Devices are Open Type, Listed Process Control Equipment and must be mounted in an enclosure. More than one disconnect switch may be required to de-energize the equipment before servicing. Signal inputs are SELV, limited energy. Caution - To reduce risk of fire or Electrical shock, Do not interconnect the outputs of different Class 2 circuits.
Temperature/ Process Controller
Model 900-TC16
English 41063-227-01 (3) Printed In China
For detailed operating instructions, please refer to the 900-TC16 User's Manual (900-UM007A-EN-E). It can be found online at http://www.ab.com/manuals/.
Significance of CAUTIONS
Indicates information that, if not heeded, could result in injury, damage to the product, or faulty operation.
ATTENTION
Installation
Dimensions
Dimensions (mm)
48
ALM1
ALM2
ALM3
HA
OUT1 STOP
MANU
OUT2 CMW
*
The main unit can be removed for maintenance without disconnecting the terminal wiring.
Do not remove the terminal block from the controller case. Doing so may result in failure or malfunction.
Names of parts on front panel
• Level key Use this key to change groups:
• Press the ˴ key and the key together for at least 3 seconds to switch to protect group .
• Mode key Press this key to change the contents of the display. Press this button for 1 s or longer for reverse scroll.
6
1.5
PV
SV
58
Watertight
packing
78 91
CN1
Adapter
1618387-8C
Terminal
cover
ALM1
ALM2
ALM3
HA
OUT1 STOP
OUT2 CMW
Disconect power to device before installing or servicing. Do not touch the terminals of controller when voltage is applied. Do not allow metal fragments or lead wire scraps to fall inside this product. This may cause electric shock, fire or malfunction. Do not use this product where subject to flammable or explosive gas. Never disassemble, repair or modify the product. The life expectancy of the output relays varies greatly with the switching capacity and other switching conditions. Always use the output relays within their rated load and electrical life expectancy. If an output relay is used beyond its life expectancy, its contacts may become fused or burned. Use copper wire only 24-14 AWG stranded or solid. Torque screws to 0.74 to 0.90 Nm or 6.5 to 8 lb-in. Only two wires of same type and size per terminal. Correctly set the temperature controller settings to match the control target. If the settings are not compatible with the control target, the product may operate in an unexpected manner, resulting in damage to the product or an accident. To maintain safety in the event of malfunction of the temperature controller, we recommend taking safety measures, for example, installing an excessive temperature rise prevention alarm on a separate line. If malfunction prevents control, they may result in an accident. To reduce the risk of electrical shock or fire, install in a Pollution Degree 2 environment (controlled environment relatively free of contaminants).
When the product is used under the circumstances or environment below, ensure adherence to limitations of the ratings and functions. Also, take countermeasures for safety precautions such as fail­safe installations.
*±±Use under circumstances or environment which are not described in the instruction manual.
*±Use for applications where death or serious property damage is possible and extensive safety
precautions are required.
In the pack:
• Main unit
• Watertight packing
• Adapter
• Instruction manual
• Terminal cover
1
6
11
2
7
12
3
8
48.8
44.8
13
4
9
14
5
10
15
Solderless terminal size: M3.5
• No.1 display Process value or set data symbol
PV
• No.2 display Set point, set data read-out value or changed input value
MANU
SV
• Up and Down keys Use the keys to change the values displayed on the No.2 display. Each press of key increments or advances the values displayed on the No.2 display. Each press of key decrements or returns the values displayed on the No.2 display.
Operation menu
Input type
Input type
Input
Setting
Platinum resistance thermometer
Thermocouple
Temperature input type
Infrared
Thermosensor
Analog input
• The default is “5” (shaded). will be display when a platinum resistance thermometer is mistakenly connected while input
type is not set for it. To clear the display, correct the wiring and cycle the power supply.
Input type
Current input
Voltage input
Analog
input type
• The default is “0” (shaded).
Alarms
Setting
0
No alarm function
1
Deviation upper/lower limit
1
*
Deviation upper limit
2
3
Deviation lower limit
4
Deviation upper/lower range
1
*
Deviation upper/lower limit
5
1
*
standby sequence ON
Deviation upper limit
6
standby sequence ON
Deviation lower limit
7
standby sequence ON
8
Absolute value upper limit
9
Absolute value lower limit
Absolute value upper limit
10
standby sequence ON
Absolute value lower limit
11
standby sequence ON
12
LBA (only for alarm 1)
1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for
*
different types of alarm. These are indicated by the letter "L" and "H".
• Default = "2" (shaded)
Error display (trouble shooting)
When an error has occurred, the No.1 display shows the error code. Take necessary action according to the error code, referring the table below.
No.1 display
(S. Err)
A/D converter error
(E111)
Internal circuit error
(H. Err)
If the input value exceeds the display limit (–1999 to 9999), though it is within the control range, [[[[ will be displayed under –1999 and above 9999. Under these conditions, control output and alarm output will operate normally. Refer to "900-TC User's Manual" for details of control range.
2: Error shown only for"Process value / Set point". Not shown for other status.
*
0 1
Pt100
2 3
JPt100
4 5
K
6 7
J
8 9
T
10 11
E
12
L
13
U
14 15
N
16
R
17
S
18
B
19
10 - 70°C
20
60 - 120°C
21
115 - 165°C
22
140 - 260°C
23
0 - 50mV
Input
Setting
0
4 - 20mA
1
0 - 20mA
2
1 - 5V
3
0 - 5V
4
0 - 10V
Alarm type
Meaning
Check the wiring of inputs, disconnections, shorts
Input error
and input type.
2
*
After the correction of input error, turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise
2
*
affecting the control system. Check for external noise.
Memory error
Turn the power OFF then back ON again. If the display remains the same, the controller must be repaired. If the display is restored to normal, then a probable cause can be external noise affecting the control system. Check for external noise.
2
*
Setting range
Setting range
Alarm output function
Positive alarm value (X)
Output off
LH
ON OFF
SP
X
ON OFF
SP
X
ON OFF
SP
LH ON OFF
SP
LH ON
OFF
SP
X
ON OFF
SP
X ON
OFF
SP
X
ON OFF
0
X
ON OFF
0
X
ON OFF
0
X
ON OFF
0
Action
/ -300 to 1500 (°F) / -199.9 to 900.0 (°F) / 0.0 to 210.0 (°F) / -199.9 to 900.0 (°F) / 0.0 to 210.0 (°F) / -300 to 2300 (°F) / 0.0 to 900.0 (°F) / -100 to 1500 (°F) / 0.0 to 750.0 (°F) / -300 to 700 (°F) / -199.9 to 700.0 (°F) / 0 to 1100 (°F) / -100 to 1500 (°F) / -300 to 700 (°F) / -199.9 to 700.0 (°F) / -300 to 2300 (°F) / 0 to 3000 (°F) / 0 to 3000 (°F) / 300 to 3200 (°F) / 0 to 190 (°F) / 0 to 240 (°F) / 0 to 320 (°F) / 0 to 500 (°F)
Negative alarm value (X)
Vary with "L", "H" values
ON OFF
ON OFF
Vary with "L", "H" values
Vary with "L", "H" values
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
ON OFF
Status at error
Control
output
OFF
OFF
OFF
OFF
–200 to 850 (°C) –199.9 to 500.0 (°C)
0.0 to 100.0 (°C) –199.9 to 500.0 (°C)
0.0 to 100.0 (°C) –200 to 1300 (°C) –20.0 to 500.0 (°C) –100 to 850 (°C) –20.0 to 400.0 (°C) –200 to 400 (°C) –199.9 to 400.0 (°C) 0 to 600 (°C) –100 to 850 (°C) –200 to 400 (°C) –199.9 to 400.0 (°C) –200 to 1300 (°C) 0 to 1700 (°C) 0 to 1700 (°C) 100 to 1800 (°C) 0 to 90 (°C) 0 to 120 (°C) 0 to 165 (°C)
0 to 260 (°C) Use the following ranges for scaling: –1999 to 9999, –199.9 to 999.9, Vary Depending on "L", "H" value
Use the following ranges for scaling: –1999 to 9999, –199.9 to 999.9, –19.99 to 99.99, –1.999 to 9.999
٨Initial setting group
6
*
6
*
6
*
6
*
6
X
X
*
SP
X
SP
SP
SP
X
X
X
X
6
*
6
*
X
0
6
*
0
0
6
*
0
6
*
6
*
6
*
Alarm
Operates
as above the
6
*
upper limit.
OFF
Initial setting group enables users to specify their prefer­red operating conditions (input type, alarm type, control method, etc.)
OFF
3: Refer to the adjoining tables for details of input types and alarm types.
*
4: Applicable only to models with alarm functions.
*
5: Operation is stopped when moved to the initial setting group.
*
(control/alarm are both stopped.)
OFF
Other functions
In addition to the aforementioned, there are alarm hysteresis, automatic return of display mode and others in the advanced setting group. Refer to "900-TC16 User's Manual" for details. For communications details, please refer to "900-TC communications User's Manual".
ATTENTION
(1) ±Do not use this product in the following:
* Places directly subject to heat radiated from heating equipment. * Places subject to splashing liquid or oil atmosphere (exceeds NEMA 4X). * Places subject to direct sunlight, could discolor or cause excessive heat. * Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas). * Places where intense temperature changes exceed the published ratings. *±Places subject to icing and condensation. * Places subject to vibration and large shocks.
(2) ±Use/store within the rated temperature and humidity ranges.
Provide forced-cooling if required.
(3) ±To allow heat to escape, do not block the area around the product. ±±±±±±Do not block the ventilation holes on the product. (4) ±Be sure to wire properly with correct polarity of terminals. (5) ±Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. (6) ±Do not wire the terminals which are not used. (7)±±Allow as much space as possible between the controller and devices that generate a powerful
high-frequency or surge.
Separate the high-voltage or large-current power lines from other lines, and avoid parallel or
common wiring with the power lines when you are wiring to the terminals. (8) ±Use this product within the rated load and power supply. (9) ±Make sure that the rated voltage is attained within two seconds of turning the power ON. (10) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON
before you turn the controller ON. (11) A switch or circuit breaker should be provided close to this unit.
The switch or circuit breaker should be within easy reach of the operator, and must be marked as
a disconnecting means for this unit. (12) If you remove the controller from its case, or put the controller into its case, never touch nor
apply shock to the terminals and the electronic parts inside.
Make sure the electronic components and the case are not contacted when inserting the internal
mechanism. Always ensure power is OFF when doing any maintenance on the controller or
associated circuits. (13) Cleaning: Do not use paint thinner or the equivalent. Use standard grade alcohol to clean the
outside of the product. (14)±Consider the 2 second delay required for the controller outputs to respond when you design your
control system. (15)±If an option unit is used in the system refer to its Installation Manual before operating.
Mounting
Individual mounting (mm)
60 min.
• Insert the controller through the hole in the panel. Push the adapter on from the rear and fasten temporarily, removing any gap between the controller, panel and adapter. Finally, secure two mounting screws alternately keeping the torque to between 0.29 to 0.39 N•m.
• Make sure that the surrounding temperature does not exceed the allowable operating temperature given in the specifications especially when two or more controllers are mounted.
Operation stopped.(control/alarm are both stopped.)
Input type *3
Scaling upper limit (only when setting analog input)
Scaling lower limit (only when setting analog input)
Decimal point (only when setting analog input)
°C=
°C/ °F selection
°F=
(C stands for Celsius, F for Fahrenheit)
sl-h
Set point upper limit
1300
sl-l
Set point lower limit
-200
In ON/OFF control =
cntl
In 2-PID control =
onof
Standard control =
s-hc
Heating and cooling control =
stnd
(Select standard control or heating and cooling control as required)
Self-tuning ON =
st
Self-tuning OFF =
on
Program pattern
Control period (heat) (Unit: Seconds)
Control period (cool) (Unit: Seconds)
In Reverse operation(heat) = In Direct operation(cool) =
Alarm 1 type: Specified models only
Alarm 2 type: Specified models only
Transfer output type
Transfer output upper limit
Transfer output lower limit
Linear output type
Side-by-side mounting (waterproof not possible) (mm)
(48 x number of units -2.5)
+.06
45
˴0
When waterproofing is required, be sure to mount the controller separately.
+.06
Attach the waterproof packing from the terminal
˴0
45
side and then insert the controller to the panel. Recommended panel thickness is 1 to 5 mm.
Operation indicators
• ALM1: Alarm 1 indicator Lit when alarm 1 is ON.
• ALM2: Alarm 2 indicator Lit when alarm 2 is ON.
• ALM3: Alarm 3 indicator Lit when alarm 3 is ON.
• HA: Heater burnout alarm/Heater Short alarm indicator
Lit when a heater burnout or Heater Short alarm has occurred.
• OUT1: Control output 1 indicator Lit when control output 1 is ON and not lit when it's OFF. For a current output, lit for greater than a 0% output.
Hold down
for at least 3 seconds
(No. 1 display flushes then the control stops)
Hold down
for at least
1 second
Hold and keys
down for at least 1 second
*3 *4
*3 *4
+1
0
+.06
˴0
45
The setting data for the 900-TC-8 is shown here as an example.
*5
Operation group
sp-m
6
*
prst
6
*
rset
sktr
6
*
r-s
6
*
run
al-1
6
*
al1h
6
*
al1l
6
*
al-2
6
*
al2h
6
*
al2l
6
*
Operation group should normally be used during operations.
Protect group
oapt
Restricts which parameters can be displayed or changed, and restricts change by key operation.
AT (auto-tuning)
• AT in Adjustment group Designate " : AT execute" to execute AT and " : AT cancel" to cancel AT.
“AT execute”
“AT cancel”
Also when AT execution ends, the display automatically returns to “ ”.
NOTICE
Connections
Control output 1
Relay output
•±
±250V 3A ±(resistive load)
•±Voltage output
±12V 21mA
•±Current output
±DC4-20mA ±DC0-20mA
· Since the voltage output (control output 1) is not electrically insulated from the internal wiring, one or other of the control output
terminals must be left unearthed when using an earthed (grounding) type thermocouple. (Connection makes measurements unreliable due to ground loop currents.) Basic insulation is provided between the voltage outputs (control output 2) and internal circuits.
· Basic insulation is provided between power supply, input, output and communications (for applicable models). If double insulation is required provide supplemental insulation as defined by IEC60664.
• OUT2: Control output 2 indicator Lit when control output 2 is ON and not lit when it's OFF.
• STOP: control stop indicator Lights when event input or “Run/Stop” is stopped during operation. During control stop, functions other than control output are valid.
• CMW: communications writing enable/ disable indicator Lights when communications writing is
“enabled” and is out when it is “disabled”.
POWER ON
PV/SP
0
Set point during SP ramp
0
Program start
Soak time remain
0
Run/Stop When control start =
When control stop =
Alarm value 1 *4
0
Alarm value upper limit 1
0
Alarm value lower limit 1
0
Alarm value 2 *4
0
Alarm value upper limit 2
0
Alarm value lower limit 2
0
Hold and keys
down for at least
Operation / adjustment protect
0
Initial /
Communication
protect
Parameter change protect
Move to protect group
” flashes
(The applicability of the electric terminals varies with the type of 900-TC16.)
Alarm output
11
6
1
2
12
7
Alarm 1/Heater
A
burnout alarm
8
3
13
B
-
9
4
14
Input power supply
B
5
10
15
+
•100-240V AC Type
TC/PT
•24V AC/DC Type (no polarity)
Adjustment group

6
*
6
*
6
*
6
*
6
*
6
*
6
*
6
*
: The grayed-out parameters may not be displayed according to the model and
6
*
parameter.
٨Protection function
Protection function is to prevent unwanted settings. It restricts the parameter to be used
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------­or designates if operation of the key is valid or invalid.
------------------------------------------------------------------------------------------------------
Operation / Adjustment protection
The following table shows the relationship between settings and protect limits related to Operation group and Adjustment group.
Operation group
Adjustment group
Initial setting/Communications protection
This protect level restricts movement to the initial setting group, communications setting group and advanced function setting group.
Initial setting
Set value
0 1 2
Parameter change protection
Parameter changes by key operation are restricted.
OFF “ ”: Parameter can be changed by key operation ON “ ” : Parameter cannot be changed by key operation (“ ” will light.) (Protect group parameters can all be changed.)
Analog input
*4
*4
*4
*4
3 seconds
Control output 1
+
mA
-
V
+
multi-input
Press (less than 1 second)
+
-
Specifications
Power supply voltage
Operating frequency Operating voltage range Power consumption
Indication accuracy
Event input Contact input No-contact input
Control output 1
Control output 2
Control method Alarm output
Ambient temperature
Ambient humidity Storage temperature
Altitude Recommended fuse
Weight Installation environment
11
Alarm 2
12
EV1
EV1
EV2
EV2
13
DO NOT USE
14
CT1
DO NOT USE
15
900-
900-
TC16NEIM
TC16NACEIM
ALM1
ALM2
ALM3
HA
OUT1 STOP
OUT2 CMW
MANU
Only the value set to the “ : temperature input shift” parameter is applied to the entire temperature input range. When the process value is 200 °C, the process value is treated as 201.2 °C after input shift if the input shift value is set to 1.2 °C. The process value is treated as 198.8 °C after input shift if the input shift value is set to –1.2 °C.
l.adj
Adjustment group
AT execute =
at
AT cancel =
off
ins
Temperature input shift (Unit: °C or °F)
0.0
Input shift upper limit
insh
when 2 point input shift is selected
0.0
Input shift lower limit
insl
when 2 point input shift
0.0
is selected
p
Proportional band
8.0
i
Integral time (Unit: secs)
233
d
Derivative time (Unit: secs)
40
c-sc
Cooling coefficient
1.00
Group
group
Process value Set point Others
0
٤ ٧ ٧ ٧
Communications
setting group
100-240VAC type 24V AC/DC type 50-60Hz 85 to 110% of the rated voltage Approx. 7.5VA (AC100-240V) Approx. 5VA (AC24V) Approx. 3W (DC24V) Thermocouple, platinum resistance thermometer: (±0.5 % of indication value or ±1 which is greater) ±1 digit max. Analog input: ±0.5 % FS ±1 digit max. Output current: approx. 7 mA per contact. ON:1 k max., OFF: 100 k min. ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max. Relay output: SPST-NO, 250 VAC, 3A(resistive load) Voltage output: 12 VDC, 21 mA Current output: 4 to 20 and 0 to 20 mA DC, load:600 Electrical life of relay: 100,000 operations Triac model: 1 million operations Voltage output: 12 VDC, 21 mA
ON/OFF or 2-PID control SPST-NO, 250 VAC, 1 A(resistive load), electrical life: 100,000 operations –10 to 55 C (Avoid freezing or condensation) RH 25 to 85% –25 to 65 C (Avoid freezing or condensation) Max. 2,000m T2A, 250V AC, time-lag, low-breaking capacity Approx. 150g (main unit only) Setup category II, pollution degree 2 (as per IEC61010-1)
B
B
11
11
12
13
14
15
11
RS-485
RS-485
A
A
12
12
DO
DO
NOT
NOT
13
13
USE
USE
+
14
14
CT1
Control output
15
15
-
900-
900-
TC16NCOMV2
TC16NCOM
• °C / °F : temperature unit The temperature unit is displayed
when the configured display value is a temperature.
When this parameter is set to "°C",
C ” is displayed, and when set to
PV
“ °F”, “F ” is displayed.
This flashes while ST(Self-Tuning) is activated.
: Protection indicator
SV
Lit when Setting Change Protect is ON (disables the Up and Down Keys).
• MANU: Manual output indicator Lit when the Auto/Manual Mode is set
to Manual Mode.
6
*
c-db
of-r
6
*
6
*
6
*
soak
6
*
wt-b
6
*
6
*
6
*
6
*
Adjustment group is for entering parameter values and shift values for control.
Set value
123
Default setting : 0 (shaded)
Advanced function
setting group
C,
max.
+
Control output 2
B
B
RS-485
A
DO NOT USE
DO NOT USE
DO NOT USE
900-
TC16NACCOM
Dead band
0.0
Manual reset value (Unit: %)
50.0
Hysteresis (heat)
Hysteresis (cool)
Soak time
1
Wait band
off
SP ramp set value
MV upper limit
ol-l
MV lower limit
-5.0
: Can be displayed and changed : Can be displayed : Can not be displayed and change to other groups not possible
11
RS-485
12
13
CT2
14
15
A
CT1
TC16NCOMP3
11
11
Voltage output:
Control output 2
12
12
12 VDC, 21 mA
-
DO NOT
13
13
USE
14
14
CT1
15
15
900-
900-
TC16P1V2
: Change to other groups possible : Change to other groups
not possible Default setting : 1 (shaded)
Loading...