Rockwell Automation 1606-XLSRED40 User Manual

4.5 (2)

Reference Manual

Bulletin 1606 Switched Mode Power Supplies

Catalog Number: 1606-XLSRED40

Index

 

 

Page

 

 

 

Page

1.

Intended Use .......................................................

3

14.

Certifications ....................................................

12

2.

Installation Requirements...................................

3

15.

Physical Dimensions and Weight .....................

13

3.

Input and Output Characteristics .......................

4

16.

Accessories ........................................................

14

4.

Power Losses........................................................

5

17.

Application Notes.............................................

15

5.

Lifetime Expectancy and MTBF...........................

6

17.1.

Recommendations for Redundancy.........

15

6.

Terminals and Wiring..........................................

7

17.2. Inductive and Capacitive Loads................

15

7.

Functional Diagram.............................................

8

17.3.

Lateral Installation Clearances ............

15

8.

Front Side and User Elements.............................

8

17.4. 1+1 Redundancy up to 20A......................

16

9.

EMC......................................................................

9

17.5. N+1 Redundancy, Example with 60A ......

16

10.

Environment ......................................................

10

17.6.

Mounting Orientations ............................

17

11.

Protection Features ...........................................

11

 

 

 

 

12.

Safety Features..................................................

11

 

 

 

 

13.

Dielectric Strength ............................................

11

 

 

 

 

Terminology and Abbreviations

PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .

Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.

T.b.d.—To be defined, value or description will follow later.

DC 24V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery whether it is full (13.7V) or flat (10V)

24Vdc—A figure with the unit (Vdc) at the end is a momentary figure with no additional tolerance included.

may, shall, should—Three key words indicating, respectively: flexibility of choice with no implied preference, a mandatory requirement, flexibility of choice

1+1 Redundancy—Use of two identical power supplies in parallel to provide continued operation following most failures in a single power supply. The two power supply outputs should be isolated from each other by using diodes or other switching arrangements. E.g. two 10A power supplies are needed to achieve a 10A redundant system.

N+1 Redundancy—Use of three or more identical power supplies in parallel to provide continued operation following most failures in a single power supply. All power supply outputs should be isolated from each other by using diodes or other switching arrangements. E.g. to achieve a 40A redundant system, five 10A power supplies are required in a N+1 redundant system.

 

 

N+1

 

 

 

 

Redundancy

 

 

AC

AC

AC

AC

AC

AC

DC

DC

DC

DC

DC

DC

IN 1

IN 2

IN 1

IN 2

IN 1

IN 2

OUT

OUT

OUT

 

+

-

 

 

 

 

Load

 

 

 

1+1

Redundancy

AC

AC

DC

DC

IN 1

IN 2

OUT

+

-

Load

Bulletin 1606 Switched Mode Power Supplies

Mosfet Redundancy Module

For N+1 and 1+1 Redundant Systems Dual Input with Single Output Suitable for all Power Supplies

Only 72mV Voltage Drop at 20A Output Current

Only 2.15W Loss at 20A and 6.3W at 40A Output Current 160% (65A) Peak Load Capability

Reverse Input Polarity Protection Full Power Between -40°C and +70°C Width only 36mm

Rugged Metal Housing Easy Wiring:

Distribution Terminal for Negative Pole Included 3 Year Warranty

Description

The 1606-XLSRED40 is a redundancy module which can be used to build 1+1 and N+1 redundant systems. It is equipped with two input channels, which can be connected to power supplies with up to 20A output current and one output, which can carry nominal currents up to 40A. The module is suitable for power supplies with constant current overload behavior as well as any kind of “Hiccup” overload behavior.

The novelty of this redundancy module is the utilization of mosfets instead of diodes for the decoupling of the two input channels. This reduces the heat generation and the voltage drop between input and output. The redundancy module does not require an additional auxiliary voltage and is self-sufficient even in case of a short circuit across the output.

Due to the low power losses, the unit is very slender and only requires 36mm width on the DIN rail. Large connection terminals allow for a safe and fast installation with a large international approval package. This unit is suitable for nearly every application.

Catalog Numbers

Redundancy 1606-XLSRED40 12-28V Standard unit

Module

Accessory

1606-XLC

Wall/panel mount

 

 

bracket

Specification Quick Reference

 

 

Input voltage

 

DC 12-28V

±30%

 

 

 

Input voltage

 

8.4-36.4Vdc

 

 

 

 

range

 

 

 

 

 

 

Input current

 

2x 0-20A

continuous

 

 

 

 

 

2x 20-32.5A

for 5 seconds

 

 

 

Output current

 

0-40A

continuous

 

 

 

 

 

40-65A

for 5 seconds

 

 

 

 

 

65A

at cont. overload

 

 

 

 

 

 

or short circuit

 

 

 

Input to output

typ. 72mV

input: 2x10A

 

 

 

voltage drop

 

typ. 112mV

input: 1x20A

 

 

 

 

 

typ. 140mV

input: 2x20A

 

 

 

Power losses

 

typ. 700mW

at no load

 

 

 

 

 

typ. 2.15W

input: 2x10A

 

 

 

 

 

typ. 2.65W

input: 1x20A

 

 

 

 

 

typ. 6.3W

input: 2x20A

 

 

 

Temperature range

-40°C to +70°C

operational,

 

 

 

 

 

 

no de-rating req.

 

 

 

Dimensions

 

36x124x127mm*) WxHxD

 

 

 

*) plus 4mm in depth for the screw terminal

 

 

 

 

Certification Marks

 

 

 

 

 

 

 

 

IND. CONT. EQ.

UL 60950-1

 

 

 

 

 

 

 

 

UL 508

 

Class I Div 2

 

 

 

 

 

 

 

 

IECEx

ATEX

Marine

EMC, LVD

 

 

 

II 3G Ex nA IIC T4 Gc

 

 

All parameters are specified at 24V, 40A output current, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

2

Rockwell Automation Publication 1606-RM010A-EN-P — February 2014

Bulletin 1606 Switched Mode Power Supplies

1. Intended Use

This redundancy module is designed for installation in an enclosure and is intended for general use such as in industrial control, office, communication and instrumentation equipment.

This redundancy module can be used with any type of power supply as long as the maximum ratings are not exceeded. It is suitable for power supplies with constant current overload behavior as well as any kind of “Hiccup” overload behavior.

Do not use this redundancy module in equipment where malfunction may cause severe personal injury or threaten human life.

This device is designed for use in hazardous, non-hazardous, ordinary or unclassified locations.

2. Installation Requirements

This device may only be installed and put into operation by qualified personnel.

This device does not contain serviceable parts.

If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection.

Mount the unit on a DIN rail so that the input terminals are located on top and the output terminals on the bottom of the unit. For other mounting orientations, see derating requirements in the present document (refer to section 17.6).

This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%!

Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase the side clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply). See section 17.3 for further information in combination with poser supplies.

SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth connection and not one of the screws on the housing.

-Turn power off before working on the device. Protect against inadvertent re-powering

-Make sure that the wiring is correct by following all local and national codes

-Do not modify or repair the unit

-Do not open the unit as high voltages are present inside

-Use caution to prevent any foreign objects from entering the housing

-Do not use in wet locations or in areas where moisture or condensation can be expected

-Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.

WARNING: EXPLOSION HAZARDS!

Substitution of components may impair suitability for this environment. Do not disconnect the unit unless power has been switched off or the area is known to be non-hazardous.

A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and meets the requirements of the EN 60079-15:2010.

Notes for use in hazardous location areas:

The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group II Category 3 (Zone 2) environments and is evaluated according to EN 60079-0:2009 and EN 60079-15:2010.

All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise.

 

Rockwell Automation Publication 1606-RM010A-EN-P — February 2014

3

Bulletin 1606 Switched Mode Power Supplies

3. Input and Output Characteristics

Number of inputs

-

2

 

Number of outputs

-

1

 

Input voltage

nom.

DC 12-28V ±30%

The input circuitry must meet the SELV requirements

 

 

 

 

stipulated by IEC/EN/UL 60950-1.

Input voltage range

-

8.4-36.4Vdc

 

 

 

 

 

Voltage drop, input to output

typ.

140mV

at 2x20A, see Fig. 3-1

 

 

typ.

72mV

at 2x10A, see Fig. 3-1

 

 

typ.

112mV

at 1x20A, see Fig. 3-2

Input current

nom.

2x 0-20A

continuous

 

 

nom.

2x 20-32.5A

for 5 seconds

 

 

max

2x 32.5A

at continuous overload or short circuit

Peak input current

max.

1000A

for max. 1ms per input

Output current

nom.

40A

continuous

 

 

nom.

40-65A

for 5 seconds

 

 

max.

65A

at continuous overload or short circuit

Reverse current

max.

1mA

at 24V, per input, -40°C to +70°C

Reverse voltage

max.

40Vdc

voltage applied to the output, continuously allowed

Output capacitance

typ.

320μF

 

Note:

Ensure that the continuous output current does not exceed 65A. Check the short-circuit current of the power sources and if the

 

power source can deliver more than 65A together, use an appropriate fuse on the output.

Fig. 3-1 Input to output voltage drop when both inputs draw current

(typical 1+1 redundant case, when the output voltages of the two units are equal)

160mV

Voltage Drop, typ

 

 

 

 

 

 

XLSRED40

 

Output

Variable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24V,20A

 

I1

 

 

IOUT

 

Load,

140mV

 

 

 

 

 

 

 

 

 

0-40A

 

A... 25°C

 

B

A

 

 

+

A

 

 

A

 

 

120mV

 

 

 

 

 

V U1

Input 1

Output

UOUT

V

 

 

B... 60°C

 

 

 

 

 

-

 

100mV

 

 

 

 

 

 

 

 

 

 

 

 

 

80mV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60mV

 

 

 

 

 

24V,20A

 

I2

 

 

 

 

 

40mV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

A

 

 

 

 

 

20mV

 

Input / Output Current

 

 

-

V U2

Input 2

 

 

 

 

0mV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output:

0

10A

20A

30A

40A

I1

= I2

 

U1 = U2

 

Voltage Drop = U1 - UOUT

Input:

0

2x5A

2x10A

2x15A

2x20A

 

 

 

 

 

 

 

 

 

 

 

Fig. 3-2 Input to output voltage drop when only one input draws current

Voltage Drop, typ.

 

 

 

 

XLSRED40

 

Output

Variable

160mV

 

 

 

 

 

 

 

 

 

 

 

 

 

24V,20A

I1

 

 

OUT

 

Load,

140mV

 

 

 

 

 

 

I

 

0-20A

A... 25°C

 

 

 

+

A

 

 

A

 

 

120mV

 

 

 

V U1

Input 1

Output

UOUT

V

 

B... 60°C

 

 

 

-

 

 

 

 

 

 

100mV

 

 

B

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80mV

 

 

 

 

 

 

 

 

 

 

 

60mV

 

 

 

 

 

 

 

 

 

 

 

40mV

 

 

 

 

Not used or

 

 

 

 

 

 

 

 

 

 

power supply

 

Input 2

 

 

 

 

20mV

 

 

 

 

 

 

 

 

 

 

 

 

 

with lower

 

 

 

 

 

 

Output Current

 

 

 

 

 

 

0mV

 

voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5A

10A

15A

20A

 

 

 

Voltage Drop = U1 - UOUT

 

All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise.

4

Rockwell Automation Publication 1606-RM010A-EN-P — February 2014

Rockwell Automation 1606-XLSRED40 User Manual

Bulletin 1606 Switched Mode Power Supplies

4. Power Losses

DC 24V

Power losses

typ.

2.15W

input: 2x10A

 

typ.

6.3W

input: 2x20A

 

typ.

2.6W

input: 1x20A,

 

 

 

(only one input is connected to input voltage)

Standby power losses

typ.

0.35W

at no output current,

 

 

 

(only one input is connected to input voltage)

 

typ.

0.7W

at no output current,

 

 

 

(both inputs are connected to input voltages)

Fig. 4-1 Power losses when both inputs draw equal current

Power Losses, typ.

 

 

 

 

 

 

 

 

 

XLSRED40

 

Output

Variable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24V,20A

 

I1

 

 

IOUT

 

Load,

7W

 

 

 

 

 

 

 

 

 

 

 

 

0-40A

 

 

 

 

 

 

 

 

 

+

A

 

 

A

 

 

6.0

 

 

 

 

 

 

 

 

e.g.

 

V U1

Input 1

Output

UOUT

V

 

A... 25°C

 

 

 

 

 

 

24.5V

-

 

5.0

 

 

 

 

 

 

 

 

 

 

 

 

 

B... 60°C

 

 

 

B

A

 

 

 

 

 

 

 

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

 

 

 

 

 

 

 

 

24V,20A

 

I2

 

 

 

 

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

A

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

e.g.

 

V U2

Input 2

 

 

 

 

 

 

 

Output Current

 

24.5V

-

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5

10

15

20

25

30

35

40A

I1 = I2

 

U1 = U2

 

Losses = ( U1* I1 + U2* I2 ) - UOUT * IOUT

Fig. 4-2 Power losses when only one input is used

Power Losses, typ.

 

 

 

 

 

 

XLSRED40

 

Output

Variable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4W

 

 

 

 

 

 

 

24V,20A

I1

 

 

IOUT

 

Load,

 

 

 

 

 

 

 

 

 

 

0-20A

3.5

 

 

 

 

 

 

 

+

A

 

 

A

 

 

A... 25°C

 

 

 

 

 

 

V U1

Input 1

Output

UOUT

V

 

3.0

 

 

 

 

 

 

 

B... 60°C

 

 

 

 

 

-

 

 

 

 

 

 

2.5

 

 

 

 

 

 

B

A

 

 

 

 

 

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

 

Input 2

 

 

 

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Current

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Losses = U1

* I1 - UOUT * IOUT

 

 

 

0

2.5

5

7.5

10

12.5

15

17.5 20A

 

 

 

 

 

 

 

 

 

 

Note: As soon as voltage is applied on input 2, an additional 0.35W will be consumed. It is not relevant whether this channel contributes to the output current or not.

All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise.

 

Rockwell Automation Publication 1606-RM010A-EN-P — February 2014

5

Bulletin 1606 Switched Mode Power Supplies

5. Lifetime Expectancy and MTBF

The redundancy module has two input channels which are completely independent from each other. Each control circuit, auxiliary voltage source, or other circuitry in the module are designed separately for each input. The dual input redundancy module can be considered as two single redundancy modules combined together in one housing. The only common point is the circuit trace that ties the two separate circuits together at the output.

The MTBF figures below are for the entire dual input module. If the MTBF number of only one path is needed, simply double the value from the table.

Input / output current

Input: 2x10A

Input: 2x20A

 

conditions

Output: 20A

Output: 40A

 

 

 

 

 

Lifetime expectancy*)

649 000h *)

246 000h *)

at 24V and 40°C

 

 

1 835 000h *)

696 000h *)

at 24V and 25°C

MTBF**)

SN 29500, IEC 61709

3 386 000h

2 706 000h

at 24V 40°C

 

 

5 667 000h

4 686 000h

at 24V 25°C

MTBF**)

MIL HDBK 217F

116 000h

97 000h

Ground Fixed GF40 (24V and 40°C)

 

 

155 000h

128 000h

Ground Fixed GF25 (24V and 25°C)

 

 

612 000h

522 000h

Ground Benign GB40 (24V and 40°C)

 

 

813 000h

687 000h

Ground Benign GB25 (24V and 25°C)

*) The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer specification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years (131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.

**) MTBF stands for Mean Time Between Failure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product. The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that

statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it can not be determined if the failed unit has been running for 50 000h or only for 100h.

 

All parameters are specified at 24V, 40A output current, 26°C ambient and after a 5 minutes run-in time, unless noted otherwise.

6

Rockwell Automation Publication 1606-RM010A-EN-P — February 2014

Loading...
+ 12 hidden pages