Rockwell Automation 1734-AENT User Manual

4.3 (6)
Rockwell Automation 1734-AENT User Manual

User Manual

1734 POINT I/O EtherNet/IP Adapters

Catalog Number 1734-AENT, Series B

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Allen-Bradley, Rockwell Automation, POINT I/O, ArmorPOINT I/O, RSLogix, RSLinx, Logix5000, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

Preface

Who Should Use this Manual

Purpose of this Manual

Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:

who should use this manual

the purpose of this manual

related documentation

conventions used in this manual

Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Series B 1734 POINT I/OEtherNet/IP Adapter modules.

This manual is a reference guide for the 1734-AENT Series B POINT I/O EtherNet/IP Adapter, a communications adapter for POINT I/O modules. It describes the procedures you use to install, wire, configure, troubleshoot, and use your adapter module.

ATTENTION: You must only use Series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).

About the Example Applications

This manual presents two example applications that demonstrate the procedures for configuring and communicating with POINT I/O modules using the 1734-AENT adapter. We intend the example applications as building blocks to help you get your own system up and running. We recommend that you set up and run the example applications and use them as guides.

Here is the type of system you’ll be setting up.

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

i

1734-AENT 10.88.70.2

Slot 0 1 2 3

Local

Data

chassis

 

 

1756-ENBT

L63 10.88.70.4 (slot 3) controller (slot 1)

Switch

0

0 2

1734-AENT Series B

 

 

 

 

 

 

POINT I O

 

 

 

POINT I/O

 

 

Network

 

 

 

 

 

Module

 

 

 

 

 

 

Status

 

 

 

 

 

 

Activity

 

 

 

 

 

 

Network

 

 

 

 

 

 

Status

 

 

 

 

 

 

Point Bus

 

 

 

 

 

 

Status

 

 

 

 

 

 

System

 

 

 

 

 

 

Power

 

 

 

 

 

 

Field

 

 

 

 

 

 

Power

 

 

 

 

 

IP ADDRESS

 

 

 

 

 

 

 

Slot 0

1

2

3

4

10.88.70.26

Programming terminal

31393

System Components

We used the following components for the example applications. You need the same or similar components to set up your own control system using POINT I/O modules on an EtherNet/IP network.

Quantity

Product Name

Catalog Number

 

 

 

 

Hardware

 

 

 

 

1

POINT I/O EtherNet/IP adapter

1734-AENT

 

 

 

1

POINT I/O 24V DC sink output module

1734-OV4E/C

 

 

 

1

POINT I/O relay output module

1734-OW2/C

 

 

 

1

DIN rail

199-DR1 or equivalent

 

 

 

1

ControlLogix chassis

1756-A4 (or 1756-A7, 1756-A13,1756-A17)

 

 

 

1

ControlLogix power supply

1756-PA72 (or 1756-PB72)

 

 

 

1

L63 controller

1756-L63

 

 

 

1

ControlLogix EtherNet/IP bridge module

1756-ENBT

 

 

 

1

Personal computer that supports

Any appropriate model running Windows NT

 

RSLogix 5000 software

4.0, Service Pack 6A or higher

 

 

 

1

Ethernet switch

Refer to manufacturer’s specifications

 

 

 

1

24V DC power supply

1734-EP24DC

 

 

 

 

Associated media and connectors as needed

 

 

 

 

Software

 

 

 

 

1

RSLinx communications software,

9355-WAB, 9355-WABOEM, 9355-WABC

 

version 2.31.00 or later

 

 

 

 

ii

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Quantity

Product Name

Catalog Number

 

 

 

1

RSLogix 5000 programming

9324-RLD300ENE

 

software, version 17 or later

 

 

 

 

Related Documentation

The following documents contain additional information concerning Rockwell Automation products. To obtain a copy, contact your local Rockwell Automation office or distributor.

Resource

Description

 

 

1734 POINT I/O® Selection Guide, publication 1734-SG001

A description and overview of the 1734 series I/O modules and compatible

 

control platforms.

 

 

EtherNet/IP Design Considerations Reference Manual, publication

Using EtherNet/IP for Industrial Control.

ENET-RM002.

 

 

 

EtherNet/IP Modules in Logix5000Control Systems User Manual,

A manual describing how to use EtherNet/IP modules with Logix5000

publication ENET-UM001

controllers and communicate with various devices on the Ethernet network.

 

 

EtherNet/IP Embedded Switch Technology Application Guide,

Describes how to install, configure, and maintain linear and device-level Ring

publication ENET-AP005

(DLR) networks using Rockwell Automation EtherNet/IP devices with

 

embedded switch technology.

 

 

ControlLogixChassis and Power Supplies Installation

Describes how to install and troubleshoot standard and ControlLogix-XT

Instructions, publication 1756-IN005.

versions of the 1756 chassis and power supplies, including redundant power

 

supplies.

 

 

ControlLogix EtherNet/IP Bridge Module Installation Instructions,

ControlLogix EtherNet/IP Bridge Module installation instructions.

publication 1756-IN019

 

 

 

ControlLogix System User Manual, publication 1756-UM001

Detailed information on how to install, configure and troubleshoot the

 

ControlLogix Sequence of Events module in your ControlLogix application.

 

 

RSLinx® Classic Getting Results Guide, publication LINX-GR001

Information on how to install and navigate the RSLinx Classic software. It

 

explains how to access and navigate the help, and how to effectively use the

 

RSLinx Classic software.

 

 

1734 POINT I/O EtherNet/IP Adapter Installation Instructions,

Installation instructions for installing the 1734 POINT I/O EtherNet/IP Adapter.

publication 1734-IN042

 

 

 

Allen-Bradley Industrial Automation Glossary, publication

A glossary of industrial automation terms and abbreviations.

AG-QR071

 

 

 

Industrial Automation Wiring and Grounding Guidelines,

Detailed information on proper wiring and grounding techniques.

publication 1770-IN041.

 

 

 

EtherNet/IP Media Planning and Installation Manual (ODVA).

Installing an EtherNet/IP network

 

 

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

iii

Common Techniques Used in this Manual

The following conventions are used throughout this manual:

Bulleted lists such as this one provide information, not procedural steps.

Numbered lists provide sequential steps or hierarchical information.

Italic type is used for emphasis.

Rockwell Software products contain extensive tutorials and help screens. We recommend that you use these tutorials and help screens to learn about the products.

For more information about Rockwell Software products, visit the Rockwell Software website at http://www.rockwellautomation.com/software/.

iv

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Table of Contents

Overview of the 1734 POINT I/O

EtherNet/IP Adapter

Preface

Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i

Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i About the Example Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i

System Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ii

Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii Common Techniques Used in this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . vi

Chapter 1

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

Adapter Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 What the Adapter Does . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

Physical Features of Your Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Hardware/Software Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Important Adapter Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Set the Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Adapter Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Empty Slots and RIUP Situations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Power Up a System for the First Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Use of the Common Industrial Protocol (CIP) . . . . . . . . . . . . . . . . . . . . . . . 6 Understand the Producer/Consumer Model . . . . . . . . . . . . . . . . . . . . . . . . . 6

Specify the Requested Packet Interval (RPI) . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Support for Rack-optimized and Direct Connections . . . . . . . . . . . . . . . . . 7 Mixing Rack-optimized and Direct Connections. . . . . . . . . . . . . . . . . . 8

Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Determine Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Understand Messaging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Configure Autobaud. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Chapter Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Install Your 1734 POINT I/O

EtherNet/IP Adapter

Chapter 2

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Mount the POINT I/O Adapter on a DIN Rail. . . . . . . . . . . . . . . . . 12

Install POINT I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Remove POINT I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Replace An Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Wire the Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Wire a POINT I/O Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Chapter Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

v

Table of Contents

Configure the Adapter with RSLogix5000 software

Chapter 3

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Configuration Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Gateway Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Subnet Mask . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

Set the Network Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

Set the Network Address for POINT I/O Adapters . . . . . . . . . . . . . 22 Use the Rockwell BootP/DHCP Utility. . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Save the Relation List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

Use DHCP Software to Configure Your Adapter . . . . . . . . . . . . . . . . . . . 27 Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Configure the Adapter for Direct Connection in RSLogix 5000 Software

Chapter 4

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

Configure the I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Add the Local EtherNet/IP Bridge to the I/O Configuration. . . . . 32

Add the POINT I/O Adapter to the I/O Configuration. . . . . . . . . . . . . 35

Add the POINT I/O Modules to the I/O Configuration . . . . . . . . 38 Edit the Controller Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Create the Ladder Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Download the Program to the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . 44 Verify the Module Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

Configure the Adapter with Fixed IP Address. . . . . . . . . . . . . . . . . . . . . . . 48

Recover From an Overloaded Adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49 Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software

Chapter 5

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Set Up the Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Set Up the POINT I/O Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

Create the Example Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Configure the I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 Add the Local EtherNet/IP Bridge to the I/O Configuration. . . . . 54

Add the I/O Adapter to the I/O Configuration . . . . . . . . . . . . . . . . . 56

Add the POINT I/O Module and Configure for Rack-optimized

Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59 Add the POINT I/O Module and Configure For Direct Connection 61

Download the Program to the Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . 63

vi

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

 

 

Table of Contents

 

Verify the Module Chassis Size . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . 65

 

Access Module Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 68

 

Chapter Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 68

 

Chapter 6

 

Troubleshoot the Adapter

Interpret the Status Indicators. . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 69

 

Status Indicators for POINT I/O Adapters. . . .

. . . . . . . . . . . . . . . . . 70

 

Appendix A

 

Specifications

General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 73

 

Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 74

 

EtherNet Communication . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 75

 

Environmental Specifications . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 75

 

Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 77

 

Appendix B

 

Adapter Web Dialogs

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 79

 

Work with the Home Page. . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 79

 

Work with the Diagnostics Pages . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 81

 

Use the Diagnostic Overview Page . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 82

 

Use the Network Settings Page . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 83

 

Use the Ethernet Statistics Page. . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 84

 

Use the I/O Connections Page . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 86

 

Use the Advanced Diagnostics Page . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 87

 

Work with the Configuration Pages . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 88

 

Use the Identity Page . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 90

 

Use the Network Configuration Page . . . . . . . . .

. . . . . . . . . . . . . . . . . 91

 

Use the Services Page . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 92

 

Work with the Browse Chassis Page . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 93

 

Appendix C

 

Configure the RSLinx Ethernet

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 95

Communication Driver

Install the RSLinx Software . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 95

 

Configure the AB_ETH Driver . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 96

 

Configure the AB_ETH/IP Driver . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . 98

Index

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . .101

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

vii

Table of Contents

viii

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Chapter 1

Overview of the 1734 POINT I/O EtherNet/IP

Adapter

Overview

Adapter Features

This chapter provides an overview of the POINT I/O® Series B EtherNet/IP adapter, its primary features, and how to use it. You need to understand the concepts discussed in this chapter to configure your adapter and use it in an EtherNet/IP control system.

The following table lists where to find specific information.

Topic

Page

 

 

Adapter Features

1

 

 

What the Adapter Does

2

 

 

Physical Features of Your Adapter

3

 

 

Hardware/Software Compatibility

3

 

 

Important Adapter Considerations

4

 

 

Set the Chassis Size

4

 

 

Adapter Replacement

5

 

 

Empty Slots and RIUP Situations

5

 

 

Power Up a System for the First Time

6

 

 

Use of the Common Industrial Protocol (CIP)

6

 

 

Understand the Producer/Consumer Model

7

 

 

Specify the Requested Packet Interval (RPI)

7

 

 

Support for Rack-optimized and Direct Connections

7

 

 

Mixing Rack-optimized and Direct Connections

8

 

 

Chapter Summary

9

 

 

The POINT I/O adapters provide connectivity to EtherNet/IP networks for POINT I/O modules. The POINT I/O adapter is for the I/O backplane that provides connectivity through an RJ-45 connector.

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

1

Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter

What the Adapter Does

Some of the module’s features are as follows:

EtherNet/IP messages encapsulated within standard TCP/UDP/IP protocol

Common application layer with ControlNet and DeviceNet networks

Interfacing via Category 5 rated twisted pair cable

Half/full duplex 10 Mbit or 100 Mbit operation

DIN rail mounting

Communication to and from other POINT I/O modules on the same DIN rail

Communication supported by RSLinx software

IP address assigned via standard BootP or DHCP tools

I/O configuration via RSLogix 5000 software

No network scheduling required

No routing tables required

Support of connections from multiple controllers simultaneously

You must use RSLogix 5000 to configure these features. For more details on configuration, see Configuration Requirements in Chapter 3.

The I/O adapters perform the following primary tasks:

Control of real-time I/O data (also known as implicit messaging) - the adapter serves as a bridge between I/O modules and the network

L

E

 

6

N

 

3

B

 

 

T

 

 

 

 

EtherNet/IP Network

 

 

 

 

 

 

 

 

 

 

 

 

 

A

POINT

 

E

ControlLogix

 

Other

 

 

E

 

N

 

Network

 

 

N

I/O

 

I/O

 

 

 

 

B

 

Devices

 

 

T

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Support of messaging data for configuration and programming information (also known as explicit messaging)

2

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Overview of the 1734 POINT I/O EtherNet/IP Adapter

Chapter 1

 

 

Physical Features of Your

Adapter

The 1734 Adapters have the following components:

Removable Terminal Block (RTB);

Network address Thumbwheel

Connector (one RJ45 EtherNet/IP connector)

Status indicators (Module Status; Network Status; POINTBus Status; Network Activity; Link 1 Activity/Status; Link 2 Activity/Status; System Power; Field Power)

Physical Features of the 1734-AENT Series B Adapters

Network address thumbwheel

2 00

 

 

 

 

 

Status indicators

 

 

 

B

 

RTB removal handle

-AENT

Series

 

 

 

Module

 

1734

IO

 

Status

 

 

 

 

Network

 

POINT

 

 

Activity

 

 

 

Status Bus

 

 

 

 

 

Network

 

 

 

 

 

Point

 

 

 

 

 

Status

 

 

 

 

 

System

 

 

 

 

 

Power

 

 

 

 

 

Field

 

 

 

 

 

Power

 

 

 

 

 

Removable Terminal

 

 

 

 

 

Block (RTB)

EtherNet

DIN rail locking screw

network

(orange)

RJ45

 

connector

 

31533

Hardware/Software

Compatibility

The I/O adapters and the applications described in this manual are compatible with the following firmware revisions and software releases.

Contact Rockwell Automation if you need software or firmware upgrades to use this equipment

Product

Firmware Revision/ Software Release

 

 

1734-AENT Series B adapter

4.002 or later

 

 

1756-ENBT module

4.5 or later

 

 

Logix controller

17 or later

 

 

RSLogix 5000 software

17 or later

 

 

RSLinx software

2.56 or later

 

 

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

3

Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter

Important Adapter

Considerations

Before you begin using your adapter, note the following important considerations.

ATTENTION: You must only use Series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).

Set the Chassis Size

The I/O adapters for EtherNet/IP require configuration of their chassis size before you can make any I/O connections. The factory default setting for the chassis size is one slot, which represents the adapter by itself.

You must set the chassis size to a number equaling one slot for the adapter plus one slot for each I/O module present in the backplane of the adapter.

For example, a POINT I/O system consisting of a 1734-AENT adapter, one 1734-IB8, one 1734-OB8, and one 1734-OB8S POINT Guard I/O module uses a chassis size of 4. The adapter stores this chassis size setting in non-volatile memory.

Each time the adapter is powered up, the adapter compares the number of I/O modules present on its backplane to the chassis size value from non-volatile memory. The adapter does not allow any I/O connection until the number of I/O modules present equals the chassis size value minus one for the adapter itself.

4

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Overview of the 1734 POINT I/O EtherNet/IP Adapter

Chapter 1

 

 

Adapter Replacement

Note that during a connection request from the controller, the chassis size setting is not communicated to the adapter. You must always set this chassis size using a separate operation. This includes situations when you are replacing an adapter.

The adapter does not allow any I/O connections until it is configured with the appropriate chassis size and the proper number of POINT I/O modules are present.

Empty Slots and RIUP Situations

The POINT I/O system cannot detect an empty terminal base. For this reason, there are numerous situations in which you can potentially configure a system that is unusable or one that exercises unintended control.

In an attempt to address these situations, you must observe the following rules for

I/O system construction and the removal and reinsertion of modules.

A correct I/O system does not have any empty terminal bases.

After you cycle power, the adapter will not allow any I/O connections until the number of modules comprising the chassis plus one for the adapter equals the stored chassis size.

It cannot assume any safe operation until there is a match between the number of modules indicating their presence in the chassis and what the adapter has saved in non-volatile memory because it cannot detect empty terminal bases.

Actual module identification (such as, electronic keying) is done when connection establishment requests are received from the controller or controllers.

A POINT I/O module removed under power does not disrupt operation of the other I/O modules. On the other hand, ArmorPOINT I/O modules are not intended to be removed under power.

When you remove a module, the adapter detects what changed.

Whenever you remove a module with an active connection from the POINT I/O system, the adapter indicates this by flashing the POINTBus Status LED red and reports a minor recoverable fault.

If more than one contiguous module is removed under power, connections to all modules in the contiguous missing module set are disallowed until all modules are replaced. Because the adapter cannot detect an empty base, it does not know the physical positioning of the modules until all the missing modules are replaced.

If a module separating two sets of contiguous missing modules is removed, the two sets merge into a single set. All the modules must be replaced before connections are permitted to any module in the set.

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

5

Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter

Use of the Common

Industrial Protocol (CIP)

If modules of different types are removed and returned to the wrong locations, attempts to connect to these modules will fail during verification of the electronic ID (providing that keying has not been disabled).

If modules of the same type are removed and returned to the wrong locations, they accept connections from the controller or controllers and reconfigure with the correct data once they pass their electronic keying check.

These removal and return situations exist whether the system is under power or not. If the system is under power, the situation arises immediately. If the system is not under power, the situation arises in the next power cycle.

Power Up a System for the First Time

When you power the I/O for the first time, the adapter must assign slot addresses to every module in the backplane. All I/O modules ship configured at the same address.

When you first apply power, we expect that all but one module on the backplane exhibits a solid red Module Status LED.

One by one the adapter resets these modules and addresses them appropriately. The amount of time that this operation takes is proportional to the size of your I/ O system.

The adapter uses the Common Industrial Protocol (CIP). CIP is the application layer protocol specified for EtherNet/IP, the Ethernet Industrial Protocol, as well as for ControlNet and DeviceNet networks. It is a message-based protocol that implements a relative path to send a message from the producing device in a system to the consuming devices.

The producing device contains the path information that steers the message along the proper route to reach its consumers. Since the producing device holds this information, other devices along the path simply pass this information; they do not store it.

This has the following significant benefits:

You do not need to configure routing tables in the bridging modules, which greatly simplifies maintenance and module replacement.

You maintain full control over the route taken by each message, which enables you to select alternative paths for the same end device.

6

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Overview of the 1734 POINT I/O EtherNet/IP Adapter

Chapter 1

 

 

Understand the Producer/

Consumer Model

Specify the Requested

Packet Interval (RPI)

Support for Rack-optimized and Direct Connections

The CIP producer and consumer networking model replaces the old source and destination (master and slave) model. The producer and consumer model reduces network traffic and increases speed of transmission. In traditional I/O systems, controllers poll input modules to obtain their input status. In the CIP system, input modules are not polled by a controller. Instead, they produce (multicast or unicast) their data either upon a change of state (COS) or periodically.

Multicast is the default mode for version 17 Logix and earlier controllers and unicast is the default for version 18 with multicast as a selectable option.

The frequency of update depends upon the options chosen during configuration and where on the network the input module resides. The input module, therefore, is a producer of input data, and the controller is a consumer of the data.

The controller also produces data for other controllers to consume. The produced and consumed data is accessible by multiple controllers and other devices over the EtherNet/IP network. This data exchange conforms to the producer and consumer model.

The Requested Packet Interval or RPI is the update rate specified for a particular piece of data on the network. The RPI can be specified for the adapter and include all of the I/O modules in the I/O system (using a rack-optimized connection) or specified for a particular module (using direct connection).

When you add a module or an adapter to the I/O configuration of a controller, you must enter the RPI as a parameter. This value specifies how often to produce the data for that device. For example, if you specify an RPI of 50 ms, it means that every 50 ms the device should send its data to the controller and the controller should send the consumed (output) data to the device.

Use RPIs only for devices that exchange data. For example, a ControlLogix EtherNet/IP bridge module in the same chassis as the controller does not require an RPI, because it is not a data-producing member of the system. Its use is only as a bridge to remote racks.

The I/O adapters supports both direct and rack-optimized connections. A direct connection is a real-time data transfer link between the controller and the module occupying the slot that the configuration data references.

Direct I/O connections occur at a cyclic rate specified by the RPI during configuration. A rack-optimized connection is a grouping of data from one or more digital I/O modules into a single block of data sent over a single connection at the same data rate.

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

7

Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter

Rack-optimized connections reduce the total number of connections needed to transfer data when using many digital I/O modules in a system. The following example illustrates the benefit of rack-optimized connections.

Assume you set up a system that contains eight digital I/O modules interfaced to an adapter. If you use direct connections to transfer data to each of the these I/O modules, you need eight connections to transfer all of the data, one to each of the eight I/O modules. If you use a rack-optimized connection to transfer the data, you only need a single connection – the connection to the I/O adapter.

IMPORTANT Although rack-optimized connections offer an efficient way to use resources, there are a few limitations on their use:

• You can use only rack-optimized connections to send data to and from digital I/O modules. Analog or speciality I/O requires direct connections.

• All data is sent at the same time as the RPI rate of the I/O adapters. If the update rate required for a digital module is different from the RPI of the rack-optimized connection, a direct connection to that digital I/O module is required.

See the EtherNet/IP Embedded Switch Technology Application Guide,, publication ENET-AP005, for more information on connections.

Mixing Rack-optimized and Direct Connections

Before You Begin

You can mix communication formats for different I/O modules communicating through the same adapter. I/O modules set up to use rack optimization communicate at the rate of the RPI configured for the adapter. I/O modules configured for direct communication communicate at their own individual RPIs and ignore the rack-optimized RPI.

To effectively use your adapter, note the following considerations.

Determine Compatibility

If using the adapter with a 1756-ENBT module or 1788-ENBT module, use the following required firmware revisions for these bridge modules:

1756-ENBT firmware revision 2.3 or later

1788-ENBT firmware revision 1.33 or later

If you use the BootP Utility to assign IP addresses to the adapter, use revision 2.3.2 or later.

8

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Overview of the 1734 POINT I/O EtherNet/IP Adapter

Chapter 1

 

 

Understand Messaging

Class 3 (Explicit Message) requests through the 1734-AENT adapter to a specific POINT I/O module may not always receive a response from the I/O modules. In the case where the I/O module does not reply to the request, the adapter responds with an error code indicating a timeout.

Configure Autobaud

Chapter Summary

The adapter cannot reconfigure an I/O module that you previously configured to operate at a fixed communication rate. When you reuse a POINT I/O module from another POINT I/O system, configure the module to autobaud before using it with the adapter.

In this chapter, you were introduced to the features of the POINT I/O Adapter, and considerations for its installation and usage.

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

9

Chapter 1 Overview of the 1734 POINT I/O EtherNet/IP Adapter

Notes:

10

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Chapter 2

Install Your 1734 POINT I/O EtherNet/IP

Adapter

Overview

This chapter describes how to physically install the POINT I/O Series B EtherNet/IP adapter; and how to connect the adapter to your EtherNet/IP network. The only tools you require are a flat or Phillips head screwdriver and a drill.

This chapter includes the following topics:

Topic

Page

 

 

Mount the POINT I/O Adapter on a DIN Rail

12

 

 

Install POINT I/O Modules

13

 

 

Replace An Adapter

14

 

 

Wire a POINT I/O Adapter

15

 

 

Chapter Summary

16

 

 

ATTENTION: You must only use Series C and above POINT I/O modules with POINT I/O Adapters. Series A or Series B POINT I/O modules do not work with POINT I/O Adapters (does not apply to POINTGuard modules).

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

11

Chapter 2 Install Your 1734 POINT I/O EtherNet/IP Adapter

Mount the POINT I/O Adapter on a DIN Rail

1.Make sure the DIN rail locking screw (orange) is in horizontal position.

2.Position the adapter vertically above an IEC standard (35 x 7.5 x 1 mm)

top-hat DIN rail at a slight angle (DIN rail: Allen-Bradley part number

199-DR1; 46277-3).

3.Press down firmly to install the adapter on the DIN rail, noting that the locking mechanism locks the adapter to the DIN rail.

ATTENTION: Allow 25.4 mm (1.0 in.) of space between adjacent equipment for adequate ventilation.

4.Set the network address thumbwheel switches to the desired value. See Set the Network Address in chapter 3 for details on setting the IP address.

5.Slide the safety end cap up to remove it, exposing the backplane and power interconnections.

B

 

 

74.00

 

 

(2.91)

 

 

75.30

 

 

(2.96)

1734-

AENT Series B

52.23

 

Module

(2.06)

 

 

 

Status

 

 

Network

 

 

Activity

 

 

Network

 

 

Status

 

 

Point Bus

 

 

Status

 

 

System

 

 

Power

 

 

Field

 

 

Power

 

35.55

(1.40)

132.72

(5.23)

A

A = DIN rail

B = Secure DIN rail approximately every 200 mm (7.8 in.)

45174

 

WARNING: If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

ATTENTION: Do not remove or replace an Adapter Module while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.

12

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Install Your 1734 POINT I/O EtherNet/IP Adapter

Chapter 2

 

 

Install POINT I/O Modules

The following instructions explain how to install your POINT I/O Modules onto the DIN rail.

1.Position the mounting base vertically above the DIN rail.

2.Make certain the adapter DIN rail locking screw (orange) is in the horizontal position.

3.Slide the I/O module mounting base down, allowing the interlocking side pieces to engage the adjacent mounting base/adapter.

4.Press down firmly to install the I/O module mounting base on the DIN rail. A locking mechanism locks the mounting base to the DIN rail.

5.Rotate the keyswitch on the I/O module mounting base clockwise until the appropriate number for the module you are installing (listed on the module label) aligns with the correct notch in the base.

6.Position the I/O module vertically above its mounting base.

7.Slide the module down until it engages the latching mechanism. You will hear a clicking sound when the I/O module is properly engaged. The locking mechanism locks the module to its mounting base.

Remove POINT I/O Modules

To remove a module from its mounting base:

1.Put a flat-blade screwdriver into the slot of the orange latching mechanism in the mounting base of the I/O module to be removed.

2.Push the screwdriver toward the I/O module to disengage the latch. The module lifts up off the mounting base.

3.Pull the module off the mounting base.

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

13

Chapter 2 Install Your 1734 POINT I/O EtherNet/IP Adapter

Replace An Adapter

Use these procedures to install a replacement POINT I/O adapter to an existing system.

1.Disconnect the Ethernet connector(s) from the adapter.

2.Pull up on the Removable Terminal Block (RTB) handle to remove the terminal block.

3.Remove the adjacent module from its mounting base.

4.Use a small bladed screwdriver to rotate the DIN rail locking screw (orange) to a vertical position. This releases the locking mechanism.

5.Lift the adapter straight up to remove.

6.Slide the safety end cap up to remove it, which exposes the backplane and power connections.

ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.

WARNING: When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

7.Position the replacement adapter vertically above the DIN rail, making certain the DIN rail locking screw (orange) is in the horizontal position.

8.Slide the adapter down, allowing the interlocking side pieces to engage the adjacent module.

9.Press firmly to seat the adapter on the DIN rail, noting that the adapter locking mechanism will snap into place.

10.Set the network address on the network address thumbwheel.

11.Insert the end of the Removable Terminal Block opposite the handle into the Removable Terminal Block base unit, noting that this end has a curved section that engages with the base unit.

12.Rotate the Removable Terminal Block into the wiring base until it locks into place.

13.Replace the adjacent module in its mounting base.

14.Reconnect the Ethernet cable(s) to the adapter.

15.Set the IP Address for this module (see Set the Network Address in chapter 3).

16.Configure the adapter’s chassis size.

14

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Install Your 1734 POINT I/O EtherNet/IP Adapter

Chapter 2

 

 

Wire the Adapter

The POINT I/O adapter uses RJ45 EtherNet/IP connectors for its EtherNet/ IP connection. Connect the cord set you selected for your module to the appropriate port.

Wire a POINT I/O Adapter

Refer to the following illustration to wire the adapter.

Network address thumbwheels

RJ45 EtherNet/IP

Connector

This DC supply connects to the internal power bus.

NC = No Connection

Chas Gnd = Chassis Ground

C = Common

V = Supply

002

NC

Chas

C

V

43264

0

1

NC

NC

2

3

Chas

Chas

Gnd

Gnd

4

5

C

C

6

7

V

V

ATTENTION: Do not connect 120/240V AC power to this supply. This DC supply will be connected to the internal power bus.

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

15

Chapter 2 Install Your 1734 POINT I/O EtherNet/IP Adapter

Chapter Summary

ATTENTION: Do not wire more than two conductors on any single terminal.

WARNING: When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations.

Be sure that power is removed or the area is nonhazardous before proceeding.

WARNING: When used in a Class I, Division 2, hazardous location, this equipment must be mounted in a suitable enclosure with proper wiring method that complies with the governing electrical codes.

ATTENTION: This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.

WARNING: To comply with the CE Low Voltage Directive (LVD), this equipment must be powered from a source compliant with the following:

Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).

In this chapter, you learned how to install and wire your POINT I/O adapter module. The following chapter describes how to configure your POINT I/O adapter module to communicate on the EtherNet/IP network by providing an IP address, gateway address, and Subnet mask.

16

Rockwell Automation Publication 1734-UM018B-EN-P - October 2013

Chapter 3

Configure the Adapter with RSLogix5000 software

Introduction

This chapter guides you through the steps required to configure your modules using the RSLogix 5000 software. Note that the modules presented in this chapter can be configured using RSLogix 5000 software, version 17, or later.

Before using your adapter in an EtherNet/IP network, you need to configure it with an IP address, subnet mask, and optional Gateway address. This chapter describes these configuration requirements and the procedures for providing them. Here are ways you can do this:

Use the Rockwell BootP/DHCP utility, version 2.3 or later, that ships with RSLogix 5000 or RSLinx software.

You can also use this utility to reconfigure a device with an IP address you must change.

Use a third party DHCP server.

Use the Network Address thumbwheel switches.

Have your network administrator configure the adapter via the network DHCP server.

See the table for where to find information in this chapter..

Topic

Page

 

 

Configuration Requirements

18

 

 

IP Address

19

 

 

Gateway Address

20

 

 

Subnet Mask

21

 

 

Set the Network Address

22

 

 

Set the Network Address for POINT I/O Adapters

22

 

 

Use the Rockwell BootP/DHCP Utility

23

 

 

Save the Relation List

25

 

 

Use DHCP Software to Configure Your Adapter

27

 

 

Chapter Summary

27

 

 

Rockwell Automation Publication 1734-UM018B-EN-E - October 2013

17

Chapter 3 Configure the Adapter with RSLogix5000 software

Configuration

Requirements

Before you can use your adapter, you must configure its IP address, its subnet mask, and, optionally, a gateway address. You can use the Rockwell BootP utility, version 2.3 or later, to perform the configuration. You can also use a DHCP server or the network address switches to configure these parameters.

ATTENTION: You must only use Series C and above POINT I/O modules with 1734-AENT EtherNet/IP Adapters. Series A or Series B POINT I/O modules do not work with 1734-AENT EtherNet/IP Adapters (does not apply to POINTGuard modules).

If you need to reset the adapter to factory defaults, see Work with the Configuration Pages in Appendix B.

 

 

 

173

 

 

 

 

 

 

 

4-

 

 

 

 

 

 

 

AENT

 

 

 

 

 

 

POINTI

S

 

 

0

0

2

 

O

eries

B

 

 

 

 

 

 

Mo

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

du

 

 

 

 

 

 

 

Stat le

 

 

 

 

 

 

us

 

 

 

 

 

 

 

Network

 

 

 

 

 

Activity

 

 

 

 

 

 

Networ

 

 

 

 

 

 

Stat

k

 

 

 

 

 

us

 

 

 

 

 

 

 

Point

 

s

 

 

 

 

 

Status

 

 

 

 

 

 

Bu

 

 

 

 

 

System

 

 

 

 

 

 

Power

 

 

 

 

 

 

 

Field

 

 

 

 

 

 

 

Power

 

 

IP address

 

 

 

Ethernet address (MAC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

43519

IMPORTANT If you set the thumbwheels on the adapter to the value 888 and then power cycle the module, the following will occur.

·The DHCP Enabled function is enabled (set to True).

·The Ethernet link is negotiated automatically (the Auto Negotiate function will be set to True).

·The web server is enabled (the Disabled Web Server function is disabled).

·The password for this page resets to the factory default (the word password is the factory default password).

Note the value of the switches before you enter the 888 value, because you return the adapter to those values once this process is complete.

18

Rockwell Automation Publication 1734-UM018B-EN-E - October 2013

Configure the Adapter with RSLogix5000 software

Chapter 3

 

 

IMPORTANT If using the BootP/DHCP utility, you need to know the Ethernet hardware address of your adapter. Rockwell Automation assigns each 1734-AENT adapter a unique 48-bit hardware address at the factory. The address is printed on a label on the side of your 1734-AENT adapter as shown in the figure. It consists of six hexadecimal digits separated by colons. This address is fixed by the hardware and cannot be changed.

If you change or replace the 1734-AENT adapter, you must enter the new Ethernet hardware address of the adapter when you configure the new adapter.

Class A

Class B

Class C

IP Address

The IP address identifies each node on the IP network (or system of connected networks). Each TCP/IP node on a network (including the adapter) must have a unique IP address.

The IP address is 32 bits long and has a Network ID part and Host ID part. Networks are classified A, B, C, (or other). The class of the network determines how an IP address is formatted.

0

7

8

 

 

 

31

0

Network ID

 

 

Host ID

 

 

 

 

 

 

 

 

0

 

 

15 16

 

31

10

Network ID

 

 

Host ID

 

 

 

 

 

 

 

 

0

 

 

23 24

31

110

 

Network ID

 

 

 

Host ID

 

 

 

 

 

 

 

You can distinguish the class of the IP address from the first integer in its dotteddecimal IP address as follows:

Range of first integer

Class

 

Range of first integer

Class

 

 

 

 

 

0 1…127

A

 

192…223

C

 

 

 

 

 

128…191

B

 

224… 255

other

 

 

 

 

 

Each node on the same physical network must have an IP address of the same class and must have the same network ID. Each node on the same network must have a different Host ID thus giving it a unique IP address.

IP addresses are written as four decimal integers (0…255) separated by periods where each integer gives the value of one byte of the IP address.

EXAMPLE For example, the 32-bit IP address:

10000000 00000001 00000000 00000001 is written as 128.1.0.1

Rockwell Automation Publication 1734-UM018B-EN-E - October 2013

19

Chapter 3 Configure the Adapter with RSLogix5000 software

Gateway Address

This section applies to multi-network systems. If you have a single network system, refer to the next section.

The Gateway Address is the default address of a network. It provides a single domain name and point of entry to the site. Gateways connect individual physical networks into a system of networks.

When a node needs to communicate with a node on another network, a gateway transfers the data between the two networks. The figure shows gateway G connecting Network 1 with Network 2.

A

128.1.0.1

 

 

 

 

 

 

 

Network 1

 

128.1.0.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

128.2.0.1

 

128.2.0.2

 

128.2.0.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network 2

 

 

 

When host B with IP address 128.2.0.1 communicates with host C, it knows from C’s IP address that C is on the same network. in an Ethernet environment, B can then resolve C’s IP address into a hardware address (MAC address) and communicate with C directly.

When host B communicates with host A, it knows from A’s IP address that A is on another network (the network IDs are different). In order to send data to A, B must use the IP address of the gateway connecting the two networks. In this example, the gateway’s IP address on Network 2 is 128.2.0.3.

The gateway has two IP addresses (128.1.0.2 and 128.2.0.3). The first must be used by hosts on Network 1 and the second must be used by hosts on Network 2. To be usable, a gateway of a host must be addressed using a network ID matching its own.

20

Rockwell Automation Publication 1734-UM018B-EN-E - October 2013

Loading...
+ 88 hidden pages