Schneider Electric TAC Xenta 421A, TAC Xenta 422A Installation Instructions

5 (1)

 

 

 

 

TAC Xenta® 421A/422A

02-00002-01-en

 

 

 

 

Universal Input and Digi-

Configuration Instruction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tal Output Module

 

 

 

 

 

 

 

 

 

 

 

LONMARK CONFIGURATION AND VARIABLES

Physical Inputs and Outputs

TAC Xenta 421A/422A can be used as a normal Xenta I/O module or as a certified LONMARK® device. It has

4 Universal Inputs (UI)

5 Digital Outputs (DO)

In addition, TAC Xenta 422A has five manual switches, one for each DO that can be set

manual Off

manual On

Auto

To configure the inputs and outputs, and to specify the transmission of values, either ordinary TAC Menta®/Xenta configuration or nci SNVTs are used. The usage is explained overleaf ("SNVT vs TAC Xenta I/O module Communication".)

The use of SNVTs requires explicit information listed below.

UI Configuration

Each of the four UI:s (1-4) is configured with nciInput1-4 0 = not connected (default value)

1 = 1.8 kohm thermistor

2 = DI, green indication

3 = 0-10 V

4 = 0-20 mA

5 = 10 kohm thermistor

6 = DI, red indication

7 = DI, green inverted indication

8 = DI, red inverted indication

If configured to be a digital input (DI, any type), its function is further determined by the corresponding bit in

nciDigInNONC:

Bit 0 Bit 15

DI 1

DI 2

DI 3

DI 4

If bit=0: NO, normally open (default value)

If bit=1: NC, normally closed

Pulse counting is not available for SNVT communication.

UI Values

Depending on the UI configuration, each UI n=1-4 generates a valid value in one of these (the other two are set invalid):

nvoAnalog1-4 (0-10 V or 0-20 mA, converted to 0-100%; invalid=163.835)

nvoDigital1-4 (DI, any type)

Off: state=0, value=0

On: state=1, value=100

Invalid: state=255

nvoTemp1-4 (thermistor, any type; invalid=327.67)

UI Value Transmission

The UI value will be transmitted

a)when the change in value is large enough (set individually per UI)

b)at a specified time interval (common for all UIs)

a) is determined by

nciSndDelta1-4 (dimensionless; default value=2)

Size of change to cause transmission Ex.: 1 means

-if configured as analog input: 1%

-if configured as temperature input: 1 °

If the UI is configured as a digital input, a status change will always be transmitted.

b) is determined by

nciSndHrtBt "Heartbeat" interval in seconds (default=60)

A valid and configured UI value will be sent at least once during each interval regardless of change.

The transmissions will be distributed over time to avoid momentary communication overload.

DO Values

The digital output values to the output (DO, n=1-5) are received as:

nviDO1-5

switch:state

 

state=0 or >1: Off

 

state=1: On

For the TAC Xenta 422A, the DO values may be overridden by manual switches. Their status is indicated in

nvoHandBoard1-5 switch:state. state=0: manual Off state=1: manual On

state=255 ('invalid'): Auto

Any DO status change will immediately be transmitted.

DO Values in the Off-line Condition

The DO values are expected to be updated regularly. However, this may be prevented by communication failure or, temporarily, after power-up.

(continued ...)

02-00002-01-en, Nov 2009

(4)

Schneider Electric TAC Xenta 421A, TAC Xenta 422A Installation Instructions

To determine if all nviDO1-5 are to be considered valid, an interval counter is used:

nciRcvHrtBt No. of seconds until nviDO1-5 are considered invalid. (0: function is not used; default value.)

If this happens, due to communication failure, the behavior is determined by

nciOfflineBeh, using the following bits:

Bit 0

Bit 15

DO 1

DO 2

DO 3

DO 4

DO 5

If bit=1: Use default value as specified by

nciOfflineVal, using the following bits, where the value to be used is specified (0 or 1). (Default value=0.)

Bit 0

Bit 15

DO 1

DO 2

DO 3

DO 4

DO 5

If bit=0: Keep latest value (default).

SNVT vs TAC XENTA I/O MODULE COMMUNICATION

The TAC Xenta 421A/422A can be used in networks with either LONMARK communication or TAC Xenta I/O module communication. The device automatically determines which type of communication to use.

 

 

 

 

Green

 

 

 

Power-up

off-line

 

 

 

 

 

blink

 

 

SNVT

TAC Xenta I/O module

 

communication

 

 

received

 

 

established

 

 

 

 

 

 

Green blink

 

 

 

TAC Xenta

I/O on-line:

SNVT

 

 

I/O module

at comm.

 

 

green 0.5 Hz

TAC Xenta

or 0.1 Hz

 

communication

 

I/O module comm. established

In the Power-up state, the green LED blinks "Off-line". The

State diagram

device is open for both SNVT and TAC Xenta I/O module communication.

Previous configuration, if defined, will apply until a change is initiated.

SNVT received

Once in the TAC Xenta I/O module communication state, the device can only enter the SNVT state after a new Power-up. At this stage all nci:s must be updated, since the same memory area is used by both the SNVT and TAC Xenta I/O module communication configuration parameters.

Note! As the TAC Xenta I/O module communication state is a 'dead-end' (until power-up), any mis-addressed communication may cause the I/O module to loose its SNVT communication state.

TAC Xenta I/O module communication is inititiated by the controller at events specified below. If an I/O module intended for SNVT communication has been used in another configuration and happens to have an address that is used by the I/O module communication, the I/O module will be 'lost' in this state.

TAC Xenta I/O module communications will be initiated by the following events:

Controller power-up

I/O module power-up

Controller application download

Recovery after communication failure

The device enters the SNVT state. The device is configured

 

 

 

 

 

 

 

 

 

 

 

 

when the nci:s are updated. The green LED will light up when

 

 

 

 

 

 

 

Service pin

there is communication or approximately every 10 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

SNVT transmission is determined by the nciSndDelta1-4 or

 

 

 

 

 

 

 

 

 

 

 

 

the nciSndHrtBt values.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The device remains in the SNVT state until a TAC Xenta I/O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

module communication state is established, or until the next

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red LED (Configuration error)

 

power-up. In the SNVT state it is possible to change the con-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- blinking: unconfigured node

 

 

 

 

 

 

 

 

 

 

figuration by updating the network configuration inputs nci:s.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- steady: appl.less (or hw fault)

 

 

 

 

 

 

 

 

 

 

 

TAC Xenta I/O module Communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The TAC Xenta I/O module communication state is accepted

 

 

 

 

 

 

 

 

 

 

 

 

only after a thorough protocol initiation. This may be initiated

 

 

 

 

 

 

 

 

 

 

 

 

at any time.

 

 

 

 

 

 

 

 

 

 

 

 

In the TAC Xenta I/O module communication state, no nvi:s

 

 

 

 

 

 

 

 

 

 

 

 

or nci:s can be used. The green LED blinks on-line at about

 

Green LED (Communication)

0.5 Hz.

 

 

- SNVT: at communication or ~ once in 10 sec.s

 

 

Input SNVTs are ignored, also when the device is off-line from

 

- TAC Xenta I/O mod communication:

the controller.

 

 

 

on-line ~ every other sec; off-line ~ 5 blinks per sec

However, output SNVT transmission is still performed using a

LED indicators on front panel

hard-coded interval of about 10 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(4)

 

 

 

 

 

 

 

 

02-00002-01-en, Nov 2009

Loading...
+ 2 hidden pages