Schneider Electric VW3A3310d User Manual

5 (1)

Altivar® 61 / 71

User's manual

 

Modbus® TCP/IP Daisy Chain Ethernet Card

30072-452-37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retain for future use

 

VW3A3310d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table of contents

Important Information _________________________________________________________________________________________ 5

Before you begin_____________________________________________________________________________________________ 6

Documentation structure_______________________________________________________________________________________ 7

Introduction_________________________________________________________________________________________________ 8 Presentation _____________________________________________________________________________________________ 8 Notation ________________________________________________________________________________________________ 8

Hardware setup _____________________________________________________________________________________________ 9 Receipt _________________________________________________________________________________________________ 9 Hardware description ______________________________________________________________________________________ 9 Installing the card in the drive ________________________________________________________________________________ 9

Connecting to the Ethernet network _____________________________________________________________________________ 10 Card RJ45 connector pinout________________________________________________________________________________ 10 Example of connection to an Ethernet network _________________________________________________________________ 10 Ethernet network connection elements________________________________________________________________________ 11

Ethernet menu _____________________________________________________________________________________________ 12 Access to Ethernet menu via graphic display terminal ____________________________________________________________ 12 Access to Ethernet menu via the integrated display terminal _______________________________________________________ 12 Ethernet menu parameters_________________________________________________________________________________ 13

Configuration ______________________________________________________________________________________________ 16 List of functions to be configured ____________________________________________________________________________ 16 Configuring IP addresses __________________________________________________________________________________ 17 Reserving control ________________________________________________________________________________________ 19 Configuring IO Scanning___________________________________________________________________________________ 19 Configuring the control ____________________________________________________________________________________ 20 Configuring the fault management ___________________________________________________________________________ 23 Configuring monitored parameters ___________________________________________________________________________ 25

Diagnostics ________________________________________________________________________________________________ 26 Signalling LEDs _________________________________________________________________________________________ 26 Available information _____________________________________________________________________________________ 27 Monitoring the control _____________________________________________________________________________________ 27 Troubleshooting communication interruptions __________________________________________________________________ 28 Troubleshooting the card __________________________________________________________________________________ 29

Software setup _____________________________________________________________________________________________ 30 List of services supported __________________________________________________________________________________ 30 TCP connections ________________________________________________________________________________________ 30

Modbus TCP server _________________________________________________________________________________________ 31 Modbus TCP frames______________________________________________________________________________________ 31 Drive Modbus servers_____________________________________________________________________________________ 31 Ethernet card parameters __________________________________________________________________________________ 32 List of Modbus functions supported __________________________________________________________________________ 35 “Read Holding Registers” (3) function ________________________________________________________________________ 35 “Write Single Register” (6) function___________________________________________________________________________ 36 “Write Multiple Registers” (16 = 16#10) function ________________________________________________________________ 37 “Read/Write Multiple Registers” (23 = 16#17) function____________________________________________________________ 38 “Read Device Identification” (43 = 16#2B) function ______________________________________________________________ 39

IO Scanning service _________________________________________________________________________________________ 40 Presentation ____________________________________________________________________________________________ 40 Periodic variables ________________________________________________________________________________________ 40 Address table ___________________________________________________________________________________________ 41

FDR service _______________________________________________________________________________________________ 42 Presentation ____________________________________________________________________________________________ 42 Local configuration _______________________________________________________________________________________ 43 Downloaded configuration _________________________________________________________________________________ 44 Periodic saving __________________________________________________________________________________________ 46 Other commands ________________________________________________________________________________________ 46 Configuration file_________________________________________________________________________________________ 46

3

Table of contents

Standard Web server ________________________________________________________________________________________ 47 Web server functions _____________________________________________________________________________________ 47 Applets ________________________________________________________________________________________________ 48 Access to the Web server__________________________________________________________________________________ 49 Web server user interface__________________________________________________________________________________ 50 “Home” menu ___________________________________________________________________________________________ 50 “Monitoring” menu________________________________________________________________________________________ 50 “Altivar Viewer” page _____________________________________________________________________________________ 51 “Data Viewer” page_______________________________________________________________________________________ 52 “Altivar Chart” page_______________________________________________________________________________________ 53 “Diagnostics” menu_______________________________________________________________________________________ 53 “Ethernet Statistics” page __________________________________________________________________________________ 54 “Setup” menu ___________________________________________________________________________________________ 54 “HTTP password” and “Data write password pages” _____________________________________________________________ 55 “FDR Agent” page________________________________________________________________________________________ 56 “IO Scanner” page _______________________________________________________________________________________ 58 "E-mail" page ___________________________________________________________________________________________ 61 “Documentation” menu ____________________________________________________________________________________ 62

FTP server ________________________________________________________________________________________________ 63

Downloading from the Web server ______________________________________________________________________________ 65

SNMP agent _______________________________________________________________________________________________ 68

Setup using PL7 ____________________________________________________________________________________________ 70

Setup using Concept ________________________________________________________________________________________ 76

Setup using ProWORX NxT ___________________________________________________________________________________ 77

4

1. Important Information

NOTICE

Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.

The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.

This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.

DANGER

DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death, serious injury, or equipment damage.

WARNING

Warning indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.

CAUTION

CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.

PLEASE NOTE:

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

© 2008 Schneider Electric. All Rights Reserved.

5

2. Before you begin

Read and understand these instructions before performing any procedure with this drive.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Read and understand this manual before installing or operating the Altivar 61 (ATV61) or Altivar 71 (ATV71) drive controller. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.

The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all equipment.

Many parts of this drive controller, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.

DO NOT touch unshielded components or terminal strip screw connections with voltage present.

DO NOT short across terminals PA/+ and PC/- or across the DC bus capacitors.

Before servicing the drive controller

-Disconnect all power, including external control power that may be present.

-Place a “DO NOT TURN ON” label on all power disconnects.

-Lock all power disconnects in the open position.

-WAIT 15 MINUTES to allow the DC bus capacitors to discharge. Then follow the DC bus voltage measurement procedure given in the Installation Manual to verify that the DC voltage is less than 42 V. The drive LED is not an indicator of the absence of DC bus voltage.

Install and close all covers before applying power or starting and stopping the drive controller.

Failure to follow these instructions will result in death or serious injury.

WARNING

DAMAGED EQUIPMENT

Do not install or operate any drive or drive accessory that appears damaged.The relays, inputs, or outputs of a damaged drive may not operate in a normal manner, leading to unintended equipment operation.

Failure to follow this instruction can result in death, serious injury, or equipment damage.

WARNING

LOSS OF CONTROL

The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop.

Separate or redundant control paths must be provided for critical control functions.

System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.*

Each implementation of an Altivar 71 Modbus TCP/IP Ethernet card must be individually and thoroughly tested for proper operation before being placed into service.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

* For additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems.”

6

3. Documentation structure

The following Altivar 61 and Altivar 71 technical documents are available on the web site www.us.Telemecanique.com and on the CD ROM delivered with each drive controller.

b Installation Manual

This manual describes:

How to assemble the drive controller

How to connect the drive controller

b Programming Manual

This manual describes:

The drive controller functions

The drive controller parameters

How to use the drive display terminal (integrated display terminal and graphic display terminal)

Installation and Programming Manuals

Drive

Range

Installation Manual

Programming Manual

Family

(hp)

Module No.

Module No.

ATV61

0.5–100

1760643

1760649

 

 

(atv61s_installation_manual)

(atv61_programming_manual)

 

75–800

1760655

 

 

 

(atv61e_installation_manual)

 

ATV71

0.5–100

1755843

1755855

 

 

(atv71s_installation_manual)

(atv71_programming_manual)

 

75–700

1755849

 

 

 

(atv71e_installation_manual)

 

7

4. Introduction

4. 1. Presentation

The Ethernet card (catalog number VW3A3310d) is used to connect an Altivar 61 / 71 drive to an Ethernet network using the Modbus TCP/IP protocol and Transparent Ready services.

The VW3A3310d card is equipped with two shielded RJ45 Ethernet connectors.

The accessories for connection to the Ethernet network must be ordered separately.

The data exchanges permit the following drive functionality:

Configuration

Adjustment

Control

Monitoring

Diagnostics

The standard web server (English only) provides access to the following pages:

Altivar Viewer

Data Viewer

Ethernet

Security

The standard web server can be adapted or replaced by a customized server depending on the requirements of the application.

The graphic display terminal or the integrated display terminal can be used to access numerous functions for communication diagnostics.

4. 2. Notation

Drive terminal displays

The graphic display terminal menus are shown in square brackets.

Example: [1.9 COMMUNICATION].

The integrated 7-segment display terminal menus are shown in parentheses.

Example: (COM-).

The parameter names displayed on the graphic display terminal are shown in parentheses.

Example: [Fallback speed].

The parameter codes displayed on the integrated 7-segment display terminal are shown in round brackets. Example: (LFF).

Formats

Hexadecimal values are written as follows: 16#

Binary values are written as follows: 2#

8

Schneider Electric VW3A3310d User Manual

5. Hardware setup

5. 1. Receipt

Check that the card catalog number marked on the label is the same as that on the delivery note corresponding to the purchase order.

Remove the option card from its packaging and check that it has not been damaged in transit.

CAUTION

STATIC SENSITIVE COMPONENTS

Avoid damage to the Modbus TCP/IP card by electrostatic discharge. Observe the electrostatic precautions below when handling controller circuit boards or when testing components.

Failure to follow these instructions can result in injury or equipment damage.

Observe the following precautions for handling static-sensitive components:

Keep static-producing material such as plastic, upholstery, and carpeting out of the immediate work area.

Store the Modbus TCP/IP card in its electrostatic protective packaging when it is not installed in the drive controller.

When handling the Modbus TCP/IP card, wear a conductive wrist strap connected to the card through a minimum of 1 megohm resistance.

Avoid touching exposed conductors and component leads with skin or clothing.

5. 2. Hardware description

LEDs

Shielded female RJ45

 

 

 

Shielded female RJ45

 

 

 

Ethernet connector

 

 

 

Ethernet connector

(Port 2)

 

MAC address label

 

(Port 1)

 

 

 

 

 

 

on the Ethernet card

 

 

5. 3. Installing the card in the drive

See the ATV61 or ATV71 Installation Manual.

9

6. Connecting to the Ethernet network

6. 1. Card RJ45 connector pinout

The Ethernet card is equipped with a shielded RJ45 connector. The shielding is connected to the drive ground. Use STP (shielded twisted pair) Ethernet cable.

 

Pin

Signal

 

1

TD+

 

2

TD-

 

3

RD+

 

4

 

 

5

 

 

6

RD-

8........................1

7

 

8

 

 

 

The transmission speed is detected automatically by the card (10 Mbps or 100 Mbps).

The card can operate in half duplex or full duplex mode, whether connected to a hub or switch, regardless of the transmission speed (10 Mbps or 100 Mbps).

The card supports the ETHERNET 2 frame format (IEEE 802-3 not supported).

6. 2. Example of connection to an Ethernet network

PLC

Daisy chain and/or star topology (1)

ATV61/71 ATV61/71 ATV61/71 ATV61/71 ATV61/71

Ethernet switch

(1)When the topology is a daisy chain, if one drive is turned off, the other drive(s) stop in response to a communication network fault (CNF).

Redundancy can be added by connecting the first and last drive in the daisy chain to a hub or switch to create a loop.

10

6. Connecting to the Ethernet network

6. 3. Ethernet network connection elements

Please consult our catalog “Ethernet TCP/IP and the Web” (available on the web site www.telemecanique.com).

Connecting cables

Description

Use

 

Length

Catalog number

 

From

To

m

 

Straight shielded twisted pair cables

ATV71

Hubs

2

490 NTW 000 02

2 RJ45 connectors

(+ VW3A3310d card)

499 NpH 1pp 10

 

 

5

490 NTW 000 05

 

 

Switches

 

 

12

490 NTW 000 12

 

 

499 NpS 171 00

 

 

 

 

 

 

 

40

490 NTW 000 40

 

 

 

80

490 NTW 000 80

Hubs and switches

Description

Characteristics

Catalog number

Hubs

4 × 10BASE-T ports

499 NEH 104 10

 

4

× 100BASE-TX ports

499 NEH 141 10

 

3

× 10BASE-T ports

499 NOH 105 10

 

2

× 10BASE-FL ports, multimode fiber, ST (BFOC) connectors

 

Switches

5 × 10BASE-T/100BASE-TX ports

499 NES 251 00

 

Unmanaged basic

 

 

4

× 10BASE-T/100BASE-TX ports

499 NMS 251 01

 

1

× 100BASE-FX port, multimode fiber, SC connectors

 

 

Unmanaged

 

 

3

× 10BASE-T/100BASE-TX ports

499 NMS 251 02

 

2

× 100BASE-FX port, multimode fiber, SC connectors

 

 

Unmanaged

 

 

4

× 10BASE-T/100BASE-TX ports

499 NSS 251 01

 

1

× 100BASE-FX port, monomode fiber, SC connectors

 

 

Unmanaged

 

 

3

× 10BASE-T/100BASE-TX ports

499 NSS 251 02

 

2

× 100BASE-FX port, monomode fiber, SC connectors

 

 

Unmanaged

 

 

 

 

 

 

8

× 10BASE-T/100BASE-TX ports

499 NES 181 00

 

Unmanaged

 

 

7

× 10BASE-T/100BASE-TX ports

499 NES 271 00

 

Managed

 

 

5

× 10BASE-T/100BASE-TX ports

499 NOS 271 00

 

2

× 100BASE-FX port, multimode fiber, SC connectors

 

 

Managed

 

 

5

× 10BASE-T/100BASE-TX ports

499 NSS 271 00

 

2

× 100BASE-FX port, monomode fiber, SC connectors

 

Managed

11

7. Ethernet menu

7. 1. Access to Ethernet menu via graphic display terminal

The [ETHERNET] submenu is used to configure and display the Ethernet card parameters and can be accessed via the [1.9 - COMMUNICATION] menu.

If you are using the FDR (Faulty Device Replacement) function, you must also configure the device name in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu, [DEVICE NAME] submenu.

This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).

 

 

 

 

 

RDY

NET

+0.00 Hz

0A

 

 

 

 

 

 

 

 

 

 

 

 

1 DRIVE MENU

 

 

 

 

 

 

 

 

 

 

 

 

1.1 SIMPLY START

 

 

 

 

 

 

 

 

 

 

 

 

 

1.3 SETTINGS

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4 MOTOR CONTROL

 

 

 

RUN

NET

+50.00 Hz

80A

 

 

 

 

 

1.5 INPUTS/OUTPUTS CFG

 

 

 

 

1.9 COMMUNICATION

 

 

 

 

 

 

Code

<<

>>

Quick

 

 

COM. SCANNER OUTPUT

 

 

 

 

 

 

1.6 COMMAND

 

 

 

 

MODBUS HMI

 

 

RDY

NET +0.00 Hz

0A

 

 

1.7 APPLICATION FUNCT.

 

 

 

MODBUS NETWORK

 

 

MAIN MENU

 

ENT

 

1.8 FAULT MANAGEMENT

 

ENT

 

CANopen

 

 

1 DRIVE MENU

 

 

 

1.9 COMMUNICATION

 

 

 

ETHERNET

 

 

 

 

 

 

 

 

 

2 ACCESS LEVEL

 

 

 

1.10 DIAGNOSTICS

 

 

 

Code

<<

>>

Quick

3 OPEN / SAVE AS

 

 

 

1.11 IDENTIFICATION

 

 

 

 

 

 

 

4 PASSWORD

 

 

 

1.12 FACTORY SETTINGS

 

 

 

 

 

 

 

5 LANGUAGE

 

 

 

1.13 USER MENU

 

 

 

 

 

 

 

 

Code

 

Quick

 

 

1.14 PROGRAMMABLE CARD

 

 

 

 

 

 

 

7. 2. Access to Ethernet menu via the integrated display terminal

The (EtH-) submenu is used to configure and display the Ethernet card parameters. It can be accessed via the (COM-) menu.

Note: The device name required for the FDR (Faulty Device Replacement) function cannot be configured via the integrated display terminal.

Power-up

XXX Displays the drive state

ENT

 

ESC

 

SIM-

 

ESC

 

FLt-

 

ESC

ENT

EtH-

CON-

 

ESC

ESC

 

FCS-

 

ESC

 

LAC-

 

12

7. Ethernet menu

7. 3. Ethernet menu parameters

 

 

Code

 

Description

 

 

 

 

 

(bdr)

 

 

M [Bit rate]

 

 

 

 

 

 

 

 

Transmission speed detected on the network by the Ethernet card

 

 

 

 

 

 

 

Type:

Display (read-only)

 

 

 

 

 

 

 

Possible

[0 Mbps] (0M): Automatic detection of the Ethernet network speed

 

 

 

 

 

 

 

values:

[10 Mbps] (10M): 10 Mbps

 

 

 

 

 

 

 

 

[100 Mbps] (100M): 100 Mbps

 

 

 

 

 

 

 

Default value:

[0 Mbps] (0M)

 

 

 

 

(PAn-)

 

b [DEVICE NAME]

 

 

 

 

 

 

 

Device name used by FDR service. Accessible with an ATV71 from V1.2 and a ATV61 from V1.3 version.

 

 

 

 

 

 

 

Use the navigation selector button to increment the character (alphabetical order) and << and >> (F2 and F3) to switch

 

 

 

 

 

 

 

to the next or previous character respectively. Use F1 to change to ABC, abc, 123, *[-.

 

 

 

 

 

 

 

Type:

Configuration (read and write)

 

 

 

 

 

 

 

 

Display (read-only)

 

 

 

 

 

 

 

Possible values:

16 characters on 1 or 2 lines.

 

 

 

 

 

 

 

Default value:

[0]

 

 

 

 

(IPC-)

 

b [IP card]

 

 

 

 

(IPC1)

 

 

M [139.160.069.241] (139) (160) (069) (241)

 

 

 

 

(IPC2)

 

 

Ethernet card IP address

 

 

 

 

(IPC3)

 

 

Type:

Configuration (read and write)

 

 

 

 

(IPC4)

 

 

 

 

 

 

 

 

 

Display (read-only) if the address has been supplied by a BOOTP or DHCP server

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible

• 0 to 255 for each of fields IPC1, IPC2, IPC3 and IPC4.

 

 

 

 

 

 

 

values:

• If the value is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for an address from a BOOTP

 

 

 

 

 

 

 

 

or DHCP server.

 

 

 

 

 

 

 

 

Note: If you enter a value other than [0.0.0.0] (0) (0) (0) (0), dynamic addressing by a BOOTP

 

 

 

 

 

 

 

 

or DHCP server is disabled.

 

 

 

 

 

 

 

 

Note: After dynamic addressing by a BOOTP or DHCP server, the value [0.0.0.0] (0) (0) (0) (0)

 

 

 

 

 

 

 

 

is replaced by the address supplied.

 

 

 

 

 

 

 

Default value:

[0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPM-)

 

b [IP Mask]

 

 

 

 

(IPM1)

 

 

M [255.255.254.0] (255) (255) (254) (0)

 

 

 

 

(IPM2)

 

 

Subnet mask

 

 

 

 

 

(IPM3)

 

 

Type:

Configuration (read and write)

 

 

 

 

(IPM4)

 

 

 

 

 

 

 

 

 

Display (read-only) if the address has been supplied by a BOOTP or DHCP server

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible

• 0 to 255 for each of fields IPM1, IPM2, IPM3 and IPM4.

 

 

 

 

 

 

 

values:

• If the value of the IP address [IP card] is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for

 

 

 

 

 

 

 

 

a mask from a BOOTP or DHCP server.

 

 

 

 

 

 

 

 

Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the

 

 

 

 

 

 

 

 

address supplied.

 

 

 

 

 

 

 

Default value:

[0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPG-)

 

b [IP Gate]

 

 

 

 

(IPG1)

 

 

M [0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPG2)

 

 

Gateway IP address

 

 

 

 

(IPG3)

 

 

Type:

Configuration (read and write)

 

 

 

 

(IPG4)

 

 

 

 

 

 

 

 

 

Display (read-only) if the address has been supplied by a BOOTP or DHCP server

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible

• 0 to 255 for each of fields IPG1, IPG2, IPG3 and IPG4.

 

 

 

 

 

 

 

values:

• If the value of the IP address [IP card] is [0.0.0.0] (0) (0) (0) (0), the Ethernet card waits for

 

 

 

 

 

 

 

 

a mask from a BOOTP or DHCP server.

 

 

 

 

 

 

 

 

Note: After dynamic addressing by a BOOTP or DHCP server, the current value is replaced by the

 

 

 

 

 

 

 

 

address supplied.

 

 

 

 

 

 

 

Default value:

[0.0.0.0] (0) (0) (0) (0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

7. Ethernet menu

 

 

Code

 

Description

 

 

 

 

 

 

(IPP-)

 

b [IP Master]

 

 

 

 

(IPP1)

 

 

M [0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPP2)

 

 

 

 

 

 

 

 

 

 

(IPP3)

 

 

IP address of the device that retains control

 

 

 

 

(IPP4)

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

 

 

Display (read-only) if the address is supplied by a DHCP server

 

 

 

 

 

 

 

Possible

 

• 0 to 255 for each of fields IPP1, IPP2, IPP3 and IPP4.

 

 

 

 

 

 

 

values:

 

• If the value is [0.0.0.0] (0) (0) (0) (0), writing of the control word (CMd) is accepted

 

 

 

 

 

 

 

 

 

 

by the Ethernet card regardless of which device has sent it.

 

 

 

 

 

 

 

 

 

If the value is other than [0.0.0.0] (0) (0) (0) (0) only the device which has the IP address

 

 

 

 

 

 

 

 

 

 

[IP Master] is authorized to write the control word (CMd).

 

 

 

 

 

 

 

 

 

Note: This configuration also affects the type of communication monitoring.

 

 

 

 

 

 

 

Default value:

 

[0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPF-)

 

b [IP FDR]

 

 

 

 

 

 

(IPF1)

 

 

M [0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(IPF2)

 

 

 

 

 

 

 

 

 

 

(IPF3)

 

 

IP address of the FDR server

 

 

 

 

(IPF4)

 

 

Type:

 

Display (read-only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Possible

 

• 0 to 255 for each of fields IPF1, IPF2, IPF3 and IPF4.

 

 

 

 

 

 

 

values:

 

• If the value is [0.0.0.0] (0) (0) (0) (0), there is no server.

 

 

 

 

 

 

 

Default value:

 

[0.0.0.0] (0) (0) (0) (0)

 

 

 

 

(ISA)

 

 

M [IO Scan.activ.]

 

 

 

 

 

 

 

 

 

 

Enable IO Scanner

 

 

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[No] (nO): IO Scanner disabled.

 

 

 

 

 

 

 

values:

 

[Yes] (YES): IO Scanner enabled.

 

 

 

 

 

 

 

Default value:

 

[Yes] (YES)

 

 

 

 

(tOUt)

 

 

M [time out]

 

 

 

 

 

 

 

 

 

 

Ethernet communication monitoring time out

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[0] (0): Monitoring disabled.

 

 

 

 

 

 

 

values:

 

[0.5 s] (0.5) to [60.0 s] (60.0): Time out value (unit: 0.1 s).

 

 

 

 

 

 

 

Default value:

 

[2.0 s] (2.0)

 

 

 

 

(FdrU)

 

 

M [FDR validation]

 

 

 

 

 

 

 

 

 

 

Enable FDR service

 

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[No] (nO): FDR service disabled.

 

 

 

 

 

 

 

values:

 

[Yes] (YES): FDR service enabled.

 

 

 

 

 

 

 

Default value:

 

[Yes] (YES)

 

 

 

 

(LCFG)

 

 

M [FDR Local Config.]

 

 

 

 

 

 

 

Selection of local or server configuration

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

[No] (nO): The drive configuration is downloaded from an FDR server.

 

 

 

 

 

 

 

values:

 

[Yes] (YES): The drive configuration is local and saved in a FDR server.

 

 

 

 

 

 

 

Default value:

 

[No] (nO)

 

 

 

 

(FdrF)

 

 

M [FDR Error Mgt.]

 

 

 

 

 

 

 

 

 

 

Enable FDR file error detection

 

 

 

 

 

 

 

Type:

 

Configuration (read and write)

 

 

 

 

 

 

 

Possible

 

In the event of a problem with the FDR file (missing or invalid):

 

 

 

 

 

 

 

values:

 

[No] (nO): The Ethernet card does not trigger an [FDR fault] (Fdrd).

 

 

 

 

 

 

 

 

 

[Yes] (YES): The Ethernet card triggers an [FDR fault] (Fdrd).

 

 

 

 

 

 

 

Default value:

 

[Yes] (YES)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

7. Ethernet menu

 

 

Code

 

Description

 

 

 

 

 

 

(FdrA)

 

M [FDR Action]

 

 

 

 

 

 

 

 

FDR service command

 

 

 

 

 

 

Type:

Command (read and write)

 

 

 

 

 

 

Possible

[IDLE] (IdLE): No command.

 

 

 

 

 

 

values:

[SAVE] (SAUE): Command: save.

 

 

 

 

 

 

 

[REST] (rESt): Command: download.

 

 

 

 

 

 

 

[DEL] (dEL): Command: delete.

 

 

 

 

 

 

 

The command remains displayed during the action then reverts to the value [IDLE] (IdLE).

 

 

 

 

 

 

Default value:

[IDLE] (IdLE)

 

 

 

 

(FdrS)

 

M [FDR autosave]

 

 

 

 

 

 

 

 

Enable periodic saving of the FDR service

 

 

 

 

 

 

Type:

Configuration (read and write)

 

 

 

 

 

 

Possible

[No] (nO): Automatic saving disabled.

 

 

 

 

 

 

values:

[Yes] (YES): Automatic saving enabled.

 

 

 

 

 

 

Default value:

[No] (nO)

 

 

 

 

(Fdrt)

 

M [FDR t.autosave]

 

 

 

 

 

 

 

 

Interval for periodic saving of the FDR service

 

 

 

 

 

 

Type:

Configuration (read and write)

 

 

 

 

 

 

Possible

[2] (2) to [9999] (9999): 2 min to 9999 min.

 

 

 

 

 

 

values:

 

 

 

 

 

 

 

 

Default value:

[10] (10)

 

 

 

 

(FdrE)

 

M [FDR state]

 

 

 

 

 

 

 

 

FDR service state

 

 

 

 

 

 

 

 

Type:

Display (read-only)

 

 

 

 

 

 

Possible

[IDLE] (IdLE): “Idle”.

 

 

 

 

 

 

values:

[INIT] (INIt): Initialization.

 

 

 

 

 

 

 

[CONF] (CONF): Configuration.

 

 

 

 

 

 

 

[RDY] (rdY): Ready.

 

 

 

 

 

 

 

[GET] (GEt): Download the current configuration.

 

 

 

 

 

 

 

[SET] (SEt): Save the current configuration.

 

 

 

 

 

 

 

[APP] (APP): Write the FDR server configuration to the drive.

 

 

 

 

 

 

 

[OPE] (OPE): Operational.

 

 

 

 

 

 

 

[UCFG] (UCFG): Not configured.

 

 

 

 

 

 

Default value:

[IDLE] (IdLE)

 

 

 

 

(Fdrd)

 

M [FDR Error Code]

 

 

 

 

 

 

 

FDR service status code

 

 

 

 

 

 

Type:

Display (read-only)

 

 

 

 

 

 

Possible

[0] (0): No communication interruption

 

 

 

 

 

 

values:

[2] (2): The FDR configuration file is not compatible with the drive type

 

 

 

 

 

 

 

 

(example: the drive is not the same rating as that defined in the FDR file).

 

 

 

 

 

 

 

[3] (3): Error reading the FDR configuration file on the server.

 

 

 

 

 

 

 

[4] (4): Error writing the FDR configuration file to the server.

 

 

 

 

 

 

 

[7] (7): Time-out for receipt of the FDR configuration file from the server.

 

 

 

 

 

 

 

[9] (9): Duplication of IP address.

 

 

 

 

 

 

 

[12] (12): The FDR configuration file is missing.

 

 

 

 

 

 

Default value:

[0] (0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

8. Configuration

8. 1. List of functions to be configured

The table below gives the list of configuration functions and how they can be accessed:

Functions

 

Graphic

Integrated

PowerSuite

Standard

 

display

display

software

web

 

 

terminal

terminal

workshop

server

Entering the IP addresses

 

p

p

p

 

FDR

Entering the device name

p

 

p

 

Configuration (time delay, etc.)

p

p

p

p

(Faulty Device Replacement)

 

Commands (save, etc.)

p

p

 

p

IO Scanning

Enable IO Scanner

p

p

p

p

Configuring the IO Scanner variables

 

 

p

p

 

 

 

Reserving control (IP master)

 

p

p

p

p

Communication monitoring

 

p

p

p

p

Security of access

Changing the “username”

 

 

p

 

Changing the “HTTP password”

 

 

 

p

to the standard web server

 

 

 

 

Changing the “Write password”

 

 

p

p

Configuration using the drive graphic display terminal or the integrated display terminal is explained in the “Configuration” section. Configuration using the standard web server is explained in the “Standard web server” section.

For configuration using the PowerSuite software workshop, refer to the PowerSuite online help.

Notes:

The Ethernet card saves its configuration (IP address, mask, gateway, etc.) to the EEPROM each time the configuration is modified.

For performance reasons, Schneider Electric recommends using the Ethernet IO Scanner, not the drive communication scanner.

Configuration must be performed with the motor stopped.

16

8. Configuration

8. 2. Configuring IP addresses b Assigning IP addresses

The drive needs 3 IP addresses:

The drive IP address.

The subnet mask.

The gateway IP address (not always required).

Note: Some controllers, such as Prosoft® and DeltaV® modules, require a Modbus address to be set in addition to the IP address. This address must be set in menu 1.9 of the drive, as well as in the software for the master device.

These IP addresses can be entered:

Using the integrated display terminal.

Using the graphic display terminal.

Using the PowerSuite software workshop.

They can be provided by:

A BOOTP server (correspondence between the MAC address and the IP addresses).

A DHCP server (correspondence between Device Name [DEVICE NAME] and the IP addresses).

If an IP address other than 0.0.0.0 has been entered using the display terminal or the PowerSuite software workshop, assignment using a server is disabled.

The BOOTP service is enabled:

When no IP address other than 0.0.0.0 has been entered and

The FDR service has not been enabled ([FDR validation] parameter = [No] or a [DEVICE NAME] has not been entered).

The DHCP service is enabled:

When no IP address other than 0.0.0.0 has been entered and

The FDR service has been enabled ([FDR validation] parameter = [Yes] and a [DEVICE NAME] has been entered).

 

 

Power-up

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Initialization

 

 

An address has been entered

 

Static

 

 

 

 

 

 

[IP card] <> 0.0.0.0

 

 

addressing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No address has

been entered

 

 

 

 

 

 

 

 

 

 

[IP card] = 0.0.0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dynamic

 

 

 

 

 

 

BOOTP

 

 

 

 

 

 

[FDR validation] = [No]

 

 

 

 

 

 

addressing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

[FDR validation] = [Yes]

 

 

 

 

 

 

 

[DEVICE NAME] blank

FDR

[DEVICE NAME] has been entered

DHCP

17

8. Configuration

b Entering IP addresses in the terminal

In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu, enter the following IP addresses:

-[IP card] (IPC1) (IPC2) (IPC3) (IPC4).

-[IP Mask] (IPM1) (IPM2) (IPM3) (IPM4).

-[IP Gate] (IPG1) (IPG2) (IPG3) (IPG4) (not always required).

Note: Some controllers, such as Prosoft® and DeltaV® modules, require a Modbus address to be set in addition to the IP address. This address must be set in menu 1.9 of the drive, as well as in the software for the master device.

Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the IP addresses are not taken into account.

Note: Before entry begins, the IP address displayed is the active IP address.

If this address is modified, the new IP address entered is displayed. This IP address will be effective the next time the drive is turned on.

b Configuring BOOTP

The BOOTP service is used to assign IP addresses from the MAC address. The MAC address consisting of 6 octets (00-80-F4-80-xx-yy) must be entered in the BOOTP server. The MAC address appears on the label attached to the Ethernet card.

In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:

Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).

Do not enable the FDR service: [FDR validation] (FdrU) = [No] (nO).

b Configuring FDR

The FDR service (based on DHCP) is used to assign the IP addresses and other parameters from the device name that must be entered in the drive and in the FDR server (DHCP).

In the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu:

Leave the IP address [IP card] (IPC1) (IPC2) (IPC3) (IPC4) at the value [0.0.0.0] (0) (0) (0) (0).

Enable the FDR service: [FDR validation] (FdrU) = [Yes] (YES).

For the FDR function, select the drive configuration as either:

Local: [FDR Local Config.] (LCFG) = [Yes] (YES).

Downloaded. In this case, it is essential to consult the “FDR Service” section.

Enter the device name, [DEVICE NAME], in the [7. DISPLAY CONFIG.] menu, [7.1 USER PARAMETERS] submenu. This menu is only accessible in expert mode: In the [2 ACCESS LEVEL] (LAC-) menu, set the level to [expert] (EPr).

Turn the drive off and then back on again (control voltage if a separate power supply is being used), otherwise the device name is not taken into account.

Note: The FDR function cannot be fully configured using the integrated display terminal as it does not provide access to the device name.

18

8. Configuration

8. 3. Reserving control

It is strongly recommended that control should be reserved for a single master device.

If control were not to be reserved for a master device (for example a PLC):

Any other Modbus TCP Ethernet client could send unwanted commands.

Other clients could use the 8 available TCP connections and prevent the master from having control.

DANGER

UNINTENDED EQUIPMENT OPERATION

Ensure that a valid address for the IP master device has been specified.

Failure to follow this instruction will result in death, serious injury, or equipment damage.

Use the [IP Master] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended operation.

To configure this reservation, enter an IP address other than [0.0.0.0] (0) (0) (0) (0) in the [1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu, [IP Master] submenu.

If control has been reserved:

Only the control word (CMd) written by the master with control will be accepted via IO Scanning or via Modbus TCP messaging. 2 TCP connections are reserved for this device. In this way, you avoid other TCP clients using all the available connections

(8 maximum) and the control master no longer being able to access the drive Modbus TCP server.

Other parameters written from other IP addresses are accepted (for example, adjustments or writing a setpoint). When control has been reserved and another device attempts to write the control word (CMd):

-via IO Scanning: The Modbus TCP connection for this client is immediately reinitialized.

-via Modbus TCP messaging: Control is denied.

If control has not been reserved ([IP Master] = [0.0.0.0] (0) (0) (0) (0)), control can come from any IP address.

8. 4. Configuring IO Scanning

Refer to the “IO Scanning Service” section.

The drive IO Scanning service can be enabled or disabled in the [1.9 - COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu via parameter [IO Scan.activ.] (IOSA).

It is not possible to modify the assignment of the IO Scanning periodic variables using the display terminal (integrated or graphic).

To configure IO Scanning, use the standard web server or the PowerSuite software workshop.

19

8. Configuration

8. 5. Configuring the control

Numerous configurations are possible. For more information, refer to the Programming Manual and the Communication parameters Manual.

The following configurations are just some of the possibilities available.

b Control via Ethernet in I/O profile

The command and setpoint come from Ethernet. The command is in I/O profile.

Configure the following parameters:

 

 

 

 

Parameter

Value

Comment

Profile

I/O profile

The run command is simply obtained by bit 0 of the control word.

Setpoint 1 configuration

Network card

The setpoint comes from Ethernet.

Command 1 configuration

Network card

The command comes from Ethernet.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[I/O profile] (IO)

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

[Cmd channel 1] (Cd1)

[Com. opt card] (nEt)

b Control via Ethernet or the terminals in I/O profile

Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet and the terminals.

The command is in I/O profile.

Configure the following parameters:

 

 

 

 

 

Parameter

Value

Comment

Profile

I/O profile

The run command is simply obtained by bit 0 of the control word.

Setpoint 1 configuration

Network card

Setpoint

1 comes from Ethernet.

Setpoint 1B configuration

Analog input 1 on the terminals

Setpoint

1B comes from input AI1 on the terminals.

Setpoint switching

Input LI5

Input LI5 switches the setpoint (1 1B).

Command 1 configuration

Network card

Command 1 comes from Ethernet.

Command 2 configuration

Terminals

Command 2 comes from the terminals.

Command switching

Input LI5

Input LI5 switches the command.

Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[I/O profile] (IO)

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

[Cmd channel 1] (Cd1)

[Com. card] (nEt)

 

[Cmd channel 2] (Cd2)

[Terminals] (tEr)

 

[Cmd switching] (CCS)

[LI5] (LI5)

[1.7 APPLICATION FUNCT.] (FUn-)

[Ref.1B channel] (Fr1b)

[Ref. AI1] (AI1)

[REFERENCE SWITCH.]

 

 

[Ref 1B switching] (rCb)

[LI5] (LI5)

 

20

8. Configuration

b Control via Ethernet in CiA402 (Drivecom) profile

The command and setpoint come from Ethernet. The command is in CiA402 profile.

Note: The term Drivecom has been in use since 1991. Recently, the term has changed to DSP402, and currently is CiA402. This profile requires a specific sequence of commands to control the drive. The profile is a standard that is available for use by many brands and products to facilitate interchangeability of similar products from different manufacturers. Refer to the Communications Parameters and Programming guides for additional details.

Configure the following parameters:

Parameter

Value

Comment

Profile

Not separate

The run commands are in CiA402 profile, the command and the setpoint come

 

 

from the same channel.

Setpoint 1 configuration

Network card

The command comes from Ethernet.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[Not separ.] (SIM) (factory setting)

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

b Control via Ethernet or the terminals in CiA402 profile

Both the command and setpoint come from Ethernet or the terminals. Input LI5 at the terminals is used to switch between Ethernet and the terminals.

The command is in CiA402 profile.

Configure the following parameters:

 

 

 

 

Parameter

Value

Comment

Profile

Not separate

The run commands are in CiA402 profile, the command and the setpoint

 

 

come from the same channel.

Setpoint 1 configuration

Network card

Setpoint 1 comes from Ethernet.

Setpoint 2 configuration

Analog input 1 on the terminals

Setpoint 2 comes from input AI1 on the terminals.

Setpoint switching

Input LI5

Input LI5 switches the setpoint (1 2) and the command.

Note: Setpoint 2 is directly connected to the drive setpoint limit. If switching is performed, the functions that affect the setpoint (summing, PID, etc.) are disabled.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[Not separ.] (SIM)

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

[Ref.2 chan] (Fr2)

[Ref. AI1] (AI1)

 

[Ref. 2 switching] (rFC)

[LI5] (LI5)

21

8. Configuration

b Command in CiA402 (Drivecom) profile via Ethernet and setpoint switching at the terminals

The command comes from Ethernet.

The setpoint comes either from Ethernet or from the terminals. Input LI5 at the terminals is used to switch the setpoint between Ethernet and the terminals.

The command is in CiA402 profile.

Configure the following parameters:

 

 

 

 

Parameter

Value

Comment

Profile

Separate

The run commands are in CiA402 profile, the command and the setpoint

 

 

can come from different channels.

Setpoint 1 configuration

Network card

Setpoint 1 comes from Ethernet.

Setpoint 1B configuration

Analog input 1 on the terminals

Setpoint 1B comes from input AI1 on the terminals.

Setpoint switching

Input LI5

Input LI5 switches the setpoint (1 1B).

Command 1 configuration

Network card

Command 1 comes from Ethernet.

Command switching

Channel 1

Channel 1 is the command channel.

Note: Setpoint 1B is connected to the functions (summing, PID, etc.), which remain active, even after switching.

Configuration via the graphic display terminal or the integrated display terminal:

Menu

Parameter

Value

[1.6 - COMMAND] (CtL-)

[Profile] (CHCF)

[Separate] (SEP)

 

[Ref.1 channel] (Fr1)

[Com. card] (nEt)

 

[Cmd channel 1] (Cd1)

[Com. card] (nEt)

 

[Cmd switching] (CCS)

[Ch1 active] (Cd1)

[1.7 APPLICATION FUNCT.] (FUn-)

[Ref.1B channel] (Fr1b)

[Ref. AI1] (AI1)

[REFERENCE SWITCH.]

 

 

[Ref 1B switching] (rCb)

[LI5] (LI5)

 

22

8. Configuration

8. 6. Configuring communication interruption management b Communication monitoring

The Ethernet card can detect 2 types of communication interruptions:

-Network management (server missing, duplication of IP address, etc.).

-Communication (time out on the master traffic, etc.).

The associated information is:

 

 

 

 

 

 

Ethernet interruption type

 

Network management

Communication

Associated drive parameter

Code:

Code:

 

[External fault com.] (EPF2)

[Com. network] (CnF)

Configuring the communication

Parameter:

Parameter:

interruption or file error detection

[FDR Error Mgt.] (FdrF)

[time Out] (tOUt)

settings

Menu:

Menu:

 

[1.9 COMMUNICATION] (COM-)

[1.9 COMMUNICATION] (COM-)

 

Submenu:

Submenu:

 

[ETHERNET] (EtH-)

[ETHERNET] (EtH-)

 

 

 

Configuring the drive’s

Parameter:

Parameter:

response

[External fault mgt] (EPL)

[COM. fault mgt] (CLL)

 

Menu:

Menu:

 

[1.8 FAULT MANAGEMENT] (FLt-)

[1.8 FAULT MANAGEMENT] (FLt-)

 

Submenu:

Submenu:

 

[EXTERNAL FAULT] (EtF-)

[COM. FAULT MANAGEMENT] (CLL-)

 

 

 

b Network management

The IP address duplication management detection cannot be configured.

If the FDR (Faulty Device Replacement) service has been configured, the FDR communication interruption detection can be disabled via the [FDR Error Mgt.] (FdrF) parameter, which can be accessed via the [1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu.

In factory settings mode, a network management interruption will trigger a resettable drive stop condition [External fault com.] (EPF2) and initiate a freewheel stop.

b Communication

It is strongly recommended that control should be reserved for a single master device. Monitoring begins when the first control word is received.

DANGER

UNINTENDED EQUIPMENT OPERATION

Ensure that a valid address for the IP master device has been specified.

Failure to follow this instruction will result in death, serious injury, or equipment damage.

Use the [IP MASTER] (IPP) menu option to configure a network master device. If a valid IP address for a master device is not specified using this option, other Ethernet clients can saturate the TCP connections or send incorrect commands leading to unintended equipment operation.

If control has been reserved:

A communication interruption is triggered if the Ethernet card does not receive a Modbus TCP request within a predefined period of time (time out).

Any type of Modbus request from the master device [IP Master] is taken into account (write operation, read operation, etc.).

If control has not been reserved:

A communication interruption is triggered if the Ethernet card does not receive a control word write request (CMd) within a predefined period of time (time out).

Receipt of the command (CMd) is taken into account regardless of the sender’s IP address.

The “time out” can be set to between 0.5 and 60 s via the graphic display terminal or integrated display terminal in the [1.9 COMMUNICATION] (COM-) menu, [ETHERNET] (EtH-) submenu via the [time Out] (tOUt) parameter. The default value is 2 s.

In factory settings mode, if Ethernet is involved in the command or setpoint, a communication interruption will trigger a resettable stop condition [Com. network] (CnF) and initiate a freewheel stop.

23

8. Configuration

b Drive response

The drive response to an Ethernet communication interruption can be configured via the graphic display terminal or the integrated display terminal from the [1.8 FAULT MANAGEMENT] (FLt-) menu:

 

 

RDY

NET

+0.00Hz

0A

For communication faults

 

COM. FAULT MANAGEMENT

 

Network fault mgt

:

Freewheel

 

in the [COM. FAULT MANAGEMENT] (CLL-) submenu

 

CANopen fault mgt

:

Freewheel

 

via parameter [COM. fault mgt] (CLL)

 

Modbus fault mgt

:

Freewheel

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

 

 

Quick

 

 

 

 

 

 

 

 

 

 

RDY

NET

+0.00Hz

0A

For network management faults

 

 

EXTERNAL FAULT

 

External fault mgt

:

Freewheel

 

in the [EXTERNAL FAULT] (EtF-) submenu

 

 

 

 

 

 

 

via the [External fault mgt] (EPL) parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

 

 

Quick

 

 

The values of parameters: [COM. fault mgt] (CLL) that will trigger a stop response from the drive [Com. network] (CnF) and [External fault mgt] (EPL) that will trigger a stop response from the drive [External fault com.] (EPF2) are: [Freewheel] (YES): Freewheel stop (factory setting).

[Ramp stop] (rMP): Stop on ramp. [Fast stop] (FSt): Fast stop.

[DC injection] (dCI): DC injection stop.

The values of parameters [COM. fault mgt] (CLL) and [External fault management] (EPL) which will not trigger a stop response from the drive are:

[Ignore] (nO): Communication interruption detection is disabled.

[Per STT] (Stt): Stop according to configuration of [Stop type] (Stt).

[fallback spd] (LFF): Change to fallback speed, maintained as long as the communication interruption persists and the run command has not been removed.

[Spd maint.] (rLS): The drive maintains the speed at the time the communication interruption occurred, as long as the interruption persists and the run command has not been removed.

The fallback speed can be configured in the [1.8 - FAULT MANAGEMENT] (FLt-) menu via the [Fallback speed] (LLF) parameter.

24

Loading...
+ 56 hidden pages