Digital, On/Off Thermostat
General Instructions
T200 series thermostats provide temperature control on a variety of heating, cooling and single stage heat pump applications.
The large LCD window displays room temperature including degree increments indicated by a series of dashes. The system heat output cycles on a 1 or 2F degree field selectable differential. The cool output differential is fixed at 2F degrees. The setpoint is displayed and changed by pressing one of the setpoint buttons up or down. Installation is simplified by having all of the field wires mounted to the separate wall plate.
This is a powered thermostat, which must receive 75 mA of power at all times.
T200 Series
•LCD window display
•Jumper selectable 5 minute time delay for heating and cooling applications
•Mechanical contact for 40°F limit freeze protection (optional)
Printed in U.S.A. 5/10 |
© Copyright 2010 Schneider Electric All Rights Reserved. |
F-27027-5 |
SPECIFICATIONS Inputs
Outputs
Electrical:
Battery, Setpoint backup (Energizer 357 or equivalent).
Operating Differential, Heating 1 or 2F degrees (0.6 or 1.1C degrees), Cooling 2F degrees (1.1C degrees).
Setpoint Adjustment Range, 50 to 86° F (10 to 30°C).
Environment
Shipping Weight: 0.4 lbs (170 g).
Model |
Control Outputs |
Fan |
System |
Changeover |
Mechanical Contact |
B & O |
|
Control |
Switch |
Terminals |
|||||
|
|
|
|
||||
|
|
|
|
|
|
|
|
T201 |
Heating Only |
None |
Heat/Off |
None |
No |
No |
|
|
|
|
|
|
|
|
|
T201-FPa |
Heating Only |
None |
Heat/Off |
None |
Yes |
No |
|
T204 |
Cooling Only |
On/Auto |
Cool/Off |
None |
No |
No |
|
|
|
|
|
|
|
|
|
T205 |
Cooling & Heating |
On/Auto |
Cool/Off/Heat |
Manual |
No |
No |
|
|
|
|
|
|
|
|
|
T205-FPa |
Cooling & Heating |
On/Auto |
Cool/Off/Heat |
Manual |
Yes |
No |
|
T207 |
Cooling & Heating |
On/Auto |
Cool/Off/Heat |
Manual |
No |
Yes |
|
|
|
|
|
|
|
|
|
T207-FPa |
Cooling & Heating |
On/Auto |
Cool/Off/Heat |
Manual |
Yes |
Yes |
a On T20X-FP (freeze protection) models a relay will provide power to a valve or relay if the thermostat fails.
2 |
© Copyright 2010 Schneider Electric All Rights Reserved. |
F-27027-5 |
DISPLAY |
|
|
|
HEATING OPERATING |
|
|
|
DIFFERENTIAL |
|
|
|
HEAT CONTROL |
|
|
RH |
COOL CONTROL |
|
|
|
|
|
RC |
|
|
|
|
|
|
|
|
W |
|
|
|
Y |
|
|
|
G |
AUTO |
|
TH |
B |
HC |
|
||
FAN |
|
|
O |
CONTROL |
|
|
|
|
|
|
|
Feature |
Jumpered |
Not Jumpered |
|
|
|
|
1. |
Display |
Celsius |
Fahrenheit |
|
|
|
|
2. |
Heating operation differential |
2 degrees |
1 degree |
|
|
|
|
3. |
Heat control |
No delay |
5 minute delay |
|
|
|
|
4. |
Cool control* |
No delay |
5 minute delay |
|
|
|
|
* T201, heat only model, only has jumper options 1 thru 3. A fourth jumper location exists but is non-functional in heat only models.
F-27027-5 |
© Copyright 2010 Schneider Electric All Rights Reserved. |
3 |