Pilz PNOZ mm0p 24VDC User Manual

5 (1)

PNOZmulti communication interfaces

Configurable Control System PNOZmulti

Operating Manual-1001154-EN-13

This document is a translation of the original document.

All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.

Pilz®, PIT®, PMI®, PNOZ®, Primo®, PSEN®, PSS®, PVIS®, SafetyBUS p®, SafetyEYE®, SafetyNET p®, the spirit of safety® are registered and protected trademarks of Pilz GmbH & Co. KG in some countries.

SD means Secure Digital

Content

Section 1

Introduction

7

 

1.1

Definition of symbols

7

 

 

 

Section 2

Overview - Communication options

8

 

2.1

Communication via the fieldbus modules

8

 

2.2

Communication via the RS232/ETH interfaces

9

 

2.3

Communication via Modbus/TCP

10

 

 

 

 

Section 3

Safety

 

11

 

3.1

Intended use

11

 

3.2

Safety regulations

11

 

3.2.1

Use of qualified personnel

11

 

3.2.2

Warranty and liability

11

 

3.2.3

Disposal

12

 

 

 

Section 4

Fieldbus modules

13

 

4.1

Basics

13

 

4.1.1

Input data (to the PNOZmulti)

13

 

4.1.2

Output data (from the PNOZmulti)

13

 

4.1.3

Note on the PNOZ mc6p (CANopen)

14

 

4.1.4

Assignment of Byte 0 ... Byte 3

16

 

4.1.5

Assignment of Byte 4 ... Byte 18

17

 

4.1.5.1

Example 1

20

 

4.1.5.2

Example 2

21

 

4.2

PNOZ mc2p, PNOZ mc2.1p, PNOZ mmc11p (SDO and PDO)

21

 

4.2.1

Overview

21

 

4.2.1.1

PNOZ mc2p

21

 

4.2.1.2

PNOZ mc2.1p/PNOZ mmc11p

22

 

4.2.2

Object Directory (Manufacturer Specific Profile Area)

23

 

4.2.2.1

SDO Index 0x2000

23

 

4.2.2.2

SDO Index 0x2001 and Index 0x2002

28

 

4.2.2.3

SDO Index 0x2003

29

 

4.2.2.4

SDO Index 0x2100

34

 

4.2.2.5

SDO Index 0x2004

34

 

4.2.2.6

SDO Index 0x2005

37

 

4.3

PNOZ mc6p, PNOZ mc6.1p, PNOZ mmc6p, PNOZ mc12p (SDO)

38

 

4.3.1

Overview

38

 

4.3.2

System requirements

38

 

4.3.3

Object Directory

39

 

4.3.3.1

Index 2000

39

 

4.3.3.2

Index 2001 and 2002

42

 

4.3.3.3

Index 2003

44

 

4.3.3.4

Index 2004

48

 

4.3.3.5

Index 2005

51

 

4.3.3.6

Index 2100

51

 

4.4

PNOZ mc8p Ethernet IP / Modbus TCP

51

 

4.4.1

Introduction

51

Operating Manual PNOZmulti communication interfaces

3

1001154-EN-13

 

Content

 

4.4.2

Overview

51

 

4.4.3

Module features

52

 

4.4.4

Assigning the IP address to your PC

52

 

4.4.5

Setting the IP address of the expansion module

52

 

4.4.6

Changing IP settings

52

 

4.4.7

Data exchange

53

 

4.4.7.1

Ethernet IP

53

 

4.4.7.2

Modbus TCP

53

 

4.4.8

Web interface for commissioning and testing

54

 

4.4.9

Restricting access

54

 

4.4.10

Input and output data

55

 

4.4.10.1

Assigning the inputs/outputs in the PNOZmulti Configurator to the Ether-

55

 

 

net IP/Modbus TCP input/output data

 

 

4.5

PNOZ mc10p sercos III

56

 

4.5.1

Overview

56

 

4.5.2

System requirements

56

 

4.5.3

Object buffer

57

 

4.5.3.1

Output data

57

 

4.5.3.2

Diagnostic word

59

 

4.5.3.3

Status of the inputs, outputs and LEDs

60

 

4.5.3.4

Configuration

64

 

4.5.3.5

Element types

67

 

4.5.3.6

Input data

67

 

4.5.3.7

Diagnostic data

68

 

4.5.4

Firmware/FPGA update

69

 

4.5.5

Forcing the virtual input data

70

 

4.5.6

Communication with the sercos III Master

70

 

4.5.6.1

Synchronous data exchange

70

 

4.5.6.2

Asynchronous data access

71

 

4.5.7

Sercos Master interface

72

 

4.5.7.1

Supported profiles

72

 

4.5.7.2

Default settings

73

 

4.5.7.3

Description of IDNs

73

 

4.5.7.4

Communication channels with the PNOZmulti

74

 

4.5.7.5

Diagnostics

74

 

 

 

Section 5

RS232/Ethernet interfaces

75

 

5.1

Overview

75

 

5.2

System requirements

75

 

5.3

Interface description

75

 

5.3.1

Ethernet interfaces

75

 

5.3.1.1

RJ45 interfaces ("Ethernet")

76

 

5.3.1.2

Requirements of the connection cable and connector

76

 

5.3.1.3

Interface configuration

77

 

5.3.1.4

RJ45 connection cable

77

 

5.3.1.5

Process data exchange

77

 

5.3.2

Serial interface RS232

78

Operating Manual PNOZmulti communication interfaces

4

1001154-EN-13

 

Content

 

5.4

Communication procedure

78

 

5.5

Telegram structure

79

 

5.5.1

Header

80

 

5.5.2

Usable data

80

 

5.5.3

Information data

80

 

5.6

Usable data

81

 

5.6.1

Virtual inputs (Input Byte 0 ... Input Byte 15)

81

 

5.6.1.1

Mask (Mask Byte 0 ... Mask Byte 15)

81

 

5.6.1.2

Watchdog

81

 

5.6.2

Virtual outputs (Output Byte 0 ... Output Byte 15)

81

 

5.6.3

LED status

82

 

5.6.4

Tables

82

 

5.7

Requests

82

 

5.7.1

Send virtual inputs to the PNOZmulti

83

 

5.7.2

Send virtual inputs to the PNOZmulti, request state of the virtual outputs

84

 

 

and LED status from the PNOZmulti

 

 

5.7.2.1

Control Byte (Byte 40)

85

 

5.7.3

Request state of virtual inputs and outputs from PNOZmulti

86

 

5.7.4

Send data from the PNOZmulti in table form

87

 

5.7.5

Send input and output data (cf. fieldbus communication)

88

 

5.7.5.1

Input data (to the PNOZmulti)

88

 

5.7.5.2

Output data (from the PNOZmulti)

89

 

5.7.5.3

Control Byte (Byte 5)

90

 

5.8

Troubleshooting

91

 

5.8.1

Request format does not meet specifications

91

 

5.8.2

Error while executing a request

91

 

 

 

Section 6

Modbus/TCP

93

 

6.1

System requirements

93

 

6.2

Modbus/TCP - Basics

93

 

6.3

Modbus/TCP with PNOZmulti

94

 

6.4

Data areas

95

 

6.4.1

Overview

95

 

6.4.2

Function codes

95

 

6.4.3

Data transfer limits

96

 

6.4.4

Assignment of data areas

97

 

6.4.4.1

Virtual inputs

97

 

6.4.4.2

Control Register

98

 

6.4.4.3

Virtual outputs

99

 

6.4.4.4

LEDs

99

 

6.4.4.5

Configuration

100

 

6.4.4.6

State of the inputs from the base unit and expansion modules

102

 

6.4.4.7

State of the outputs from the base unit and expansion modules

104

 

6.4.4.8

LED status

105

 

6.4.4.9

Diagnostic word, element types

108

 

6.4.4.10

Current state of the virtual inputs

114

 

6.4.4.11

Current states of the virtual inputs for the safe Ethernet connection

115

Operating Manual PNOZmulti communication interfaces

5

1001154-EN-13

 

Content

 

6.4.4.12

State of process data

115

 

6.4.4.13

Safe Ethernet connection

116

 

6.4.5

Updating the data areas

116

 

6.4.6

Bit addressing in a Register

117

 

6.5

Example

118

 

 

 

Section 7

Safe Ethernet connection

119

 

7.1

Overview

119

 

7.2

System requirements

119

 

7.3

Function description

119

 

7.4

Configuration in the PNOZmulti Configurator

119

 

7.5

Modbus configuration

120

 

7.6

Reaction time

121

 

7.7

Application guidelines

124

 

 

 

Section 8

Diagnostic word

128

 

8.1

Introduction

128

 

8.2

Elements with diagnostic word

128

 

8.3

Structure of the diagnostic word

129

 

8.4

Evaluate diagnostic word

129

 

8.4.1

Example

131

 

8.5

Compilation of the diagnostic words

131

 

8.5.1

Function elements

132

 

8.5.2

Cascading

134

 

8.5.3

Logic elements

134

 

8.5.4

Output elements

141

 

 

 

Section 9

Appendix

143

 

9.1

Table assignment

143

 

9.2

Table 1

143

 

9.3

Table 3

149

 

9.4

Table 4

151

 

9.5

Table 5

155

 

9.6

Table 7

159

 

9.7

Table 8

166

 

9.8

Table 9

169

 

9.9

Table 10

172

 

9.10

Table 11

172

 

9.11

Element types

173

Operating Manual PNOZmulti communication interfaces

6

1001154-EN-13

 

Introduction

1 Introduction

1.1Definition of symbols

Information that is particularly important is identified as follows:

DANGER!

This warning must be heeded! It warns of a hazardous situation that poses an immediate threat of serious injury and death and indicates preventive measures that can be taken.

WARNING!

This warning must be heeded! It warns of a hazardous situation that could lead to serious injury and death and indicates preventive measures that can be taken.

ATTENTION!

This refers to a hazard that can lead to a less serious or minor injury plus material damage, and also provides information on preventive measures that can be taken.

CAUTION!

This describes a situation in which the product or devices could be damaged and also provides information on preventive measures that can be taken. It also highlights areas within the text that are of particular importance.

Information

This gives advice on applications and provides information on special features.

Operating Manual PNOZmulti communication interfaces

7

1001154-EN-13

 

Overview - Communication options

2

Overview - Communication options

2.1Communication via the fieldbus modules

With communication via the fieldbus modules, the data area provided by the PNOZmulti for communication is divided into subsections, which are stored in tables. Each table consists of one or more segments.

The Master (PC, PLC) can request a segment from a table. This is delivered with the next response telegram. The virtual input and output data is also transmitted in each telegram (exception: communication with CANopen).

Communication via the fieldbus modules is described in detail in the chapter entitled "Fieldbus modules".

The following device combinations are possible:

Fieldbus modules

Base units

PNOZmulti fieldbus modules

PNOZmulti base units with inte-

PNOZ mcXp

grated RS232 interface

PNOZ mXp

 

PNOZmulti fieldbus modules

PNOZmulti base units with inte-

PNOZ mcXp

grated Ethernet interface

PNOZ mXp ETH

 

PNOZmulti Mini fieldbus mod-

Base units PNOZmulti Mini

ules

 

PNOZ mmcXp

 

Information

If fieldbus modules are used for communication, the integrated RS232/Ethernet interface is only used to download the project during commissioning

Operating Manual PNOZmulti communication interfaces

8

1001154-EN-13

 

Pilz PNOZ mm0p 24VDC User Manual

Overview - Communication options

2.2Communication via the RS232/ETH interfaces

With communication via the integrated RS232 or Ethernet interface, data exchange is defined via a special protocol. This protocol is described in more detail in the chapter entitled RS232/Ethernet interfaces [ 75].

The following device combinations are possible:

 

Base units PNOZmulti Mini + communication

Base units PNOZmulti with integrated interface

module

Base units with inte-

Base units PNOZmulti

grated RS232 interface

Mini PNOZ mmXp

PNOZ mXp

+

 

Communication mod-

 

ule with RS232 inter-

 

face

 

PNOZ mmc2p

Base units with inte-

Base units PNOZmulti

grated Ethernet inter-

Mini PNOZ mmXp

face

+

PNOZ mXp ETH

Communication mod-

 

 

ule with Ethernet inter-

 

face PNOZ mmc1p

Information

For communication via the integrated RS232 or Ethernet interface, the interface "Inputs/outputs that are downloaded via the integrated interface" must be configured in the hardware configuration in the PNOZmulti Configurator.

Operating Manual PNOZmulti communication interfaces

9

1001154-EN-13

 

Overview - Communication options

2.3Communication via Modbus/TCP

For data exchange with Modbus/TCP, the PNOZmulti is the connection server. All the diagnostic data is defined in one data record, to which the client has direct access.

Communication with Modbus/TCP is described in detail in the chapter entitled Modbus/ TCP [ 93].

The following device combinations are possible:

 

 

Base units PNOZmulti Mini +

Base units PNOZmulti with integrated interface

Communication module

PNOZmulti base units

 

Base units PNOZmulti

 

with Ethernet interface

 

Mini

 

PNOZ mXp ETH

 

+

 

 

 

Communication mod-

 

 

 

ule with Ethernet inter-

 

 

 

face

 

 

 

PNOZ mmc1p

 

 

 

 

 

Information

For communication with Modbus/TCP, the interface "Inputs/outputs that are downloaded via the integrated interface" must be configured in the hardware configuration in the PNOZmulti Configurator.

Operating Manual PNOZmulti communication interfaces

10

1001154-EN-13

 

Safety

3 Safety

3.1Intended use

The communication interface on the configurable control system PNOZmulti is used to transfer diagnostic data to an application program. The data may only be used for non-safe- ty purposes, e.g. visualisation.

CAUTION!

For details of the intended use and application of the configurable control system PNOZmulti, please refer to the operating instructions for the respective unit.

The following is deemed improper use in particular:

}Any component, technical or electrical modification to a product

}Use of a product outside the areas described in the product documentation

}Any use that is not in accordance with the documented technical details.

3.2Safety regulations

3.2.1Use of qualified personnel

The products may only be assembled, installed, programmed, commissioned, operated, maintained and decommissioned by competent persons.

A competent person is someone who, because of their training, experience and current professional activity, has the specialist knowledge required to test, assess and operate the work equipment, devices, systems, plant and machinery in accordance with the general standards and guidelines for safety technology.

It is the company’s responsibility only to employ personnel who:

}Are familiar with the basic regulations concerning health and safety / accident prevention

}Have read and understood the information provided in this description under "Safety"

}And have a good knowledge of the generic and specialist standards applicable to the specific application.

3.2.2Warranty and liability

All claims to warranty and liability will be rendered invalid if

}The product was used contrary to the purpose for which it is intended

}Damage can be attributed to not having followed the guidelines in the manual

}Operating personnel are not suitably qualified

}Any type of modification has been made (e.g. exchanging components on the PCB boards, soldering work etc.).

Operating Manual PNOZmulti communication interfaces

11

1001154-EN-13

 

Safety

3.2.3Disposal

}In safety-related applications, please comply with the mission time tM in the safety-relat- ed characteristic data.

}When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act).

Operating Manual PNOZmulti communication interfaces

12

1001154-EN-13

 

Fieldbus modules

4

Fieldbus modules

4.1Basics

The input and output range is each reserved an area of 20 Bytes for communication via fieldbuses; this is updated approx. every 15 ms. The Master (PC, PLC) can send 20 Bytes to the PNOZmulti and receive 20 Bytes from the PNOZmulti. The Master can process the information in bytes, words or in double words.

4.1.1Input data (to the PNOZmulti)

Double Word

Word

Byte

Content

0

0

0

 

 

 

 

State of virtual inputs

 

 

1

 

 

 

 

 

 

 

 

1

2

 

 

 

 

 

 

 

3

Reserved

 

 

 

 

1

2

4

Table number

 

 

 

 

 

 

5

Segment number

 

 

 

 

 

3

6

Reserved

 

 

 

 

 

 

7

Reserved

 

 

 

 

2

4

8

Reserved

 

 

 

 

 

 

9

Reserved

 

 

 

 

 

5

10

Reserved

 

 

 

 

 

 

11

Reserved

 

 

 

 

3

6

12

Reserved

 

 

 

 

 

 

13

Reserved

 

 

 

 

 

7

14

Reserved

 

 

 

 

 

 

15

Reserved

 

 

 

 

4

8

16

Reserved

 

 

 

 

 

 

17

Reserved

 

 

 

 

 

9

18

Reserved

19Reserved

4.1.2Output data (from the PNOZmulti)

Double Word

Word

Byte

Content

0

0

0

 

 

 

 

State of virtual outputs

 

 

1

 

 

 

 

 

 

 

 

1

2

 

 

 

 

 

 

 

3

LED status

 

 

 

 

Operating Manual PNOZmulti communication interfaces

13

1001154-EN-13

 

Fieldbus modules

Double Word

Word

Byte

Content

1

2

4

Table number

 

 

 

 

 

 

5

Segment number

 

 

 

 

 

3

6

Byte 0 of Table x, Segment y

 

 

 

 

 

 

7

Byte 1 of Table x, Segment y

 

 

 

 

2

4

8

.

 

 

 

 

 

 

9

.

 

 

 

 

 

5

10

.

 

 

 

 

 

 

11

.

 

 

 

 

3

6

12

.

 

 

 

 

 

 

13

.

 

 

 

 

 

7

14

.

 

 

 

 

 

 

15

.

 

 

 

 

4

8

16

.

 

 

 

 

 

 

17

.

 

 

 

 

 

9

18

Byte 12 of Table x, Segment y

 

 

19

Reserved

 

 

 

 

4.1.3Note on the PNOZ mc6p (CANopen)

The output data on the PNOZmulti is stored as follows:

 

Object Index

Sub Index

 

 

Byte

(hex)

(hex)

PDO

COB-ID

0

2000

1

TPDO 1

180h

 

 

 

 

+ node address

1

2000

2

 

 

 

 

 

 

2

2000

3

 

 

 

 

 

 

 

3

2000

4

 

 

 

 

 

 

 

4

2000

5

 

 

 

 

 

 

 

5

2000

6

 

 

 

 

 

 

 

6

2000

7

 

 

7

2000

8

 

 

 

 

 

 

 

8

2000

9

TPDO 2

280h

 

 

 

 

+ node address

9

2000

A

 

 

 

 

 

 

10

2000

B

 

 

 

 

 

 

 

11

2000

C

 

 

 

 

 

 

 

12

2000

D

 

 

 

 

 

 

 

13

2000

E

 

 

 

 

 

 

 

14

2000

F

 

 

 

 

 

 

 

15

2000

10

 

 

 

 

 

 

 

Operating Manual PNOZmulti communication interfaces

14

1001154-EN-13

 

Fieldbus modules

 

Object Index

Sub Index

 

 

Byte

(hex)

(hex)

PDO

COB-ID

16

2000

11

TPDO 3

PNOZ mc6p: 1C0h + node

 

 

 

 

address PNOZ mc6.1p,

17

2000

12

 

 

PNOZ mmc6p:

 

 

 

 

18

2000

13

 

 

380h

 

 

 

 

19

2000

14

 

+ node address

 

 

 

 

 

The input data on the PNOZmulti is stored as follows:

 

Object Index

Sub Index

 

 

Byte

(hex)

(hex)

PDO

COB-ID

0

2100

1

RPDO

200h

 

 

 

 

+ node address

1

2100

2

 

 

 

 

 

 

2

2100

3

 

 

 

 

 

 

 

3

2100

4

 

 

 

 

 

 

 

4

2100

5

 

 

 

 

 

 

 

5

2100

6

 

 

 

 

 

 

 

6

2100

7

 

 

 

 

 

 

 

7

2100

8

 

 

 

 

 

 

 

8

2100

9

RPDO 2

300h

 

 

 

 

+ node address

9

2100

A

 

 

 

 

 

 

10

2100

B

 

 

 

 

 

 

 

11

2100

C

 

 

 

 

 

 

 

12

2100

D

 

 

 

 

 

 

 

13

2100

E

 

 

 

 

 

 

 

14

2100

F

 

 

 

 

 

 

 

15

2100

10

 

 

 

 

 

 

 

16

2100

11

RPDO 3

PNOZ mc6p:

 

 

 

 

240h

17

2100

12

 

 

 

 

 

+ node address

18

2100

13

 

 

 

 

 

PNOZ mc6.1p, PNOZ

19

2100

14

 

 

mmc6p:

 

 

 

 

 

 

 

 

400h

 

 

 

 

+ node address

 

 

 

 

 

Key to abbreviations:

 

 

 

TPDO: Transmit Process Data Object

 

 

RPDO: Receive Process Data Object

 

 

COB-ID: Communication Object Identifier

 

 

Operating Manual PNOZmulti communication interfaces

15

1001154-EN-13

 

Fieldbus modules

4.1.4Assignment of Byte 0 ... Byte 3

The current status of the virtual outputs configured for the fieldbus plus the current status of the LED are always stored in Byte 0 ... Byte 3. All other information is stored in various tables (see Appendix).

Input area

The virtual inputs are defined by the Master and transferred to the PNOZmulti. Each input has a number, e.g. input bit 4 of byte 1 has the number i12.

Byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

i7

i6

i5

i4

i3

i2

i1

i0

 

 

 

 

 

 

 

 

 

1

i15

i14

i13

i12

i11

i10

i9

i8

 

 

 

 

 

 

 

 

 

2

i23

i22

i21

i20

i19

i18

i17

i16

 

 

 

 

 

 

 

 

 

3

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output area

The virtual outputs are defined in the PNOZmulti Configurator. Each output that is used is given a number there, e.g. o0, o5... . The status of output o0 is stored in bit 0 of byte 0; the status of output o5 is stored in bit 5 of byte 0 etc.

Byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

o7

 

o6

o5

o4

o3

o2

o1

o0

 

 

 

 

 

 

 

 

 

 

1

o15

 

o14

o13

o12

o11

o10

o9

o8

 

 

 

 

 

 

 

 

 

 

2

o23

 

o22

o21

o20

o19

o18

o17

o16

 

 

 

 

 

 

 

 

 

 

The status of the LEDs is stored in Byte 3 (output area only):

 

 

 

 

 

 

 

 

 

 

Bit 0 = 1:

 

LED OFAULT is lit or flashes

 

 

 

 

 

 

 

 

 

 

 

Bit 1 = 1:

 

LED IFAULT is lit or flashes

 

 

 

 

 

 

 

 

 

 

 

Bit 2 = 1:

 

LED FAULT is lit or flashes

 

 

 

 

 

 

 

 

 

 

 

 

Bit 3 = 1:

 

LED DIAG is lit

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 4 = 1:

 

LED RUN is lit

 

 

 

 

 

 

 

 

Bit 5:

 

Communication between the PNOZmulti and the fieldbus is working

 

 

 

 

 

 

 

 

 

Bit 6:

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit 7:

 

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Manual PNOZmulti communication interfaces

16

1001154-EN-13

 

Fieldbus modules

4.1.5Assignment of Byte 4 ... Byte 18

Byte

Table

 

4

Table number

 

 

 

 

5

Segment number

 

 

 

 

6

Byte 0 of Table Segment 1

 

 

 

 

7

Byte 1 of Table Segment 1

 

 

 

 

8

Byte 2 of Table Segment 1

 

 

 

 

9

Byte 3 of Table Segment 1

 

 

 

 

10

Byte 4 of Table Segment 1

Segment 1

 

 

11

Byte 5 of Table Segment 1

 

12

Byte 6 of Table Segment 1

 

 

 

 

13

Byte 7 of Table Segment 1

 

 

 

 

14

Byte 8 of Table Segment 1

 

 

 

 

15

Byte 9 of Table Segment 1

 

 

 

 

16

Byte 10 of Table Segment 1

 

 

 

 

17

Byte 11 of Table Segment 1

 

 

 

 

18

Byte 12 of Table Segment 1

 

 

 

 

6

Byte 0 of Table Segment 2

 

 

 

 

7

Byte 1 of Table Segment 2

 

 

 

 

8

Byte 2 of Table Segment 2

 

 

 

 

9

Byte 3 of Table Segment 2

 

 

 

 

10

Byte 4 of Table Segment 2

Segment 2

 

 

11

Byte 5 of Table Segment 2

 

 

 

 

12

Byte 6 of Table Segment 2

 

 

 

 

13

Byte 7 of Table Segment 2

 

 

 

 

14

Byte 8 of Table Segment 2

 

 

 

 

15

Byte 9 of Table Segment 2

 

 

 

 

16

Byte 10 of Table Segment 2

 

 

 

 

17

Byte 11 of Table Segment 2

 

 

 

 

18

Byte 12 of Table Segment 2

 

 

 

 

.

.

.

.

 

.

.

.

 

.

.

 

 

 

Operating Manual PNOZmulti communication interfaces

17

1001154-EN-13

 

Fieldbus modules

Byte

Table

 

6

Byte 0 of Table Segment n

 

 

 

 

7

Byte 1 of Table Segment n

 

 

 

 

8

Byte 2 of Table Segment n

 

 

 

 

9

Byte 3 of Table Segment n

 

 

 

 

10

Byte 4 of Table Segment n

Segment n

 

 

11

Byte 5 of Table Segment n

 

 

 

 

12

Byte 6 of Table Segment n

 

 

 

 

13

Byte 7 of Table Segment n

 

 

 

 

14

Byte 8 of Table Segment n

 

 

 

 

15

Byte 9 of Table Segment n

 

 

 

 

16

Byte 10 of Table Segment n

 

 

 

 

17

Byte 11 of Table Segment n

 

 

 

 

18

Byte 12 of Table Segment n

 

 

 

 

Each table consists of one or more segments. Each segment is made up of 13 Bytes. The tables have a fixed assignment. The Master requests the required data using the table number and segment number. The Slave (e.g. PNOZ mc3p) repeats the two numbers and sends the requested data. If data is requested that is not available, the Slave sends the error message “FF” instead of the segment number. The segments may be requested in any sequence.

Master

Fieldbus module

Byte

 

4Table No.

5Segment No.

60

..

. .

..

18 0

Byte

 

4

 

Table No.

5

Segment No.

6

x

 

.

.

.

.

.

.

18

 

x

Operating Manual PNOZmulti communication interfaces

18

1001154-EN-13

 

Fieldbus modules

Exception: Table 9 segment 1:

With this table you can set the expanded inputs 24 - 127 and upload the expanded outputs 24 - 127. In contrast to the other tables, in this case the Master not only requests data but also sends input data to the PNOZmulti via the fieldbus module. Each input is assigned a Bit in the segment Bytes 0 ... 12 of the input data, each output is assigned a Bit in the segment Bytes 0 ... 12 of the output data.

ATTENTION!

The expanded input Bits are only updated when table 9 segment 1 is accessed. In the event of a fieldbus error, input bits i24 ... i127 in the PNOZmulti are frozen!

Byte

Master

Fieldbus module

 

 

4

 

 

Table Number 9

 

5Segment Number 1

6Segment Byte 0 (i24 ... i31)

..

. .

..

18 Segment Byte 12 (i120 ... i127)

Byte

 

 

4

 

 

Table Number 9

 

5

Segment Number 1

 

6

Segment Byte 0 (o24 ...

o31)

 

.

.

 

.

.

 

.

.

 

18 Segment Byte 12 (o120 ... o127)

Operating Manual PNOZmulti communication interfaces

19

1001154-EN-13

 

Fieldbus modules

4.1.5.1Example 1

The Master requests segment 2 from table 1. The fieldbus module repeats both these details and sends segment 2. Then the data from segment 12.70 cm table 1 is transmitted.

Master

Fieldbus module

41

52

60

..

. .

..

18 0

4

1

5

2

6

x

.

.

.

.

.

.

18

 

x

41

55

60

..

. .

..

18 0

4

1

5

5

6

x

.

.

.

.

.

.

18

 

x

Operating Manual PNOZmulti communication interfaces

20

1001154-EN-13

 

Fieldbus modules

4.1.5.2Example 2

The Master requests segment 1 from table 3. The fieldbus module repeats both of these details and sends segment 1. Then the Master requests segment 25 from table 5. As this table does not contain a segment 25, the Slave registers an error and sends back "FF".

Master

Fieldbus module

43

51

60

..

. .

..

18 0

4

3

5

1

6

x

.

.

.

.

.

.

18

 

x

45

525

60

..

. .

..

18 0

4

5

5

FF

6

x

.

.

.

.

.

.

18

 

x

4.2PNOZ mc2p, PNOZ mc2.1p, PNOZ mmc11p (SDO and PDO)

4.2.1Overview

4.2.1.1PNOZ mc2p

All the objects (variables and parameters) that are relevant for these units are entered in the object directory. Service Data Objects (SDOs) are used for read and write access. The object directory is available as an EDS file (Electronic Data Sheet), enabling SDOs to be used in the PNOZ mc2p.

Operating Manual PNOZmulti communication interfaces

21

1001154-EN-13

 

Fieldbus modules

The manufacturer-specific part of the object directory is structured as follows:

 

 

 

 

Sub-In-

 

PDO

Size

Name

Index

dex

Content

0x1A00

128

TxPDO

0x2000

0x01–

Output data

 

 

 

 

0x80

 

0x1A01

128

TxPDO

0x2001

0x01–

Diagnostic word (Low Byte)

 

 

 

 

0x80

 

0x1A02

128

TxPDO

0x2002

0x01–

Diagnostic word (High Byte)

 

 

 

 

0x80

 

0x1A03

128

TxPDO

0x2003

0x01–

Status of inputs

 

 

 

 

0x80

 

 

 

 

 

Status of input LED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

State of outputs

 

 

 

 

 

 

 

 

 

 

 

Status of LED

 

 

 

 

 

 

0x1600

20

RxPDO

0x2100

0x01–

Input data

 

 

 

 

0x14

 

Information

Data with indices 2001 to 2003 is only updated by the PNOZmulti piece by piece in each cycle. This may mean that interdependent data is inconsistent. Updating all of the data can take up to 500 ms.

4.2.1.2PNOZ mc2.1p/PNOZ mmc11p

All the objects (variables and parameters) that are relevant for these units are entered in the object directory. Service Data Objects (SDOs) are used for read and write access.

The SDOs in the PNOZ mc2.1p, PNOZ mmc11p are integrated in an ESI file (Ethercat Slave Information). The ESI file is incorporated in the EtherCAT Configurator for use of SDOs in the PNOZ mc2.1p, PNOZ mmc11p.

The manufacturer-specific part of the object directory is structured as follows:

PDO

Size

Name

Index

Sub-Index

Content

0x1A00

20

TxPDO

0x2000

0x01–0x14

Output data

 

 

 

 

 

 

0x1A01

128

TxPDO

Configurable

Configurable

Default configuration of im-

 

 

 

 

 

portant SDOs

0x1600

20

RxPDO

0x2100

0x01–0x14

Input data

 

 

 

 

 

 

Information

Data with indices 2001 to 2003 is only updated by the PNOZmulti piece by piece in each cycle. This may mean that interdependent data is inconsistent. Updating all of the data can take up to 500 ms.

Operating Manual PNOZmulti communication interfaces

22

1001154-EN-13

 

Fieldbus modules

Information

The data length and content of the PDOs can be freely configured by the

EtherCAT Master. The maximum length is stated under "Size".

4.2.2Object Directory (Manufacturer Specific Profile Area)

4.2.2.1SDO Index 0x2000

This index contains the output data

Index (hex)

Name

Content

Example/explanation

0x2000:01

Input Byte 0

Outputs Bit 0 … 7

 

 

 

Fieldbus module

 

 

 

 

 

0x2000:02

Input Byte 1

Outputs Bit 8 … 15

 

 

 

Fieldbus module

 

 

 

 

 

0x2000:03

Input Byte 2

Outputs Bit 16 … 23

 

 

 

Fieldbus module

 

 

 

 

 

0x2000:04

Input Byte 3

LED status

 

 

 

 

 

0x2000:05

Input Byte 4

Table number

 

 

 

 

 

0x2000:06

Input Byte 5

Segment number

 

 

 

 

 

0x2000:07

Input Byte 6

Byte 0

 

0x2000:08

Input Byte 7

Byte 1

 

 

 

 

 

0x2000:09

Input Byte 8

Byte 2

 

 

 

 

 

0x2000:A

Input Byte 9

Byte 3

 

 

 

 

 

0x2000:B

Input Byte 10

Byte 4

 

 

 

 

 

0x2000:C

Input Byte 11

Byte 5

 

 

 

 

 

0x2000:D

Input Byte 12

Byte 6

 

 

 

 

 

0x2000:E

Input Byte 13

Byte 7

 

 

 

 

 

0x2000:F

Input Byte 14

Byte 8

 

 

 

 

 

0x2000:10

Input Byte 15

Byte 9

 

 

 

 

 

0x2000:11

Input Byte 16

Byte 10

 

 

 

 

 

0x2000:12

Input Byte 17

Byte 11

 

 

 

 

 

0x2000:13

Input Byte 18

Byte 12

 

 

 

 

 

0x2000:14

Input Byte 19

Reserved

 

...

0x2000:3F Input Byte 62

Operating Manual PNOZmulti communication interfaces

23

1001154-EN-13

 

Fieldbus modules

Index (hex)

Name

Content

Example/explanation

 

 

 

 

0x2000:40

Input Byte 63

i0 ... i7 Safe

Inputs, safe Ethernet connection

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:41

Input Byte 64

i8 ... i15 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:42

Input Byte 65

i16 ... i23 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:43

Input Byte 66

i24 ... i31 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:44

Input Byte 67

i32 ... i39 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:45

Input Byte 68

i40 ... i47 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:46

Input Byte 69

Reserved.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2000:47

Input Byte 70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2000:48

Input Byte 71

o0 ... o7 Safe

Outputs, safe Ethernet connection

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:49

Input Byte 72

o8 ... o15 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:4A

Input Byte 73

o16 ... o23 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:4B

Input Byte 74

o24 ... o31 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:4C

Input Byte 75

o32 ... o39 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:4D

Input Byte 76

i40 ... i47 Safe

 

 

 

 

 

 

 

 

 

 

Ethernet connection

 

 

 

 

 

 

 

 

0x2000:4E

Input Byte 77

Reserved.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2000:4F

Input Byte 78

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2000: 50

Input Byte 79

I0 ... I7

Virtual inputs on the 2nd link module PNOZ ml1p:

 

 

1st expansion module,

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

0x2000:51

Input Byte 80

I8 ... I15

 

 

 

 

 

 

 

 

 

 

1st expansion module,

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

0x2000:52

Input Byte 81

I16 ... I23

Sub-Index 54:

 

 

 

 

 

 

 

1st expansion module,

 

 

 

 

 

 

 

 

 

 

I7

I6

I5

I4

I3

I2

I1

I0

 

 

left

 

 

 

 

 

 

 

 

0x2000:53

Input Byte 82

I24 ... I31

Sub-Index 55:

 

 

 

 

 

 

 

1st expansion module,

 

 

 

 

 

 

 

 

 

 

I15

I14

I13

I12

I11

I10

I9

I8

 

 

left

 

 

 

 

 

 

 

 

Operating Manual PNOZmulti communication interfaces

24

1001154-EN-13

 

Sub-Index 57:
Sub-Index 56:
Example/explanation
2nd expansion module, I31 I30 I29 I28 I27 I26 I25 I24 left
I16 ... I23
2nd expansion module, If an output has a high signal, the corresponding left Bit will contain "1"; if the output is open (low sig- I24 ... I31 nal), the Bit will contain "0".
2nd expansion module, left
I0 ... I7
3rd expansion module, left
I8 ... I15
3rd expansion module, left
I16 ... I23
3rd expansion module, left
I24 ... I31
3rd expansion module, left
I0 ... I7
4th expansion module, left
I8 ... I15
4th expansion module, left
I16 ... I23
4th expansion module, left
I24 ... I31
4th expansion module, left
I0 ... I7
5th expansion module, left
I8 ... I15
5th expansion module, left
I8 ... I15
I19 I18 I17 I16
2nd expansion module, I23 I22 I21 I20 left
I0 ... I7
Content

Fieldbus modules

Index (hex)

Name

 

 

0x2000:54

Input Byte 83

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2000:55

Input Byte 84

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2000:56

Input Byte 85

 

 

 

 

 

 

0x2000:57

Input Byte 86

 

 

 

 

 

 

0x2000:58

Input Byte 87

 

 

 

 

 

 

0x2000:59

Input Byte 88

 

 

 

 

 

 

0x2000:5A

Input Byte 89

 

 

 

 

 

 

0x2000:5B

Input Byte 90

 

 

 

 

 

 

0x2000:5C

Input Byte 91

 

 

 

 

 

 

0x2000:5D

Input Byte 92

 

 

 

 

 

 

0x2000:5E

Input Byte 93

 

 

 

 

 

 

0x2000:5F

Input Byte 94

 

 

 

 

 

 

0x2000:60

Input Byte 95

 

 

 

 

 

 

0x2000:61

Input Byte 96

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Manual PNOZmulti communication interfaces

25

1001154-EN-13

 

Fieldbus modules

Index (hex)

Name

Content

Example/explanation

 

 

 

 

0x2000:62

Input Byte 97

I16 ... I23

 

 

 

 

 

 

 

 

 

 

5th expansion module,

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:63

Input Byte 98

I24 ... I31

 

 

 

 

 

 

 

 

 

 

5th expansion module,

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:64

Input Byte 99

I0 ... I7

 

 

 

 

 

 

 

 

 

 

6th expansion module,

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:65

Input Byte 100

I8 ... I15

 

 

 

 

 

 

 

 

 

 

6th expansion module,

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:66

Input Byte 101

I16 ... I23

 

 

 

 

 

 

 

 

 

 

6th expansion module,

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:67

Input Byte 102

I24 ... I31

 

 

 

 

 

 

 

 

 

 

6th expansion module,

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:68

Input Byte 103

O0

... O7

Virtual outputs on the 3rd link module PNOZ

 

 

 

1st expansion module,

ml1p:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2000:69

Input Byte 104

O8

... O15

Sub-Index 70:

 

 

 

 

 

 

 

1st expansion module,

 

 

 

 

 

 

 

 

 

 

O7

O6

O5

O4

O3

O2

O1

O0

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:6A

Input Byte 105

O16 ... O23

Sub-Index 71:

 

 

 

 

 

 

 

1st expansion module,

 

 

 

 

 

 

 

 

 

 

O15

O14

O13

O12

O11

O10

O9

O8

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:6B

Input Byte 106

O24 ... O31

Sub-Index 72:

 

 

 

 

 

 

 

1st expansion module,

 

 

 

 

 

 

 

 

 

 

O23

O22

O21

O20

O19

O18

O17

O16

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:6C

Input Byte 107

O0

... O7

Sub-Index 73:

 

 

 

 

 

 

 

2nd expansion module,

 

 

 

 

 

 

 

 

 

 

O31

O30

O29

O28

O27

O26

O25

O24

 

 

left

 

 

 

 

 

 

 

 

 

0x2000:6D

Input Byte 108

O8

... O15

 

 

 

 

 

 

 

 

 

 

2nd expansion module,

If an output has a high signal, the corresponding

 

 

left

 

Bit will contain "1"; if the output is open (low sig-

 

 

 

 

nal), the Bit will contain "0".

 

 

 

0x2000:6E

Input Byte 109

O16 ... O23

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd expansion module,

 

 

 

 

 

 

 

 

 

 

left

 

 

 

 

 

 

 

 

 

Operating Manual PNOZmulti communication interfaces

26

1001154-EN-13

 

Fieldbus modules

Index (hex)

Name

Content

Example/explanation

0x2000:6F

Input Byte 110

O24 ... O31

 

 

 

2nd expansion module,

 

 

 

left

 

 

0x2000:70

Input Byte 111

O0

... O7

 

 

 

3rd expansion module,

 

 

 

left

 

 

0x2000:71

Input Byte 112

O8

... O15

 

 

 

3rd expansion module,

 

 

 

left

 

 

0x2000:72

Input Byte 113

O16 ... O23

 

 

 

3rd expansion module,

 

 

 

left

 

 

0x2000:73

Input Byte 114

O24 ... O31

 

 

 

3rd expansion module,

 

 

 

left

 

 

0x2000:74

Input Byte 115

O0

... O7

 

 

 

4th expansion module,

 

 

 

left

 

 

0x2000:75

Input Byte 116

O8

... O15

 

 

 

4th expansion module,

 

 

 

left

 

 

0x2000:76

Input Byte 117

O16 ... O23

 

 

 

4th expansion module,

 

 

 

left

 

 

0x2000:77

Input Byte 118

O24 ... O31

 

 

 

4th expansion module,

 

 

 

left

 

 

0x2000:78

Input Byte 119

O0

... O7

 

 

 

5th expansion module,

 

 

 

left

 

 

0x2000:79

Input Byte 120

O8

... O15

 

 

 

5th expansion module,

 

 

 

left

 

 

0x2000:7A

Input Byte 121

O16 ... O23

 

 

 

5th expansion module,

 

 

 

left

 

 

0x2000:7B

Input Byte 122

O24 ... O31

 

 

 

5th expansion module,

 

 

 

left

 

 

0x2000:7C

Input Byte 123

O0

... O7

 

 

 

6th expansion module,

 

 

 

left

 

 

Operating Manual PNOZmulti communication interfaces

27

1001154-EN-13

 

Fieldbus modules

Index (hex)

Name

Content

Example/explanation

0x2000:7D

Input Byte 124

O8 ... O15

 

 

 

6th expansion module,

 

 

 

left

 

0x2000:7E

Input Byte 125

O16 ... O23

 

 

 

6th expansion module,

 

 

 

left

 

0x2000:7F

Input Byte 126

O24 ... O31

 

 

 

6th expansion module,

 

 

 

left

 

0x2000:80

Input Byte 127

Reserved

 

 

 

 

 

4.2.2.2SDO Index 0x2001 and Index 0x2002

This index contains the diagnostic words and the output bits for the Element IDs.

Index (hex)

Name

Content

Example/explanation

 

 

 

 

 

 

 

 

 

0x2001:01

Input Byte 128

Low Byte diag-

The diagnostic word is displayed in the PNOZmulti Config-

 

 

 

nostic word.

urator and on the PVIS expanded diagnostics (see chapter

 

 

 

Element ID=1

entitled Diagnostic word [

128] and the online help for the

 

 

 

 

PNOZmulti Configurator)

 

 

 

 

 

 

 

 

 

...

...

 

 

 

 

 

 

 

 

 

 

 

 

 

Element-ID = 1,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2001:64

Input Byte 227

Low Byte diag-

 

 

 

 

 

 

 

 

 

 

 

e.g. diagnostic word of E-STOP:

 

 

 

 

 

 

 

 

 

 

nostic word.

 

 

 

 

 

 

 

 

 

 

Low Byte:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Element ID=100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

0

 

0

 

0

 

0

 

0

 

1

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Message: Pushbutton operated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2001:65

Input Byte 228

Output Bits of

Each element is assigned an ID in the PNOZmulti Configu-

...

...

 

Element ID = 1

rator. If the element's output = 0 (no enable), the corre-

 

... 100

sponding bit is set.

 

 

 

 

 

 

 

 

 

 

 

0x2001:71

Input Byte 240

 

 

 

 

 

 

 

 

 

 

 

 

Sub

 

 

 

 

 

 

 

Element ID

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Index

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

8

7

6

 

5

 

4

 

3

 

2

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

66

16

15

14

13

 

12

 

11

 

10

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

67

24

23

22

21

 

20

 

19

 

18

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6F

88

87

86

85

 

84

 

83

 

82

 

81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

96

95

94

93

 

92

 

91

 

90

 

89

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

71

-

-

 

-

 

-

 

100

 

99

 

98

 

97

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2001:72

Input Byte 241

Reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

...

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2001:80

Input Byte 255

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Manual PNOZmulti communication interfaces

28

1001154-EN-13

 

Fieldbus modules

Index (hex)

Name

Content

Example/explanation

 

 

 

 

 

0x2002:01

Input Byte 256

High Byte diag-

See Index 2001 for comment

 

 

 

 

 

 

nostic word.

Element ID = 1,

 

 

 

 

 

 

 

Element ID=1

 

 

 

 

 

 

 

e.g. diagnostic word of E-STOP:

 

 

 

 

 

 

 

 

 

...

...

...

High Byte:

 

 

 

 

 

 

 

0x2002:64

Input Byte 355

High Byte diag-

 

 

 

 

 

 

 

 

 

0

0

0

 

0

0

0

0

1

 

 

nostic word.

 

 

 

 

 

 

 

 

 

 

 

Message: Wiring error, clock error

 

 

 

 

 

Element ID=100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2002:65

Input Byte 356

Reserved

 

 

 

 

 

 

 

 

 

...

...

 

 

 

 

 

 

 

 

 

 

0x2002:80

Input Byte 383

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.2.2.3SDO Index 0x2003

This index contains the state of the inputs/outputs plus the LED status

Index

Input

 

 

 

 

 

 

 

 

 

 

 

(hex)

Byte

Content

Example/Comment

 

 

 

 

 

 

0x2003:01

384

I0

... I7 base unit

 

 

 

 

 

 

 

 

 

 

 

IM0 ... I7 base unit Mini

For example: The safety system consists of one base unit

 

 

 

 

PNOZ m1p and one expansion module PNOZ mi1p

 

0x2003:02

385

I8

... I15 base unit,

 

 

 

 

 

 

 

 

 

 

 

 

I8

... I15 base unit Mini

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:03

386

I16 ... I19 base unit

 

 

 

 

 

 

 

 

 

 

 

IM16 ... IM19 base unit

 

 

 

 

 

 

 

 

 

 

 

Mini

 

 

 

 

 

 

 

 

 

0x2003:04

387

0

 

Sub-Index 1: PNOZ m1p

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I7

I6

I5

I4

I3

I2

I1

 

I0

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:05

388

0

 

Sub-Index 2: PNOZ m1p

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I15

I14

I13

I12

I11

I10

I9

 

I8

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:06

389

I0

... I7 1st expansion

Sub-Index 3: PNOZ m1p

 

 

 

 

 

 

 

module, right

 

 

 

 

 

 

 

 

 

 

 

0

0

0

0

I19

I18

I17

 

I16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:07

390

I0

... I7 2nd expansion

Sub-Index 4:

 

 

 

 

 

 

 

 

 

module, right

 

 

 

 

 

 

 

 

 

 

 

0

0

0

0

0

0

0

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:08

391

I0

... I7 3rd expansion

Sub-Index 5:

 

 

 

 

 

 

 

 

 

module, right

 

 

 

 

 

 

 

 

 

 

 

0

0

0

0

0

0

0

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:09

392

I0

... I7 4th expansion

Sub-Index 6: PNOZ mi1p

 

 

 

 

 

 

 

module, right

 

 

 

 

 

 

 

 

 

 

 

I7

I6

I5

I4

I3

I2

I1

 

I0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Manual PNOZmulti communication interfaces

29

1001154-EN-13

 

Fieldbus modules

Index

Input

 

 

 

 

 

 

 

 

 

 

 

 

(hex)

Byte

Content

Example/Comment

 

 

 

 

 

0x2003:A

393

I0 ... I7 5th expansion

 

 

 

 

 

 

 

 

 

 

 

 

 

module, right

If an input has a high signal, the corresponding bit will be

0x2003:B

394

I0 ... I7 6th expansion

"1"; if an input has a low signal, the bit will be "0".

 

 

 

module, right

 

 

 

 

 

 

 

 

 

 

 

0x2003:C

395

I0 ... I7 7th expansion

INFORMATION:

 

 

 

 

 

 

 

module, right

On the base units PNOZmulti Mini, the status of the con-

 

 

 

0x2003:D

396

I0 ... I7 8th expansion

figurable inputs/outputs is only displayed if they are con-

 

 

module right

figured as inputs in the PNOZmulti Configurator.

 

0x2003:E

397

Reserved

Assignment of Bytes on the base units PNOZmulti Mini:

...

...

 

Sub-Index 1: PNOZ mmxp

 

 

 

 

0x2003:10

399

 

 

 

 

 

 

 

 

 

 

 

 

 

I7

I6

I5

I4

IM3

IM2

IM1

IM0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub-Index 2: PNOZ mmxp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I15

I14

I13

I12

I11

I10

I9

I8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sub-Index 3: PNOZ mmxp

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

0

 

0

 

0

IM19

IM18

IM17

IM16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:11

400

LED I0 ... I7 base unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For example: The safety system consists of one base unit

 

 

 

PNOZ m1p and one expansion module PNOZ mi1p

 

0x2003:12

401

LED I8 ... I15 base unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:13

402

LED I16 ... I19 base unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:14

403

0

Sub-Index 11: PNOZ m1p

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I7

 

I6

 

I5

 

I4

I3

I2

I1

I0

 

 

 

 

 

 

 

 

 

 

 

0x2003:15

404

0

Sub-Index 12: PNOZ m1p

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I15

 

I14

 

I13

 

I12

I11

I10

I9

I8

 

 

 

 

 

 

 

 

 

 

 

0x2003:16

405

LED I0 ... I7 1st expan-

Sub-Index 13: PNOZ m1p

 

 

 

 

 

 

sion module, right

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

0

 

0

 

0

I19

I18

I17

I16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:17

406

LED I0 ... I7 2nd expan-

Sub-Index 14:

 

 

 

 

 

 

 

 

 

sion module, right

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

0

 

0

 

0

0

0

0

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:18

407

LED I0 ... I7 3rd expan-

Sub-Index 15:

 

 

 

 

 

 

 

 

 

sion module, right

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

0

 

0

 

0

0

0

0

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0x2003:19

408

LED I0 ... I7 4th expan-

Sub-Index 16: PNOZ mi1p

 

 

 

 

 

 

sion module, right

 

 

 

 

 

 

 

 

 

 

 

 

 

I7

 

I6

 

I5

 

I4

I3

I2

I1

I0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Manual PNOZmulti communication interfaces

30

1001154-EN-13

 

Loading...
+ 146 hidden pages