than One ArmorStart LT Motor Controller in a Single Branch Circuit

on Industrial Machinery

Appendix A

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .179 ArmorStart LT Product Family . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .180

Multiple-Motor Branch Circuits and Motor Controllers Listed

for Grooup Installation – General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .181 Maximum Fuse Ampere Rating According to 7.2.10.4(1)

and 7.2.10.4(2). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183

Complete Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .183

Explanatory Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .185 Input and Output Conductors of Bulletin 290E and 291E

Controllers (a) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .191

Input and Output Conductors of Bulletin 294E Controllers (b) . . . . .191 Combined Load Conductors (c). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .191

 

Appendix B

 

CIP Information

High Level Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

193

 

Product Code and Name Strings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

193

 

CIP Explicit Connection Behavior. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

194

14

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Table of Contents

EDS Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .194

CIP Object Requirements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .194

Identity Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .195

CLASS CODE 0x0001 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .195

Message Router . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .196

CLASS CODE 0x0002 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .196

Assembly Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .196

CLASS CODE 0x0004 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .196

I/O Assemblies. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .197

Connection Manager Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .203

CLASS CODE 0x0006 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .203

Class 1 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .204

Class 3 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .205

Discrete Input Point Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206

CLASS CODE 0x0008 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206

Discrete Output Point Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206

CLASS CODE 0x0009 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .206

Discrete Output Point Object Special Requirements . . . . . . . . . . . .207

Analog Input Point Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .211

CLASS CODE 0x000A. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .211

Analog Output Point Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .211

CLASS CODE 0x000B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .211

Parameter Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .212

CLASS CODE 0x000F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .212

Parameter Group Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .213

CLASS CODE 0x0010 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .213

Discrete Input Group Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214

CLASS CODE 0x001D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214

Discrete Output Group Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214

CLASS CODE 0x001E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .214

Control Supervisor Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .215

CLASS CODE 0x0029 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .215

Overload Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .216

CLASS CODE 0x002C. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .216

Device Level Ring (DLR) Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .217

CLASS CODE 0x0047 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .217

Extended Device Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .217

CLASS CODE 0x0064 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .217

DPI Fault Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .218

CLASS CODE 0x0097 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .218

DPI Alarm Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .222

CLASS CODE 0x0098 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .222

TCP/IP Interface Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .223

CLASS CODE 0x00F5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .223

Ethernet Link Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .224

CLASS CODE 0x00F6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .224

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

15

Table of Contents

 

 

 

Trip and Warning Email Object . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . .226

 

CLASS CODE 0x0376 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . .226

 

Appendix C

 

Using DeviceLogix

Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . .229

 

DeviceLogix Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . .230

 

DeviceLogix Programming Example. . . . . . . . . . . . . . . . . . . . .

. . . . . . .230

 

ArmorStart LT 294E Example Configuration. . . . . . . . . . . .

. . . . . . .236

 

Download the AOP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . .237

 

Use of the AOP Profile in RSLogix . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . .242

Support and Feedback

Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Back Cover

 

Installation Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Back Cover

 

New Product Satisfaction Return . . . . . . . . . . . . . . . . . . . . . . . . . .

Back Cover

 

Documentation Feedback. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Back Cover

 

Trademark List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Back Cover

16

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Chapter 1

Product Overview

Description

ArmorStart LT is available with Full Voltage, Full Voltage Reversing, or Variable Speed motor control performance. It comes equipped with a UL Listed At-motor disconnect that supports a lock-out tag-out (LOTO) provision. ArmorStart LT is listed as suitable for group installations per UL and can be applied with either branch circuit breaker protection or fuse protection. It provides a robust IP66/ UL Type 4/12 enclosure suitable for water washdown environments in a single box construction that will minimize inventory needs. All external connections are made from the bottom of the unit minimizing accidental contact by moving equipment. ArmorStart LT as a standard will come with quick disconnect receptacles for the I/O and network connections. And finally, ArmorStart LT will include DeviceLogix, a high-performing local logic engine when a fast I/O response is critical to the application.

ArmorStart LT leverages the capabilities of the Rockwell Automation® Integrated Architecture so you can achieve an unmatched level of integration and ease

of use. The architecture of ArmorStart LT allows Premiere Integration with Allen-Bradley® ControlLogix® or CompactLogix™ line of Automation Controllers and PLCs. RSLogix™ 5000 is the only programming tool needed which consolidates controller programming, device configuration, and maintenance into a single, integrated environment. ArmorStart LT includes tools such as an Add-on Profile that will automatically generate PLC tag names for quick and efficient configuration and programming.

The ArmorStart LT is available with options that can further reduce installation and commissioning time and cost, such as:

Quick disconnect receptacles for power, control, and motor connections

Local Hand-Off-Auto keypad for manual control

Internal power supply (IPS) eliminating the need to run additional control power to each unit

Bulletin 294 can be ordered with an electromechanical brake connection (source brake)

EDS Tag Generator tool with RS Logix 5000

The G2 gland option is rated IP66/ UL Type 4

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

17

Chapter 1 Product Overview

Features

The ArmorStart LT provides many features and benefits that are unsurpassed in the market place:

Robust IP66, UL Type 4/12 enclosure

UL Listed, Suitable for Group Motor Applications

UL Listed, At-motor disconnect switch

Native support for EtherNet/IP

Embedded dual port ethernet switch

Device Level Ring (DLR) with Beacon frame performance

IEEE 1588 Transparent Clock

RSLogix 5000 Add-On Profile

6 user configurable I/O points

DeviceLogix

Embedded web server support

Configurable e-mail response for fault or alarm events

Optional internal power supply

Optional electromechanical brake contactor

Optional local control via Hand-Off-Auto keypad

Optional quick disconnect for power and motor connections

IMPORTANT Not all options are available for Bulletin 290E/291E/294E. Refer to the catalog configurator for details.

18

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Product Overview Chapter 1

Feature Description

Standard Features Across Product Family

 

UL Listed “Suitable for Group Motor Applications” — Where NFPA 70

 

(NEC) or 79 are required installation standards, this Listing allows two or more

 

motors to be connected to the same branch circuit without individual motor

 

branch short circuit or ground fault protection. Refer to Appendix A for details.

 

At-motor disconnect switch — ArmorStart LT offers a local ON/OFF motor

 

disconnecting means with lockout-tagout provision. Industrial standards require

 

a local at-motor disconnect to be within eye sight of the motor for maintenance

 

or other shutdown reasons. Refer to your installation code for details.

 

User configurable I/O — ArmorStart LT offers 6 user configurable I/O points

 

to be used with sensors and actuators. By default all 6 points are configured as

 

sinking 24V DC inputs. The user has the option to select any point as a sourcing

 

24V DC output.

 

RSLogix 5000 Add-On Profile (AOP) — ArmorStart LT offers for

 

Allen-Bradley ControlLogix or CompactLogix PLCs a downloadable Add-On

 

Profile. The AOP simplifies setup and commissioning via predefined tags and

 

commissioning wizards. The AOP also allows copy and paste functionality for

 

quick setup and configuration of multiple ArmorStart LTs.

 

 

 

IMPORTANT AOP support for EtherNet/IP network only and requires RSLogix 5000

 

revision 17.01 or later. There is a known compatibility issue with revision 20.0.

 

Update RSLogix 5000 to 20.1 or greater.

 

 

 

DeviceLogix — ArmorStart LT offers local programmable logic via

 

DeviceLogix. DeviceLogix is a stand-alone program that resides within the

 

ArmorStart LT. It is programmed locally using the Add-On-Profile and

 

implements operations such as, AND, OR, NOT, Timers, Counters, Latches,

 

and Analog operations. DeviceLogix can run as a stand-alone application,

 

independent of the network or collaboratively with the PLC. However,

 

unswitched control power must be maintained for DeviceLogix to operate.

 

Quick disconnect for I/O and network — ArmorStart LT offers quick

 

disconnect connectors for I/O and communications.

 

EtherNet/IP node address — ArmorStart LT offers external accessible address

 

switches for device node address configuration. The address can be set statically

 

or dynamically.

 

EMI filter — ArmorStart LT for VFD application (Bulletin 294) provides an

 

internal EMI filter and is CE compliant. For CE compliant installations refer to

 

the recommended EMI/RFI cord grip accessory. For availability of the quick

 

disconnect shielded motor cable contact your local sales representative for

 

details.

 

Local and remote status and diagnostics — ArmorStart LT offers

 

comprehensive status and diagnostics for I/O, Network, and device health via 12

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

19

Chapter 1 Product Overview

Network Options

LEDs found on the electronic control module (ECM). If a fault occurs a local fault reset button allows the user to quickly get the process started after corrective action is taken. The user can also configure the embedded webserver to send an e- mail when a fault or warning occurs.

Gland plate entrance — ArmorStart LT offers different methods of connecting three-phase, control power, and motor. ArmorStart LT has conduit entrance openings, as standard.

Native EtherNet/IP — ArmorStart LT supports native EtherNet/IP without additional modules or adapters. EtherNet/IP allows complete integration of control with information across multiple Common Industrial Protocol (CIP™) networks. EtherNet/IP allows users to integrate I/O control, device configuration, and data collection across multiple networks enabling internet connectivity and information.

Embedded dual port switch — ArmorStart LT EtherNet/IP version includes a dual port 10/100 mb/s ethernet switch that supports linear or Device Level Ring (DLR) topology.

Figure 1 - Linear Topology

Device Level Ring (DLR) - ArmorStart LT EtherNet/IP version offers DLR support with beacon frame performance. DLR provides a single fault tolerant network solution for EtherNet/IP.

Figure 2 - DLR with Beacon Performance — No Fault

20

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Product Overview

Chapter 1

 

 

Figure 3 - DLR with Beacon Performance — Fault

In this example the fault is precisely identified by the link status message and the supervisor opens the blocked port to allow network traffic to continue normally.

IEEE 1588 transparent clock —ArmorStart LT EtherNet/IP version supports the IEEE 1588 transparent clock when used with precision time protocols (PTP). A transparent clock measures and adjusts for packet delays, therefore removing the negative effects that these variations can cause within a synchronized distributed network of devices.

Embedded web server — ArmorStart LT EtherNet/IP version offers a web server that can be accessed via a standard internet browser. The web server provides status, diagnostics, and configuration capabilities.

E-mail notification — ArmorStart LT via the embedded web server, supports configuration of the Simple Mail Transfer Protocol (SMTP). Once properly configured, the motor controller will e-mail the user with specific fault/trip messages.

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

21

Chapter 1 Product Overview

Factory-Installed Options

Internal power supply (IPS) — ArmorStart LT offers the user an optional

 

24V DC internal power supply. The internal power supply provides all control

 

and I/O power needs and is sourced from the incoming 3-phase power. This

 

eliminates the need to run separate control power to each unit, reducing

 

installation time and cost. The local at-motor disconnect will remove power

 

from the motor terminals and outputs when in the OFF condition.

 

Hand/Off/Auto (HOA) keypad — ArmorStart LT offers an optional local

 

Hand-Off-Auto keypad. This key pad allows local start/stop motor control

 

regardless of PLC status. This option can be used for troubleshooting or

 

maintenance operations. The HOA can also be disabled when local control

 

is not allowed, using parameter 67.

 

Source brake — ArmorStart LT provides an optional, internally-controlled

 

electromechanical motor brake contactor. The motor brake power is sourced

 

from 3-phase power, L1 and L2.

 

Quick disconnect gland — ArmorStart LT offers a plug -n- play solution that

 

simplifies wiring and installation. These factory installed quick disconnect

 

receptacles provide connectivity to ArmorConnect® media for three-phase,

 

control, and motor connections. The cables are ordered separately.

22

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Product Overview

Chapter 1

 

 

ArmorStart LT Characteristics

Figure 4 - Bulletin 290E/291E ArmorStart LT

0 Off

1 On

On/Off Switch

LockOut/TagOut Provision

Wiring Access

Gland Plate – Conduit/Cord Grip or

ArmorConnect® Media (optional)

HOA Keypad (optional)

IP Address Switches

Status and Diagnostic LEDs

Reset

ECM (Electronic

Control Module)

6 Configurable I/Os

Dual Port EtherNet/IP

(This is replaced by a DeviceNet connector, when DeviceNet communication is selected)

Protective Earth (PE)

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

23

Chapter 1 Product Overview

Catalog Number Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a

valid catalog number.

290 E - F A Z - G1 - Option 1 - Option 2

— — — — — —— ——

a

b

c

d

e

f

g

h

a

Bulletin Number

Code

Description

290Full-Voltage Starter

291Reversing Starter

b

Communications

Code

Description

EEtherNet/IP

DDeviceNet

 

c

 

Enclosure Type

 

 

Code

Description

FUL Type 4/12

 

d

 

Overload Selection

 

 

Code

Description

A0.25…3.5 A

B1.1…7.6 A

e

Control Voltage

Code

Description

ZExternal 24V DC control power

PInternal power supply

 

f

 

Gland Plate Options

 

(Power and Motor)

 

 

Code

Description

G1

Conduit entry

G2

ArmorConnect

G3

Gland Kits

 

 

 

g

 

Option 1

 

 

Code

Description

3Hand/Off/Auto selector keypad

3FR

Hand/Off/Auto selector keypad with

 

Forward/Reverse

 

h

 

Option 2

 

 

Code

Description

blank

No option

 

 

 

 

IP66/UL Type 4 is available with all gland options. UL Type 4/12 is available with G1 and G3 gland option.See selection guide 290-SG001_-EN-P Accessories section for gland configurations and ordering.

Leave blank unless there is a customer-specific option defined by the factory.

24

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Product Overview

Chapter 1

 

 

ArmorStart LT Characteristics

Figure 5 - Bulletin 294E ArmorStart LT

0

Off

1 On

On/Off Switch

Wiring Access

LockOut/TagOut Provision

Gland Plate – Conduit/Cord Grip or

ArmorConnect Media (optional)

Hand-Off-Auto

Keypad (optional)

Reset

IP Address Switches

Status and Diagnostic LEDs

ECM (Electronic Control Module)

6 Configurable I/Os

Protective Earth (PE)

 

Dual Port EtherNet/IP

 

 

 

Bottom View

(This is replaced by a DeviceNet connector,

 

when DeviceNet communication is selected)

 

 

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

25

Chapter 1 Product Overview

Catalog Number Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations will produce a

valid catalog number.

294

E

- F

D1P5

Z

- G1

- Option 1

- Option 2

——

——

a

b

c

d

e

f

g

h

 

a

 

Bulletin Number

 

 

Code

Description

294

VFD Starter

 

 

b

Communications

Code

Description

EEtherNet/IP

DDeviceNet

 

c

 

Enclosure Type

 

 

Code

Description

FUL Type 4/12

 

d

 

Output Current

 

 

Code

Description

D1P5

1.5 A (0.4 kW), 0.5 Hp

D2P5

2.5 A (0.75 kW), 1.0Hp

D4P2

3.6 A (1.5 kW), 2.0Hp

 

 

e

Control Voltage

Code

Description

ZExternal 24V DC control power

PInternal power supply

 

f

 

Gland Plate Options

 

(Power and Motor)

 

 

Code

Description

G1

Conduit entry

G2

ArmorConnect

G3

Gland kits

 

 

 

g

 

Option 1

 

 

Code

Description

3Hand/Off/Auto selector keypad with Jog

function

 

h

 

Option 2

 

 

Code

Description

SB

Source Brake

blank

No option

 

 

 

 

IP66/UL Type 4 is available with all gland options. UL Type 4/12 is available with G1 and G3 gland option.See selection guide 290-SG001_-EN-P Accessories section for gland configurations and ordering.

Leave blank unless there is a customer-specific option defined by the factory.

26

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Product Overview

Chapter 1

 

 

Basic Operation

Group Motor Installations for USA and Canada Markets

The ArmorStart LT Distributed Motor controllers are listed for use with each other in group installations per NFPA 79, Electrical Standard for Industrial Machinery and NFPA 70, the National Electrical Code. When applied according to the group motor installation requirements, two or more motors are permitted on a single branch circuit. Group Motor Installation has been successfully used for many years in the USA and Canada.

Note: For additional information regarding group motor installations with the

ArmorStart LT Distributed Motor Controller, see Appendix A.

Control Circuit

ArmorStart LT accepts a 24V DC Class 2 input power supply for switched and unswitched power. The control voltage provides power to the inputs (unswitched) and outputs (switched). Unswitched control voltage is used to ensure no loss of network connectivity, sensor, or other field input status under normal operation. The control power terminal connections are labeled A1, A2, and A3. Switched power is identified as (+A1) (-A2). Unswitched power is identified as (+A3) (-A2).

As an option, ArmorStart LT can be supplied with an internal power supply (IPS) eliminating the need for an external control power. The IPS is sourced from the line side of 3-phase power and is not impacted by the status of the local at-motor disconnect switch.

Figure 6 - Control Circuit Wiring Diagram — Single External Power Supply

L1

L2

L3

 

 

 

 

ArmorStart LT

 

 

 

 

 

Off

 

 

Switched Control Power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unswitched Control Power

 

 

 

Disconnect

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EtherNet

Inputs

Outputs

Motor

 

 

 

 

Comms

Control

 

Motor

 

 

 

 

 

 

 

 

 

 

 

Controller

 

A3

 

 

 

 

 

A1

A2

 

 

 

T1

T2

T3

 

 

 

 

 

 

 

 

 

* Control power output is determined by disconnect status

 

L

+

 

 

 

 

 

 

24VDC

-

 

 

 

 

 

 

N

 

 

 

 

 

 

Class 2

 

 

 

 

 

 

 

External

 

 

 

 

 

 

 

24VDC Power

 

 

 

 

 

 

Supply

 

 

 

 

 

 

 

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

27

Chapter 1 Product Overview

Figure 7 - Control Circuit Wiring Diagram — Multiple External Power Supplies

 

 

 

 

 

 

 

ArmorStart LT

 

L1

L2

L3

Switched Control Power

 

 

 

 

Off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unswitched Control Power

 

 

 

 

Disconnect

 

*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EtherNet

Inputs

Outputs

Motor

 

 

 

 

 

Comms

Control

 

 

Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

Controller

 

A3

 

 

 

 

 

 

A1

A2

 

 

 

 

T1

T2

T3

 

 

 

 

 

 

 

 

 

 

* Control power output is determined by disconnect status

 

Class 2

L

+

 

 

 

 

 

 

External Switched

24VDC

 

 

 

 

 

 

 

24VDC Power Supply

-

 

 

 

 

 

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

Class 2

L

+

 

24VDC

External Unswitched

 

N

-

24VDC Power Supply

Figure 8 - Control Circuit Wiring Diagram — Internal Power Supply (optional)

L1

L2

L3

Off

 

 

Disconnect

Motor

Controller

T1 T2 T3

ArmorStart LT

Internal Power

Supply

*

*

EtherNet

Inputs

Outputs

Motor

Comms

Control

 

 

* Control power output is determined by disconnect status

28

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Product Overview

Chapter 1

 

 

Motor Circuit

The ArmorStart LT Distributed Motor Controllers are rated to operate the following types of three-phase squirrel-cage induction motors:

Bulletin 290E/291E:

0.5 Hp (0.37 kW) to 5 Hp (3 kW) @ 480/277V AC Bulletin 294E:

0.5 Hp (0.37 kW) to 2 Hp (1.5 kW) @ 480/277V AC

Local I/O

The ArmorStart LT provides as standard, 6 user configurable I/O points. By default, all points are configured as an Input. When not using the AOP, the user will need to refer to parameter 49 [IOPointConfiguration], to define an output point.

When using the AOP, the I/O point is configured from the General screen

in the Module Definition section by clicking the “Change” button, see Figure 9. This allows user to view and configure the I/O mix, refer to Figure 10.

Figure 9 - Defining I/O Point

Figure 10 - Current I/O Point Configuration

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

29

Chapter 1 Product Overview

Overload Protection

The ArmorStart LT Distributed Motor Controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished

electronically with an I2t algorithm. The ArmorStart LT’s overload protection is programmable via the communication network, providing the user with greater flexibility.

The Bulletin 290E/291E includes programmable overload Class 10, 15, and 20 protection. The Bulletin 294E provides overload protection: 150% for 60s and 200% for 3s.

Refer to Chapter 6, Specifications, for additional information.

Mode of Operation

Full-Voltage Start

Bulletin 290E/291E

This method is used in applications requiring across-the-line starting, in which

 

 

full inrush current and locked-rotor torque are realized. The ArmorStart LT

 

Bulletin 290E offers full-voltage starting and Bulletin 291E offers full-voltage

 

starting for reversing applications, from 0.5 Hp (0.37 kW) to 5 Hp (3 kW) at

 

480Y/277V AC, 3-phase power.

 

Figure 11 - Full-Voltage Start

 

100%

 

 

 

 

 

 

 

 

 

 

 

 

Percent

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

 

Time (seconds)

30

Rockwell Automation Publication 290E-UM001B-EN-P - June 2012

Loading...
+ 222 hidden pages