Flowserve MX-QX User Manual

0 (0)

 

USER INSTRUCTIONS

MX/QX Profibus DP / PA Field Unit

Installation

FCD LMENIM2336-03 – 12/12

Operation

 

Maintenance

 

 

Experience In Motion

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Contents

 

1

Introduction

5

 

 

 

 

 

 

1.1  Purpose

5

 

 

 

 

 

 

1.2  How to Use this Manual

5

 

 

 

 

 

 

1.3  User Safety

6

 

 

 

 

 

 

1.4  User Knowledge

6

 

 

 

 

 

 

1.5  MX/QX PB System Capabilities and Features

7

 

 

 

 

 

 

1.5.1  General Network Specification

10

 

 

 

 

2 System Components and Installation

12

 

 

 

 

 

 

2.1  Introduction

12

 

 

 

 

 

 

2.2  Hardware

13

 

 

 

 

 

 

2.2.1  MX/QX Actuator

14

 

 

 

 

 

 

2.2.2  MX/QX PB Field Unit

14

 

 

 

 

 

 

2.2.3  Network Host Station

15

 

 

 

 

 

 

2.2.4  Network Cabling for PROFIBUS DP

16

 

 

 

 

 

 

2.2.5  Network Cabling for PROFIBUS PA

20

 

 

 

 

 

 

2.3  Other Network Components

23

 

 

 

 

 

 

2.4  Site and Network Cable Preparation

24

 

 

 

 

 

 

2.4.1  Site Preparation

24

 

 

 

 

 

 

2.4.2  Network Cable Preparation

25

 

 

 

 

 

 

2.4.3  MX/QX PB Device Installation

30

 

 

 

 

 

 

2.5  MX/QX PB Device Setup

31

 

 

 

 

 

 

2.5.1  Proportional Band

33

 

 

 

 

 

 

2.5.2  Deadband

33

 

 

 

 

 

 

2.5.3  Valve Data

33

 

 

 

 

 

 

2.6  MX/QX PB Device Description, Capabilities and Device Type Manager File Installation

34

 

 

 

 

 

 

2.6.1  MX/QX PB Device Description

34

 

 

 

 

 

 

2.6.2 MX/QX PB Device Type Manager

34

 

 

 

 

 

 

2.7  Installation Verification

34

 

 

 

 

 

 

2.7.1  Network Cabling Installation Verification

34

 

 

 

 

 

 

2.7.2  MX/QX PB Device Installation Verification

35

 

 

 

 

 

 

2.8  Configuration Confirmation

35

 

 

 

 

 

 

2.8.1  Checking Connections

35

 

 

 

 

 

 

2.8.2  View Settings

35

 

 

 

 

 

 

2.8.3  Checking the Normal Display

36

 

 

 

 

 

3

Software

38

 

 

 

 

 

 

3.1  PROFIBUS Protocol

38

 

 

 

 

 

 

3.2  PROFIBUS Function, Transducer, and Physical Blocks

38

 

 

 

 

 

 

3.3  Analog Input (AI) Function Block

41

 

 

 

 

 

 

3.4  Analog Output (AO) Function Block

44

 

 

 

 

 

 

3.5  Discrete Input (DI) Function Block

48

 

 

 

 

 

 

3.6  Discrete Output (DO) Function Block

50

 

 

 

 

 

 

3.7  Transducer Block

52

 

 

 

 

 

 

3.8  GSD and Electronic Device Description, and DTM Files

53

 

 

 

 

2

4

Associated Documents

54

 

 

 

 

 

 

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

5 How to Order Parts

55

A  Appendix – Wiring Diagrams

56

 

 

B  Appendix – Feature Definitions

62

 

 

C  Appendix – PROFIBUS Function Block

80

Glossary

85

 

 

Tables

 

Table 2.1 – Maximum Segment Length

17

 

 

Table 2.2 – Total Network Length (with up to nine repeaters)

17

Table 2.3 – Recommended PROFIBUS DP Cable Parameters

17

 

 

Table 2.4 – Recommended PROFIBUS DP Cable Types

18

 

 

Table 2.5 – Recommended PROFIBUS PA Cable Parameters (Type A – shielded twisted-pair)

20

Table 2.6

– Recommended PROFIBUS PA Cable Types

20

 

 

 

Table 2.7

– Recommended Lengths of PROFIBUS PA Spurs (Stubs)

21

 

 

 

Table 2.8

– Details of Terminal Block Cable Assignments

29

Table 3.1

– Description of the Function Blocks

40

 

 

 

3

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Figures

 

Figure 1.1 – Typical PROFIBUS DP Network with DCS or PLC as the Host System

8

 

 

 

 

Figure 1.1a – Typical PROFIBUS DP Network with Redundancy Option (Single Master)

9

 

 

 

 

Figure 1.1b – Typical PROFIBUS DP Network with Redundancy Option (Dual Master)

9

 

 

 

 

Figure 1.2 – Typical PROFIBUS PA Network with DCS or PLC as the Host System

10

 

 

 

 

Figure 2.1 – MX/QX-05 Actuator

13

 

 

 

 

Figure 2.2 – MX/QX PB DP Field Unit

14

 

 

 

 

Figure 2.3 – MX/QX PB PA Field Unit

15

 

 

 

 

Figure 2.4 – Typical Cycle Time (Each Station with 2 Bytes I/O)

16

 

 

 

 

Figure 2.5 – Copper PROFIBUS Distance vs. Baud Rate Chart

18

 

 

 

 

Figure 2.6 – Cable Topologies

19

 

 

 

 

Figure 2.7 – Use of Shielded Cable in PROFIBUS DP

19

 

 

 

 

Figure 2.8 – PROFIBUS PA Cable Topologies

21

 

 

 

 

Figure 2.9 – Use of Shielded Cable in PROFIBUS PA

22

 

 

 

 

Figure 2.10 – PROFIBUS PA Power Supply

23

 

 

 

 

Figure 2.11 – PROFIBUS Segments

24

 

 

 

 

Figure 2.12a – PROFIBUS DP Cable Connections

25

 

 

 

 

Figure 2.12b – PROFIBUS DP Cable Connections (Redundancy Option with Single Master)

25

 

 

 

 

Figure 2.12c – PROFIBUS DP Cable Connections (Redundancy Option with Dual Master)

26

 

 

 

 

Figure 2.13 – PROFIBUS PA Cable Connections to Terminal Blocks

26

 

 

 

 

Figure 2.14 – Removing Outer Plastic Jacket

27

 

 

 

 

Figure 2.15 – Separating Cable Parts

27

 

 

 

 

Figure 2.16 – Stripping Conductors

28

 

 

 

 

Figure 2.17 – Applying Heat-Shrink Tubing

28

 

 

 

 

Figure 2.18 – Ring Tongue Connectors

29

 

 

 

 

Figure 2.19 – Connecting Network Cable to the MX/QX Terminal Block

30

 

 

 

 

Figure 2.20a – MX/QX PB DP Primary Board Mounted to MX/QX Main Board

30

 

 

 

 

Figure 2.20b – MX/QX PB DP Primary and Redundant Boards Mounted to MX/QX Main Board

30

 

 

 

 

Figure 2.21 – MX/QX PB DP Setup Sequence

31

 

 

 

 

Figure 2.22 – MX/QX PB PA Setup Sequence

32

 

 

 

 

Figure 2.23 – Normal Display, Field Unit is Communicating with Host

36

 

 

 

 

Figure 2.24a – No Communications

36

 

 

 

 

Figure 2.24b – No Communications

37

 

 

 

 

Figure 2.25 – Hardware Failure, No Communication, Bus Power Lost

37

 

 

 

 

Figure 3.1 – MX/QX Actuator Block Overview

39

 

 

 

 

Figure 3.2 – Summary of the Parameters of the Analog Input Function Block

41

 

 

 

 

Figure 3.3 – Analog Input Block

42

 

 

 

 

Figure 3.4 – Analog Input Block Scaling and Filtering

43

 

 

 

 

Figure 3.5 – Summary of the Parameters of the Analog Output Block

44

 

 

 

 

Figure 3.6 – Analog Output Function Block

45

 

 

 

 

Figure 3.7 – Analog Output Block Scaling

47

 

 

 

 

Figure 3.8 – Summary of the Parameters of the Discrete Input Function Blocks

49

 

 

 

 

Figure 3.9 – Discrete Input Function Block

49

 

 

 

 

Figure 3.10 – Summary of the Parameters of the Discrete Output Function Block

50

 

 

 

4

Figure 3.11 – Discrete Output Function Block

51

 

 

Figure 3.12 – PROFIBUS PA Configuration Requirements

53

 

 

 

 

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

1 Introduction

1.1  Purpose

This manual explains how to install and operate the Flowserve Limitorque MX/QX PROFIBUS field unit, referred to as the MX (Multi-turn)/QX (Quarter-turn) PB (PROFIBUS) field unit. Actuators containing the PB field unit may be connected by shielded twisted-pair, or shielded two-wire cable to form a PROFIBUS communication system network. The name PROFIBUS is derived from Process Fieldbus. The PROFIBUS communication system is a digital, serial, two-way open bus system that supports a variety of communication rates. The MX/QX PB unit supports a communication rate up to 1.5 Mbit/sec. This system allows a network host station such as a distributed control system (DCS) or a programmable logic controller (PLC) to control and monitor the actuators, including the acquisition of status and alarm data from each MX/QX.

1.2  How to Use this Manual

Each section provides the MX/QX PB user with information on installing and operating the MX/QX PB field unit.

Section 1. Introduction  The introduction details user safety and knowledge requirements, system capabilities, and features.

Section 2. System Components and Installation  The system components section focuses on the description of the PROFIBUS system hardware and software components, and provides details for installing and configuring a field unit.

Section 3. Software  The software section provides details regarding the software that the MX/QX PB uses to communicate.

Section 4.

Associated Documents  This section provides a list of documents on related subjects for

5

additional MX/QX and PROFIBUS system information.

 

Section 5.

How to Order Parts  This section provides part numbers and ordering contact

 

information.

 

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Appendix A – Wiring Diagram  This section contains the detailed wiring connection information for the MX/QX field unit.

Appendix B – Feature Definitions  This section contains the Flowserve Limitorque actuator

Transducer Block I/O (Input/Output) channels and parameters.

Appendix C – PROFIBUS Function Block  This section contains the PROFIBUS Function Block parameters and descriptions.

Glossary  The glossary contains a terminology list of abbreviations, acronyms and their descriptions.

1.3  User Safety

Safety notices in this manual detail precautions the user must take to reduce the risk of personal injury and damage to the equipment. The user must read and be familiar with these instructions before attempting installation, operation, or maintenance. Failure to observe these precautions could result in serious bodily injury, damage to the equipment, warranty void, or operational difficulty. The user must follow all applicable local and state safety regulations.

Safety notices are presented in this manual in three forms:

cWARNING: Refers to personal safety and alerts the user to potential danger. Failure to follow warning notices could result in personal injury or death.

aCAUTION: Direct the user’s attention to general precautions that, if not followed, could result in personal injury and/or equipment damage.

NOTE: Highlights information critical to the user’s understanding of the actuator’s installation and operation.

1.4  User Knowledge

It is recommended that the user read this manual in its entirety before the MX/QX PB field unit is installed and operated.

The user needs to have a fundamental knowledge of electronics and an understanding of valve actuators and digital control systems. Refer to the Glossary for information regarding the terms used throughout this manual.

The following websites have documents on PROFIBUS and electric actuators:

www.PROFIBUS.com

www.flowserve.com

www.iec.ch

For PROFIBUS technology and cabling information, refer to the following documents:

6

• PROFIBUS DP Specification, IEC 61158 Type 3 and IEC 61784.

• PROFIBUS Profile – PROFIBUS PA – Profile for Process Control Devices, Version 3.02, November 2008, PROFIBUS International Order No. 3.042.

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Installation Guidelines for PROFIBUS – FMS/DP Version 1.0, PROFIBUS International Order No. 2.112.

Profibus Installation Guideline For Cabling and Assembly, Version 1.0.6, PROFIBUS International Order No. 8.022.

Profibus Installation Guideline For Commissioning, Version 1.0.2, PROFIBUS International Order No. 8.032.

Technical Guideline: PROFIBUS PA User & Installation Guideline, Version 2.2, February 2003.

PROFIBUS Specification - Slave Redundancy Version 1.2, PROFIBUS International Order No. 2.212, November 2004.

1.5  MX/QX PB System Capabilities and Features

Flowserve Limitorque’s MX/QX PROFIBUS (PB) field unit conforms to the open fieldbus standard EN50170. It is suitable for use on PROFIBUS and uses a twisted-pair or two-conductor shielded cable for connection to the network. A PROFIBUS device is an intelligent device within the actuator that can send multiple variables to the control system over a high-resolution and distortion-free digital communication network. The device provides control and self-test capabilities, which allow abnormal conditions to be easily and immediately identified before an unplanned shutdown.

The MX/QX PB unit may command its actuator to: open, stop, close, move to a set position, perform an emergency shutdown operation, read and control relays, monitor analog inputs and position, and monitor modes and alarms. Commands to the unit come over the network from the master network host station, which may be a Personal Computer (PC), Distributed Control System (DCS), Programmable Logic Controller (PLC), or some other microprocessor-based device. The master is defined as an active network node which means that it has addressing, and read and write privileges to slave devices that are assigned to it.

Additional features and capabilities are:

The system reduces the cost of wiring and installation by using existing wiring and multi-drop connections, if it meets PROFIBUS requirements. It is also possible to have more than one PROFIBUS communication network on the same cabling.

Multiple-master operations through the use of the PROFIBUS token being passed between masters (active nodes). Each master has its own set of slaves and may only write to those slaves.

Master-slave operations where the master, active node, has the right to address, and send or fetch messages from the slaves (passive nodes).

The devices are interoperable, as devices from different suppliers communicate with one another on the same network.

The PROFIBUS communication system supports up to 32 devices per segment, with up to 126 addressable devices with the use of repeaters.

Segmentation is used for the following reasons:

Isolation is desired between two areas or buildings.

Media conversion (copper to fiber or fiber to copper) is desired.

• The maximum of 32 nodes has been reached (31 + repeater).

7

 

The maximum distance has been reached.

It is desirable to “reform” the signal to full voltage levels (noisy environment).

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

The devices used to create a segment are Repeaters for copper networks, Optical Link Modules for glass or plastic-coated glass fiber-optic networks, and Optical Bus Terminals for plastic fiber-optic networks. Each of these devices provides either electrical or optical isolation between segments.

The MX/QX PB field unit fits in the actuator in the sealed electrical housing compartment. There are two different communication board options for the MX/QX PB field unit: MX/QX PB DP, which supports PROFIBUS DP (Decentralized Periphery) RS-485 physical layer and MX/QX PB PA, which

supports PROFIBUS PA (Process Automation) IEC 1158 physical layer. The MX/QX PB DP field unit is available with Flying and System Redundancy.

PROFIBUS DP ensures high-speed data transmission of user data, and is designed especially for communication between a master host station and distributed devices at the field level.

PROFIBUS PA uses the expanded PROFIBUS DP protocol for data transmission and implements the PA profile that specifies the characteristics of the field device. This transmission technique ensures intrinsic safety and powers the field devices over the bus. PROFIBUS PA is designed for high-speed and reliable communications, with the ability to link sensors and actuators to a common fieldbus line, even in potentially explosive areas.

PROFIBUS PA devices can be integrated into PROFIBUS DP networks using segment couplers.

The adjustments to the MX/QX PB settings may be made locally at the actuator and over the PROFIBUS network using a DPV1 network configuration tool.

A typical MX/QX PB DP system is shown in Figure 1.1 in a Master/Slave Configuration, Figure 1.1a shows a typical PROFIBUS DP network with redundancy option in a single master configuration, Figure 1.1b shows a typical PROFIBUS DP network with redundancy option in a dual master configuration, and Figure 1.2 shows a typical MX/QX PB PA system.

Figure 1.1 – Typical PROFIBUS DP Network with DCS or PLC as the Host System

Distributed Control

System (Host)

Control Highway

PROFIBUS DP-V1

Interface

T Terminator

PB

Actuator

Power for the fieldbus devices and cable shield grounding are discussed in Sections 2.4 and 2.5.

PROFIBUS DP Network

Terminator

 

 

 

T

PB

PB

PB

Actuator

Actuator

Actuator

8

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Figure 1.1a – Typical PROFIBUS DP Network with Redundancy Option (Single Master)

Distributed Control

System (Host)

Control Highway

PROFIBUS DP-V1

Interface

 

T

Terminator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROFIBUS DP Network

 

 

 

 

 

 

 

Terminator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PBDP-A

PBDP-B

 

PBDP-A

PBDP-B

 

PBDP-A

PBDP-B

 

PBDP-A

PBDP-B

 

 

 

 

 

Actuator

 

 

Actuator

 

 

Actuator

 

 

Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 1.1b – Typical PROFIBUS DP Network with Redundancy Option (Dual Master)

Distributed Control

System (Host)

Control Highway

 

 

 

 

PROFIBUS DP-V1

 

 

 

 

 

 

 

 

 

 

 

 

PROFIBUS DP-V1

 

 

 

 

 

Interface-1

 

 

 

 

 

 

 

 

 

 

 

 

Interface-2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T

Terminator

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminator

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T

 

 

 

 

 

 

 

PROFIBUS DP Network

 

 

 

 

 

 

 

 

 

 

 

T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PBDP-A

PBDP-B

 

PBDP-A

PBDP-B

 

PBDP-A

PBDP-B

 

PBDP-A

PBDP-B

 

 

 

 

 

 

 

 

 

 

 

Actuator

 

 

Actuator

 

 

Actuator

 

 

Actuator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Figure 1.2 – Typical PROFIBUS PA Network with DCS or PLC as the Host System

Distributed Control

System (Host)

Control Highway

PROFIBUS PA

Interface

Power for the fieldbus devices and cable shield grounding are discussed in Sections 2.4 and 2.5.

Junction Box

PA

PA

PA

Actuator

Actuator

Actuator

Tree

PA

Actuator

PA

Actuator

PA

Actuator

PA

Actuator

PA

Actuator

PA

Actuator

PA

Actuator

PA

Actuator

PA

Actuator

Point to Point

Bus with spurs (or drops)

Daisy Chain

1.5.1  General Network Specification

System Specifications:

Communicates using the PROFIBUS DP or PROFIBUS PA protocol.

PROFIBUS DP is V1 compliant.

Employs high-speed communication.

Complies with EN50170 fieldbus standard.

PA Physical Layer with IEC1158-2.

DP Physical Layer with RS-485.

Network Specification:

Several topologies are available including point-to-point, bus, tree, ring, or a combination of these.

Network features include:

PROFIBUS DP high-speed communications up to 1.5 Mbit/sec.

PROFIBUS PA communications are 31.25kbits/sec (segment coupler side).

Master/slave communications.

Multiple-master network systems.

Redundant PROFIBUS DP with single or multiple-master communications.

MX/QX Field Unit Specification:

The field unit mounts inside the actuator, is software controlled, and has the following features:

Input and Output Function Blocks.

Device descriptions – describes device and parameters.

Network communication – compliant with EN50170.

Configurable by user – locally and via network.

10

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

PROFIBUS Master Specification

The PROFIBUS master is the network system host, and can be a PC, DCS, PLC, or some other microprocessor-based device. The master is defined as the network node that has addressing, and read/write privileges to slave devices that are assigned to it. A PROFIBUS network can have more than one master, but one, and only one, token is active at a given time. The token provides the right to access the transmission medium, as is passed between the active nodes (masters) with a token telegram. The master host station acts as the bus arbiter, and does the following:

Recognizes and adds new devices on the link.

Removes non-responsive devices from the link.

Distributes a priority-driven token for unscheduled cyclic transmissions between masters.

Ensures cyclic data transferred on a periodic basis.

Issues requests for process data from the field devices.

Issues commands to the field devices.

High Speed Data Exchange – Startup Sequence

Power ON / Reset – Power on / Reset of master or slave.

Parameterization – download of parameters into the field device (selected during configuration by the user).

I/O Configuration – download of I/O configuration into the field device (selected during configuration by the user).

Data Exchange – cyclic data exchange (I/O Data) and field device reports diagnostics.

NOTE: In the application profile definition, only Function Blocks may have cyclic parameters. Physical Blocks and Transducer Blocks do not have cyclic parameters. PROFIBUS DP/V1 is part of the requirement to access Acyclic parameters through the Function Block specification and is composed of a slot number and an index number. Acyclic services are performed between two data exchange cycles. A PROFIBUS Class 2 Master is required for acyclic data exchange (Function Blocks). An Electronic Device Descriptor File is used in the configuration tool of the Master to gain access to the Function Block parameters (refer to Chapter 3, Software).

Device Configuration Tool Requirements

Generally, the device configuration tool can be executed independently of the control system configuration tool. The general requirements are as follows:

A PROFIBUS DP or PA network is inserted as an object of a control system project (or independent project).

Within that network, a device is logically attached along with object name, PROFIBUS DP/PA address, and how many objects are to be attached.

Editing this device will allow the user to select the type of device (actuator, sensor, etc.).

The configuration tool will then display the extended parameters with initial values.

These parameters may be uploaded from the device to display the actual values (if a network connection is possible).

New values can be entered and then downloaded to the device through the network connection.

There will also be a method for monitoring the online parameter values.

11

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

2 Systemand InstallationComponents

2.1  Introduction

This section is an overview of the components used in the PROFIBUS system and their integration with the MX/QX actuator. The MX/QX PB field unit is installed in the control compartment of the actuator as shown in Figures 2.1a and 2.1b. The PROFIBUS network cable from the host control station connects to the fieldbus unit at the actuator terminal block.

The Network Cabling section of this chapter is broken into two sections; PROFIBUS DP and

PROFIBUS PA.

Refer to Appendix A for detailed wiring connections.

12

Flowserve MX-QX User Manual

 

 

 

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

 

2.2  Hardware

 

 

 

 

Figure 2.1a – MX-05 Actuator

 

 

Figure 2.1b – QX-05 Actuator

 

 

 

 

10

 

 

 

1

3

 

 

 

 

 

 

 

13

 

 

3

 

2

2

 

 

 

 

 

12

 

 

 

 

11

 

 

 

 

10

 

5

 

 

 

4

 

 

 

 

5

12

 

 

 

 

 

9

8 7

 

6

1

 

 

7

 

 

 

 

6

 

 

 

 

4

 

 

 

 

9

 

11

 

 

9

 

 

 

 

 

 

 

 

9

 

 

 

 

OPTIONAL

 

2

3

 

15

 

 

14

 

3

 

 

 

 

8

Item

Description

 

Item

 

1

Handwheel

 

1

Handwheel

2

Declutch lever

 

2

Declutch lever (QX-05)

3

Oil fills (dotted arrow depicts fill on declutch side)

 

3

Oil fill

4

Controls compartment (field unit location)

 

4

Controls cover

5

LCD display

 

5

LCD display

6

Control knobs

 

6

Control knob

7

Ground lug

 

7

Ground lug

8

Thrust/torque base

 

8

Baseplate

9

Conduit entries

 

9

Conduit entry

10

Terminal compartment

 

10

Terminal compartment

11

Electric motor

 

11

Motor

12

Nameplate

 

12

Certification nameplate

13Tag nameplate

14Oil plug

15

Stem nut stops

13

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

2.2.1  MX and QX Actuators

The MX and QX actuators are designed for operation of ON-OFF and modulating valve applications. The MX is a multi-turn actuator, while the QX is a quarter-turn actuator.

Both the MX and QX include the following features:

Non-intrusive setup.

Separately sealed terminal compartment.

Unique absolute encoder for valve position sensing (no battery required).

32-character LCD for indication and calibration.

Enhanced electronic control, monitoring, and diagnostic capabilities with Built-In Self Test (BIST) and LimiGard™ technology.

NOTE: Recommended storage procedures are detailed in the MX and QX Maintenance and Spare Parts Manual LMENIM2314 and LMENIM3314 respectively. Failure to comply with recommended procedures will void the warranty. For longer-term storage, contact Flowserve for procedure and recommendations.

2.2.2  MX/QX PB Field Unit

The MX/QX PB field unit interface board is installed in the actuator controls compartment (Figure 2.1). The MX/QX PB DP version is shown in Figure 2.2, and the MX/QX PB PA version is shown in Figure 2.3. Each unit permits the actuator to be controlled as a slave by one or more master host stations over their respective PROFIBUS network. The MX/QX PB DP version supports two forms of redundancy when two PB DP field unit boards are installed in a single actuator:

a.Flying redundancy provides slave hardware redundancy in the form of an active and standby PB DP field unit installed in each actuator. This form is commonly utilized in applications where a single master is present.

b.System redundancy provides for both slave hardware redundancy, in the form of an active and standby PB field unit installed in each actuator, and cable redundancy in the form of dual masters connected to the active and standby PB DP field units.

Figure 2.2 – MX/QX PB DP Field Unit

14

Note: Field unit board jumpers, JP1 and JP2, are set to “A” position on Primary board and “B” position on Redundant board.

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Figure 2.3 – MX/QX PB PA Field Unit

The following commands and feedback information are transmitted through this unit:

OPEN, CLOSE, and STOP commands.

ESD (Emergency Shutdown) commands.

Go-to-position commands.

Redundancy switch-over commands (Profibus DP Redundancy option).

Position feedback.

Actuator status, alarm, and diagnostic messages.

User analog input feedback.

Discrete input feedback.

Discrete output relays.

2.2.3  Network Host Station

The PROFIBUS master is considered to be the network host station, which is typically a DCS, PC, PLC or other microprocessor-based PROFIBUS-compliant device. In a mono-master network, the network host device is the only active network node. This is common in a standard Master-Slave PROFIBUS network. In a multi-master network, there are two or more active nodes. This is managed in a token ring, where the token, a uniquely structured message, circulates continuously among the active network nodes. In the case of multiple Masters, only one Master has read/write privileges to its Slaves (passive nodes) at any one time, and the control token is passed continuously in ascending order to all other active network nodes.

2.2.3.1  Token Bus and Token Passing in a Multi-Master Network

During the bus initialization and startup, the bus access control creates the token ring by recognizing the active network nodes in ascending order. The bus access control automatically determines the addresses of all active nodes on the bus, and records them together with its own node address, creating a List of Active Stations. The Lowest Station Address (LSA) begins with the active token, allowing it to fetch and send data messages to its passive slaves (referred to as polling). At completion of its request frame (polling telegram), and acknowledgement or response frame returned from the slave, the token is passed to the Next Station (NS) with a token telegram. The active node from which the node was passed is called the Previous Station (PS). This continues until the token is being passed from the Highest Station Address (HSA). At completion of the HSA polling telegram, the token is passed to the LSA. The List of Active Stations is required during network operation to remove a faulty active node, or to add a node, without disturbing data on the bus.

15

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

2.2.3.2  Token Rotation Time

The time required for the rotation of the token to all active nodes is the token rotation time. The Time Target Rotation (TTR) is adjustable, and is used to specify the maximum allowed time of one rotation.

2.2.3.3  Bus Cycle Time

Based on the number of slaves attached to each master and the amount of data to be transferred, a Bus Cycle Time is calculated by the master. This is the amount of time required for a master to poll all slaves. This, along with the Token Rotation Time, makes PROFIBUS network access deterministic.

Figure 2.4 – Typical Cycle Time (Each Station with 2 Bytes I/O)

 

20.0

 

 

 

 

 

18.0

 

 

 

 

 

16.0

 

1.5 MBaud

 

 

 

 

 

 

 

 

14.0

 

500 kBaud

14.1

 

(ms)

 

 

 

 

12.0

 

 

 

 

Time

10.0

 

7.7

 

 

 

 

 

 

Cycle

8.0

 

 

 

 

 

 

8.8

 

 

 

 

 

6.0

4.6

 

6.1

 

 

 

 

 

 

4.0

 

 

 

 

2.0

 

 

 

 

2.0

3.3

 

 

 

 

 

 

 

 

2.0

 

 

 

 

0.9

 

 

 

0.0

 

 

 

 

 

 

 

 

 

1

5

10

20

30

Number of Slaves

2.2.4  Network Cabling for PROFIBIS DP

Network cabling should be in accordance with PROFIBUS Decentralized Periphery (DP) guidelines. To achieve immunity to electromagnetic interference, ensuring high data integrity, certain cables and guidelines are recommended. Additionally, the following items should be taken into account when planning the network:

Transmission rate – Within a network, only one transmission rate can be used; the MX/QX PB DP works at baud rates up to 1.5 Mbps.

The level of Master and Slave redundancy, if any.

The required number of nodes.

The type of network components needed – terminals, connectors, connecting cables, termination.

The type of cable to be used and its characteristics.

The number of segments and/or repeaters.

The overall span of the network – adding repeaters and long cable lengths can increase transmission time.

Cable termination – active termination resistors are required at the ends of all segments.

16

In general, the following rules apply for PROFIBUS networks:

 

The higher the baud rate, the shorter the distance allowed between nodes.

The higher the baud rate, the shorter the maximum distance of a segment.

The higher the baud rate, the shorter the maximum distance of an entire network.

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

These distance rules (or limitations) are based on the physical characteristics of the RS-485 topology and are not a limitation of the PROFIBUS protocol. If the distance required between two stations or the total network distance is greater than allowed by the PROFIBUS specifications for copper cable, a conversion to fiber-optic cable may be required. Figure 2.5 shows the baud rate versus copper cable distance using PROFIBUS.

Table 2.1 provides the guidelines for maximum segment length versus baud rate.

Table 2.1 – Maximum Segment Length

Baud Rate

9600 to 187.5K

500K

 

1.5M

Maximum Segment Length (meters)

 

400

 

200

1,000

 

 

 

 

 

 

Table 2.2 provides the guidelines for maximum network length versus baud rate (assuming the use of up to 9 repeaters).

Table 2.2 – Total Network Length (with up to nine repeaters)

Baud Rate

9600 to 187.5K

500K

 

1.5M

Total Network Length (meters)

 

4,000

 

2,000

10,000

 

 

 

 

 

 

NOTE: The maximum lengths are estimates and depend on the condition of the actual cable.

Tables 2.3 and 2.4 detail the various types of cable which can be used for network cabling. For additional guidelines, see the following publications:

PROFIBUS Networks SIMATIC NET 6GK1970-5CA20-0AA1.

PROFIBUS Technical Guideline for PROFIBUS-DP/FMS, Version 1.0, September 1998; PROFIBUS Guideline, Order No. 2.112.

There are different types of electrical data transfer cables:

Standard bus cable.

Standard bus cable with halogen-free sheath (type FRNC).

Cable with PE sheath for use in the food and drug manufacturing industries.

Direct buried cable with additional protective sheath for buried service.

Trailing cable – This is a special cable type which is used where parts of the machine move occasionally or continuously.

Festooned cable – Comparable to a trailing cable, but has an additional strain relief element.

NOTE: Cable must meet the requirements as listed in table 2.3 to ensure reliable network communications.

Table 2.3 – Recommended PROFIBUS DP Cable Parameters

Characteristic impedence at 3-20 MHz (ohms)

135-165

 

 

Operating capacitance (pF/m)

< 30

 

 

Loop resistance (ohms/km)

≤ 110

 

 

Core diameter (mm)

> 0.64

 

 

Core cross-section (mm2)

> 0.34

17

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance 

FCD LMENIM2336-03 – 12/12

Table 2.4 – Recommended PROFIBUS DP Cable Types

 

 

 

 

 

FC Standard Cable (Siemens AG)

 

6XV1 830-0EH10

 

 

 

FRNC Cable (Siemens AG)

 

6XV1 830-0CH10

 

 

 

FC Food Cable (Siemens AG)

 

6XV1 830-0GH10

 

 

 

FC Ground Cable (Siemens AG)

 

6XV1 830-3FH10

 

 

 

FC Trailing Cable (Siemens AG)

 

6XV1 830-3EH10

 

 

 

Festoon Cable (Siemens AG)

 

6XV1 830-3GH10

 

 

 

PROFIBUS Data Cable (Belden Wire and Cable)

 

3079A/3076F

 

 

 

PROFIBUS DP Cable (Moeller GmbH)

 

ZB4-900-KB1

 

 

 

PROFIBUS DP Cable (Kerpenwerk GmbH)

 

7422/7436

 

 

 

PROFIBUS DP Cable (ABB Automation GmbH)

 

NDC110-NO

 

 

 

Figure 2.5 – Copper PROFIBUS Distance vs. Baud Rate Chart

 

 

 

 

12,000

 

 

 

 

 

 

 

 

 

 

10,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Network

 

8,000

 

 

 

 

 

 

 

 

Segment

 

 

 

 

 

 

 

 

 

 

(m)

6,000

 

 

 

 

 

 

 

 

 

Distance

4,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2,000

1,000

1,000

1,000

1,000

400

 

 

1,000

1,000

 

 

 

 

 

 

200

100

100

100

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9.6

19.2

93.75

187.5

500

1,500

3,000

6,000

12,000

Baud Rate (kBaud)

There are several topologies available for both redundant and non-redundant PROFIBUS networks:

Point-to-point – A single cable from master to slave.

Daisy chain – A single cable daisy chained in and out of each field unit device. End of segment devices only have one incoming cable.

Tree – Cables and electronic devices (such as repeaters or link modules) are used to branch out from different points.

Ring – Often implemented with fiber-optic cable which forms a circle or ring when used with Optical Link Modules. This topology yields redundancy so that any single component fault or cable break does not affect the network (except for the component).

Combination of the above.

NOTE: Bus with Spurs, also referred to as stub lines, are not recommended by PROFIBUS as they can create parallel resistance and cause disturbances and reflections on the main trunk or bus line.

18

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Figure 2.6 – Cable Topologies

Distributed Control

System (Host)

Network

 

PROFIBUS

 

Interface

Repeater

 

 

Tree

Schematic topology: Details such as terminators and power supplies not shown

Daisy Chain

Daisy Chain

Bus with spurs (or drops)

Point-to-point

2.2.4.1  Cable Shielding and Grounding for PROFIBUS DP

For best performance, PROFIBUS DP cables should be shielded. Per PROFIBUS Technical Guidelines, the cable shield should be connected at the beginning and end of the segment. Alternatively, a 10-12 AWG ground wire may be run to each MX/QX.

In Figure 2.7, the grounding point is shown at the junction of the field devices and at each field device.

Figure 2.7 – Use of Shielded Cable in PROFIBUS DP

Field

Device

T

PROFIBUS T

Interface

 

 

 

 

 

Field

 

Field

Device

 

Device

 

 

 

 

 

19

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

2.2.5  Network Cabling for PROFIBUS PA

Network cabling should be in accordance with PROFIBUS Process Automation (PA) guidelines using twisted-pair shielded cable. The data line is normally also used to supply power to the field devices. PROFIBUS PA is a combination of the PROFIBUS-DP V1 protocol and the IEC 61158-2 transmission technique.

The following items should be taken into account when planning the network:

Transmission rate – Within a network, only one transmission rate can be used; typical restrictions of PA are 31.25kbits/sec.

The required number of nodes.

The type of network components needed – Terminals, connectors, connecting cables, termination.

The type of cable to be used and its characteristics.

The number of segments and/or repeaters.

The overall span of the network – Adding repeaters and long cable lengths can increase transmission time.

Cable termination – Active termination resistors are required at the ends of all segments.

Tables 2.5 and 2.6 detail the recommended cable parameters and various types of cable that can be used for network cabling. For additional guidelines, see the following publications:

• PROFIBUS Networks SIMATIC NET

6GK1970-5CA20-0AA1

Technical Guideline – PROFIBUS PA User and Installation Guideline Version 2.2 February 2003, PROFIBUS Guideline Order No. 2.092

Table 2.5 – Recommended PROFIBUS PA Cable Parameters (Type A – shielded twisted-pair)

Characteristic impedence

100 ohms ±20%

 

 

Maximum capacitance

2 nF/km

 

 

Loop resistance

44 ohms/km

 

 

Conductor cross-sectional area

0.8 mm2 (AWG 18)

Maximum length of network (including spurs)

1900 m

 

 

Table 2.6 – Recommended PROFIBUS PA Cable Types

PA, Ex and Non-Ex

NPC080-NO

(ABB Automation Products GmbH)

 

 

 

PA, Ex and Non-Ex

NPC150-NO

(ABB Automation Products GmbH)

 

 

 

PROFIBUS FC Process Cable (Siemens AG)

6XV1 830-5.H10

 

 

PROFIBUS Data Cable (Beldon Wire & Cable)

3079A & 3076F

 

 

UNITRONICS Bus PA (Lapp Kabel GmbH)

2170 235 1x2x1.0

 

 

20

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Table 2.7 – Recommended Lengths of PROFIBUS PA Spurs (Stubs)

Number of Spur

Length of Spur Cable

Length of Spur Cable

Cables

Intrinsically Safe (m)

Non-Intrinsically Safe (m)

19 to 24

 

30

30

 

 

 

15 to 18

30

60

 

 

 

13 to 14

30

90

 

 

 

1 to 12

30

120

 

 

 

NOTE: The maximum lengths are estimates and depend on the condition of the actual cable.

There are several topologies for PROFIBUS networks:

Daisy Chain – A single cable daisy chained in and out of each device. End devices only have one cable.

Tree – Cables and electronic devices (such as repeaters or link modules) are used to branch out from different points.

Star – Similar to a Tree configuration but the cables all originate from one centralized point that is comprised of electronic devices (such as repeaters or link modules).

• Combination of the above.

Figure 2.8 – PROFIBUS PA Cable Topologies

Distributed Control

System (Host)

Control Highway

Schematic topology: Details such

as terminators and power supplies not shown

 

 

PROFIBUS

Junction

 

 

Interface

 

 

 

 

Box

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tree

Daisy Chain

Bus with spurs (or drops)

Point-to-point

21

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

2.2.5.1  Cable Shielding and Grounding for PROFIBUS PA

For best performance, PROFIBUS PA cables must be shielded. When using shielded cable, connect each cable shield to the trunk shield, and connect the overall shield to the PROFIBUS power supply ground.

In Figure 2.9, the grounding point is shown at a connection point of power supply return.

Figure 2.9 – Use of Shielded Cable in PROFIBUS PA

Field

Device

 

 

Shielded Wire Pair

PROFIBUS

T

T

Interface

 

 

 

 

 

 

Connect Shield

Field

Device

to Ground at one

 

 

 

 

 

 

place only

 

 

 

Field

Device

2.2.5.2  PROFIBUS PA Power Supply

The MX/QX PB/PA board requires a nominal 24 VDC (9-32 VDC) on the PA bus to power the MX/QX PB/PA board and make the actuator visible on the network. The required power supply is typically connected to a segment coupler to the bus, usually located at the host end of the cable. Validate the requirements of the segment coupler to determine actual power and voltage.

NOTE: If the actuator does not have three-phase power and the network is active, the MX/QX PB/PA board will report this condition to the host.

22

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Figure 2.10 shows a typical PROFIBUS PA power supply arrangement.

Figure 2.10 – PROFIBUS PA Power Supply

Field

Device

+

Fieldbus

Power - Supply

 

 

 

 

Shielded Wire Pair

 

 

 

 

 

Field

 

 

 

 

 

 

 

 

 

 

PROFIBUS PA

 

 

 

 

 

 

 

 

 

Device

 

T

 

 

T

 

 

 

 

 

 

 

 

 

Interface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: Bus power supply may be integrated with the PROFIBUS PA bus interface.

Field

Device

2.3  Other Network Components

In addition to the network cables, the following components may be used in the PROFIBUS network. Each network is designed based on its application and therefore may not require all of these components.

Bus Terminal Blocks/Junction Box – Provides multiple connections to the bus (network).

Active Bus Terminal – Provides active termination so that other stations may be powered down for service without affecting the network.

Connectors – Enable connections to junction boxes, terminators or other connectors. Useful in installations where devices will be periodically disconnected or when a device is only going to be temporarily disconnected. Some PROFIBUS connectors also include termination resistors for line termination.

Couplers – Provide one or several connection points to a network segment.

Repeaters – The PROFIBUS Physical Layer (RS-485) dictates that no more than 32 nodes can exist in a shielded twisted-pair (copper) segment. A node is defined as any station, active or passive, that is connected to the network. Media converters (copper to fiber-optic, fiber-optic to copper) and repeaters do not have PROFIBUS addresses and, therefore, are not included in the 126 possible addressable nodes.

RS-485 repeaters may be used to extend the recommended distance of a segment and “reform” the signal to full voltage levels. Repeaters are included in the total number of allowable nodes per segment; therefore, a segment that begins with a repeater and ends with a repeater may have 30 nodes between them. The maximum number of repeaters allowed in a PROFIBUS network is nine. (Refer to Figure 2.11.)

Terminators – Used at each end of a PROFIBUS segment to prevent signal reflections.

Power Supplies – Different types of power supplies can be used in a PROFIBUS network:

Non-intrinsically safe power supply.

Standard linear or switching power supply used with a power conditioner.

Intrinsically safe power supply (9-32 VDC; nominal 24 VDC for PA).

23

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

For cable connecting information on these components, refer to the following:

Installation Guidelines for PROFIBUS – FMS/DP Version 1.0, PROFIBUS International Order No. 2.112.

Technical Guideline: PROFIBUS PA User & Installation Guideline, Version 2.2, February 2003.

Figure 2.11 – PROFIBUS DP Segments

2.4  Site and Network Cable Preparation

2.4.1  Site Preparation

Prepare the installation site and associated equipment for operation of the MX/QX PB-controlled actuators as follows:

1.

Prepare a detailed site plan consisting of the following:

 

Actuator locations and tag numbers.

 

Junction boxes and terminal strip locations and tag numbers.

 

Terminators and power supplies/conditioners, and repeaters.

2.

Provide free access to the MX/QX control panel and terminal block for setup, configuration, and

 

troubleshooting.

3.

Prepare the cable and label all wires. See Section 2.4.2.

4.

Install power and control wires in separate conduits.

5.

Install and verify earth grounds. The cable shields should be tied together. Ground the bus shield

 

at the end of each segment. The MX/QX PB unit should not connect either conductor of the cable

 

to ground at any point in the network. Refer to Sections 2.2.4.1 and 2.2.5.1.

 

NOTE: An effective local earth ground is defined as a low impedance (less than 5 ohms) path to

24

either:

 

 

 

A ground electrode placed in the close vicinity of the actuator, free of any ground loop currents OR

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

A safety ground, free of ground loop currents, running from the actuator back to the system ground electrode. If the signal wiring is run on aerial cable where it may be exposed to high-energy electrostatic discharge (such as lightning), a low impedance path to ground which is capable of high current must be provided a short distance from the actuator as described above OR

A power distribution grid identifying the impact of power isolation to a particular actuator or group of actuators.

2.4.2  Network Cable Preparation

Care must be taken during cable preparation:

When stripping the insulation, use wire strippers that do not nick the wire.

Use crimp ferrules to prevent stranded wires from getting loose and shorting to other wires.

Use vibration-resistant wiring terminals that hold the ferrule securely.

2.4.2.1  Network Cable Connection to the MX/QX PB Unit

The field device is connected to the PROFIBUS network through the MX/QX terminal block.

The PROFIBUS DP network cable is connected to the terminal block as shown in Figure 2.12.

NOTE: The MX/QX PB DP device is sensitive to polarity. Cable polarity should be maintained through all connection points.

The PROFIBUS PA network cable is connected to the terminal block as shown in Figure 2.13.

NOTE: The MX/QX PB PA device is equipped with automatic polarity identification. It is not polarity sensitive.

Figure 2.12a – PROFIBUS DP Cable Connections to Terminal Blocks

Earth ground

3

Network data PBDP-A (-)

 

14

Network data PBDP-A (+)

IN

 

 

13

4

 

Network data PBDP-A (-)

OUT

Network data PBDP-A (+)

5

 

 

Figure 2.12b – PROFIBUS DP Cable Connections (Redundancy option with single master) to Terminal Blocks

Earth ground

 

 

 

 

 

 

 

 

3

 

 

Network data PBDP-A (-)

 

 

14

15

Note: External jumper connection required between

Network data PBDP-A (+)

IN

 

 

a) Terminals 14 & 15

 

 

16

b) Terminals 13 & 16

 

 

 

13

 

 

 

 

 

 

 

4

 

 

Network data PBDP-A (-)

 

 

 

OUT

Network data PBDP-A (+)

 

 

5

 

 

 

 

 

 

25

flowserve.com

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Figure 2.12c – PROFIBUS DP Cable Connections (Redundancy option with dual master) to Terminal Blocks

Earth ground

 

 

 

 

Network data PBDP

-A(-)

 

 

3

IN

 

14

Network data PBDP

-A(+)

 

 

13

 

 

 

 

 

 

 

4

OUT

 

 

 

5

 

 

 

 

Network data PBDP

-B(-)

OUT

 

1

Network data PBDP -B(+)

 

 

2

 

 

 

 

15

IN

16

 

Network data PBDP -A(-) Network data PBDP -A(+)

Network data PBDP -B(-) Network data PBDP -B(+)

Figure 2.13 – PROFIBUS PA Cable Connections to Terminal Blocks

Earth ground

 

3

Network data PBPA1(-)

4

Network data PBPA1(+)

5

 

14

Network data PBPA1(-)

Network data PBPA1(+)

13

 

26

PB DPV1 / PA Field Unit Installation and Maintenance  FCD LMENIM2336-03 – 12/12

Shielded twisted-pair cables in compliance to PROFIBUS standards must be used.

Shields are connected to earth ground. PB/DP connects at the ends of each segment.

PB/PA connects at only a single point in the segment.

Clean earth-ground connection (less than 5 ohms) provides noise protection and a clear, safe path for surge currents.

Prepare the network cable for connection to the MX/QX terminals as follows:

aCAUTION: Strip stranded conductors carefully, do not damage the strands. This will weaken the conductor and can cause the conductor to break. This type of damage may not be apparent and failure can occur without warning.

1.Remove two to three inches (5 to 8 cm) of the outer jacket of the cable as shown in Figure 2.14. Do not cut or nick the shield or the insulated conductors.

Figure 2.14 – Removing Outer Plastic Jacket

NOTE: Excess cable should be cut and removed, not coiled or looped, to prevent noise induction into the network.

2.Separate the cable parts. Unbraid the shield and peel back the shield to the same point where the outer jacket was removed as shown in Figure 2.15.

Figure 2.15 – Separating Cable Parts

27

flowserve.com

Loading...
+ 61 hidden pages