Rockwell Automation 1606-XLP15A User Manual

0 (0)

Reference Manual

Bulletin 1606 Switched Mode Power Supplies

Catalog Number: 1606-XLP15A

Index

 

 

Page

 

 

 

Page

1.

Intended Use .......................................................

3

18. Certifications ...................................................

15

2.

Installation Requirements...................................

3

19.

Physical Dimensions and Weight .....................

16

3.

AC-Input...............................................................

4

20.

Application Notes .............................................

17

4.

DC-Input...............................................................

5

20.1.

Peak Current Capability ...........................

17

5.

Input Inrush Current ...........................................

5

20.2.

Back-feeding Loads ..................................

17

6.

Output .................................................................

6

20.3.

External Input Protection .........................

18

7.

Hold-up Time.......................................................

7

20.4.

Parallel Use to Increase Output Power ....

18

8.

Efficiency and Power Losses................................

8

20.5.

Parallel Use for Redundancy ....................

19

9.

Functional Diagram.............................................

9

20.6.

Series Operation .......................................

19

10.

Front Side and User Elements.............................

9

20.7.

Inductive and Capacitive Loads ................

19

11.

Terminals and Wiring........................................

10

20.8.

Operation on Two Phases ........................

20

12.

Lifetime Expectancy and MTBF.........................

10

20.9.

Use Without PE on the Input ...................

20

13.

EMC ....................................................................

11

20.10. Use in a Tightly Sealed Enclosure ............

21

14.

Environment ......................................................

12

20.11. Mounting Orientations ............................

22

15.

Protection Features ...........................................

13

 

 

 

 

16.

Safety Features ..................................................

13

 

 

 

 

17.

Dielectric Strength ............................................

14

 

 

 

 

Terminology and Abbreviations

PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .

Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.

T.b.d.—To be defined, value or description will follow later.

AC 230V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%) included. E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)

230Vac—A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included.

50Hz vs. 60Hz—As long as not otherwise stated, AC 230V parameters are valid at 50Hz mains frequency.

may—A key word indicating flexibility of choice with no implied preference.

shall—A key word indicating a mandatory requirement.

should—A key word indicating flexibility of choice with a strongly preferred implementation.

Bulletin 1606 Switched Mode Power Supplies

Power Supply

100-240V Wide Range Input NEC Class 2 Compliant Adjustable Output Voltage Efficiency up to 77.2%

Compact Design, Width only 22.5mm

Full Output Power Between -10°C and +60°C Large International Approval Package

3 Year Warranty

Description

Compact size, light weight, simple installation onto the DIN rail and the integration of only the highest quality components are the factors that make the XLP family of power supplies so easy to deploy and use within seconds.

A rugged electrical and mechanical design as well as high immunity against electrical disturbances on the mains provide reliable output power. This power supply offers superior protection for equipment connected to the public mains network or exposed to a critical industrial environment.

The XLP family of power supplies offers output voltages from 5 to 56Vdc and power ratings from 15W to 120W.

Specification Quick Reference

Output voltage

DC 5V

 

Adjustment range

5 – 5.5V

 

Output current

3A at 5V

 

Output power

15W

 

Output ripple

< 50mVpp

20Hz to 20MHz

Input voltage

AC 100-240V

-15% / +10%

Mains frequency

50-60Hz

±6%

AC Input current

0.28 / 0.17A

at 120 / 230Vac

Power factor

0.51 / 0.44

at 120 / 230Vac

AC Inrush current

typ. 16 /31A

peak value at

 

 

120/230Vac, 40°C

 

 

and cold start

DC Input

88-375Vdc

 

Efficiency

76.8 / 77.2%

at 120 / 230Vac

Losses

4.6 / 4.5W

at 120 / 230Vac

Temperature range

-10°C to +70°C

operational

Derating

0.4W/°C

+60 to +70°C

Hold-up time

typ. 45 / 186ms

at 120 / 230Vac

Dimensions

22.5x75x91mm

WxHxD

Weight

130g / 0.29lb

 

 

Catalog Numbers

 

 

 

Certifications

 

 

 

 

 

1606-XLP15A

 

 

 

 

 

 

 

 

Power Supply

5V Standard unit

 

 

 

 

 

 

 

 

 

 

 

UL 60950-1

Class I Div 2

 

 

 

 

 

 

 

 

UL 508

NEC Class 2

 

Marine RINA

 

 

 

 

 

 

CSA 22.2 No107.1

Marine EMC, LVD

GOST R

C-Tick

 

 

 

 

 

 

 

 

 

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

2

Rockwell Automation Publication 1606-RM019A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

1. Intended Use

This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment.

Do not use this power supply in equipment where malfunction may cause severe personal injury or threaten human life.

This device is designed for use in non-hazardous, ordinary or unclassified locations.

2. Installation Requirements

This device may only be installed and put into operation by qualified personnel.

This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.

Should damage or malfunction occur during installation or operation, immediately turn power off and send unit to the factory for inspection.

Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to Mounting.

This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%!

Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).

SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for earth connection and not one of the screws on the housing.

-Turn power off before working on the device. Protect against inadvertent re-powering

-Make sure that the wiring is correct by following all local and national codes

-Do not modify or repair the unit

-Do not open the unit as high voltages are present inside

-Use caution to prevent any foreign objects from entering the housing

-Do not use in wet locations or in areas where moisture or condensation can be expected

-Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.

WARNING: EXPLOSION HAZARDS!

Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous.

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

 

Rockwell Automation Publication 1606-RM019A-EN-P — March 2014

3

Bulletin 1606 Switched Mode Power Supplies

3. AC Input

AC input

nom.

AC 100-240V

-15% / +10%, TN/TT/IT-mains

AC input range

 

85-264Vac

continuous operation

 

 

 

264–300Vac

< 0.5s

 

 

Allowed voltage L or N to earth

max.

300Vac

 

 

 

Input frequency

nom.

50–60Hz

±6%

 

 

Turn-on voltage

typ.

59Vac

steady-state value, see Fig. 3-1

Shut-down voltage

typ.

54Vac

steady-state value, see Fig. 3-1

 

 

AC 100V

AC 120V

AC 230V

 

Input current (rms)

typ.

0.34A

0.28A

0.17A

at 5V, 3A see Fig. 3-3

 

 

 

 

 

 

Power factor *)

typ.

0.52

0.51

0.44

at 5V, 3A see Fig. 3-4

Crest factor **)

typ.

3.45

3.53

3.94

at 5V, 3A

Start-up delay

typ.

630ms

630ms

630ms

see Fig. 5 2

Rise time

typ.

10ms

10ms

10ms

at 5V, 3A, see Fig. 3-2

 

 

 

 

 

 

Turn-on overshoot

max.

100mV

100mV

100mV

see Fig. 3-2

*)

The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.

**)

The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.

 

Fig. 3-1 Input voltage range

Fig. 3-2 Turn-on behavior, definitions

POUT

Rated

max.

input range

 

 

500ms

Shut-down

Turn-on

VIN

 

 

54V 59V 85V

264V 300Vac

Intput

 

 

 

Voltage

 

 

 

Output

- 5%

 

Overshoot

 

 

Voltage

 

 

 

Start-up

Rise

 

delay

Time

Fig. 3-3 Input current vs. output load

Input Current, typ.

0.4A

0.35

 

a) 100Vac

a

 

 

 

 

0.30b) 120Vac b

0.25

 

c) 230Vac

 

0.20

0.15 c

0.10

0.05

Output Current

0

0 0.5 1.0 1.5 2.0 2.5 3.0A

Fig. 3-4 Power factor vs. output load

Power Factor, typ.

 

 

 

 

0.55

a) 100Vac

 

 

 

a

 

 

 

 

0.50

b) 120Vac

 

 

 

 

 

 

b

 

c) 230Vac

 

 

 

 

0.45

 

 

 

 

c

0.40

 

 

 

 

 

0.35

 

Output Current

 

 

0.30

 

 

 

 

 

 

 

 

0.5

1.0

1.5

2.0

2.5

3.0A

 

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

4

Rockwell Automation Publication 1606-RM019A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

4. DC Input

DC input

nom.

DC 110-300V

-20%/+25%

DC input range

min.

88-375Vdc

continuous operation

DC input current

typ.

0.16A / 0.057A

110Vdc / 300Vdc, at 5V, 3A

 

 

 

 

Turn-on voltage

typ.

80Vdc

steady state value

Shut-down voltage

typ.

60Vdc

steady state value

 

 

 

Fig. 4-1

Wiring for DC Input

Instructions for DC use:

Battery

Power Supply

+

AC

L

internal

fused

 

+

N

Load

PE

-

 

-

DC

a)Use a battery or similar DC source.

For other sources, please contact Rockwell Automation.

b)Connect +pole to L and –pole to N.

c)Connect the PE terminal to an earth wire or to the machine ground.

5. Input Inrush Current

A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and ambient temperature dependent.

The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.

 

 

AC 100V

AC 120V

AC 230V

 

Inrush current

max.

13Apeak

16Apeak

31Apeak

40°C ambient, cold start

 

typ.

11Apeak

13Apeak

26Apeak

40°C ambient, cold start

Inrush energy

max.

0.1A2s

0.1A2s

0.4A2s

40°C ambient, cold start

Fig. 5-1 Input inrush current, typical behavior

Fig. 5-2

Input inrush current, zoom into first peak

Input:

230Vac

 

 

Output:

5V, 3A

Output:

5V, 3A

Ambient:

25°C

Ambient:

25°C

Upper curve:

Input current 5A/DIV

Input current curve: 5A/DIV, 500μs / DIV

Lower curve:

Input voltage 500V/DIV

Ipeak

23A

Time basis:

10ms / DIV

 

 

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

 

Rockwell Automation Publication 1606-RM019A-EN-P — March 2014

5

Bulletin 1606 Switched Mode Power Supplies

6. Output

Output voltage

nom.

5V

 

Adjustment range

min.

5-5.5V

guaranteed

 

max.

6V *)

at clockwise end position of potentiometer

Factory setting

 

5.1V

±0.2%, at full load, cold unit

Line regulation

max.

10mV

85-264Vac

Load regulation

max.

100mV

static value, 0A 3A

Ripple and noise voltage

max.

50mVpp

20Hz to 20MHz, 50Ohm

 

 

 

 

Output capacitance

typ.

4 800μF

 

 

 

 

 

Output current

nom.

3A

at 5V, see Fig. 6-1

 

nom.

2.72A

at 5.5V, see Fig. 6-1

 

 

 

 

Output power

nom.

15W

 

Short-circuit current

min.

hiccup mode

see Fig. 6-2

 

max.

3A rms-current

short circuit impedance <10mOhm, unit makes start-up

 

 

 

attempts at short-circuit (hiccup mode)

*) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. There is no guarantee this value can be achieved. The typical value achievable by turning the potentiometer to the clockwise end position

is 5.8V.

Fig. 6-1 Output voltage vs. output current, typ.

Fig. 6-2 Hiccup mode; output current at shorted output, 230Vac, typ.

Output Voltage

 

Adjustment

 

6V

 

 

 

 

Range

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

3

 

Continuous

 

 

 

 

2

 

Hiccup Mode

 

 

 

 

 

 

 

 

 

 

 

1

 

Output Current

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

0

0.5

1.0

1.5

2.0

2.5

3.0

3.5A

Output

45ms

Current

3.3A

 

0

t

 

235ms

235ms

Peak current capability (up to several milliseconds)

The power supply can deliver a peak current which is higher than the specified short term current. This helps to start current demanding loads or to safely operate subsequent circuit breakers.

The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be discharged and causes a voltage dip on the output. Detailed curves can be found in section 20.1.

Peak current voltage dips

typ.

from 5V to 2.4V

at 6A for 50ms, resistive load

 

typ.

from 5V to 1.0V

at 15A for 2ms, resistive load

 

typ.

from 5V to 0.8V

at 15A for 5ms, resistive load

 

 

 

 

 

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

6

Rockwell Automation Publication 1606-RM019A-EN-P — March 2014

 

 

 

 

 

 

 

Bulletin 1606 Switched Mode Power Supplies

 

 

 

 

 

 

 

 

 

 

 

7. Hold-up Time

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AC 100V

AC 120V

AC 230V

 

 

 

 

 

 

 

 

 

 

 

Hold-up Time

typ.

61ms

93ms

340ms

at 5V, 1.5A, see Fig. 7-1

 

 

 

typ.

29.5ms

45ms

186ms

at 5V, 3A, see Fig. 7-1

Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on at this time.

Fig. 7-1 Hold-up time vs. input voltage

Hold-up Time

150ms

 

a

b

c

d

 

 

 

 

 

125

 

 

 

 

 

100

 

 

 

 

 

75

 

 

 

a) 5V 1.5A typ.

 

 

 

b) 5V 1.5Amin.

 

 

 

 

50

 

 

 

c) 5V 3A typ.

 

 

 

d) 5V 3A min.

 

 

 

 

25

 

Input Voltage

 

0

 

 

 

 

 

 

 

85

120

155

 

190

230Vac

Fig. 7-2 Shut-down behavior, definitions

Zero Transition

Input

Voltage

Output

 

 

 

- 5%

 

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

 

 

Hold-up Time

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

 

Rockwell Automation Publication 1606-RM019A-EN-P — March 2014

7

Rockwell Automation 1606-XLP15A User Manual

Bulletin 1606 Switched Mode Power Supplies

8. Efficiency and Power Losses

 

 

AC 100V

AC 120V

AC 230V

 

Efficiency

typ.

75.8%

76.8%

77.2%

at 5V, 3A (full load)

Power losses

typ.

0.2W

0.3W

0.6W

at 0A

 

typ.

2.3W

2.3W

2.4W

at 5V, 1.5A (half load)

 

typ.

4.9W

4.6W

4.5W

at 5V, 3A (full load)

Fig. 8-1 Efficiency vs. output current at 5V, typ.

Fig. 8-2 Losses vs. output current at 5V, typ.

Efficiency

 

 

 

 

 

 

Power Losses

 

 

 

 

 

 

 

 

 

 

 

5W

 

 

 

 

 

a

78%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

c

 

a) 100Vac

 

 

 

b

77

 

 

 

 

 

4

b) 120Vac

 

 

 

c

76

 

 

 

 

 

b

 

c) 230Vac

 

 

 

 

 

 

 

 

 

a

3

 

 

 

 

 

 

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

 

 

 

a) 100Vac

2

 

 

 

 

 

 

73

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

 

 

 

b) 120Vac

1 c

 

 

 

 

 

 

 

 

 

c) 230Vac

 

 

 

 

 

 

71

 

Output Current

 

 

b

 

Output Current

 

70

 

 

 

0 a

 

 

 

 

 

 

 

 

 

 

 

 

0

0.5

1.0

1.5

2.0

2.5

3.0A

0

0.5

1.0

1.5

2.0

2.5

3.0A

 

 

 

 

 

 

 

Fig. 8-3 Efficiency vs. input voltage at 5V, 3A, typ.

Efficiency

 

 

 

 

78%

 

 

 

 

77

 

 

 

 

76

 

 

 

 

75

 

 

 

 

74

 

 

 

 

73

 

Input Voltage

 

72

 

 

 

 

 

 

85

120

155

190

225 260Vac

Fig. 8-4 Losses vs. input voltage at 5V, 3A, typ.

Power Losses

 

 

 

5W

 

 

 

 

4.75

 

 

 

 

4.50

 

 

 

 

4.25

 

 

 

 

4.00

 

 

 

 

3.75

 

Input Voltage

 

 

 

 

 

85

120

155

190

225 260Vac

 

All parameters are specified at 5V, 3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.

8

Rockwell Automation Publication 1606-RM019A-EN-P — March 2014

Loading...
+ 16 hidden pages