Flowserve MX Electronic Actuator User Manual

4.7 (3)

 

USER INSTRUCTIONS

Limitorque MX Electronic Actuator

Installation

FCD LMENIM2306-06 - 10/13

Operation

 

Maintenance

 

 

Experience In Motion

 

 

 

Limitorque MX Electronic Actuator 

FCD LMENIM2306-06 – 10/13

 

Contents

 

1

Important Notes

7

 

2

Quick Start

9

 

 

2.1

Calibrate – Position Limits

9

 

 

 

2.1.1 Entering the Setup Mode

10

 

 

 

2.1.2 Electrical Operation Feature

10

 

 

 

2.1.3 Handwheel Operation Feature

11

 

 

2.2 DDC/Modbus Option

13

 

 

2.3

Check the Settings

13

 

3

Installation and Operation

14

 

 

3.1

Preparing the Stem Nut

14

 

 

 

3.1.1 Type “B” Bases: Torque-only Applications

14

 

 

 

3.1.2 Type “A” Bases: Thrust-only Applications

16

 

 

 

3.1.3 Type “BL” Drive: Splined Drive Application

20

 

 

3.2

Mechanical Installation Onto Valve or Gearbox

20

 

 

 

3.2.1 Mounting (Type “B” Bases): Torque-only

21

 

 

 

3.2.2 Removal (Type “B” Bases): Torque-only

21

 

 

 

3.2.3 Mounting (Type “A” Bases): Thrust-only

21

 

 

 

3.2.4 Removal (Type “A” Bases): Thrust-only

21

 

 

3.3

Electrical Connections

22

 

 

 

3.3.1 Removing Terminal Cover

22

 

 

 

3.3.2 Terminal Compartment Documents

22

 

 

 

3.3.3 Sealing Cable/Conduit Entries

22

 

 

 

3.3.4 Recommended Terminal Connections

22

 

 

 

3.3.5 Termination of Cables

24

 

 

 

3.3.6 Cable Connections

24

 

 

 

3.3.7 Network Installations

24

 

 

 

3.3.8 Foundation Fieldbus Installation

28

 

 

 

3.3.9 Network Wiring – Profibus DP/PA Installation

29

 

 

 

3.3.10 Network Wiring – DeviceNet

29

 

 

 

3.3.11 HART Installation

30

 

 

 

3.3.12 Replacing Terminal Cover

30

 

 

 

3.3.13 External Earth/Ground Connections

30

 

 

3.4

Terminal Block Shield Installation

30

 

 

3.5

Commissioning the Actuator

30

 

 

 

3.5.1 Default Configuration Set

31

 

 

 

3.5.2 View the Existing Settings

32

 

 

 

3.5.3 Entering the Setup Mode

32

 

 

 

3.5.4 Setting Position Limits

33

 

 

3.6

Operating the MX Actuator

36

 

 

 

3.6.1 Manual Operation

36

 

 

 

3.6.2 Electrical Operation

36

 

 

 

3.6.3 Local Control

36

 

 

 

3.6.4 Remote Control

37

 

 

 

3.6.5 Local Indication

37

 

4

Customizing the Actuator

38

 

 

4.1

Changing the Existing Settings

38

2

 

4.2

Password Entry

41

 

4.3 New Password

41

 

 

4.4

Valve Setup

42

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

4.4.1 Close Direction

42

4.4.2 Close Seating

42

4.4.3 Open Seating

42

4.5 Torque Switch Timer

43

4.5.1 Status

43

4.5.2 Torque Timer

43

4.6 Torque Setup

44

4.6.1 Close Torque Valve or Open Torque Valve

44

4.7 Position Setup

45

4.7.1 Set Position Limits for Electrical Operation

45

4.7.2 Set Position Limits for Manual Operation

45

4.8 Modutronic Option

47

4.8.1 Status

47

4.8.2 Proportional Band

47

4.8.3 Fail Position

47

4.8.4 Deadband

47

4.8.5 Polarity (20 mA)

47

4.8.6 Delay After Stop

48

4.8.7 4-20 mA Signal Range

48

4.8.8 Set High Reference

48

4.8.9 Set Low Reference

48

4.8.10 Modutronic LCD Display

49

4.9 DDC/Modbus Option

49

4.9.1 Status

49

4.9.2 Network Address

50

4.9.3 Protocol

50

4.9.4 Analog Scale

50

4.9.5 ESD Action

50

4.9.6 Proportional Band

51

4.9.7 Deadband

51

4.9.8 Offset

51

4.9.9 Move To

51

4.9.10 Comm Loss Delay

51

4.9.11 Comm Loss Action

51

4.10 FF Option

51

4.10.1 Status

52

4.10.2 Terminate Bus

52

4.10.3 Analog Scale

52

4.10.4 ESD Action

52

4.10.5 OPEN/CLOSE Mode

52

4.10.6 Proportional Band

52

4.10.7 Deadband

52

4.10.8 Comm Loss Delay

53

4.10.9 Comm Loss Action

53

4.11 PB Option

53

4.11.1 Status

54

4.11.2 PB DP Operation

54

4.11.3 Comm Loss Delay

55

4.11.4 Comm Loss Action

55

4.12 DN Option

56

4.12.1 Status

56

4.12.2 Baud Rate

56

3

flowserve.com

Limitorque MX Electronic Actuator 

FCD LMENIM2306-06 – 10/13

4.12.3 Network Address

56

4.12.4 Analog Scale

56

4.12.5 ESD Action

56

4.12.6 Proportional Band

57

4.12.7 Deadband

57

4.12.8 Comm Loss Delay

57

4.12.9 Comm Loss Action

57

4.13 HART Option

58

4.13.1 Status

58

4.13.2 Multi-drop

58

4.13.3 Input Action

59

4.13.4 Fail Position

59

4.13.5 Polling Address

59

4.13.6 Save Settings

59

4.13.7 Change Prop/Deadband

59

4.13.8 ESD Action

59

4.13.9 Change clock

60

4.14 Status and Alarm Contacts

60

4.14.1 Status and Alarm Contact Default Settings

60

4.14.2 Status Function

61

4.14.3 Contact

61

4.14.4 Valve Position

62

4.15 Two-speed Timer (Optional)

62

4.15.1 Status

62

4.15.2 Start Position

62

4.15.3 Stop Position

62

4.15.4 Pulse Time – ON

62

4.15.5 Pulse Time – OFF

63

4.16 Analog Output

63

4.16.1 APT Polarity Option

66

4.16.2 ATT Polarity Option

66

4.17 Remote Mode

67

4.17.1 Local Control

67

4.17.2 LED Customization

68

4.18 ESD (Emergency Shutdown) Overrides

68

4.18.1 ESD Override

68

4.18.2 Inhibit

69

4.18.3 Local Command

69

4.18.4 Stop

69

4.18.5 Jammed Valve*

69

4.18.6 Lost Phase*

69

4.18.7 Overtorque*

70

4.18.8 Motor Thermostat

70

4.18.9 Oil Over Temperature

70

4.18.10 Two-speed Timer

70

4.18.11 Network ESD

70

4.18.12 Torque Switch Timer

71

4.19 Inputs

71

4.19.1 Input Standard Remote Control

71

4.19.2 Status

72

4

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

 

 

4.19.3 Custom Input Mode #1 – Momentary ESD/PSESD (Optional)

72

 

 

4.19.4 Custom Input Mode #2 – Momentary ESD/CSE (Optional)

74

 

 

4.19.5 Custom Input Mode #3 – ESD Time Delay Relay

74

 

 

4.19.6 Custom Input Mode #4 – Multi-position mode (optional)

74

 

 

4.19.7 Limigard Controls

76

 

 

4.19.8 SIL Mode – Standard SIL (Optional)

76

 

 

4.19.9 SIL Mode – Enhanced SIL (Optional)

77

 

4.20 Monitor Relay

80

 

4.21 Diagnostic Reset

81

 

4.22 TAG Number

82

 

4.23 LCD Contrast

82

 

4.24 Torque Boost

82

 

4.25 Motor Thermostat

83

 

4.26 Change Valve Data

83

 

4.27 Change Port

84

5

Troubleshooting

85

 

5.1

View Diagnostics Routine

85

 

5.2

Troubleshooting Problems/Corrective Action

85

 

 

5.2.1 Actuator Fails to Operate

86

 

 

5.2.2 Jammed Valve Detected

86

 

 

5.2.3 Actuator Operates but Does Not Drive Valve

87

 

 

5.2.4 Valve Does Not Seat Correctly

87

 

 

5.2.5 Status Messages

87

 

5.3

View Diagnostics

90

 

5.4

View Hardware Status

90

 

5.5

View Motor Status

91

 

5.6 View Power Supply

91

 

5.7

View Identification

92

 

5.8

View Torque Profile

92

 

5.9

View Operation Log

93

 

5.10 View DNET Status?

94

6

Maintenance

96

 

6.1

Lubrication

96

 

 

6.1.1 Oil Capacities

96

 

 

6.1.2 Checking Oil Level

96

7

Regulatory Information

97

 

7.1

Special Conditions for Safe Use (denoted by X after the certificate number)

 

 

 

for Atex and IECEx Applications

99

 

7.2

Statement of Compliance With Applicable European Directives

99

5

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Figures

Figure 1.1 – MX-05 Actuator

7

Figure 2.1 – Electrical operation

11

Figure 2.2 – Handwheel operation

12

Figure 3.1 – B4 base

14

Figure 3.2 – B4E base

15

Figure 3.3 – Exploded view of B4/B4E base (MX-05 shown)

15

Figure 3.4 – B1 base

16

Figure 3.5 – Exploded view of B1 base

16

Figure 3.6 – A1 base

16

Figure 3.7 – Exploded view of A1/A1E base (MX-05/10/20/40 only)

17

Figure 3.8 – Exploded view of thrust base (MX-85 only)

19

Figure 3.9 – Exploded view of thrust base (MX-140/MX-150 only)

20

Figure 3.10 – Power terminal connector size limitations

23

Figure 3.11 – Terminal block rating; power terminals

23

Figure 3.12 – Control terminal connector size limitations

23

Figure 3.13 – View of terminal block

25

Figure 3.14 – Standard wiring diagram

25

Figure 3.15 – Removing outer plastic jacket

26

Figure 3.16 – Separating cable parts

26

Figure 3.17 – Stripping conductors and applying heat shrink tubing

27

Figure 3.18 – Ring tongue connectors

27

Figure 3.19 – Terminal block shield

30

Figure 3.20 – User network connection for loop topology/Typical for all two-wire network protocols

31

Figure 3.21– External earth/ground connection – housing

31

Figure 3.22 – View settings

33

Figure 3.23 – Position setup – electrical operation

35

Figure 3.24 – Declutch lever shows direction of engagement (MX-05 shown)

36

Figure 3.25 – Control panel

37

Figure 4.1 – Entering the setup mode

39

Figure 4.2 – Main menu selections

40

Figure 4.3 – Changing settings

40

Figure 4.4 – Password entry

41

Figure 4.5 – New password

42

Figure 4.6 – Torque Switch Timer

43

Figure 4.7 – MX Nameplate

44

Figure 4.8 – Torque setup

44

Figure 4.9 – Electrical operation

46

Figure 4.10 – Handwheel operation

46

Figure 4.11 – Modutronic option

48

Figure 4.12 – Modutronic signals

49

Figure 4.13 – DDC

50

Figure 4.14 – FF

53

Figure 4.15 – Profibus DP

54

Figure 4.16 – Profibus PA

55

Figure 4.17 – DN option

57

Figure 4.18 – HART

58

Figure 4.19 – Status and alarm contacts (Shown with optional boards needed)

61

6

 

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Figure 4.20 – Two-speed timers

63

 

Figure 4.21 – Change analog out

63

 

Figure 4.22 – Change analog out voltage – APT

64

 

Figure 4.23 – Change analog out current

64

 

Figure 4.24 – Change analog out voltage – ATT

65

 

Figure 4.25 – Change analog out current – ATT

65

 

Figure 4.26 – Remote mode

67

 

Figure 4.27 – Local control

67

 

Figure 4.28 – ESD overrides

69

 

Figure 4.29 – Custom input modes

73

 

Figure 4.30 – Inputs

75

 

Figure 4.31 – Inputs

76

 

Figure 4.32 – SIL control (Standard)

77

 

Figure 4.33 – SIL control (Enhanced)

78

 

Figure 4.34 – SIL control (Enhanced)

80

 

Figure 4.35 – Diagnostic reset

81

 

Figure 4.36 – TAG number

82

 

Figure 4.37 – LCD contrast

82

 

Figure 4.38 – Torque boost

83

 

Figure 4.39 – Motor thermostat

83

 

Figure 4.40 – Change valve data

84

 

Figure 4.41 – Change port and Bluetooth settings

84

 

Figure 5.1 – Initialize routine

89

 

Figure 5.2 – Diagnostic overview

90

 

Figure 5.3 – View hardware status

90

 

Figure 5.4 – View motor status

91

 

Figure 5.5 – View power supply

91

 

Figure 5.6 – View identification

92

 

Figure 5.7 – View torque profile

92

 

Figure 5.8 – View operation log

93

 

Figure 5.9 – View DNET status

94

 

Figure 7.1 - Typical IEC nameplate

101

 

Figure 7.2 - Typical ATEX nameplate

102

 

Tables

 

 

Table 3.1 - Hardware and torque for thrust base mounting

18

 

Table 3.2 – Terminal block rating; control terminals

24

 

Table 3.3 – Required ratings for external wires

24

 

Table 3.4 – Loop topology connections

27

 

Table 3.5 – Foundation fieldbus connections

28

 

Table 3.6 – Profibus cable specifications

29

 

Table 3.7 – DeviceNet cable specifications

29

 

Table 3.8 – Default configurations

32

 

Table 3.9 – LED indicators – default settings

37

 

Table 4.1 – Digital input terminals

79

 

Table 7.1 – EMC, EMI standards

100

 

7

flowserve.com

 

 

 

 

Limitorque MX Electronic Actuator 

FCD LMENIM2306-06 – 10/13

 

Figure 1.1 – MX-05 Actuator

 

 

 

 

 

 

 

 

 

Piece

Description

 

 

 

 

 

1

Handwheel

 

 

 

 

1

2

Declutch Lever (MX-05)

 

 

 

 

 

3

Oil Fill

 

 

 

 

 

4

Controls Cover

 

 

3

 

2

5

LCD

 

 

 

 

 

 

 

12

 

 

 

6

Control Knob

 

 

 

 

 

 

 

11

 

 

 

7

Ground Lug

 

10

 

 

 

8

Thrust/Torque Base

 

 

4

 

 

9

Conduit Entry

 

 

 

5

 

10

Terminal Compartment

 

 

 

2

11

Motor

 

 

 

 

 

 

 

 

 

9

8

7

 

6

12

Nameplate

 

 

 

 

 

1 Important Notes

Please read this manual in its entirety before attempting to install or operate your MX actuator. A full understanding of the installation and operation options will assist you in installing the actuator in the most effective manner. Limitorque has designed the MX actuator for long life even in the harshest environments. Flexible control and protection options are provided to ensure the actuator meets your requirements.

All actuator enclosures are sealed by O-rings, and cable entries are supplied with threaded plugs to protect the terminal compartment until the unit is wired. If the actuator cannot be installed immediately, it is recommended that it be stored in a clean, dry place, preferably in an area that is not subject to large fluctuations in temperature.

Disconnect all incoming power before opening any cover on the actuator. The user/operator must ensure that safe working practices are employed at all times and are in accordance with local or national standards that are enforced at the particular site.

To install and commission the actuator, only the terminal compartment cover needs to be removed. See Figure 1.1, Item 10. Settings for commissioning the actuator are done externally; therefore, no other covers need to be

8removed. The actuator was assembled in ideal dry conditions and the total sealing of the enclosure protects all electrical components against deterioration.

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

NOTE: Removal of any cover, other than the terminal compartment cover, will invalidate the unit warranty. Exposure of actuator components to an environment that results in deterioration of internal components will also invalidate the unit’s warranty.

During final field installation, ensure that all cable entries are correctly sealed in accordance with National Standards or Regulatory Authorities. All temporary transit plugs must be removed and any unused cable entries closed in an approved manner. See Section 3.3.3, Sealing Cable/Conduit Entries.

9

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

2 Quick Start

Quick Start provides step-by-step instructions for commissioning each MX actuator. This information is also available in Bulletin LMENIM2310, Quick Start-Up Instructions. These instructions are for the following:

Position limits calibration – can be performed one of two ways:

1.Electrical operation: See Section 2.1.2, Electrical Operation Feature.

2.Handwheel operation: See Section 2.1.3, Handwheel Operation Feature.

DDC operation: See Section 2.2, DDC Option.

FF operation: See Section 4.10, FF Option.

PB operation: See Section 4.11, PB Option.

DeviceNet operation: See Section 4.12. DN Option.

When these Quick Start instructions are complete, the position limits will be set and the actuator will be ready for normal operation.

NOTE: The actuator has been configured with all customer-specified parameters and no further calibration should be necessary. If full valve data was not provided when ordering, or if changes are needed for parameters, see Sections 3.5 and 6, Commissioning the Actuator and Customizing the Actuator.

2.1 Calibrate – Position Limits

1.Install the MX actuator on the valve.

2.Refer to the nameplate for the correct main power supply voltage. Switch on the main power to the unit.

3.Turn the red knob to the STOP position. The “SET CLOSE POSITION LIMIT” message will be displayed. When the red knob is in “LOCAL” or “REMOTE,” the liquid crystal display (LCD) screen will read “SET POSITION LIMITS.”

4.Calibrate end position limits one of two ways:

Electrically, using the control panel. See Section 2.1.2, Electrical Operation Feature.

Manually, using the handwheel. See Section 2.1.3, Handwheel Operation Feature.

Once the position limits have been set, the screen message will indicate the valve position as a percentage of the valve opening.

While setting limit switches, place the red selector knob in the “LOCAL” position to permit the actuator to run open or

closed in push-to-run mode (inching) only.

10

a CAUTION: Extreme care must be taken as the valve approaches its end position.

The unit will not function with the red selector knob in the “REMOTE” position until both limit switches are set.

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

The existing configuration of the actuator/valve parameters may be viewed by entering the “SETUP” mode.

2.1.1 Entering the Setup Mode

1. Place the red selector knob in the “STOP” position.

2. Within 10 seconds, place the black control knob in the “YES” position, then the “NO” position, then again in the “YES” position (in quick succession—approximately one-two seconds).

3. The message “SETUP?” will appear in the LCD display for 10 seconds. If no setup action is taken within 10 seconds, the unit will reset.

4. Use the black control knob to answer “YES” or “NO” to the questions appearing in the display.

2.1.2 Electrical Operation Feature

This feature allows for quick and simple calibration. To set the position limits electrically, enter the “CHANGE SETTINGS” mode via the “SETUP” mode.

1.Enter the “SETUP” mode as detailed in Section 2.1.1, Entering the Setup Mode.

2.When screen prompt reads “CHANGE SETTINGS,” select “YES.”

3.The screen will display the “CHANGE SETTINGS” mode menu items. Select “NO” until screen displays “CHANGE POSITION SETUP.” User may select to set close limit first or open limit first.

4.Select “YES.” “CLOSE” or “OPEN VALVE - OK?” is displayed.

5.Place the red selector knob in the “LOCAL” position. Move the black knob in the intended direction. The LCD screens are shown in Figure 2.1.

6.When valve has reached desired position, return the red selector switch to “STOP” and complete calibration.

The position settings are now complete. The actuator will now function as ordered, and may be run electrically to inspect for correct operation.

aCAUTION: On some valves, position limits could be set adjacent to each other, so be careful that the Close and Open limits are set sufficiently apart to permit operation. If the limits are set adjacent of each other, an error message will be displayed: “KEEP OPEN(CLOSE) LIMIT?”

NO FURTHER MOVEMENT IS PERMITTED UNTIL THE ERROR IS CORRECTED.

Should the User elect to proceed with the setting, an error will be displayed on the screen after re-booting stating “IDENTICAL LIMITS”. THE ACTUATOR WILL NOT MOVE UNTIL THE ERROR IS CORRECTED.

11

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Figure 2.1 – Electrical operation

STOP

YES

Switch to

YES

YES2

YES

STOP

 

 

SET CLOSE

 

CLOSE VALVE

 

CLOSE VALVE

CLOSE VALVE

SAVE CLOSE

 

IDENTICALLIMITS

POSITION LIMIT?

 

OK ?

LOCAL

RETURN TO STOP

OK ?

LIMIT OK?

 

KEEPCLOSELIMIT?

 

 

 

 

 

 

 

 

YES1

 

 

 

 

NO ” operates

NO

 

 

 

 

NO

 

NO

close direction

NO

NO

 

NO

 

 

 

 

YES

 

Switch to

 

STOP

YES

 

YES2

YES

 

 

 

 

 

 

 

 

 

SET OPEN

 

OPEN VALVE

 

OPEN VALVE

OPEN VALVE

SAVE OPEN

 

IDENTICALLIMITS

POSITION LIMIT?

 

OK ?

LOCAL

RETURN TO STOP

OK ?

LIMIT OK?

 

KEEPOPENLIMIT?

 

 

 

 

 

 

 

 

YES1

 

 

 

 

YES” operates

YES

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

NO

open direction

 

NO

NO

 

NO

 

YES

 

YES

 

 

YES

 

 

 

SET POSITION

 

POSITION

 

 

SETUP?

Enter “SETUP ” mode

NOTE 1: If open and close limits

PRECISION?

 

XXX% OPEN?

 

 

 

 

are not identical

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE 2: If open and close limits

NO

 

 

 

 

 

 

 

 

are identical

 

NO

 

 

NO

 

 

 

 

 

 

 

YES

 

 

YES

 

 

 

 

 

 

 

 

100% OPEN

 

 

 

 

NO

POSITION

 

 

EXIT

 

 

 

 

 

 

 

SETUP?

STATUS OK?

 

 

 

 

 

XXX.X% OPEN?

 

 

 

 

 

 

 

NO

2.1.3 Handwheel Operation Feature

To set the position limits manually, enter the “CHANGE SETTINGS” mode via the “SETUP” mode.

1.Enter the “SETUP” mode as detailed in Section 2.1.1, Entering the Setup Mode.

2.When LCD reads “CHANGE SETTINGS?”, select “YES.”

3.The LCD will display the “CHANGE SETTINGS” mode menu items. Select “NO” until screen displays “CHANGE POSITION SETUP?”

4.Select “YES.” See Figure 2.2. Manually set position limits:

a.Close position limit

1.“SET CLOSE POSITION LIMIT?” is displayed.

2.Select “YES.” “CLOSE VALVE - OK?” is displayed.

3.Depress the declutch lever, and at the same time slowly rotate the handwheel until the clutch is fully engaged. Release the lever; the clutch will be retained in the handwheel mode by spring-loaded latches.

4.Ensure the valve is fully closed, then move the valve in the open direction for one handwheel turn to allow for coasting of the motor.

5.When the valve is in the desired position, select “YES” again. The LCD will read “SAVE CLOSE LIMIT OK?”

6.Select “YES” if the valve’s close limit position is correct. The close position limit is set.

b.Open position limit

12

1. “SET OPEN POSITION LIMIT?” is displayed.

2. Select “YES.” “OPEN VALVE - OK?” is displayed.

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

3.Depress the declutch lever, and at the same time slowly rotate the handwheel until the clutch is fully engaged. Release the lever; the clutch will be retained in the handwheel mode by spring-loaded latches.

4.Ensure the valve is fully open, then move the valve in the close direction for one handwheel turn to allow for coasting of the motor.

5.When the valve is in the desired position, select “YES” again. The LCD will read “SAVE OPEN LIMIT OK?”

6.Select “YES” if the valve’s open position limit is correct. The open position limit is set.

7.Move the valve in the close direction. The open lamp should extinguish within one turn of the handwheel.

8.Move the valve back in the open direction and check that the open lamp illuminates just before the full open position is reached (approximately 1/2 to 1 turn).

9.If the calibration requires adjustment, select “NO” at the “SET CLOSE POSITION LIMIT?” prompt and repeat the “SET OPEN POSITION LIMIT?” routine.

10.Select “NO” to exit “POSITION SETUP?” or “YES” to return to “SET CLOSE POSITION LIMIT?”

aCAUTION: On some valves, position limits could be set adjacent to each other, so be careful that the Close and Open limits are set sufficiently apart to permit operation. If the limits are set adjacent to each other, an error message will be displayed: “KEEP OPEN(CLOSE) LIMIT?”

NO FURTHER MOVEMENT IS PERMITTED UNTIL THE ERROR IS CORRECTED.

Should the User elect to proceed with the setting, an error will be displayed on the screen after re-booting stating “IDENTICAL LIMITS”. THE ACTUATOR WILL NOT MOVE UNTIL THE ERROR IS CORRECTED.

Figure 2.2 – Handwheel operation

STOP

YES

YES

YES

 

SET CLOSE

CLOSE VALVE

SAVE CLOS E

 

 

POSITION LIMIT?

OK ?

 

LIMIT OK?

 

 

 

 

Declutch actuator;

 

 

 

 

NO

NO

Rotate handwheel to

NO

 

 

CLOSE” position limit

 

 

 

 

 

 

YES

 

YES

 

 

YES

 

SET OPEN

OPEN VALVE

 

SAVE OPEN

 

 

POSITION LIMIT?

OK ?

 

LIMIT OK?

 

 

NO

 

Rotate handwheel to

 

 

 

NO OPEN” position limit

NO

 

 

YES

 

 

 

 

YES

 

 

 

 

 

 

 

SET POSITION

POSITION

 

 

SETUP?

Enter “SETUP” mode

 

PRECISION?

XXX% OPEN

 

 

 

NO

NO

 

 

NO

 

YES

 

 

 

 

 

EXIT

100%

 

 

 

 

 

SETUP?

STATUS OK

NO

13

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

2.2 DDC/Modbus Option

The following instructions assume that all DDC option parameters are set with the exception of the address.

1.After setting position limits, remain in the “SETUP” mode. If not in the “SETUP” mode, enter the “SETUP” mode as detailed in Section 2.1.1, Entering the Setup Mode.

2.When LCD reads “CHANGE SETTINGS?”, select “YES.”

3.The LCD will display the “CHANGE SETTINGS” mode menu items. Select “NO” until screen displays “CHANGE DDC?” Select “YES.” LCD will display DDC menu items.

4.Select “YES” for each menu item until “DDC ADDRESS OK?” appears. Select “NO.”

5.Enter an address from one to 250 by toggling “NO” until the correct address is displayed. User may select to hold the knob in the “NO” direction and the number will automatically increment by one until the preferred address is reached.

aCAUTION: The network address must be entered in accordance with the user address assignment sheet. This assignment sheet should correspond to the contract specifications. The same address must not be used anywhere else in the same network.

The DDC address does not have to be set to exit the setup.

2.3 Check the Settings

1.Operate the valve to the fully “CLOSE” position. Verify that the “CLOSE” (default GREEN) LED illuminates just as the travel limit is reached, and the valve position is displayed as “0% OPEN.”

2.Operate the valve to the fully “OPEN” position. Verify that the “OPEN” (default RED) LED illuminates just as the travel limit is reached, and the valve position is displayed as “100% OPEN.”

14

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

3 Installation and Operation

3.1 Preparing the Stem Nut

The MX has two (2) basic base designs:

Torque-only base, designated by a “B” prefix

Thrust-only base, designated by an “A” prefix

3.1.1 Type “B” Bases: Torque-only Applications

Standard B4/B4E Base

The standard MX actuator base is the B4 torque-only. It includes a mounting plate and steel torque nut, which may be machined to fit a valve or gearbox. A B4E torque nut can be provided and may be installed to allow for extended stem acceptance.

NOTE: Some MX actuators are supplied with single piece drive sleeves that have been bored and keyed. These are typically mounted directly to gearboxes. The MX actuator maybe mounted in any position as long as the handwheel is accessible.

Figure 3.1 – B4 base

15

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Figure 3.2 – B4E base

Figure 3.3 – Exploded view of B4/B4E base (MX-05 shown)

Baseplate

Drive sleeve

MX base

Torque nut

Retaining ring

Disassembly

1.Remove the retaining ring (B4 base) or spiral-wound ring (B4E base) that retains the torque nut in the drive sleeve.

2.Remove the torque nut. If the torque nut is difficult to remove, insert a suitable device into the drive sleeve through bore and gently tap it loose from the handwheel end.

3.Machine the torque nut to suit the valve stem or gearbox input shaft (see LMENSS2326, MX Performance and Dimensions for maximum stem capacity). Ensure sufficient clearance for a smooth, sliding fit.

Reassembly

1.Clean the torque nut thoroughly and lightly grease.

2.Replace the torque nut in the drive sleeve. Ensure the torque nut meshes with the drive lugs.

3.Refit the retaining ring (B4 base) or spiral-wound ring (B4E base).

Optional B1 Base (not available for MX-85, MX-140 and MX-150)

16An optional torque base assembly may be added to allow for a greater stem acceptance. This base is supplied with a fixed bore and key as defined by ISO 5210.

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Disassembly

No disassembly is required since the torque nut has been machined to an international standard. Clean the bore and lightly grease.

Figure 3.4 – B1 base

NOTE: Fill base with a Lithium based EP0 grease.

Figure 3.5 – Exploded view of B1 base

Pipe plug

Socket head cap screw (M8 x 20)

Torque nut (B1)

Housing,

 

torque/thrust

Bearing

Pipe plug

Retainer, bearing

Pilot, torque/thrust

Thrust nut assembly

Washer (M4)

Socket head

cap screw (M4 x 8)

Socket head set screw

MX-05 B1

MX-40 B1

3.1.2 Type “A” Bases: Thrust-only Applications

Standard A1/A1E Base

The standard MX actuator thrust base is the A1, and may be bolted directly to the actuator. The thrust base contains a bronze alloy thrust nut that may be machined to suit the valve stem.

An A1E (extended) thrust nut can be provided and may be installed to reach shorter stems.

Figure 3.6 – A1 base

Disassembly – Units MX-05/10/20/40

Refer to Figure 3.7.

Disassembly of the main housing from the base may be recommended to allow the base to remain on the valve if the

17

actuator must be removed for service.

 

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Pilot removal

MX-10/20: Remove the screw and washer holding the valve pilot to the thrust base and remove pilot.

MX-40: Turn counterclockwise (CCW) and remove.

Thrust bearing and nut removal

1.Remove the first set of thrust washers and bearing.

2.Remove stem nut.

NOTE: The thrust washers, bearing, and thrust nut may be removed at the same time. The second set of thrust washers and bearing does not have to be removed.

3.Machine the thrust nut to suit the valve stem. Ensure sufficient clearance to avoid unnecessary wear and heating during operation.

Reassembly – Units MX-05/10/20/40

Refer to Figure 3.7.

1.Clean the thrust nut, washers, and bearing(s) thoroughly.

2.Slide second set of thrust washers and bearing in place if removed.

NOTE: Order of assembling thrust washers and bearing must be as follows: washer, thrust bearing, washer.

Pilot installation

MX-05/10/20: Slide pilot into thrust base assembly and secure with washer and screw. Tighten fully.

MX-40: Place pilot into thrust base and turn clockwise (CW) until pilot is tight.

NOTE: Fill base with Nebula EP 0, Conoco Conolith EP 00, Mobil SHC 632, Dynalife-L-EP0, Triton ELL, or Lithium based EP0 grease.

Disassembly – Units MX-85

Refer to Figure 3.8.

Disassembly of the main housing from the base may be recommended to allow the base to remain on the valve if the actuator must be removed for service.

Thrust base mounting plate removal

Remove the six socket head cap screws holding the valve mounting plate to the thrust base housing and remove mounting plate.

Figure 3.7 – Exploded view of A1/A1E base (MX-05/10/20/40 only)

Housing

Quad ring

Socket head cap

 

Thrust washer

 

Thrust Nut

 

Thrust washer

Pipe plug

O-ring

Thrust pilot

Needle bearing

18

Quad ring

Washer

Socket head cap screw Thrust base standard nut

Thrust base extended nut

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Thrust bearing and nut removal

1.Remove the first set of thrust washers and bearing.

2.Remove stem nut.

NOTE: The thrust washers, bearing, and stem nut may be removed at the same time. The second set of thrust washers and bearing does not have to be removed.

3.Machine the stem nut to suit the valve stem. Ensure sufficient clearance to avoid unnecessary wear and heating during operation.

Reassembly – Units MX-85

Refer to Figure 3.8.

1.Clean the stem nut, washers, and bearing(s) thoroughly.

2.Slide second set of thrust washers and bearing in place if removed.

3.Install stem nut. Lubricate thoroughly.

4.Install first set of thrust washers and bearing.

NOTE: Order of assembling thrust washers and bearing must be as follows: washer, thrust bearing, washer.

NOTE: Fill base with Nebula EP 0, Conoco Conolith EP 00, Dynalife-L-EP0, Mobil SHC 632, Triton ELL, or Lithium based EP0 grease.

Thrust baseplate installation

Mount baseplate to thrust base housing and install the six socket head cap screws to the proper torque per Table 3.1.

Table 3.1– Hardware and torque for thrust base mounting

Screw Size

 

Torque

ft-lb

 

N m

 

 

M8 or 516 in. (8 mm)

 

 

16-19

12-14

 

M10 or 38 in. (9 mm)

25-30

 

33-40

M12 or 1/2 in. (13 mm)

40-50

 

53-67

 

 

 

 

M16 or 58 in. (16 mm)

90-100

 

122-135

M20 or 3/4 in. (19 mm)

180-200

 

244-271

 

 

 

 

NOTE: Screw mounting torque for mounting thrust base to main housing or thrust baseplate to thrust base housing.

19

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Figure 3.8 – Exploded view of thrust base (MX-85 only)

Pipe plug Housing

 

Socket head

 

cap screws

 

Thrust bearing

Thrust nut

 

Baseplate Thrust bearing

 

Socket head

 

cap screws

Thrust

 

Quad ring washer

Quad ring

Thrust

O-ring washer

A

A

Section A-A

Section A-A

View shown

View shown

with standard nut

with extended nut

Disassembly – Units MX-140/MX-150

Refer to Figure 3.9.

Disassembly of the main housing from the base may be recommended to allow the base to remain on the valve if the actuator must be removed for service.

Pilot removal

Remove the two screws and washers holding the valve pilot to the thrust base and remove pilot.

Thrust bearing and nut removal

1.Remove the first set of thrust washers and bearing.

2.Remove stem nut.

NOTE: The thrust washers, bearing, and stem nut may be removed at the same time. The second set of thrust washers and bearing does not have to be removed.

3.Machine the stem nut to suit the valve stem. Ensure sufficient clearance to avoid unnecessary wear and heating during operation.

Reassembly – Units MX-140

Refer to Figure 3.9.

1.Clean the stem nut, washers, and bearing(s) thoroughly.

2.Remove pipe plug.

3.Slide second set of thrust washers and bearing in place if removed.

4.Install stem nut. Lubricate thoroughly.

5.Install first set of thrust washers and bearing.

6.Install pipe plug.

NOTE: Order of assembling thrust washers and bearing must be as follows: washer, thrust bearing, washer.

20NOTE: Fill base with Nebula EP 0, Conoco Conolith EP 00, Dynalife-L-EP0, Mobil SHC 632, Triton ELL, or Lithium based EP0 grease.

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Pilot installation

Slide pilot into thrust base assembly and secure with the two washers and screws. Tighten fully.

3.1.3 Type “BL” Drive: Splined Drive Application

Steel alloy splined nuts are provided to a standard involute spline category for rising and rotating stem valves per customer requirements. Disassembly and reassembly is the same as the B4 base and the torque nut. See Section 3.1.1, Type “B” Bases: Torque-only Applications.

Figure 3.9 – Exploded view of thrust base (MX-140/MX-150 only)

 

 

Housing

Pipe plug

 

 

 

 

 

Thrust

 

 

 

bearing

 

 

 

Thrust nut

 

 

Thrust

 

Socket

 

 

head cap

 

bearing

Thrust

screws

 

O-ring

 

Thrust

washers

Pipe plug

 

Quad ring

 

pilot

 

 

 

 

 

 

 

Quad ring

 

 

 

Thrust

 

 

 

washers

A

Socket head Washers

B

 

cap screws

 

 

 

 

Section A-A

Section B-B

B

View shown with

View shown with

 

 

standard nut

extended nut

A

3.2 Mechanical Installation Onto Valve or Gearbox

NOTE: Refer to MX Maintenance and Spare Parts bulletin (LMENIM2314) for more detailed instructions.

Before installing the actuator onto a valve or gearbox, check the following to ease installation:

Verify that mounting flange is suited dimensionally to mate with the actuator base. Ensure that it is perpendicular to the valve stem or gearbox input shaft.

Ensure the stem nut mates with the valve stem or input shaft. For screwed nuts, it is advisable to run the stem nut down the entire length of the stem to check for tightness. Keyed or splined shafts should exhibit a smooth, sliding fit with the key installed.

Ensure there is adequate engagement of the stem nut with the valve stem or input shaft when mounted. Generally, the minimum length of engagement is 1.5 times the diameter of the stem.

Verify that mounting studs or bolts are the correct length to suit the thickness of the mounting plate.

Verify hardware specifications for English style:

Socket head cap screw per ASTM A 574 and ANSI 18.3.

Hex head cap screw per SAE J429 Grade 5.

Verify hardware specifications for metric style: hex and socket head cap screws per Property Class 12.9.

Clean and lubricate the valve stem or input shaft.

Ensure adequate lifting facilities and slings are available at the installation site.

NOTE: Do not use the handwheel to lift the actuator.

21

 

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

3.2.1 Mounting (Type “B” Bases): Torque-only

Refer to Figures 3.1 - 3.5.

1.Ensure torque nut is secured inside actuator drive sleeve with retaining ring.

2.Lower actuator onto the valve or gearbox stem. Align the stem nut key and keyway with valve or gearbox stem key seat.

3.Verify that the actuator and valve mounting adapter flanges mate correctly.

4.Secure the actuator to the valve mounting adapter with mounting bolts.

3.2.2 Removal (Type “B” Bases): Torque-only

Refer to Figures 3.1 – 3.5.

1.Remove the bolts that secure the actuator to the valve mounting adapter. If type B1 base is used in addition to the standard type B4 baseplate, you may leave the B1 base attached to the actuator and remove as a unit.

2.Lift the actuator from the actuator mounting adapter.

3.2.3 Mounting (Type “A” Bases): Thrust-only

Refer to Figures 3.6 – 3.9.

1.The following are two options for mounting the type A base actuator:

a.If the type A thrust base was removed from the valve mounting adapter, replace the thrust base onto the valve mounting adapter. Ensure the thrust base stem nut has the lugs positioned upward to engage with the drive sleeve slots when the actuator is reinstalled. Rotate the bronze nut while holding the base steady.

or

b. If the thrust base is installed on the valve mounting adapter, proceed to step two.

2.Lower the actuator along the threaded valve stem and onto the valve mounting plate. Ensure the thrust base stem nut lugs properly engage and align with the drive sleeve slots.

3.Install the bolts to secure the actuator to the thrust base assembly.

3.2.4 Removal (Type “A” Bases): Thrust-only

1.Remove the bolts that secure the actuator to the thrust base assembly.

2.Remove the type A thrust base by removing the bolts that secure the actuator to the valve mounting adapter. or

Leave the type A thrust base mounted to the valve mounting adapter until ready to remount the actuator. The thrust base will maintain valve position provided that the valve stem threads are locking.

3.Lift the complete actuator from the thrust base.

22

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

3.3 Electrical Connections

Verify that the supply voltage details on the nameplate are correct for this installation. Setup is non-intrusive; therefore, remove only the terminal cover to make electrical connections and to commission the actuator.

cWARNING: The removal of any other covers without Limitorque’s approval will void the warranty. Limitorque will not accept responsibility for any damage or deterioration that may occur as a result of cover removal.

3.3.1 Removing Terminal Cover

Remove the terminal cover as follows:

1.Remove the four cover screws using a 6 mm hexagonal wrench.

2.Remove the cover. XP units have long-spigoted covers and two tapped holes 180° apart. If the XP cover is difficult to remove, fit two of the cover screws into the tapped holes in the cover flange and jack out the cover. Take care to turn the screws by equal increments. Do not lever the cover off with a screwdriver, or similar object, since this may damage the flamepath on an explosionproof unit or the O-ring seal and seating face.

3.3.2 Terminal Compartment Documents

The OEM and user installation kits, wiring diagram, and test report are contained in the terminal compartment or with the actuator. Do not place them in the terminal compartment when the electrical connections have been completed.

NOTE: This instruction does not apply to valve manufacturers or similar installers of the actuator onto a valve prior to shipping to site. It is important that these items are available at the final destination site.

3.3.3 Sealing Cable/Conduit Entries

The sealing of cables and conduit entries should be done in accordance with National Standards or the Regulatory Authorities that have certified the actuators. This is particularly true for units that are certified for use in hazardous areas where the method of sealing must be to an approved standard and cable glands, reducers, plugs, and adapters must be approved and separately certified. All conduit entries should be sealed against the climatic conditions prevailing on-site, especially if temporary submersion is possible. All unused conduit entries should be sealed with threaded metal plugs. Plastic plugs are installed by Limitorque for shipping only and must not be used as permanent seals.

3.3.4 Recommended Terminal Connections

Power Terminals

Ring tongue connectors used on the power terminals should comply with the dimensions shown in Figure 3.10. For Additional information, consult terminal manufacturer.

Figure 3.11 details the allowable voltage and current parameters for the terminal block power terminals. Preload the M5 screws to 1.6-3.2 N m (1.2-2.33 ft-lb).

Control Terminals

Ring tongue connectors used on the control terminals should comply with the dimensions shown in Figure 3.12. For additional information, consult terminal manufacturer. Preload the M3 screws to 0.33-0.66 N m (0.25-0.50 ft-lb).

NOTE: Alternative manufacturers may be substituted only if dimensions are in accordance with Figure 3.12.

NOTE: The use of spade terminals is not recommended for secure electrical connections.

23

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Figure 3.10 – Power terminal connector size limitations

MAX. THICKNESS = 1.6 mm

 

NOT TO

 

 

EXCEED 3.5

 

NOT TO

NOT TO

NOT TO

EXCEED 9.8

EXCEED 6.5

EXCEED 15

 

 

NOT TO

 

 

EXCEED 9.6

 

TO BE SIZED

TO BE SIZED

 

FOR M5 SCREW

 

FOR M5 SCREW

NOT TO

 

 

 

EXCEED 15

 

 

SPADE AND SNAP

FLANGED

RING TERMINAL

TERMINALS

SPADE TERMINAL

 

Figure 3.11 – Terminal block rating; power terminals

Description

L1

L2

L3

 

30 AMP

20 AMP

15 AMP

 

 

 

 

 

STD Rating

8 Awg/10 mm2

10 Awg/6 mm2

14 Awg/2.5 mm2

 

600 VAC

RMS

150 VDC

 

 

 

 

Increased

27 AMP

18 AMP

13.5 AMP

 

 

 

8 Awg/10 mm2

10 Awg/6 mm2

14 Awg/2.5 mm2

Safety Rating

500 VAC

RMS

150 VDC

 

 

 

 

 

Note: Ratings will be the same for L1, L2, or L3, e.g., if 10 Awg is selected, then L1, L2 and L3 will have the same limitations.

Figure 3.12 – Control terminal connector size limitations

NOT TO

MAX. THICKNESS = 1.0 mm

 

 

EXCEED 7.6

 

NOT TO

 

NOT TO

NOT TO

EXCEED 5

EXCEED 4.0

NOT TO

EXCEED 5

 

EXCEED 8.2

 

 

TO BE SIZED

 

TO BE SIZED

FOR M3 SCREW

 

 

 

FOR M3 SCREW

 

SPADE AND SNAP

 

RING TERMINAL

TERMINAL

 

3X M5 SCREW

54X M3 SCREW

3X M5 SPRING

WASHER 54X M3 SPRING WASHER

FIGURE 3.13

THE USE OF THE SPRING WASHERS ARE REQUIRED

ON INCREASED SAFETY APPLICATIONS.

NOTE: All dimensions are in mm.

NOTE: Limitorque recommends the use of the following connector for optimum results: Thomas and Betts #RZ22-6.

24NOTE: Alternative manufacturers may be substituted only if the dimensions are in accordance with Figure 3.12. Table 3.2 lists the maximum allowable voltage and current parameters for the terminal block control terminals.

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Table 3.2 – Terminal block rating; control terminals

 

Low Voltage Row

STD Rating

Increased Safety Rating

 

1 points 1-16, 50 Volt

0.5 AMP AC RMS

0.45 AMP AC RMS

 

 

 

 

 

 

2 points 17-35, 125 Volt

0.5 AMP AC RMS

0.45 AMP AC RMS

 

 

 

 

 

3 and 4 points 36-54, 250 Volt

5 AMP AC RMS

4.5 AMP AC RMS

 

 

 

 

3.3.5 Termination of Cables

All terminations should be made with insulated ring terminals using the appropriate crimping tool. See Figures 3.10 and 3.11 for power terminal connection recommendations. See Figure 3.12 and Table 3.2 and 3.3 for control terminal connection recommendations.

3.3.6 Cable Connections

See Figure 3.14 for connection information.

1.Connect the main power supply cables, including the earth/ground wire using the M5 screws provided.

2.Attach the earth/ground wire to the separate screw on the inside of the terminal compartment.

3.Use the M3 screws installed in the terminal block to connect the control cables in accordance with the wiring diagram and the project specification.

4.Ensure that all connections are tight, including any spare termination screws that have not been used.

NOTE: A “Customer Connection(s) Diagram” sticker is attached to the interior of the terminal compartment cover. This may be removed and user termination numbers inscribed adjacent to Limitorque’s terminal block numbers for field connection reference. The diagram may also be used to assist in locating the terminal block positions. Service and factory contacts are contained on the sticker.

Certification is based on the use of appropriately rated wire for the application. Installation shall be in accordance with the current issue of the applicable national and or local electric code or regulations.

Table 3.3 – Required ratings for external wires

Up to

 

Use wire rated at least

40°C Ambient

 

75°C

 

 

 

 

55°C Ambient

 

90°C

 

 

 

60°C and 65°C Ambient1

 

105°C

Note 1: Refer to unit nameplate.

3.3.7 Network Installations

The Limitorque MX offers a number of network options: DDC-Modbus, Foundation Fieldbus H1, Profibus DP_V1, Profibus PA, and DeviceNet.

Ensure that the network cable type is Belden 3074F, Belden 3105, Belden 9841 or another cable that is within 5% of the following specifications.

Nominal impedance: 120 ohms @ 1 MHz

 

Line to shield capacitance: 23.0 pF/ft (75.5 pF/m)

 

Line to line capacitance: 12.8 pF/ft (42.0 pF/m)

25

Using other cables may result in decrease of internodal distance and/or an increase in communication error.

flowserve.com

Flowserve MX Electronic Actuator User Manual

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Particular care should be taken when terminating twisted-pair shielded cables in a control network. Avoid nicks, cuts, or abrasions in the insulation of data communication cables, since this may result in inadvertent ground connection. Also, excess cable should be cut, not coiled or looped, to prevent noise induction into the network.

Limitorque strongly recommends remote communication wiring be routed separately from mains line power wiring. Specifically, instrumentation wiring, including communication, analog and discrete signal wiring, should be routed in conduit that is separated from power lines. If the recommendation is not followed, the intergrity of instrumentation signals may be comprimised. If the signal is comprimised, the MX will enter a“safe-state” whereby all motion is prohibited until communication is sucessfully re-established.

Figure 3.13 – View of terminal block

Figure 3.14 – Standard wiring diagram

NOTE: Most current wiring diagram is shipped within the terminal compartment of the MX.

 

 

 

PE

 

 

 

 

L1

Three-phase supply

 

 

 

L2

 

 

 

L3

 

Motor

Reversing

 

Close

27

 

contactor

 

Stop

26

 

 

 

Open

25

 

 

*

Dig Com #1-Ve

28

 

FS1 FS2

Close inhibit/

35

 

 

interlock Input 1

 

 

 

 

Open inhibit/

34

 

 

 

interlock Input 2

 

 

 

 

 

 

 

Dig Com #2-Ve

29

 

 

 

E.S.D. Input 0

30

 

 

 

Dig Com #3-Ve

32

 

 

FS3

 

 

 

 

 

0 VAC

23

LimiGard

 

Control

110 VAC

24

 

supply

24 VDC +Ve

22

 

 

 

 

 

0 VDC

21

 

 

Aux.

24 VDC +Ve

6

 

Power

input

 

0 VDC

7

 

board

(Optional)

*Jumpers may be added to connect digital commons - pt. 28 & 29, 31& 32 Note: 110 VAC control supply from actuator is optional.

Main processor board

Position

Torque

sensor

sensor

TE

OP

REMO

(YESEN)

STOP

)

LOCAL

CLOSE

 

(NO

Limitorque

 

Control panel

Circuit shown with valve in fully closed position and with power off.

Status feedback

 

output switches

 

Default setting

44

CLOSE

S1a

 

position

 

45

OPEN

S1b

48

 

position

49

 

CLOSE

S2a

46

47

position

 

OPEN

S2b

50

51

position

 

Monitor relay

 

Show n

 

54

with

 

53

power

 

 

 

supply off

 

52

 

 

View of terminal block

Grounding lug

 

Cable Preparation

 

Prepare the network cable for connection to the MX actuator terminal block as illustrated in Figures 3.15 through 3.18.

26

a CAUTION: Strip stranded conductors carefully; do not damage the strands. This will weaken the conductor.

 

Do not nick conductors when stripping away the insulation. Nicking stresses the conductor and can cause the

conductor to break. This type of damage may not be apparent and failure can occur later without warning.

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

1.Remove 2 to 3 in. (5 to 8 cm) of the outer plastic jacket as shown in Figure 3.15. Do not cut or nick the drain wire or the insulated conductors.

Figure 3.15 – Removing outer plastic jacket

2.Separate the cable parts. Unbraid the braided shield and peel back the foil shield to the same point where the outer jacket was removed as shown in Figure 3.16.

3.Cut away the braided shield and the foil shield. Strip the insulation from the conductors approximately 1/2 inch (1 cm) as shown in Figure 3.17.

4.Apply heat shrink tubing to insulate the drain wire and to provide stress relief to the cable.

5.Install ring tongue connectors as shown in Figure 3.18.

a CAUTION: Do not melt the insulation.

6.Connect the network cables to the MX actuator terminal block per Table 3.4 and appropriate wiring diagram. Table 3.3 details a connection for the loop topology.

Figure 3.16 – Separating cable parts

27

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

Figure 3.17 – Stripping conductors and applying heat shrink tubing

Figure 3.18 – Ring tongue connectors

Table 3.4 – Loop topology connections

Terminal Block Number DDC

4DATA-A1* (-)

5DATA-A1 (+)

14

DATA-A2* (-)

 

 

13

DATA-A2 (+)

 

 

3

Surge Protection

In terms of voltage, DATA is negative with respect to DATA*.

NOTE: Surge protection must be grounded to be effective.

NOTE: Ground each segment of the cabling at only one point to prevent ground loops, which can affect system performance. Verify the actuator is properly grounded.

Limitorque defines an effective local earth ground as the M3 taps on the housing next to the terminal block. See figure 3.21.

NOTE: Safety ground may not be disturbed.

28NOTE: Shielding is not sufficient to prevent induction of stray voltages onto signal leads from the power lines. A network wiring diagram for a loop is shown in Figure 3.20.

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

After installation is complete and prior to operation, inspect the network cable and its connection to each field unit for the following:

There should not be:

Nicks in the insulation—this can cause a short to the grounded shield.

Cut strands in a stranded conductor—this can cause a poor connection and eventually an open circuit.

Cable armor shorted to the cable shield/drain wire—this may not be at ground potential and could be subject to lightning surges.

Shield/drain wire grounded at more than one end of each cable segment (the section between each adjacent actuator on the loop). This will avoid ground loop problems.

Ground/earth connection except at true ground potential and effective at all times.

3.3.8 Foundation Fieldbus Installation

Ensure that the Foundation Fieldbus cable type is Belden 3076F, or another cable that is within 5% of the following specifications.

Characteristic impedance: 100 ohms @ 31.25 kHz

Resistance, each wire: 7.32 ohms/1000 ft

Attenuation: 0.914 dB/1000 ft @ 39 kHz

Capacitative Unbalance: 3.6 pF/ft

Using other cables may result in decrease of internodal distance and/or an increase in communication error.

Particular care should be taken when terminating twisted-pair shielded cables in a FF control network. Avoid nicks, cuts, or abrasions in the insulation of data communication cables, since this may result in inadvertent ground connection. Also, excess cable should be cut, not coiled or looped, to prevent noise induction into the network.

Cable Preparation

Prepare the network cable for connection to the MX actuator terminal block as follows in Figure 3.15 through 3.18. Table 3.5 details connections for Foundation Fieldbus.

Table 3.5 – Foundation fieldbus connections

Terminal Block Number

FF Function

4DATA (-)

5DATA (+)

The shield must be connected to ground or earth at only one place. The cable shield is generally grounded at the power conditioner.

Reference the Fieldbus Foundation Application Guide 31.25 kbit/s Wiring and Installation guide for more information on network wiring.

aCAUTION: Strip stranded conductors carefully; do not damage the strands. This will weaken the conductor. Do not nick conductors when stripping away the insulation. Nicking stresses the conductor and can cause the conductor to break. This type of damage may not be apparent and failure can occur later without warning.

29

flowserve.com

Limitorque MX Electronic Actuator  FCD LMENIM2306-06 – 10/13

3.3.9 Network Wiring – Profibus DP/PA Installation

Profibus DP is based on RS 485 communication. The standard EN 50170 specifies the cable for use with Profibus DP.

The following specifications need to be fulfilled by the Profibus cable:

Table 3.6 – Profibus cable specifications

Parameter

 

Type – Profibus DP

Impedance

 

135 to 165 ohm/3 to 20 MHz

 

 

 

 

Capacity

 

< 30 pF/m

 

 

 

Resistance

 

< 110 ohm/km

 

 

 

Wire gauge

 

> 0.64 mm

 

 

 

Conductor area

 

> 0.34 mm2

The Profibus DP cable is a shielded twisted pair cable.

In general, there are two different types of cables available. The most commonly used cable has solid wire for the Profibus line. When there is a need for more flexiblity (bending) and higher environmental resistance, a cable with stranded wire for the Profibus line and special jackets shall be used. Limitorque recommends the use of:

• Belden 3079A Specifications, 22 AWG, shielded, solid two conductor

Key Specifications

Capacitance/ft = 8.5 pF

Nominal Impedance (ohms) – 150.0

Network Wiring - Profibus PA

Please refer to IEC 61158 & ANSI/ISA S.50.02 Part 2-1992 for network wiring guidelines. Refer to Table 3.5 for connections.

3.3.10 Network Wiring – DeviceNet

DeviceNet is a CAN-based protocol that uses five wires including a shield. Two of the conductors are used for 24 VDC power and up to 8 amps (4 amps for NEC Class 2) may be passed along the hi-way from a suitable power source. Two conductors are used for the CAN bus signals, CAN_H and CAN_L, which are usually smaller in diameter. Flowserve recommends Belden 3082A cable for connecting to a DeviceNet network. The specifications for this cable are preferred.

Table 3.7 – DeviceNet cable specifications

 

Belden

AWG (Stranding)

Insulation

Nominal

Nom

Nominal

Test

Maximum

 

dia. Inches

material

Impedance

Frequency

Attenuation

 

Part No.

O.D.

Capacitance

 

 

Nom. DCR

(color code)

 

(ohms)

 

(MHz)

dB/100ft

 

 

2 – 15 AWG (19 x 28)

Power pair

 

 

 

 

 

 

 

3.6 ohm/1000 ft

 

 

 

 

 

 

 

(Black/Red)

 

 

 

0.125

0.13

 

 

11.8 ohm/km

 

 

 

 

3082A

 

12.2 mm

120

12.0 pF/ft

0.5

0.25

 

 

 

 

2 – 18 AWG (19 x 30)

Data pair

 

 

 

1

1.36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.9 ohm/1000 ft

 

 

 

 

 

 

 

(Blue/White)

 

 

 

 

 

 

 

22.7 ohm/km

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 – 22 AWG (19 x 34)

Power pair

 

 

 

 

 

 

 

17.5 ohm/1000 ft

 

 

 

 

 

 

 

(Black/Red)

 

 

 

0.125

0.29

 

 

57.4 ohm/km

 

 

 

 

3084A

 

7.2 mm

120

12.0 pF/ft

0.5

0.50

 

 

 

30

2 – 18 AWG (19 x 36)

Data pair

1

1.70

 

 

 

 

 

 

28.0 ohm/1000 ft

 

 

 

 

 

 

 

(Blue/White)

 

 

 

 

 

 

 

91.9 ohm/km

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Loading...
+ 74 hidden pages