INSTALLATION
MANUAL
R22 SPLIT SERIES
Installation Manual |
English |
|
R22 Split Series |
||
|
||
|
|
MODELS
FDM20JEVLK RD20JEVLK
FDM25JEVLK RD25JEVLK
FDM30JEVLK RD30JEVLK
FDM40JEVLK RD40JEVLK
FDM50JEVLK RD50JETLK
FDM60JEVLK RD60JETLK
FDYM20JEVLK RYD20JEVLK
FDYM25JEVLK RYD25JEVLK
FDYM30JEVLK RYD30JEVLK
FDYM40JEVLK RYD40JEVLK
FDYM50JEVLK RYD50JETLK
FDYM60JEVLK RYD60JETLK
IM-CCC/E-0311(0)-DAIKIN (SASO)
Part No.: R08019036182
OUTLINE AND DIMENSIONS
Indoor Unit
All dimensions are in mm
B
|
|
|
|
D |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
C |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
I |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
J |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
K |
|
|
|
|
|
<![if ! IE]> <![endif]>H |
|
|
|
|
|
|
|
|
O |
|
|
|
<![if ! IE]> <![endif]>L |
|
|
|
E |
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
<![if ! IE]> <![endif]>A |
|
|
M |
N |
|
|
|
G |
|
|
|
|
|
|
|
|
|
|
|
|
F |
|
|
|
|
|
|
|
|
|
|
|
|
Dimension |
A B C D E F G H |
I |
J K L M N O |
|||||||||||||
Model |
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
FD(Y)M20JEVLK |
31 |
1041 |
1002 |
962 |
10 |
1065 |
72 |
261 |
411 |
351 |
225 |
211 |
232 |
213 |
114 |
|
FD(Y)M25JEVLK |
31 |
1176 |
1137 |
1097 |
10 |
1200 |
72 |
261 |
411 |
351 |
225 |
211 |
232 |
213 |
114 |
Indoor Unit
K |
|
All dimensions are in mm |
|
|
|
|
|
|
|
|
|
|
|
|
|
<![endif]>J
|
I |
|
|
|
H |
|
|
|
|
|
L |
|
|
|
M |
|
|
<![if ! IE]> <![endif]>G |
<![if ! IE]> <![endif]>N |
<![if ! IE]> <![endif]>B |
|
<![if ! IE]> <![endif]>P |
|
<![if ! IE]> <![endif]>A |
|
|
|
D |
E |
F |
<![if ! IE]> <![endif]>O |
|
|||
|
C |
|
|
Dimension |
A |
B |
C |
D |
E |
F |
G |
H |
I |
J |
K |
L |
M |
N |
O |
P |
|
Model |
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
FD(Y)M30JEVLK |
40 |
292 |
1295 |
232 |
213 |
70 |
128 |
1228 |
1185 |
284 |
1262 |
460 |
420 |
241 |
12 |
230 |
|
FD(Y)M40JEVLK |
|||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
<![endif]>Original Instruction English
1-1
Indoor Unit
All dimensions are in mm
E E
K |
A |
A |
K |
|
|
B |
|
|
|
C |
|
G
|
D |
H |
<![if ! IE]> <![endif]>L |
|
<![if ! IE]> <![endif]>I |
|
<![if ! IE]> <![endif]>F |
<![if ! IE]> <![endif]>J |
M |
N |
|
Dimension |
A |
B |
C |
D |
E |
F |
G |
H |
I |
J |
K |
L |
M |
N |
|
Model |
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
FD(Y)M50JEVLK |
359 |
1369 |
1326 |
1287 |
594 |
384 |
541 |
256 |
173 |
306 |
256 |
161 |
248 |
220 |
|
FD(Y)M60JEVLK |
359 |
1569 |
1526 |
1487 |
694 |
378 |
541 |
256 |
173 |
306 |
356 |
161 |
248 |
220 |
Outdoor Unit
L K L
<![if ! IE]><![endif]>M T N
All dimensions are in mm
A
O D
<![if ! IE]><![endif]>P
<![if ! IE]><![endif]>B
<![if ! IE]><![endif]>Q
<![if ! IE]> <![endif]>N |
C |
|
G H
<![if ! IE]><![endif]>E F
<![if ! IE]><![endif]>R S
I J
Dimension |
A |
B |
C |
D |
E |
F |
G |
H |
I |
J |
K |
L |
M |
N |
O |
P |
Q |
R |
S |
T |
|
Model |
|||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
R(Y)D20JEVLK |
855 |
628 |
328 |
508 |
181 |
44 |
93 |
149 |
101 |
113 |
603 |
126 |
164 |
15 |
49 |
3 |
23 |
73 |
75 |
362 |
|
R(Y)D25JEVLK |
855 |
730 |
328 |
520 |
182 |
44 |
93 |
149 |
101 |
113 |
603 |
126 |
164 |
15 |
34 |
3 |
23 |
73 |
75 |
362 |
|
R(Y)D30JEVLK |
855 |
730 |
328 |
513 |
182 |
44 |
93 |
149 |
101 |
113 |
603 |
126 |
164 |
15 |
47 |
3 |
23 |
73 |
75 |
362 |
1-2
Outdoor Unit
All dimensions are in mm
A
N M
P
<![if ! IE]><![endif]>L
<![if ! IE]><![endif]>K
|
|
C |
|
|
D |
T |
|
|
|
||
<![if ! IE]> <![endif]>B |
<![if ! IE]> <![endif]>F |
|
|
|
R |
|
|
|
<![if ! IE]> <![endif]>E |
|
|
|
G |
<![if ! IE]> <![endif]>H |
|
|
<![if ! IE]> <![endif]>S |
||
|
U |
|
|
|
Q |
J |
|
|
|
||
Dimension |
A B C D E F G H J K L M N P Q R S T U |
||
Model |
|||
|
|
R(Y)D40JEVLK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R(Y)D50JETLK |
1030 |
852 |
428 |
410 |
412 |
827 |
72 |
196 |
91 |
488 |
448 |
142 |
141 |
83 |
23 |
49 |
26 |
28 |
80 |
R(Y)D60JETLK |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
<![endif]>English
1-3
INSTALLATION MANUAL
This manual provides the procedures of installation to ensure a safe and good standard of operation for the air conditioner unit.
Special adjustment may be necessary to suit local requirements.
Before using your air conditioner, please read this instruction manual carefully and keep it for future reference. This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for commercial use by lay persons.
SAFETY PRECAUTIONS
!WARNING
•Installation and maintenance should be performed by qualiÀed persons who are familiar with local code and regulation, and experienced with this type of appliance.
•All Àeld wiring must be installed in accordance with the national wiring regulation.
•Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring work according to the wiring diagram.
•The unit must be GROUNDED to prevent possible hazard due to insulation failure.
•All electrical wiring must not touch the refrigerant piping, or any moving parts of the fan motors.
•ConÀrm that the unit has been switched OFF before installing or servicing the unit.
•Disconnect from the main power supply before servicing the air conditioner unit.
•DO NOT pull out the power cord when the power is ON. This may cause serious electrical shocks which may result in Àre hazards.
•Keep the indoor and outdoor units, power cable and transmission wiring, at least 1m from TVs and radios, to prevent distorted pictures and static. (Depending on the type and source of the electrical waves, static may be heard even when more than 1m away).
! CAUTION
Please take note of the following important points when installing.
•Do not install the unit where leakage of Áammable gas may occur.
If gas leaks and accumulates around the unit, it may cause Àre ignition.
•Ensure that drainage piping is connected properly.
If the drainage piping is not connected properly, it may cause water leakage which will dampen the furniture.
• Do not overcharge the unit.
This unit is factory pre-charged.
Overcharge will cause over-current or damage to the compressor.
•Ensure that the unit·s panel is closed after service or installation.
Unsecured panels will cause the unit to operate noisily.
•Sharp edges and coil surfaces are potential locations which may cause injury hazards.
Avoid from being in contact with these places.
•Before turning off the power supply, set the remote controller·s ON/OFF switch to the “OFF” position to prevent the nuisance tripping of the unit. If this is not done, the unit·s fans will start turning automatically when power resumes, posing a hazard to service personnel or the user.
•Do not install the units at or near doorway.
•Do not operate any heating apparatus too close to the air conditioner unit or use in room where mineral oil, oil vapour or oil steam exist, this may cause plastic part to melt or deform as a result of excessive heat or chemical reaction.
•When the unit is used in kitchen, keep Áour away from going into suction of the unit.
•This unit is not suitable for factory used where cutting oil mist or iron powder exist or voltage Áuctuates greatly.
•Do not install the units at area like hot spring or oil reÀnery plant where sulphide gas exists.
•Ensure the color of wires of the outdoor unit and the terminal markings are same to the indoors respectively.
•IMPORTANT: DO NOT INSTALL OR USE THE AIR CONDITIONER UNIT IN A LAUNDRY ROOM.
•Don·t use joined and twisted wires for incoming power supply.
•The equipment is not intended for use in a potentially explosive atmosphere.
NOTICE
Disposal requirements
Your air conditioning product is marked with this symbol. This means that electrical and electronic products shall not be mixed with unsorted household waste.
Do not try to dismantle the system yourself: the dismantling of the air conditioning system, treatment of the refrigerant, of oil and of other parts must be done by a qualiÀed installer in accordance with relevant local and national legislation.
Air conditioners must be treated at a specialized treatment facility for re-use, recycling and recovery. By ensuring this product is disposed of correctly, you will help to prevent potential negative consequences for the environment and human health. Please contact the installer or local authority for more information.
Batteries must be removed from the remote controller and disposed of separately in accordance with relevant local and national legislation.
1-4
IMPORTANT & SEQUENCE AS FOLLOW:
For model FD(Y)M20JEVLK & FD(Y)M25JEVLK:
2) Left Cushion
3) Right Cushion
4) Indoor Unit
1) Carton Box
UNPACKING
1)After take off the bands, lift the unit out from the carton box
2)Remove the right and left cushion.
For model FD(Y)M30JEVLK & FD(Y)M40JEVLK:
1) Carton Box
<![endif]>English
2) Top Carton
3) Indoor Unit
4) Bottom Carton
UNPACKING
1)After take off the bands, lift the carton box
2)Remove the top cushion.
3)Lift the unit and remove the bottom carton.
1-5
For model FR(Y)M50JEVLK & FD(Y)M60JEVLK:
1) Carton Box
2) Top Cushion
3) Indoor Unit
4) Packing bottom
UNPACKING
1)After take off the bands, lift the carton box
2)Remove the top cushion.
3)Lift the unit and remove the bottom carton.
For model R(Y)D20JEVLK, R(Y)D25JEVLK, R(Y)D30JEVLK, R(Y)D40JEVLK, R(Y)D50JETLK & R(Y)D60JETLK:
1. After take off the bands, pull out the carton box from the top side of the unit.
* This product is not designed for re-packing. In case of re-packing, contact to Daikin Dealer. 1-6
INSTALLATION DIAGRAM
Indoor unit
Hanger
Return Duct
Supply Duct
Wrap the insulated pipe with the Ànishing tape from bottom to top
Drain Piping |
Thermal Insulation |
Air Intake
Air Intake
Air Discharge
Outdoor unit
<![endif]>English
1-7