Schneider Electric TK-2001, TK-2012, TK-2201, TK-3001, TK-3201 Data Sheet

...
0 (0)

TK-2001, TK-2012, TK-2201,

TK-3001, TK-3201, TK-4001,

TK-4012, TK-4212 TK-4212-201

Pneumatic Bulb Thermostats

General Instructions

For proportional temperature control of pneumatic valves and actuators to maintain discharge temperature of reheat systems and sampling chamber or return air temperature of terminal units and as a proportional low limit thermostat.

GENERAL INFORMATION

Proportional control type of pneumatic instrument, using balanced lever system actuated by a liquid-filled thermal copper element with a 3’ (914 mm) capillary.

Maximum Safe Air Pressure: 30 psig (207 kPa). Maximum Sale Case Temperature: 140°F (60°C).

Mounting: Directly by means of top mounting holes or with a right angle mounting bracket included with thermostat.

Air Connections: Post with barb for 1/4" O.D. plastic tubing.

Air Consumption for Sizing Air Compressor: .016 scfm (8 ml/s) @ 15 psig (103 kPa), .024 scfm (11 ml/s) @ 20 psig (138 kPa).

Air Capacity for Sizing Air Mains: 36 scim (10 ml/s) @ 15 psig (103 kPa), 50 scim (14 ml/s) @ 20 psig (138 kPa). Dimensions: 4-5/8" (117 mm) high x 2-1/8" (54 mm) wide x 1-5/8" (41 mm) deep.

Options

None

ACCESSORIES

 

AT-208

Duct mounting kit

Tool-95

Pneumatic calibration tool kit

Printed in U.S.A. 12/09

© Copyright 2009 Schneider Electric All Rights Reserved.

F-12585-8

Schneider Electric TK-2001, TK-2012, TK-2201, TK-3001, TK-3201 Data Sheet

Table-1 Model Chart.

Part

Description and

Max. Safe

Bulb Style

Control Dial

 

Supply Air

BulbTemp.

Dimensions in

Throttling Range

Pressure psig

Number

Actiona

°F (°C)

inches (mm)

Range °F (°C)

 

(kPa)

 

 

 

 

 

 

TK-2001

 

 

Straight

 

 

 

 

 

 

7/32 x 14 (6 x 356)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TK-3001

Heating

 

Coiled

 

Adjustable 2-10°F

15 (103)

 

DAb

 

1 x 5 (25 x 127)

Dial Marked

 

 

 

 

 

(1-6°C)/10 psi (69 kPa)

 

 

 

 

 

Averaging

Cooler-Warmer

 

 

TK-4001

 

140 (60)

Factory Set

 

 

 

1/8 x 48 (3 x 1.2 m)

60-90

 

 

 

 

 

4°F (2°C)/

 

 

 

 

 

 

(15-32)

 

 

 

 

 

Straight

15 (103) RAa

TK-2201

Heating-Cooling

 

10 psi (69 kPa)

 

 

 

7/32 x 14 (6 x 356)

 

 

Cooling

 

 

20 (138) DA

 

 

 

 

 

 

 

 

 

20 (138) DAa

 

 

Coiled

 

 

TK-3201

15 (103) RA

 

 

 

 

1 x 5 (25 x 127)

 

 

Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Straight

 

 

 

 

TK-2012

Heating

 

3/16 x 11-1/4 (5 x

 

 

 

 

 

 

286)

 

 

15 (103)

 

 

DAb

 

 

 

 

TK-4012

 

Averaging

 

Adjustable 5-25°F

 

 

 

 

 

 

 

 

 

3/32 x 54 (2 x 1.4 m)

 

 

 

 

 

 

 

(3-14°C)/

 

 

 

 

 

 

Dial Marked

 

 

 

 

 

 

15 (103) RAa

 

Heating-Cooling

 

 

10 psi (69 kPa) Factory

 

230 (110)

Averaging

Cooler-Warmer

Cooling

 

TK-4212

20 (138) DA

Set

 

 

3/32 x 54 (2 x 1.4 m)

30-90 (-1 to 32)

20 (138) DA

a

 

15 (103) RA

 

 

10°F (6°C)/

 

 

 

 

 

 

10 psi (69 kPa)

Heating

 

 

Heating-Cooling

 

 

 

 

15 (103

 

TK-4212-201

Low Limitc

 

Averaging

 

 

Full Output

 

20 (138) DA Full

 

3/32 x 54 (2 x 1.4 m)

 

 

20 (138) DAa

 

Output 15 (103)

 

 

 

 

Heating

 

aDirect Acting (DA) - Increase output pressure on temp. rise. Reverse Acting (RA) - Decrease output pressure on temp. rise.

bField changeable to reverse acting.

cAT 20 psi (138 kPa) unit can bleed down a branch line from a controlling thermostat. At 15 psi (103 kPa) unit is inoperative, i.e. passes controlling thermostat signal.

DIMENSIONS

Figure-1 Mounting Dimensions.