DAIKIN FWEC2 User Manual

4.5 (2)

INSTALLATION AND OPERATION MANUAL

Advanced electronic controller

Manuale d'installazione e d'uso

FWEC2 COMANDO LCD PER TERMINALI

Installation and operation manual FWEC2 LCD CONTROLLER FOR INDOOR UNITS

Manuel d'installation et d'utilisation FWEC2 CONTRÔLEUR LCD POUR UNITÉS TERMINALES

Installationsund Bedienungsanleitung

FWEC2 LCD-STEUERUNG FÜR TERMINALS

Manual de instalación y de uso

FWEC2 MANDO LCD PARA TERMINALES

Manual de instalação e de uso

FWEC2 COMANDO LCD PARA TERMINAIS

Handleiding voor gebruik en onderhoud

FWEC2 LCD BEDIENING VOOR TERMINALS

BESZERELÉSI ÉS FELHASZNÁLÓI KÉZIKÖNYV

FWEC2 LCD VEZÉRLŐ TERMINÁLOKHOZ

РУКОВОДСТВО ПО УСТАНОВКЕ И ЭКСПЛУАТАЦИИ FWEC2 LCD (LCD) ПАНЕЛЬ УПРАВЛЕНИЯ ДЛЯ ТЕРМИНАЛОВ

Italiano

English

Français

Deutsch

Español

Portugues

Nederlands

Hungarian

русский

FWEC2 LCD

1

 

2

 

 

 

3

 

4

 

 

 

5

6

 

7

 

 

 

8

 

9

 

 

 

DAIKIN FWEC2 User Manual

NOTES

FWEC2

Advanced electronic controller

Manuale d'installazione e d'uso

CARATTERISTICHE GENERALI

Il comando LCD è progettato per comandare tutti i terminali d'impianto con motore asincrono monofase plurivelocità. Rispetto alla versione standard è presente una gestione avanzata dell'umidità e la comunicazione seriale.

La soluzione (figura 1), realizza un sistema Master-Slave (fino a 247 terminali slave), in cui uno dei comandi svolge la funzione di Master e controlla tutti gli altri elementi slave.

La connessione si realizza mediante il bus RS485, costituito da un semplice cavo schermato a 2 conduttori.

Il master (che è identificato dall'indirizzo 255), invia ai comandi slave le seguenti informazioni:

(1)Modalità di funzionamento (Raffreddamento o riscaldamento)

(2)Set point per la temperatura ambiente.

Ciascun comando Slave mantiene la gestione del selettore delle velocità e la regolazione della temperatura ambiente è consentita con un delta di ± 2°C intorno al valore del set point inviato dal comando master

FUNZIONI PRINCIPALI E DOTAZIONE:

Regolazione della temperatura dell'aria tramite variazione automatica della velocità del ventilatore.

Regolazione della temperatura dell'aria tramite on-off del ventilatore ad una velocità fissa.

Gestione di valvole On/Off per impianti a due o quattro tubi.

Gestione di resistenza per supporto in riscaldamento.

Commutazione Raffreddamento/Riscaldamento nelle seguenti modalità:

-manuale a bordo

-manuale a distanza (centralizzato)

-automatica, in funzione della temperatura dell'acqua

-automatica, in funzione della temperatura dell'aria

Funzione di Deumidifica

Comunicazione Seriale

INOLTRE È DOTATO DI:

contatto pulito per consenso esterno (ad esempio; contatto finestra, ON/OFF remoto, sensore di presenza ecc.) che può abilitare o disabilitare il funzionamento dell'unità (logica contatto: vedi parametri configurazione scheda).

contatto pulito per commutazione Raffreddamento/ Riscaldamento remota centralizzata (logica contatto: vedi parametri configurazione scheda).

contatto pulito per l'abilitazione della funzione economy da remoto (logica contatto: vedi parametri configurazione scheda).

sonda remota di temperatura per l'acqua (accessorio).

sonda di temperatura interna

sonda di umidità interna

sonda remota di temperatura per l'aria (accessorio) (tale sonda, se presente, viene utilizzata al posto di quella interna, per la lettura della temperatura ambiente).

Sonda remota di umidità (accessorio - da utilizzare in abbinamento alla sonda remota di temperatura)

Il pannello di comando è composto da:

display LCD

tastiera

DISPLAY LCD (VEDI FIGURA 2)

(1)temperatura ambiente

(2)umidità ambiente

(3)temperatura impostata

ON

stato ventilatori. Se lampeggiante indica ventilatori

 

 

fermi in attesa di chiamata del termostato.

 

 

Se simbolo acceso fisso indica ventilatori in

 

 

funzione

 

OFF

stato ventilatori. Ventilatori fermi in seguito alla

 

 

velocità impostata su Off o al comando spento

 

AUTO

logica ventilazione automatica

 

 

velocità ventilatore

 

 

modalità di funzionamento: Raffreddamento.Se

 

 

lampeggiante indica la mancanza del consenso

 

 

acqua al funzionamento della ventilazione.

 

 

modalità di funzionamento: Riscaldamento. Se

 

 

lampeggiante indica la mancanza del consenso

 

 

acqua al funzionamento della ventilazione.

 

 

Deumidifica. Se lampeggiante indica la mancanza

 

 

di consenso per la deumidificazione; con simbolo

 

 

acceso fisso indica invece che tale funzione è

 

 

attiva

 

 

opzione Economy attiva

 

 

presenza di allarme

 

 

 

 

controllo Minima Temperatura

 

 

valvola aperta

 

 

resistenza elettrica. Con simbolo lampeggiante

 

 

 

 

indica resistenza in funzione; con simbolo acceso

 

 

fisso indica solamente resistenza selezionata

 

 

comunicazione seriale attiva. Il simbolo lampeg-

 

 

 

 

giante indica che il comando è il master

 

TASTIERA (VEDI FIGURA 3)

tastoOn/Off:accensione/spegnimentotermostato. Durantelaproceduradimodificaparametripermette di tornare al funzionamento normale

tasti Up e Down: modifica della temperatura di regolazione del termostato (Riscaldamento:[5.0- 30.0°C], Raffreddamento: [10.0-35.0°C]). Durante la procedura di modifica parametri vengono utilizzati per selezionare i parametri o modificarne il valore

tasto SEL: in modalità Riscaldamento selezione della resistenza elettrica come funzione ausiliaria

tasto Mode: selezione della modalità di funzionamento Riscaldamento / Raffreddamento

tasto Fan: selezione della velocità di funzionamento

tasto EC: selezione modalità Economy

FWEC2

Manuale d'installazione e d'uso

Advanced electronic controller

1

FC66002764

COMBINAZIONI DI TASTI ATTIVE

Con termostato in Off: accesso alla procedura di configurazione parametri

Con termostato in On: visualizza momentanea della temperatura dell'acqua

Selezione della funzione minima temperatura aria

Selezione deumidifica

CONFIGURAZIONE SCHEDA

La scheda è configurabile in base al tipo di terminale/impianto da gestire, attraverso la modifica di alcuni parametri.

LISTA PARAMETRI

P00 = configurazione comando (vedi "Configurazioni Previste") per selezionare il tipo di terminale da gestire.

P01 = tipo di installazione del comando -000: bordo terminale

-001: parete

P02 = indirizzo Modbus (per rendere attiva la modifica di tale parametro (escluso il caso di passaggio interno tra valori) è necessario togliere e ridare alimentazione alla fine della programmazione)

-0: disabilitata la comunicazione seriale -1-247: slave

-255: master

P03 = zona neutra [20-50°C/10]; parametro utilizzato in caso di configurazioni con commutazione raffreddamento/ riscaldamento automatica in funzione della temperatura dell'aria.

P04 = sonda acqua: -0: non prevista

-1: prevista

In base al valore impostato verrà gestito opportunamente il relativo allarme sonda e consenso per la resistenza elettrica

P05 = Logica di configurazione utilizzo ingressi digitali 1

 

e 2:

 

 

 

 

 

 

-

0:

DIN1 = -

DIN2 = -

 

-

1:

DIN1 = -

DIN2 = OnOff

 

-

2:

DIN1 = Est/Inv

DIN2 = -

 

 

-

3:

DIN1 = Eco

DIN2 = -

 

-

4:

DIN1 = Est/Inv

DIN2 = On/Off

 

-

5:

DIN1 = Eco

DIN2 = On/Off

 

-

6:

DIN1 = Est/Inv

DIN2 = Eco

 

P06 = logica di utilizzo ingresso digitale 1:

-0: [aperto/chiuso] = [Raffred./Riscald] = [-/ECO]

-1: [aperto/chiuso] = [Riscald./Raffred] = [ECO/-]

P07 = logica di utilizzo ingresso digitale 2:

-0: [aperto/chiuso] = [Off/On] = [-/ECO]

-1: [aperto/chiuso] = [On/Off] = [ECO/-]

P08 = sonda umidità remota:

-0 : non prevista

-1 : prevista

In base al valore impostato verrà eventualmente gestito il relativo allarme sonda.

PROCEDURA DI CONFIGURAZIONE

PARAMETRI

■ Mettere in OFF il termostato

■ Premere contemporaneamente i tasti

Indicazione livello:

001= inserimento password

Utilizzare i tasti per modificare il valore del display

fino al valore di password 10, quindi premere . Se corretta si avrà accesso ai parametri

Valore parametro

 

 

selezionato

 

 

 

Indicazione livello:

 

 

 

 

 

 

Parametro

 

 

 

002= selezione

 

 

 

password

selezionato: P...

 

 

 

Utilizzare i tasti per scorrere i vari parametri (vedi "Lista Parametri" sopra descritta)

Premere per attivare la modifica del parametro (il valore comincerà a lampeggiare)

Indicazione livello:

003 = modifica parametro

Utilizzare i tasti per modificare il valore

Premere per salvare il nuovo valore impostato o per annullare la modifica

Una volta conclusa la modifica di parametri interessati premere il tasto per uscire dalla procedura

NB: la procedura di parametrizzazione ha una durata limitata. Una volta scaduto tale periodo (2 minuti circa) il termostato verrà riportato allo stato Off mantenendo solo le modifiche salvate.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manuale d'installazione e d'uso

FWEC2

 

 

 

 

 

 

 

2

Advanced electronic controller

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONFIGURAZIONI PREVISTE (PARAMETRO P00)

Il comando LCD può essere configurato in diversi modi in base al tipo di sistema. Le varie configurazioni si ottengono configurandoopportunamenteilparametroP00 (vediprocedura di configurazione parametri comando).

001

Tubi impianto: 2

Valvola: NO

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: LOCALE MANUALE

002

Tubi impianto: 2

Valvola: NO

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: DISTANZA MANUALE

003

Tubi impianto: 2

Valvola: NO

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: AUTOMATICO

LATO ACQUA

004

Tubi impianto: 2

Valvola: NO

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: LOCALE MANUALE

005

Tubi impianto: 2

Valvola: NO

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: DISTANZA MANUALE

006

Tubi impianto: 2

Valvola: NO

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: AUTOMATICO

LATO ACQUA

007

Tubi impianto: 2

Valvola: NO

Resistenza: SI

Velocità ventilazione: 3

Logica commutazione estate/inverno: LOCALE MANUALE

008

Tubi impianto: 2

Valvola: NO

Resistenza: SI

Velocità ventilazione: 3

Logica commutazione estate/inverno: DISTANZA MANUALE

009

Tubi impianto: 2

Valvola: NO

Resistenza: SI

Velocità ventilazione: 3

Logica commutazione estate/inverno: AUTOMATICO

LATO ARIA

010

Tubi impianto: 2

Valvola: NO

Resistenza: SI

Velocità ventilazione: 4

Logica commutazione estate/inverno: LOCALE MANUALE

011

Tubi impianto: 2

Valvola: NO

Resistenza: SI

Velocità ventilazione: 4

Logica commutazione estate/inverno: DISTANZA MANUALE

012

Tubi impianto: 2

Valvola: NO

Resistenza: SI

Velocità ventilazione: 4

Logica commutazione estate/inverno: AUTOMATICO

LATO ARIA

013

Tubi impianto: 2

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: LOCALE MANUALE

014

Tubi impianto: 2

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: DISTANZA MANUALE

015

Tubi impianto: 2

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: AUTOMATICO

LATO ACQUA

016

Tubi impianto: 2

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: LOCALE MANUALE

017

Tubi impianto: 2

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: DISTANZA MANUALE

FWEC2

Manuale d'installazione e d'uso

Advanced electronic controller

3

FC66002764

CONFIGURAZIONI PREVISTE (PARAMETRO P00)

018

Tubi impianto: 2

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: AUTOMATICO

LATO ACQUA

019

Tubi impianto: 2

Valvola: 3 VIE

Resistenza: SI

Velocità ventilazione: 3

Logica commutazione estate/inverno: LOCALE MANUALE

020

Tubi impianto: 2

Valvola: 3 VIE

Resistenza: SI

Velocità ventilazione: 3

Logica commutazione estate/inverno: DISTANZA MANUALE

021

Tubi impianto: 2

Valvola: 3 VIE

Resistenza: SI

Velocità ventilazione: 3

Logica commutazione estate/inverno: AUTOMATICO

LATO ARIA

022

Tubi impianto: 2

Valvola: 3 vie

Resistenza: SI

Velocità ventilazione: 4

Logica commutazione estate/inverno: LOCALE MANUALE

023

Tubi impianto: 2

Valvola: 3 VIE

Resistenza: SI

Velocità ventilazione: 4

Logica commutazione estate/inverno: DISTANZA MANUALE

024

Tubi impianto: 2

Valvola: 3 VIE

Resistenza: SI

Velocità ventilazione: 4

Logica commutazione estate/inverno: AUTOMATICO

LATO ARIA

025

Tubi impianto: 4

Valvola: NO

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: LOCALE MANUALE

026

Tubi impianto: 4

Valvola: NO

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: DISTANZA MANUALE

027

Tubi impianto: 4

Valvola: NO

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: AUTOMATICO

LATO ARIA

028

Tubi impianto: 4

Valvola: NO

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: LOCALE MANUALE

029

Tubi impianto: 4

Valvola: NO

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: DISTANZA MANUALE

030

Tubi impianto: 4

Valvola: NO

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: AUTOMATICO

LATO ARIA

031

Tubi impianto: 4

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: LOCALE MANUALE

032

Tubi impianto: 4

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: DISTANZA MANUALE

033

Tubi impianto: 4

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 3

Logica commutazione estate/inverno: AUTOMATICO

LATO ARIA

034

Tubi impianto: 4

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: LOCALE MANUALE

Manuale d'installazione e d'uso

FWEC2

4

Advanced electronic controller

FC66002764

CONFIGURAZIONI PREVISTE (PARAMETRO P00)

035

Tubi impianto: 4

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: DISTANZA MANUALE

036

Tubi impianto: 4

Valvola: 2/3 VIE

Resistenza: NO

Velocità ventilazione: 4

Logica commutazione estate/inverno: AUTOMATICO

LATO ARIA

037

Tubi impianto: 4

Valvola: NO

Resistenza: SI

Velocità ventilazione: 3

Logica commutazione estate/inverno: LOCALE MANUALE

038

Tubi impianto: 4

Valvola: NO

Resistenza: SI

Velocità ventilazione: 4

Logica commutazione estate/inverno: LOCALE MANUALE

COMUNICAZIONE SERIALE

Collegamento alla rete di comunicazione RS485

La rete di comunicazione, tipologia Bus, è costituita da un semplice cavo schermato a 2 conduttori, connesso direttamente alle porte seriali RS485 dei comandi (morsetti A, B e GND).

"Per la realizzazione della rete utilizzare cavo AWG 24 (diam. 0,511 mm)"

La rete di comunicazione deve avere la seguente struttura generale (figura 4).

Nel caso di soluzione "MASTER-SLAVE" dovrà essere installata una resistenza di terminazione su entrambi i comandi agli estremi della rete.

NB: (1) Rispettare la polarità della connessione: indicata con A(-) e B(+)

(2) Evitare anelli di massa (schermatura a terra solo ad una estremità)

____________________________________________________________

ATTENZIONE:

Utilizzare cavo schermato AWG24

Colori suggeriti per la rete di comunicazione: A

(-) colore Marrone; B (+) colore Giallo

____________________________________________________________

LOGICHE

COMMUTAZIONE RAFFREDDAMENTO/RISCALDAMENTO

Sono presenti 4 differenti logiche di selezione della modalità di funzionamento del termostato definite in base alla configurazione impostata sul comando:

1.Locale: scelta dall'utente agendo sul tasto

2.Distanza: in funzione dello stato dell'ingresso digitale DI1 (logica contatto: vedi parametri configurazione scheda)

3.In funzione della temperatura dell'acqua

Estate

Inverno

Temp. acqua

NB: nel caso di allarme sonda acqua il controllo della modalità torna temporaneamente nella modalità Locale.

4. in funzione della temperatura dell'aria:

Estate

Inverno

Temp. aria

Dove:

Set è la temperatura impostata con le frecce

ZN è la zona neutra (parametro P03)

La modalità di funzionamento del termostato è indicata sul

display dai simboli (raffreddamento) e (riscaldamento)

VENTILAZIONE

Il controllo può gestire terminali a 3 o 4 velocità

SELEZIONE VELOCITÀ FUNZIONAMENTO

Utilizzando il tasto Fan è possibile scegliere fra le seguenti velocità:

Vel. automatica: in funzione della temperatura impostata e quella dell'aria ambiente

Con configurazioni a 3 velocità :

dove:

1 = velocità minima

2 = velocità media

3 = velocità massima

RAFFREDDAMENTO

RISCALDAMENTO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Manuale d'installazione e d'uso

 

 

 

 

 

 

 

Advanced electronic controller

5

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Con configurazioni a 4 velocità dove:

sm = velocità superminima 1 = velocità minima

2 = velocità media

3 = velocità massima

RAFFREDDAMENTO

Temp. aria

RISCALDAMENTO

Temp. aria

NB: nelle configurazioni con 4 velocità e valvola, la ventilazione in riscaldamento viene ritardata di 0.5°C per consentire una prima fase di convezione naturale

Vel. disattivata: selezionabile solo in riscaldamento e con configurazioni a 4 velocità, fa funzionare il terminale in sola convezione naturale

 

Vel. superminima: selezionabile solo con con-

 

 

figurazioni a 4 velocità, utilizza come velocità

 

 

fissa la superminima

 

Vel. minima

 

Vel. media

 

 

Vel. massima

NB: nel caso di velocità fissa la logica di attivazione del ventilatore sarà pari a quella della logica automatica

CONSENSO DELL'ACQUA

Il funzionamento della ventilazione è vincolato al controllo della temperatura acqua dell'impianto. In base alla modalità di lavoro avremo differenti soglie di consenso in riscaldamento e raffreddamento

RAFFREDDAMENTO

NO

Temp. acqua

RISCALDAMENTO

NO

Temp. acqua

L'assenza di tale consenso, alla chiamata del termostato, verrà indicata sul display con il lampeggio del simbolo della

modalità attiva ( o )

Tale consenso viene ignorato in caso di:

sonda acqua non prevista (P04 = 0) o in allarme perché scollegata

in Raffreddamento con configurazioni a 4 tubi

LOGICHE

FORZATURE

La normale logica di ventilazione verrà ignorata nel caso di particolari situazioni di forzatura che possono essere necessarie per il corretto controllo della temperatura o funzionamento del terminale. Si possono avere:

In Raffreddamento:

con comando a bordo macchina (P01 = 0) e configurazioni con valvola: viene mantenuta la minima velocità disponibile anche a temperatura raggiunta.

comando a bordo e configurazioni senza valvola: ogni 10minuti di ventilatore fermo viene eseguito un lavaggio di 2 minuti alla velocità media per permettere alla sonda aria una lettura più corretta della temperatura ambiente.

In Riscaldamento

con resistenza attiva: viene forzata la ventilazione alla velocità media.

una volta spenta la resistenza: viene mantenuta, per 2 minuti, una post ventilazione alla velocità media. (NB: tale ventilazione verrà completata anche se il termostato dovesse venir spento o si passasse alla modalità raffreddamento)

DISPLAY

Il display visualizza lo stato del ventilatore

On lampeggiante: ventilatore in standby

On fisso: ventilatore acceso

OFF: ventilatore disattivato per lavorare in sola convezione naturale

e la velocità di funzionamento (con eventuale indicazione della logica "automatica") attiva o selezionata (nel caso di ventilatore in stand-by)

Vel. superminima

Vel. minima

Vel. media

Vel. massima

NB: nel caso la velocità attiva sia diversa da quella selezionata da utente (in caso di forzatura..), una prima pressione del tasto Fan visualizzerà quest'ultima; una pressione successiva cambierà tale impostazione.

Manuale d'installazione e d'uso

FWEC2

6

Advanced electronic controller

FC66002764

VALVOLA

Il controllo può gestire valvole a 2 o 3 vie di tipo ON OFF con tensione di alimentazione 230V

APERTURA

L'apertura della valvola viene comandata in funzione del set di lavoro e della temperatura dell'aria

RAFFREDDAMENTO

Temp. aria

RISCALDAMENTO

Temp. aria

CONSENSO DELL'ACQUA

Il controllo della temperatura dell'acqua per il consenso all'apertura interessa solo configurazioni con valvole a 3 vie e resistenza elettrica.

In tali configurazioni verrà fatto un controllo della temperatura dell'acqua in caso di:

Riscaldamento con resistenza: il funzionamento della resistenza comporta una forzatura della ventilazione; è necessario quindi evitare l'eventuale passaggio di acqua troppo fredda nel terminale.

Temp. acqua

Post ventilazione dovuta allo spegnimento resistenza: mantenuta fino allo scadere del tempo stabilito, anche nel caso di cambio della modalità di funzionamento. Durante tale post ventilazione il consenso dell'acqua coinciderà con quello visto per la ventilazione.

DISPLAY

L'indicazione di valvola attiva sul display sarà data dal simbolo

RESISTENZA ELETTRICA

La resistenza elettrica è un dispositivo gestito come eventuale supporto nella fase di riscaldamento.

SELEZIONE

Se prevista dalla configurazione la resistenza può essere selezionata in riscaldamento tramite il tasto Sel

ATTIVAZIONE

Temp. aria

L'utilizzo della resistenza elettrica, se selezionata da utente, viene utilizzata su chiamata del termostato in base alla temperatura ambiente

NB: l'attivazione comporta una forzatura della ventilazione

CONSENSO DELL'ACQUA

Il consenso per l'attivazione della resistenza è legato al controllo della temperatura dell'acqua. Di seguito la logica di consenso relativa

Tale consenso non verrà dato nel caso di sonda dell'acqua non prevista o scollegata

RISCALDAMENTO

ON

OFF

Temp. acqua

DISPLAY

Il display visualizzerà le seguenti informazioni

Resistenza selezionata da utente: simbolo fisso

Resistenza attiva: simbolo lampeggiante

ECONOMY

La funzione Economy prevede una correzione del setpoint di 2.5°C e una forzatura alla minima velocità disponibile per ridurre il funzionamento del terminale.

Raffreddamento: set + 2.5°C

Riscaldamento: set - 2.5°C

ATTIVAZIONE

La funzione è attivabile con la pressione del tasto

DISPLAY

Sul display la funzione Economy è indicata da simbolo

CONTROLLO MINIMA TEMPERATURA

Tale logica permette di controllare, con termostato spento, che la temperatura ambiente non scenda troppo, forzando eventualmente il terminale in modalità riscaldamento per il tempo necessario.

Se presente la resistenza elettrica essa verrà utilizzata solo nel caso in cui fosse stata precedentemente selezionata come risorsa in Riscaldamento.

SELEZIONE

Il controllo Minima Temperatura è selezionabile, a termostato

spento, con la pressione contemporanea dei tasti . La stessa combinazione di tasti disattiva tale funzionamento

ATTIVAZIONE

Se tale controllo è selezionato, il terminale si accenderà nel caso in cui la temperatura ambiente scenda al di sotto dei

9°C.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Manuale d'installazione e d'uso

 

 

 

 

 

 

 

Advanced electronic controller

7

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temp. aria

Una volta riportata la temperatura sopra i 10°C il termostato ritornerà nella situazione di Off.

NB: un eventuale Off da ingresso digitale inibirà tale logica.

DISPLAY

Il display visualizza le seguenti informazioni

Controllo Minima Temperatura selezionato: simbolo

Controllo Minima Temperatura attivo: indicazione DEFR

DEUMIDIFICA

La funzione di deumidifica, utilizzabile nella sola modalità raffreddamento, prevede di far funzionare il terminale con lo scopo di ridurre del 10% l'umidità presente in ambiente al momento della selezione della funzione stessa

SELEZIONE

Il deumidifica è selezionabile/deselezionabile, in Raffreddamento,

con la pressione contemporanea dei tasti . Con sonda acqua non prevista (P04=0) o mancanza di sonda d'umidità remota nel caso di installazioni a bordo (P08=0) tale selezione non sarà consentita. Se selezionata, la zona neutra per la commutazione automatica lato aria è forzata a 5°

LOGICA

Una volta selezionata, la logica di Deumidifica imposta come set di umidità da raggiungere l'umidità presente al momento della selezione meno il 10%. In caso di umidità ambiente inferiore al 40% il set di riferimento verrà impostato al 30%. La velocità di ventilazione verrà forzata alla minima o, nel caso di temperatura molto superiore al set impostato, alla media velocità

Velocità media

Velocità minima

Dovendo portare l'umidità al valore impostato la ventilazione (e la valvola, se presente) verrà attivata anche nel caso in cui la temperatura ambiente abbia già raggiunto il set relativo (visibile sul display dal simbolo 3. Nel caso si scenda troppo al di sotto di tale soglia tale logica verrà momentaneamente inibita.

Inibita

Temp. aria

CONSENSO DELL'ACQUA

Il consenso per l'attivazione della deumidifica è legato al controllo della temperatura dell'acqua. Di seguito la logica di consenso relativa

Temp. acqua

Il mancato consenso prevede l'inibizione momentanea della logica di deumidifica.

Lo stesso verrà fatto nel caso la sonda venga scollegata.

NB: una volta raggiunta l'umidità di riferimento o messo in Off il comando, la deumidifica verrà deselezionata

DISPLAY

Il display visualizza le seguenti informazioni:

Deumidifica attiva: simbolo acceso

Deumidifica momentaneamente inibita: simbolo lampeggiante

ALLARMI

Il comando gestisce due tipologie di allarmi:

Allarmi Gravi: causano lo spegnimento forzato del termostato

Allarmi Non Gravi: non forzano lo spegnimento del termostato ma inibiscono eventuali funzionalità critiche

ALLARMI GRAVI

Codice allarme

Cod. A01 = errore sonda esterna di temperatura dell'aria (se termostato installato a Bordo)

Cod. A02 = errore sonda interna di temperatura dell'aria (se termostato installato a Parete e sonda esterna di temperatura dell'aria sconnessa)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manuale d'installazione e d'uso

FWEC2

 

 

 

 

 

 

 

8

Advanced electronic controller

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALLARMI NON GRAVI

Termostato OFF

Termostato ON

Cod. A03 = errore sonda di temperatura dell'acqua

Cod A04= errore sonda umidità esterna (solo se sonda di temperatura remota installata)

Cod A05 = errore sonda umidità interna

NB: l'indicazione del codice allarme è visualizzato solo con termostato spento

MODBUS

Il protocollo implementato nel comando è il Modbus RTU (9600, N, 8, 2) su RS485

FUNZIONI IMPLEMENTATE

0x03 : Read Holding Registers

0x04 : Read Input Registers

0x10 : Write Multiple registers

ECCEZIONI IMPLEMENTATE

Exception Code 02: Invalidate data address

LISTA PARAMETRI DI SUPERVISIONE

INDIRIZZO

REGISTRO

TIPO

U.D.M.

 

 

 

 

0

Stati

R

-

 

 

 

 

1

Velocità

R

-

 

 

 

 

2

Temperatura aria

R

[°C/10]

 

 

 

 

3

Umidità

R

%

 

 

 

 

4

Temperatura acqua

R

[°C/10]

 

 

 

 

5

P00: Configurazione

R

-

 

 

 

 

6

P05: Config. DIN

R

-

 

 

 

 

7

T. Setpoint attivo

R

[°C/10]

 

 

 

 

8

T. Setpoint utente

R

[°C/10]

 

 

 

 

9

Versione LCD

R

-

 

 

 

 

 

 

 

 

50

Digitali 1

R/W

-

 

 

 

 

51

-

R/W

-

 

 

 

 

52

Setpoint - Raffreddamento

R/W

[°C/10]

 

 

 

 

53

Setpoint - Riscaldamento

R/W

[°C/10]

 

 

 

 

54

Minimo Setpoint – Raffr.

R/W

[°C/10]

 

 

 

 

55

Massimo Setpoint – Raffr.

R/W

[°C/10]

 

 

 

 

56

Minimo Setpoint – Risc.

R/W

[°C/10]

 

 

 

 

57

Massimo Setpoint – Risc.

R/W

[°C/10]

 

 

 

 

58

Velocità

R/W

-

 

 

 

 

59

Correzione Economy

R/W

[°C/10]

 

 

 

 

DESCRIZIONE REGISTRI DI SOLA LETTURA [R]

■ Registro "STATI"

H

Bit 15

Bit 14

Bit 13

Bit 12

Bit 11

Bit 10

Bit 9

Bit 8

 

 

 

 

 

 

 

 

-

-

P04

Deum

P06

P07

DI2

DI1

 

 

 

 

 

 

 

 

L

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

 

 

 

 

 

 

 

 

Vh

Vc

Allarme

MinT

Eco

P01

S/W

On/Off

 

 

 

 

 

 

 

 

-On/Off: stato terminale (0: Off, 1=On)

-S/W: modalità di funzionamento (0: S=raffreddamento,1: W=riscaldamento)

-P01: parametro "installazione bordo/parete"

-Eco: logica Economy attiva

-Min.T: logica Minima Temperatura selezionata

-Allarme: indicazione generale di allarme (si attiva al manifestarsi di uno qualsiasi degli allarmi gestiti)

-Vc: stato uscita digitale Vc

-Vh: stato uscita digitale Vh

-DI1: valore logico ingresso dig.1 (lo stato fisico dell'ingresso dipende dalla logica associata)

-DI2: valore logico ingresso dig.2 (lo stato fisico dell'ingresso dipende dalla logica associata)

-P07: parametro "Logica DIN 2"

-P06: parametro "Logica DIN 1"

-Deum: deumidifica in funzione (0:no, 1:si)

-P04: parametro "sonda acqua prevista"

REGISTRO "VELOCITÀ" : velocità alla quale sta funzionando il termina

-0: nessuna ventilazione attiva

-1: velocità superminima

-2: velocità minima

-3: velocità media

-4: velocità massima

REGISTRO "TEMPERATURA ARIA": temperatura ambiente letta dal comando e visualizzata a display (NB: tale temperatura corrisponde alla lettura da sonda remota se comando a bordo mentre, nel caso di comando a parete e sonda remota scollegata, lettura della sonda interna)

REGISTRO "UMIDITÀ": umidità ambiente letta dal comando dalla sonda relativa a quella di temperatura utilizzata

REGISTRO "TEMPERATURA ACQUA": temperatura dell'acqua letta dalla sonda relativa (SW)

Registro "P00" : parametro "Configurazione comando"

Registro "T. SETPOINT ATTIVO" : setpoint utilizzato per la regolazione

Registro "T. SETPOINT UTENTE" : setpoint impostato da utente (potrebbe discostare dal setpoint attivo in seguito a correzioni per logiche di economy, …o per utilizzo del setpoint da supervisione)

Registro "VERSIONE LCD" : definisce il tipo di comando e la versione software installata (0xHHSS: HH: carattere ASCII, SS:versione sw)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Manuale d'installazione e d'uso

 

 

 

 

 

 

 

Advanced electronic controller

9

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIZIONE REGISTRI DI LETTURA/SCRITTURA [R/W]

■ Registro "DIGITALI 1":

H

Bit 15

Bit 14

Bit 13

Bit 12

 

Bit 11

Bit 10

Bit 9

Bit 8

 

 

 

 

 

 

 

 

 

En.Vel

En.Min/

En.Set

En.MinT

 

En.ECO

En.RE

En.S/W

En.On/

Max

 

Off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

Bit 7

Bit 6

Bit 5

Bit 4

 

Bit 3

Bit 2

Bit 1

Bit 0

 

 

 

 

 

 

 

 

 

-

-

Lock

MinT

 

Eco

RE

S/W

On/Off

 

 

 

 

 

 

 

 

 

-On/Off: On/Off da supervisione

-S/W: Modalità da supervisione (0: Raffreddamento, 1: Riscaldamento)

-RE: selezione Resistenza da supervisione

-Eco: attivazione Economy da supervisione

-MinT.: attivazione controllo Minima Temperatura da supervisione

-Lock: blocco tastiera (0: non bloccata, 1: bloccata)

-En.On/Off :abilitazione controllo On/Off da supervisione

-En.S/W: abilitazione controllo modalità da supervisione

-En.RE: abilitazione selezione Resistenza Elettrica da supervisione

-En.ECO: abilitazione attivazione economy da supervisione

-En.MinT: abilitazione selezione logica di Minima Temperatura da supervisione

-En.Set: abilitazione forzatura setpoint da supervisione

-En.Min/Max: abilitazione soglie setpoint da supervisione

-En.Vel: abilitazione selezione velocità ventilatore da supervisione

Registro "SETPOINT - RAFFREDDAMENTO": setpoint da supervisione per la modalità Raffreddamento

Registro "SETPOINT - RISCALDAMENTO": setpoint da supervisione per la modalità Riscaldamento

Registro "MINIMO SETPOINT - RAFFR. ": limite inferiore per setpoint in raffreddamento

Registro "MASSIMO SETPOINT - RAFFR. ": limite superiore per setpoint in raffreddamento

Registro "MINIMO SETPOINT - RISC. ": limite inferiore per setpoint in riscaldamento

Registro "MASSIMO SETPOINT - RISC. ": limite superiore per setpoint in riscaldamento

Registro "VELOCITÀ": selezione velocità ventilatori da supervisore

Registro "CORREZIONE ECONOMY": correzione setpoint nel caso di economy da supervisore (tale correzione viene tolta od aggiunta al setpoint in base alla modalità di funzionamento)

PROCEDURA DI AUTODIAGNOSI

Tale procedura permette di verificare il corretto funzionamento delle singole uscite del comando stesso.

Per eseguire tale procedura seguire le indicazioni sotto riportate:

■ Mettere in Off il termostato

■ Premere contemporaneamente i tasti

livello 001: Inserimento password

Utilizzare i tasti per modificare il valore del display fino al valore di password per la autodiagnosi (030) e premere .

Verrà visualizzata la seguente schermata:

Premere il tasto per accendere in successione le varie uscite del termostato.

Simbolo

Azionamento

Morsetti

 

 

 

 

Velocità superminima

N-V0

 

 

 

 

Velocità minima

N-V1

 

 

 

 

Velocità media

N-V2

 

 

 

 

Velocità massima

N-V3

 

 

 

 

Valvola

N-Vc

 

 

 

 

Resistenza

N-Vh

 

Seconda valvola

 

 

 

 

 

nessun simbolo

Nessuna uscita attiva

 

 

 

 

È possibile verificare, una ad una, le uscite del controllo elettronico osservando il relativo componente (valvola, ventilatore..) o verificando la presenza di una tensione di 230 V ai morsetti corrispondenti.

premere il tasto per uscire dalla procedura di autodiagnosi (dopo alcuni minuti il termostato uscirà automaticamente comunque).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manuale d'installazione e d'uso

FWEC2

 

 

 

 

 

 

 

10

Advanced electronic controller

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SCHEDA ELETTRONICA (VEDI FIGURA 6)

Dove

Vc

Valvola

 

 

Vh

Valvola Caldo / Resistenza

 

 

V0

Vel.superminima

 

 

V1

Vel. minima

 

 

V2

Vel. media

 

 

V3

Vel. massima

 

 

N

Neutro

 

 

L

Fase

 

 

PE

Terra

 

 

A-B-GND

RS 485

 

 

SU

Sonda umidità remota

 

 

SW

Sonda acqua

 

 

SA

Sonda aria remota

 

 

DI1

Ingresso dig.1

 

 

CI12

Comune DI1-2

 

 

DI2

Ingresso dig.2

 

 

NB:

Per collegamenti di potenza utilizzare cavo sezione 1 mm2

Per ingressi digitali utilizzare cavo tipo AWG 24

Per prolungamenti sonde e RS485 utilizzare cavo schermato tipo AWG 24

SCHEMI ELETTRICI

(Vedi allegato Schemi Elettrici)

Tabella Unità/Schemi

UNITA’

TIPO

CONFIGURAZIONE

SCHEMA

 

 

 

 

FWL-M-V

-

1-2-3-13-14-15-25-26-27-31-32-33

FC66002554

 

 

7-8-9-19-20-21-37

FC66002555

 

 

 

 

 

 

FWB

-

4-5-6-16-17-18-28-29-30-34-35-36

UT66000887

 

 

10-11-12-22-23-24-38

UT66000890

 

 

 

 

 

 

 

04/12

1-2-3-13-14-15-25-26-27-31-32-33

UT66000889

 

 

 

 

7-8-9-19-20-21-37

UT66000892

 

 

 

 

 

 

FWD

06/12 3PH

7-8-9-19-20-21-37

UT66000894

 

 

 

16/18

1-2-3-13-14-15-25-26-27-31-32-33

UT66000888

 

 

 

 

 

7-8-9-19-20-21-37

UT66000891

 

 

 

 

 

 

 

16/18 3PH

7-8-9-19-20-21-37

UT66000893

 

 

 

 

 

FWL-M-V

-

 

 

 

 

 

EPIMSB6

FWB

-

FC66002557

 

 

 

 

 

FWD

-

 

 

 

 

 

SCHEMI ELETTRICI

(Vedi allegato Schemi Elettrici)

Tabella Configurazioni/Schemi

CONFIG.

UNITA’

SCHEMA

 

 

 

 

 

 

 

 

FWL-M-V

FC66002554 (1)

 

 

 

 

 

 

 

 

01-02-03

FWD

UT66000889 (6)

 

 

 

 

 

 

 

 

 

UT66000888 (5)

 

 

 

 

 

 

 

 

 

 

 

 

04-05-06

FWB

UT66000887 (4)

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002555 (2)

 

 

 

 

 

 

 

 

 

 

UT66000892 (9)

 

 

 

 

 

 

 

 

07-08-09

FWD

UT66000894 (11)

 

 

 

 

 

 

 

 

 

UT66000891 (8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UT66000893 (10)

 

 

 

 

 

 

 

 

10-11-12

FWB

UT66000890 (7)

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002554 (1)

 

 

 

 

 

 

 

 

13-14-15

FWD

UT66000889 (6)

 

 

 

 

 

 

 

 

 

UT66000888 (5)

 

 

 

 

 

 

 

 

 

 

 

 

16-17-18

FWB

UT66000887 (4)

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002555 (2)

 

 

 

 

 

 

 

 

 

 

 

UT66000892 (9)

 

 

 

 

 

 

 

 

 

 

 

 

19-20-21

FWD

UT66000894 (11)

 

 

 

 

 

 

 

 

 

UT66000891 (8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UT66000893 (10)

 

 

 

 

 

 

 

 

 

22-23-24

FWB

UT66000890 (7)

 

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002554 (1)

 

 

 

 

 

 

 

 

 

25-26-27

FWD

UT66000889 (6)

 

 

 

 

 

 

 

 

 

UT66000888 (5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28-29-30

FWB

UT66000887 (4)

 

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002554 (1)

 

 

 

31-32-33

 

 

 

 

 

FWD

UT66000889 (6)

 

 

 

 

 

 

 

 

 

UT66000888 (5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34-35-36

FWB

UT66000887 (4)

 

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002555 (2)

 

 

 

 

 

 

 

 

 

 

 

UT66000892 (9)

 

 

 

 

 

 

 

 

 

37

FWD

UT66000894 (11)

 

 

 

 

 

 

 

 

 

UT66000891 (8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UT66000893 (10)

 

 

 

 

 

 

 

 

 

38

FWB

UT66000890 (7)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Manuale d'installazione e d'uso

Advanced electronic controller

11

FC66002764

SCHEMI ELETTRICI

Legenda dei simboli degli schemi elettrici:

 

 

 

Vo

Velocità Superminima

 

 

 

 

 

 

 

 

V1

Velocità Minima

 

 

 

 

 

 

 

 

V2

Velocità Media

 

 

 

 

 

 

 

 

V3

Velocità Massima

 

 

 

 

 

 

 

 

L

Fase

 

 

 

 

 

 

 

 

PE

Terra

 

 

 

 

 

 

 

 

N

Neutro

 

 

 

 

 

 

 

 

RE

Resistenza Elettrica

 

 

 

 

 

 

 

 

SW

Sonda Acqua

 

 

 

 

 

 

 

 

SA

Sonda Aria

 

 

 

 

 

 

 

 

SU

Sonda Umidità

 

 

 

 

 

 

 

 

BK

Nero (Vel. Massima)

 

 

 

 

 

 

 

 

BU

Blu (Vel. Media)

 

 

 

 

 

 

 

 

RD

Rosso(Vel. Superminima/Minima)

 

 

 

 

 

 

 

 

WH

Bianco (comune)

 

 

 

 

 

 

 

 

GY

Grigio

 

 

 

 

 

 

 

 

BN

Marrone (Vel Minima)

 

 

 

 

 

 

 

 

 

GN

Verde

 

 

 

 

 

 

 

 

YE

Giallo

 

 

 

 

 

 

 

 

 

 

 

MS

Microinterruttore Flap

 

 

 

 

 

 

 

 

DI1

Ingresso digitale 1

 

 

 

 

 

 

 

 

DI2

Ingresso digitale 2

 

 

 

 

 

 

 

 

CI12

Comune ingressi digitali

 

 

 

 

 

 

 

 

A/B/GND

RS 485

 

 

 

 

 

 

 

 

F

Fusibile (non fornito)

 

 

 

 

 

 

 

 

IL

Interruttore di linea (non fornito)

 

 

 

 

 

 

 

 

CN

Morsettiera Terminale

 

 

 

 

 

 

 

 

RHC

Selettore remoto Riscald./Raffredd.

 

 

 

 

 

 

 

 

EXT

Contatto ON OFF remoto

 

 

 

 

 

 

 

 

EPIMSB6

Scheda di potenza per gestire 4 terminali

 

 

 

 

 

 

 

 

EPIB6

Scheda di potenza per unità tipo FWD

 

 

 

 

 

 

 

 

M

Motore Ventilatore

 

 

 

 

 

 

 

 

VHC

Valvola solenoide Raffr./Risc.

 

 

 

 

 

 

 

 

VC

Valvola solenoide Raffreddamento

 

 

 

 

 

 

 

 

VH

Valvola solenoide Riscaldamento

 

 

 

 

 

 

 

 

TSA

Termostato di sicurezza automatico

 

 

 

 

 

 

 

 

TSM

Termofusibile di sicurezza

 

 

 

 

 

 

 

 

SC

Scatola cablaggi

 

 

 

 

 

 

 

 

…..

Collegamenti elettrici a cura dell'installatore

 

 

 

 

 

 

 

 

ECONOMY

Selettore remoto COMFORT / ECONOMY

 

 

 

 

 

 

 

 

 

 

INSTALLAZIONE COMANDO A PARETE

NB: per l'installazione del comando a parete è consigliabile l'utilizzo di una scatola elettrica, dietro al comando, per l'alloggiamento dei cavi.

NB: prima dell'installazione rimuovere, con cautela, la pellicola protettiva del display; la rimozione della pellicola può provocare la comparsa di aloni scuri sul display che scompaiono dopo alcuni secondi e non sono indice di difettosità del comando.

ISTRUZIONI PER IL MONTAGGIO A PARETE

1.Togliere la vite di chiusura del comando (FIGURA 8).

2.In caso di utilizzo di una scatola da incasso portafrutti 503, passare i cavi attraverso la feritoia della base del comando ed utilizzare per il fissaggio gli appositi fori.

3.Altrimenti forare la parete dove si vuole installare il comando, in corrispondenza delle asole di fissaggio (5 x 8 mm) poste nella base del comando; passare i cavi attraverso la feritoia della base e fissarla con delle viti alla parete (precedentemente forata) (FIGURA 9).

4.Eseguire i collegamenti elettrici sulla morsettiera del terminale seguendo lo schema elettrico relativo.

5.Richiudere il comando utilizzando la vite tolta nel punto 1.

DATI TECNICI

 

90-250Vac 50/60Hz

 

 

Alimentazione

Potenza 8W

 

 

 

Fusibile di protezione: 500mA ritardato

 

 

Temp. Funzionamento

Range 0-50°C

 

 

Temp. Stoccaggio

Range -10-60°C

 

 

 

Normal Open 5A @ 240V (Resistivo)

 

 

Relè

Isolamento: distanza bobina-contatti 8mm

 

4000V dielettrico bobina-relè

 

 

 

 

Temperatura ambiente max.: 105°C

 

 

Connettori

250V 10A

 

 

 

Contatto pulito

 

 

Ingressi digitali

Corrente di chiusura 2mA

 

 

 

Max resistenza di chiusura 50 Ohm

 

 

Ingressi analogici

Sonde di Temperatura ed umidità relativa

 

 

Uscite di potenza

Relè (vedi sopra)

 

 

Sonde di Temperatura

Sonde NTC 10K Ohm @25°C

 

Range -25-100°C

 

 

 

Sonde di umidità

Sonda di tipo resistive

 

Range 20-90%RH

 

 

 

Manuale d'installazione e d'uso

FWEC2

12

Advanced electronic controller

FC66002764

FWEC2

Advanced electronic controller

Installation and operation manual

GENERAL CHARACTERISTICS

LCD controller has been designed to manage the operation of indoorunitswithsingle-phasemultispeed asynchronousmotor. Compared to the standard model it has the added features of advanced humidity control and serial communication.

This controller allows to set (figure 1) up a Master-Slave system (up to 247 slave terminals), in which one of the Microprocessor controllers plays the role of Master and controls all of the other slave elements.

In this case as well the connection is made via an RS485 bus, consisting of a simple shielded 2-conductor cable.

The master (identified by the address 255) sends the following information to the slave controllers:

(1)Operating mode (Cooling or Heating)

(2)Setpoint for room temperature.

The speed selector of each slave controller remains enabled and the room temperature can be adjusted within a range of

± 2°C around the setpoint value transmitted by the master controller.

MAIN FUNCTIONS AND FEATURES:

Air temperature adjustment through automatic variation of fan speed;

Regulation of air temperature via fan on-off control (fan runs at a fixed speed),

Control of On-Off valves for two or four-pipe systems

Control of electrical heater for auxiliary heating.

Cooling/heating switching in the following modes:

-local manual switching

-remote, manual (centralised);

-automatic, depending on water temperature

-automatic, depending on air temperature

Dehumidify Function

Serial Communication

ADDITIONAL FEATURES INCLUDE:

no-voltage contact for external activation (e.g. window contact, remote ON/OFF, occupancy sensor, etc.) which may enable or disable unit operation (contact logic: see circuit board configuration parameters).

no-voltage contact for centralised remote Cooling/Heating changeover (contact logic: see circuit board configuration parameters).

no-voltage contact for remote enabling of the economy mode (contact logic: see circuit board configuration parameters).

remote water temperature probe (accessory FWTSKAA)

built-in temperature probe

built-in humidity probe

remote air temperature probe (accessory FWTSKAA) (this probe, if present, is used in place of the internal one for the measurement of room temperature).

Remote humidity probe (accessory FWHSKAA - to be used in combination with the remote temperature probe)

The control panel is composed of:

LCD display

key board

LCD DISPLAY (SEE FIGURE 2)

(1)room temperature

(2)room humidity

(3)set temperature

ON

fan status. When flashing it indicates that fans are

 

 

off standing for a call from the thermostat. If the

 

 

symbol is steadily lit it means that the fans are

 

 

running

 

OFF

fan status. Fans are off as speed is set to Off or

 

 

the control is off.

 

AUTO

automatic ventilation logic

 

 

fan speed

 

 

operation mode: Cooling. When flashing it indicates

 

 

that water circuit is not enabled to fan ventilation.

 

 

operation mode: Heating. When flashing it indicates

 

 

that water circuit is not enabled to fan ventilation.

 

 

Dehumidification. When flashing it indicates that

 

 

the circuit is not enabled to dehumidification. If the

 

 

symbol is steadily lit it means that the function is

 

 

active.

 

 

Economy option enabled

 

 

 

 

 

 

Alarm triggered

 

 

 

Minimum Temperature Control

 

 

 

 

 

 

 

valve open

 

 

 

 

electrical heater: If the symbol flashes it means that

 

 

the electrical heater is on; if steadily lit it means only

 

 

that the electrical heater has been selected

 

 

 

 

serial communication active. The flashing symbol

 

 

indicates that the controller is the master

 

 

 

 

 

KEY BOARD (SEE FIGURE 3)

On/Off key: Thermostat On/Off. During the procedure of parameter modification, it permits to return to normal operating conditions

Up and Down keys: changing of thermostat setting temperature (Heating:[5.0-30.0°C], Cooling: [10.0-35.0°C]). During the procedure of parameter modification, they are used to select the parameters or to change their value

SEL key: in the heating mode, the electrical heater element can be selected as auxiliary function

Mode key: selection of Heating/Cooling operating mode

Fan key: selection of operating speed

EC key: selection of Economy mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Installation and operation manual

 

 

 

 

 

 

 

Advanced electronic controller

1

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ACTIVE KEY COMBINATIONS

PARAMETER CONFIGURATION PROCEDURE

With OFF thermostat: access to the parameter configuration procedure

With ON thermostat: display of current water temperature

Selection of Minimum air temperature function

Selection of dehumidify option

BOARD CONFIGURATION

The board can be configured according to the type of unit/ system to be governed by changing some parameters.

PARAMETER LIST

P00 = controller configuration (see “Available configurations”) to select the type of unit to be managed.

P01 = type of controller installation -000: on the unit

-001: wall mounted

P02 = Modbus address (in order for the change in this parameter to become active (excepting in the case of internaltransferbetweenvalues,itisnecessarytoswitchthe power off and back on again at the end of programming) -0: serial communication disabled

-1-247: slave -255: master

P03 = neutralzone[20-50°C/10];parameterusedincaseof configurations with automatic cooling/heating changeover according to air temperature.

P04 = water sensor -0: not available

-1: available

Based on the set value, the sensor alarm and the electrical heater functions will be controlled

P05 = Configuration logic for use of digital inputs 1 and 2:

-

0:

DIN1 = -

DIN2

= -

-

1:

DIN1 = -

DIN2

= OnOff

-2: DIN1 = Sum/Win DIN2 = -

- 3: DIN1 = Eco

DIN2 = -

-4: DIN1 = Sum/Win DIN2 = On/Off

- 5: DIN1 = Eco

DIN2 = On/Off

-6: DIN1 = Sum/Win DIN2 = Eco

P06 = logic for use of digital input 1:

-0: [open/closed] = [Cooling/Heating] = [-/ECO]

-1: [open/closed] = [Heating/Cooling] = [ECO/-]

P07 = logic for use of digital input 2:

-0: [open/closed] = [OFF/ON] = [-/ECO]

-1: [open/closed] = [On/Off] = [ECO/-]

P08 = Remote humidity sensor

-0 : not available

-1 : available

Based on the set value, the associated probe alarm will be triggered accordingly.

■ Switch the thermostat OFF

■ Push the

keys at the same time

level indication: 001= password entry

Use keys to modify the display value up to the password value “10”, and press .

If it is correct, you will have access to the parameters

Value of selected

parameter

 

 

 

 

level indication :

 

 

 

 

 

 

 

 

 

Selected

 

 

 

 

002= parameter

 

 

 

 

selection

parameter

 

 

 

 

P...

Use keys to scroll the various parameters (see “Parameter list” described above)

Press to confirm the parameter change (the value will start flashing)

level indication:

003 = edit parameter

use keys to change the value

Press to save the new value setting or to cancel the modification

After completing the modification of the parameters con-

cerned press key to exit the procedure

N.B.: the parameter configuration phase is of limited duration. Once a certain time has elapsed (around 2 minutes) the thermostat will switch back into the Off status and only the saved changes will be retained.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation and operation manual

FWEC2

 

 

 

 

 

 

 

2

Advanced electronic controller

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE CONFIGURATIONS (PARAMETER P00)

The LCD controller can be configured in various ways according to the type of system. Various configurations can be obtained through the P00 parameter (see configuration procedure of controller parameters).

001

System pipes: 2

Valve: NO

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: LOCAL MANUAL

002

System pipes: 2

Valve: NO

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: REMOTE MANUAL

003

System pipes: 2

Valve: NO

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: AUTOMATIC WATER SIDE

004

System pipes: 2

Valve: NO

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: LOCAL MANUAL

005

System pipes: 2

Valve: NO

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: REMOTE MANUAL

006

System pipes: 2

Valve: NO

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: AUTOMATIC WATER SIDE

007

System pipes: 2

Valve: NO

Electrical heater: YES

Fan speed: 3

Summer/winter switching logic: LOCAL MANUAL

008

System pipes: 2

Valve: NO

Electrical heater: YES

Fan speed: 3

Summer/winter switching logic: REMOTE MANUAL

009

System pipes: 2

Valve: NO

Electrical heater: YES

Fan speed: 3

Summer/winter switching logic: AUTOMATIC AIR SIDE

010

System pipes: 2

Valve: NO

Electrical heater: YES

Fan speed: 4

Summer/winter switching logic: LOCAL MANUAL

011

System pipes: 2

Valve: NO

Electrical heater: YES

Fan speed: 4

Summer/winter switching logic: REMOTE MANUAL

012

System pipes: 2

Valve: NO

Electrical heater: YES

Fan speed: 4

Summer/winter switching logic: AUTOMATIC AIR SIDE

013

System pipes: 2

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: LOCAL MANUAL

014

System pipes: 2

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: REMOTE MANUAL

015

System pipes: 2

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: AUTOMATIC WATER SIDE

016

System pipes: 2

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: LOCAL MANUAL

017

System pipes: 2

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: REMOTE MANUAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Installation and operation manual

 

 

 

 

 

 

 

Advanced electronic controller

3

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVAILABLE CONFIGURATIONS (PARAMETER P00)

018

System pipes: 2

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: AUTOMATIC WATER SIDE

019

System pipes: 2

Valve: 3 WAYS

Electrical heater: YES

Fan speed: 3

Summer/winter switching logic: LOCAL MANUAL

020

System pipes: 2

Valve: 3 WAYS

Electrical heater: YES

Fan speed: 3

Summer/winter switching logic: REMOTE MANUAL

021

System pipes: 2

Valve: 3 WAYS

Electrical heater: YES

Fan speed: 3

Summer/winter switching logic: AUTOMATIC AIR SIDE

022

System pipes: 2

Valve: 3 ways

Electrical heater: YES

Fan speed: 4

Summer/winter switching logic: LOCAL MANUAL

023

System pipes: 2

Valve: 3 WAYS

Electrical heater: YES

Fan speed: 4

Summer/winter switching logic: REMOTE MANUAL

024

System pipes: 2

Valve: 3 WAYS

Electrical heater: YES

Fan speed: 4

Summer/winter switching logic: AUTOMATIC AIR SIDE

025

System pipes: 4

Valve: NO

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: LOCAL MANUAL

026

System pipes: 4

Valve: NO

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: REMOTE MANUAL

027

System pipes: 4

Valve: NO

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: AUTOMATIC AIR SIDE

028

System pipes: 4

Valve: NO

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: LOCAL MANUAL

029

System pipes: 4

Valve: NO

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: REMOTE MANUAL

030

System pipes: 4

Valve: NO

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: AUTOMATIC AIR SIDE

031

System pipes: 4

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: LOCAL MANUAL

032

System pipes: 4

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: REMOTE MANUAL

033

System pipes: 4

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 3

Summer/winter switching logic: AUTOMATIC AIR SIDE

034

System pipes: 4

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: LOCAL MANUAL

035

System pipes: 4

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: REMOTE MANUAL

Installation and operation manual

FWEC2

4

Advanced electronic controller

FC66002764

AVAILABLE CONFIGURATIONS (PARAMETER P00)

036

System pipes: 4

Valve: 2-3 WAYS

Electrical heater: NO

Fan speed: 4

Summer/winter switching logic: AUTOMATIC AIR SIDE

037

System pipes: 4

Valve: NO

Electrical heater: YES

Fan speed: 3

Summer/winter switching logic: LOCAL MANUAL

038

System pipes: 4

Valve: NO

Electrical heater: YES

Fan speed: 4

Summer/winter switching logic: LOCAL MANUAL

SERIAL COMMUNICATION

Connection to the RS485 communication network

The communication network (bus type) relies on a simple shielded 2-conductor cable, directly connected to the RS485 serial ports of the controllers (terminals A, B and GND).

“For the network use a cable AWG 24 (diam. 0.511 mm)”

The communication network must have the following general structure (figure 4).

In the case of the “MASTER-SLAVE” solution a termination resistor will have to be installed on both controllers at the furthest ends of the network.

N.B.: (1) Comply with the polarity of the connection: indicated with A(-) and B(+)

(2) Ground shield at one end only

____________________________________________________________

WARNING:

Use a shielded cable AWG24

Colours suggested for the communication

network: A (-) Brown ; B (+) Yellow

____________________________________________________________

LOGICS

COOLING/HEATING SWITCHING

Four logics are present to select the thermostat operating modes according to the controller configuration setting:

1.Local: user choice made through the key

2.Distance:dependingontheDigitalInputDI1status(contact logic: see configuration parameters of board)

3.Depending on water temperature

Summer

Winter

Water temp.

N.B.: in case of water sensor alarm, the controller returns to the Local mode temporarily.

4. depending on air temperature

Summer

Winter

Air temp.

Where:

Set is the temperature setting made by the arrows

ZN is the neutral zone (parameter P03)

The thermostat operating mode is indicated on the display by the symbols (cooling) and (heating)

FAN SPEED CONTROL

The controller can govern 3 or 4-speed indoor units

OPERATING SPEED SELECTION

Using Fan key it is possible to select the following speeds:

Automatic ventilation: depending on the set temperature and the room air temperature

With 3-speed configurations : where:

1 = low speed

2 = medium speed

3 = maximum speed

COOLING

HEATING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Installation and operation manual

 

 

 

 

 

 

 

Advanced electronic controller

5

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

With 4-speed configurations : where:

sm = extra-low speed 1 = low speed

2 = medium speed

3 = maximum speed

COOLING

Air temp.

HEATING

Air temp.

N.B.: in case of 4-speed configuration and valve, ventilation in heating mode is shifted by 0.5°C to permit a natural convection phase

Speed disabled: Can be selected only in heating mode and with 4-speed configuration only. The indoor unit operates by natural convection only.

 

Extra low speed: can be selected only with

 

 

4-speed configuration. It works at extra low

 

 

 

 

speed only.

 

Low speed

 

Medium speed

 

High speed

N.B.: In the case of fixed speed, the fan on/off logic will be equivalent to the automatic logic.

WATER CONTROL

The ventilation operation depends on the system water temperature control. Based on the operation mode, different heating or cooling thresholds will be enabled.

COOLING

NO

Water temp.

HEATING

NO

Water temp.

Upon a call of the thermostat, the absence of the enabling signal will be indicated on the display by the flashing of the

symbol representing the active mode ( or ) The enabling signal is ignored:

if the water sensor is not included (P04 = 0) or in alarm status because disconnected

in the cooling mode with 4-pipe configurations

LOGICS

FORCED OVERRIDES

The normal fan operating logic will be ignored in particular override situations that may be necessary to ensure correct control of the temperature or the unit’s operation. This may occur:

in the cooling mode:

on-board controller (P01 = 0) and configurations with valve: the minimum speed available will be maintained even once the temperature has been reached.

on-board controller and valveless configurations: every 10 minutes in which the fan remains idle a 2 minute fan rotation is carried out at medium speed to enable the air sensor to read the room temperature more accurately.

In the heating mode

while the electrical heater is on: the fan is forced to run at medium speed

once the electrical heater has gone off: a 2 minute postventilation cycle will be run at medium speed. (N.B.: this cycle will be completed even if the thermostat is switched off or in the event of a changeover to the cooling mode)

DISPLAY

The display shows the fan status

On flashing: fan in standby mode

On steadily lit: fan on

OFF: fan disabled to operate by natural convection only

and fan speed (with indication of “automatic” logic if proper) enabled or selected (in case of stand-by fan)

Extra low speed

Low speed

Medium speed

High speed

N.B.: if the active speed is different from the one selected by the user (in the case of a forced override), pressing the

button Fan the selected speed will be displayed; pressing again will change this setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation and operation manual

FWEC2

 

 

 

 

 

 

 

6

Advanced electronic controller

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

The controller can manage 2 or 3-way On/OFF type valves, with 230V voltage.

OPENING

The valve opening is controlled according to the operating setpoint and air temperature setpoint

COOLING

Air temp.

HEATING

Air temp.

WATER CONTROL

The checking of water temperature to enable valve opening is a function that concerns only configurations with 3-way valves and electrical heater.

In such configurations the water temperature will be checked in the following cases:

Heating with electrical heater: operation of the electrical heater will force the fan to switch on; it is therefore necessary to prevent excessively cold water from passing through the unit.

Water temp.

Post-ventilation due to switching off of the electrical heater: this function will be maintained until the set time has elapsed, even if the operating mode is changed. During post-ventilation the water temperature enabling signal will coincide with the one seen for fan operation.

DISPLAY

The active valve indication on the display will be shown by the symbol

ELECTRICAL HEATER

The electrical heater is a device used where necessary in the heating mode.

SELECTION

If provided for in the configuration, the electrical heater can be selected in the heating mode by pressing the Sel key

ACTIVATION

Air temp.

If the electrical heater is selected by the user, it will be activated on a call from the thermostat based on the room temperature

N.B.: switching it on will force the fan on as well

WATER CONTROL

Enabling of the electrical heater is tied to the water temperature. The related enabling logic is described below

The enabling signal will not be given if the water sensor is either not present or disconnected

HEATING

ON

OFF

Water temp.

DISPLAY

The display will show the following information

electrical heater selected by the user: steadily symbol

active electrical heater: flashing symbol

ECONOMY

The Economy function corrects the setpoint by 2.5°C and forces the fan to run at the minimum available speed to reduce unit operation.

Cooling: setpoint + 2.5°C

Heating: setpoint -2.5°C

ACTIVATION

This function can be activated by pressing the key

DISPLAY

The Economy function is shown on the display by the symbol

MINIMUM TEMPERATURE CONTROL

This logic makes it possible to keep the room temperature from falling too far when the thermostat is off by forcing the unit into the heating mode if necessary and for the time required.

If the electrical heater is present, it will be used only if it was previously selected as a resource in the heating mode.

SELECTION

When the thermostat is off, you can select the minimum temperature control by pressing at the same time the keys

.

The same key combination disables this function.

ACTIVATION

If this control is selected, the unit will switch on when the room temperature falls below 9°C.

Air temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Installation and operation manual

 

 

 

 

 

 

 

Advanced electronic controller

7

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When temperature exceeds 10°C the thermostat will resume the Off status.

N.B.: Any Off command from digital input will disable this logic

DISPLAY

The display shows the following information

Minimum temperature control selected: symbol

Minimum temperature control enabled: DEFR

DEHUMIDIFICATION

The dehumidification function, enabled only in the cooling mode, activates operation of the indoor unit in order to achieve a 10% reduction in the level of humidity present in the room at the time the function itself was selected.

SELECTION

Dehumidification can be selected/unselected in the Cooling

mode by simultaneously pressing the buttons. If the water probe (P04=0) or the remote humidity probe is not available, in cases where the controller is installed directly on the unit (P08=0), selection will not be enabled. If selected, the dead band for automatic switching on the air side will be brought to 5°

LOGIC

Once selected, the dehumidification logic sets the target humidity level as the humidity present at the time the function was selected minus 10%. Where the room humidity is less than 40% the target level will be set at 30%.

The fan will be forced to run at low speed or, if the temperature is much higher than the setpoint, at medium speed.

Med. speed

Min. speed

In order to bring the humidity to the set value, the fan (and valve, if present) will be activated even if the room temperature has already reached the programmed setpoint (indicated on the display by the symbol 3). Should the room temperature fall too far below this threshold, the logic will be temporarily inhibited.

Inhibited

Air temp.

WATER CONTROL

Enabling of the dehumidification function is tied to the water temperature. The related enabling logic is described below

Water temp.

If enabling conditions do not exist, the dehumidification function will be temporarily inhibited.

The same will occur in the event that the probe is disconnected.

N.B.: once the target level of humidity is reached or the controller is switched off, the dehumidify option will be unselected

DISPLAY

The display shows the following information:

Dehumidification ON: symbol lit

Dehumidification temporarily inhibited: flashing symbol

ALARMS

This control manages two types of alarms:

Serious Alarms: cause the forced switching off of the thermostat

Non-serious Alarms: do not cause the forced switching off of the thermostat, but disable possible critical functions

SERIOUS ALARMS

Alarm code

Code A01= error of external air temperature sensor (in case of on-board thermostat)

CodeA02= error of internal air temperature sensor (in case of wall mounted thermostat and disconnected external air temperature sensor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation and operation manual

FWEC2

 

 

 

 

 

 

 

8

Advanced electronic controller

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NON-SERIOUS ALARMS

Thermostat OFF

Thermostat ON

Code A03 = water sensor error

Code A04 = remote humidity probe error (only if a remote temperature probe is installed)

Code A05 = internal humidity probe error

N.B.: the alarm code is displayed only when the thermostat is switched off

MODBUS

The protocol implemented in the controller is Modbus RTU (9600, N, 8, 2) on RS485

FUNCTIONS IMPLEMENTED

0x03 : Read Holding Registers

0x04 : Read Input Registers

0x10 : Write Multiple registers

EXCEPTIONS IMPLEMENTED

Exception Code 02: Invalidate data address

LIST OF SUPERVISION PARAMETERS

ADDRESS

REGISTER

TYPE

U.M.

 

 

 

 

0

Status

R

-

 

 

 

 

1

Speeds

R

-

 

 

 

 

2

Air temperature

R

[°C/10]

 

 

 

 

3

Humidity

R

%

 

 

 

 

4

Water temperature

R

[°C/10]

 

 

 

 

5

P00:Configuration

R

-

 

 

 

 

6

P05:Config. DIN

R

-

 

 

 

 

7

T. Active setpoint

R

[°C/10]

 

 

 

 

8

T. User setpoint

R

[°C/10]

 

 

 

 

9

LCD version

R

-

 

 

 

 

 

 

 

 

50

Digital 1

R/W

-

 

 

 

 

51

-

R/W

-

 

 

 

 

52

Setpoint - Cooling

R/W

[°C/10]

 

 

 

 

53

Setpoint - Heating

R/W

[°C/10]

 

 

 

 

54

Minimum Setpoint – Cool.

R/W

[°C/10]

 

 

 

 

55

Maximum Setpoint – Cool.

R/W

[°C/10]

 

 

 

 

56

Minimum Setpoint – Heat.

R/W

[°C/10]

 

 

 

 

57

Maximum Setpoint – Heat.

R/W

[°C/10]

 

 

 

 

58

Speeds

R/W

-

 

 

 

 

59

Economy Correction

R/W

[°C/10]

 

 

 

 

DESCRIPTION OF READ-ONLY REGISTERS [R]

■ “Staus” “REGISTER”

H

Bit 15

Bit 14

Bit 13

Bit 12

Bit 11

Bit 10

Bit 9

Bit 8

 

 

 

 

 

 

 

 

-

-

P04

Deum

P06

P07

DI2

DI1

 

 

 

 

 

 

 

 

L

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

 

 

 

 

 

 

 

 

Vh

Vc

Alarm

MinT

Eco

P01

S/W

On/Off

 

 

 

 

 

 

 

 

-On/Off: unit status (0: Off, 1=On)

-S/W: operation mode (0: S=cooling,1:W=heating)

-P01: “on unit/wall-mounted” parameter

-Eco: Economy logic active

-Min.T: Minimum Temperature logic selected

-Alarm: general alarm indication (activated when any of the managed alarms is triggered)

-Vc: status of digital output Vc

-Vh: status of digital output Vh

-DI1: logical value of dig. input 1 (the physical status of the input depends on the associated logic)

-DI2: logical value of dig. input 2 (the physical status of the input depends on the associated logic)

-P07: “DIN 2 Logic” parameter

-P06: “DIN 1 Logic” parameter

-Dehum: dehumidification ON (0:no, 1:yes)

-P04: “water probe present” parameter

“SPEED” REGISTER: current operating speed of the indoor unit

-0: fan OFF

-1: extra-low speed

-2: low speed

-3: medium speed

-4: high speed

“AIR TEMPERATURE” REGISTER: room temperature read by the controller and shown on the display (N.B.: this temperature corresponds to the reading of the remote probe if the controller is located on the unit, or the reading of the internal probe in the case of a wall-mounted controller and remote probe disconnected)

“HUMIDITY” REGISTER: room humidity read by the controller via the probe associated with the temperature probe used

“WATER TEMPERATURE” REGISTER: value read by the water probe (SW)

“P00” Register: “Controller configuration” parameter

“T. ACTIVE SETPOINT” Register: setpoint used for temperature control

“T. USER SETPOINT” Register: setpoint programmed by the user (it may differ from the active setpoint due to corrections based on economy logics,…or use of the setpoint imposed by the supervision software)

“LCD VERSION” Register : defines the controller type and software version installed (0xHHSS: HH: ASCII character, SS:sw version)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Installation and operation manual

 

 

 

 

 

 

 

Advanced electronic controller

9

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESCRIPTION OF READ/WRITE REGISTERS [R/W]

■ “Digital 1” REGISTER:

H

Bit 15

Bit 14

Bit 13

Bit 12

 

Bit 11

Bit 10

Bit 9

Bit 8

 

 

 

 

 

 

 

 

 

En.Vel

En.Min/

En.Set

En.MinT

 

En.ECO

En.RE

En.S/W

En.On/

Max

 

Off

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

Bit 7

Bit 6

Bit 5

Bit 4

 

Bit 3

Bit 2

Bit 1

Bit 0

 

 

 

 

 

 

 

 

 

-

-

Lock

MinT

 

Eco

RE

S/W

On/Off

 

 

 

 

 

 

 

 

 

-On/Off: On/Off via supervision system

-S/W: Mode set via supervision system (0: Cooling, 1: Heating)

-RE: selection of electrical heater via supervision system

-Eco: Economy mode ON via supervision system

-MinT.: Minimum Temperature control ON via supervision system

-Lock: keypad lock (0: unlocked, 1: locked)

-En.On/Off :enabling of On/Off control via supervision system

-En.S/W: enabling of mode control via supervision system

-En.RE: enabling of selection of electrical heater function via supervision system

-En.ECO: enabling of economy mode activation via supervision system

-En.MinT: enabling of selection of Minimum Temperature logic via supervision system

-En.Set: enabling of forced override of setpoint via supervision system

-En.Min/Max: enabling of setpoint thresholds via supervision system

-En.Vel: enabling of selection of fan speed via supervision system

“SETPOINT - COOLING” Register: setpoint imposed by supervision system for the Cooling mode

“SETPOINT - HEATING” Register: setpoint imposed by supervision system for the Heating mode

“MINIMUM SETPOINT - COOL.” Register : lower limit for setpoint in cooling mode

“MAXIMUM SETPOINT - COOL.” Register “: upper limit for setpoint in cooling mode

“MINIMUM SETPOINT - HEAT.” Register “: lower limit for setpoint in heating mode

“MAXIMUM SETPOINT - HEAT.” Register “: upper limit for setpoint in heating mode

“SPEED” Register: selection of fan speed via supervision system

“ECONOMY CORRECTION” Register: correction of setpoint in the case of economy mode imposed by supervisor (this correction is an amount subtracted from or added to the setpoint, based on the operating mode)

SELF-DIAGNOSIS PROCEDURE

This procedure allows you to check whether the individual outputs of the controller function correctly.

To run the procedure, follow the directions below: ■ Switch the thermostat off

■ Push the keys at the same time

001 level: password entry

Use the keys to change the value on the display until arriving at the password for self-diagnosis (030) and press .

The following screen will be displayed:

Press the button to switch on the various thermostat outputs in sequence.

 

Symbol

 

Actuation

 

Terminals

 

 

 

 

 

 

 

 

 

 

Extra low speed

 

N-V0

 

 

 

 

 

 

 

 

 

 

Min. speed

 

N-V1

 

 

 

 

 

 

 

 

 

 

Med. speed

 

N-V2

 

 

 

 

 

 

 

 

 

 

Max. speed

 

N-V3

 

 

 

 

 

 

 

 

 

 

Valve

 

N-Vc

 

 

 

 

 

 

 

 

 

 

Electrical heater

 

N-Vh

 

 

 

Second valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

no symbol

 

no active outlet

 

 

 

 

 

 

 

 

 

 

The electronic controller outputs can be checked one by one either by observing the respective component (valve, fan..) or verifying whether a voltage of 230 V is present at the corresponding terminals.

To exit the self-diagnosis procedure press (after a few minutes the thermostat will automatically exit in any case).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation and operation manual

FWEC2

 

 

 

 

 

 

 

10

Advanced electronic controller

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ELECTRONIC BOARD (FIGURE 6)

Where

Vc

Valve

 

 

Vh

Heat valve/heater

 

 

V0

Extra low speed

 

 

V1

Low speed.

 

 

V2

Medium speed

 

 

V3

High speed

 

 

N

Neutral

 

 

L

Phase

 

 

PE

Ground

 

 

A-B-GND

RS 485

 

 

SU

Remote humidity sensor

 

 

SW

Water sensor

 

 

SA

Remote air probe

 

 

DI1

Dig.1 input

 

 

CI12

DI1-2 Common

 

 

DI2

Dig. 2 input

 

 

N.B.:

For power connections use cable w/ cross section size of 2 mm2

For digital inputs used AWG 24 cable

For sensor extensions and RS485 use AWG 24 shielded cable

WIRING DIAGRAMS

(See Wiring Diagrams enclosed)

UNIT TABLE/DIAGRAMS

UNIT

TYPE

CONFIGURATION

DIAGRAM

 

 

 

 

FWL-M-V

-

1-2-3-13-14-15-25-26-27-31-32-33

FC66002554

 

 

7-8-9-19-20-21-37

FC66002555

 

 

 

 

 

 

FWB

-

4-5-6-16-17-18-28-29-30-34-35-36

UT66000887

 

 

10-11-12-22-23-24-38

UT66000890

 

 

 

 

 

 

 

04/12

1-2-3-13-14-15-25-26-27-31-32-33

UT66000889

 

 

 

 

7-8-9-19-20-21-37

UT66000892

 

 

 

 

 

 

FWD

06/12 3PH

7-8-9-19-20-21-37

UT66000894

 

 

 

16/18

1-2-3-13-14-15-25-26-27-31-32-33

UT66000888

 

 

 

 

 

7-8-9-19-20-21-37

UT66000891

 

 

 

 

 

 

 

16/18 3PH

7-8-9-19-20-21-37

UT66000893

 

 

 

 

 

FWL-M-V

-

 

 

 

 

 

EPIMSB6

FWB

-

FC66002557

 

 

 

 

 

FWD

-

 

 

 

 

 

WIRING DIAGRAMS

(See Wiring Diagrams enclosed)

CONFIGURATION TABLE/DIAGRAMS

CONFIG.

UNIT

DIAGRAM

 

 

 

 

 

 

 

 

FWL-M-V

FC66002554 (1)

 

 

 

 

 

 

 

 

01-02-03

FWD

UT66000889 (6)

 

 

 

 

 

 

 

 

 

UT66000888 (5)

 

 

 

 

 

 

 

 

 

 

 

 

04-05-06

FWB

UT66000887 (4)

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002555 (2)

 

 

 

 

 

 

 

 

 

 

UT66000892 (9)

 

 

 

 

 

 

 

 

07-08-09

FWD

UT66000894 (11)

 

 

 

 

 

 

 

 

 

UT66000891 (8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UT66000893 (10)

 

 

 

 

 

 

 

 

10-11-12

FWB

UT66000890 (7)

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002554 (1)

 

 

 

 

 

 

 

 

13-14-15

FWD

UT66000889 (6)

 

 

 

 

 

 

 

 

 

UT66000888 (5)

 

 

 

 

 

 

 

 

 

 

 

 

16-17-18

FWB

UT66000887 (4)

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002555 (2)

 

 

 

 

 

 

 

 

 

 

 

UT66000892 (9)

 

 

 

 

 

 

 

 

 

19-20-21

FWD

UT66000894 (11)

 

 

 

 

 

 

 

 

 

UT66000891 (8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UT66000893 (10)

 

 

 

 

 

 

 

 

22-23-24

FWB

UT66000890 (7)

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002554 (1)

 

 

 

 

 

 

 

 

 

25-26-27

FWD

UT66000889 (6)

 

 

 

 

 

 

 

 

 

UT66000888 (5)

 

 

 

 

 

 

 

28-29-30

FWB

UT66000887 (4)

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002554 (1)

 

 

 

 

 

 

 

 

 

31-32-33

FWD

UT66000889 (6)

 

 

 

 

 

 

 

 

 

UT66000888 (5)

 

 

 

 

 

 

 

 

 

 

 

 

34-35-36

FWB

UT66000887 (4)

 

 

 

 

 

 

 

 

 

 

FWL-M-V

FC66002555 (2)

 

 

 

 

 

 

 

 

 

 

UT66000892 (9)

 

 

 

 

 

 

 

 

 

37

FWD

UT66000894 (11)

 

 

 

 

 

 

 

 

 

UT66000891 (8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UT66000893 (10)

 

 

 

 

 

 

 

 

 

38

FWB

UT66000890 (7)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FWEC2

Installation and operation manual

Advanced electronic controller

11

FC66002764

WIRING DIAGRAMS

Key to symbols used in wiring diagrams:

 

 

 

Vo

Extra low speed

 

 

 

 

 

 

 

 

V1

Min. speed

 

 

 

 

 

 

 

 

V2

Med. speed

 

 

 

 

 

 

 

 

V3

Max. speed

 

 

 

 

 

 

 

 

L

Phase

 

 

 

 

 

 

 

 

PE

Ground

 

 

 

 

 

 

 

 

N

Neutral

 

 

 

 

 

 

 

 

RE

Electrical heater

 

 

 

 

 

 

 

 

SW

Water sensor

 

 

 

 

 

 

 

 

SA

Air sensor

 

 

 

 

 

 

 

 

SU

Humidity sensor

 

 

 

 

 

 

 

 

BK

Black (Max. speed)

 

 

 

 

 

 

 

 

BU

Blue (Med. speed)

 

 

 

 

 

 

 

 

RD

Red (Extra low speed)

 

 

 

 

 

 

 

 

WH

White (common)

 

 

 

 

 

 

 

 

GY

Grey

 

 

 

 

 

 

 

 

BN

Brown (Min. speed)

 

 

 

 

 

 

 

 

 

 

GN

Green

 

 

 

 

 

 

 

 

YE

Yellow

 

 

 

 

 

 

 

 

MS

Flap microswitch

 

 

 

 

 

 

 

 

 

 

 

DI1

Digital 1 input

 

 

 

 

 

 

 

 

DI2

Digital 2 input

 

 

 

 

 

 

 

 

 

CI2

Digital input common

 

 

 

 

 

 

 

 

A/B/GND

RS 485

 

 

 

 

 

 

 

 

F

Fuse (not supplied)

 

 

 

 

 

 

 

 

 

IL

Circuit breaker (not supplied)

 

 

 

 

 

 

 

 

CN

Terminal board

 

 

 

 

 

 

 

 

 

RHC

Heating/Cooling remote selecting switch

 

 

 

 

 

 

 

 

EXT

Remote ON/OFF contact

 

 

 

 

 

 

 

 

EPIMB6

Circuit board to control 4 indoor units

 

 

 

 

 

 

 

 

 

 

EPIB6

Circuit board for FWD units

 

 

 

 

 

 

 

 

M

Fan motor

 

 

 

 

 

 

 

 

VHC

Solenoid valve –Cool/Heat.

 

 

 

 

 

 

 

 

 

VC

Solenoid valve - Cooling

 

 

 

 

 

 

 

 

VH

Solenoid valve - Heating

 

 

 

 

 

 

 

 

 

TSA

Automatic safety thermostat

 

 

 

 

 

 

 

 

TSM

Safety fuse

 

 

 

SC

Wiring box

 

 

 

 

 

 

 

 

.....

Electrical connections to be made by

 

 

 

 

installer

 

 

 

 

 

 

 

 

ECONOMY

COMFORT / ECONOMY remote selecting

 

 

 

 

 

switch

 

 

 

 

 

 

 

 

 

 

INSTALLATION OF WALL-MOUNTED CONTROLLER

NB: for wall mounting of the controller it is advisable to use an electric box behind the controller to accommodate the cables.

NB: Prior to installation, carefully remove the protective film from the display; removal of the film may cause some dark streaks to appear on the display but these will disappear after a few seconds and are not signs of a controller defect.

INSTRUCTIONS FOR WALL MOUNTING

1.Remove the fastening screw of the controller (FIGURE 8).

2.If a 503 electrical enclosure is used, pass the cables through the slot at the bottom of the controller and use the holes provided for fastening.

3.Otherwise, in the wall where you wish to mount the controller, drill holes to match up with the fastening slots (5x8mm) on the base of the controller; pass the cables through the slot on the base and screw it to the wall (previously drilled) (FIGURE 9).

4.Make the electrical connections to the indoor unit terminal block as per the wiring diagram.

5.Close the controller box and fix with the screw removed as described at point 1.

TECHNICAL DATA

 

90-250Vac 50/60Hz

 

 

Power supply

Electrical input 8W

 

 

 

Protection fuse 500mA delayed

 

 

Operating temp.

Range 0-50°C

 

 

Storage temp.

Range -10-60°C

 

 

 

NO 5A @ 240V (Resistive)

 

 

Relay

insulation: coil-contact distance 8 mm

 

4000V coil-relay dielectric

 

 

 

 

Max ambient temperature 105°C

 

 

Connectors

250V 10A

 

 

 

Clean contact

 

 

Digital inputs

Closing current 2mA

 

 

 

Max. closing resistance 50 Ohm

 

 

Analog inputs

Temperature and relative humidity probes

 

 

Power outputs

Relay (see above)

 

 

Temperature sensors

NTC sensors 10K Ohm @25°C

 

Range -25-100°C

 

 

 

Humidity probe

Resistive-type probe

 

Range 20-90%RH

 

 

 

Installation and operation manual

FWEC2

12

Advanced electronic controller

FC66002764

FWEC2

Advanced electronic controller

Manuel d'installation et d'utilisation

CARACTÉRISTIQUES GÉNÉRALES

Le contrôleur LCD a été conçu pour commander toutes les unités terminales à moteur asynchrone monophasé à plusieurs vitesses. Par rapport à la version standard sont prévues une gestion avancée de l’humidité et la communication sérielle. La version (figure 1), pourvoit à un système Maître-Secondaire (jusqu’à 247 unités internes Secondaire). Dans le cas de cette solution une des commandes exerce la fonction Maître et de ce fait contrôle tous les autres éléments Secondaire.

Dans ce cas également, la connexion se produit par l’intermédiaire du bus RS485, comprenant un simple câble blindé à 2 conducteurs.

La commande Master (identifiée par l’adresse 255) transmet aux commandes Slave les informations suivantes:

(1)Modalité de fonctionnement (rafraîchissement ou chauffage)

(2)Valeur programmée de température ambiante.

Chaque commande Slave maintient le contrôle du sélecteur de vitesse et, pour le réglage de la température ambiante, est admis un écart de ± 2°C autour de la valeur programmée transmise par la commande Master.

PRINCIPALES FONCTIONS:

Réglage de la température de l’air par variation automatique de la vitesse du ventilateur.

Réglage de la température de l’air par commande On-Off du ventilateur à une vitesse fixe

Contrôle de vannes On-Off pour systèmes à deux ou à quatre tubes.

Gestion de la résistance d’appoint pour le chauffage.

Commutation Rafraîchissement/Chauffage dans les modalités suivantes:

-manuelle sur l’appareil,

-manuelle à distance (centralisée)

-automatique, en fonction de la température de l’eau

-automatique, en fonction de la température de l’air

Fonction de Déshumidification

Communication sérielle

IL EST DOTÉ DE:

contactlibrepourcommandeexterne(parex.:contactfenêtre, ON/OFF à distance, détecteur de présence, etc.) qui peut activer ou désactiver le fonctionnement de l’unité (logique contact : voir les paramètres de configuration de la carte).

contact libre pour commutation Rafraîchissement / Chauffage à distance centralisée (logique contact: voir les paramètres de configuration de la carte).

contact libre pour l’activation de la fonction economy à distance (logique contact) : voir les paramètres de configuration de la carte).

sonde de température éloignée pour l’eau (accessoire).

sonde de température interne

sonde d’humidité interne

sond de température éloignée pour l’air (accessoire). Si présente, cette sonde est utilisée à la place de la sonde interne pour lalecture de la température ambiante.

Sonde d’humidité éloignée (accessoire – à utiliser en combinaison avec la sonde de température éloignée)

Le panneau de commande se compose des éléments suivants:

moniteur LCD

clavier

MONITEUR LCD (VOIR FIGURE 2)

(1)Température ambiante

(2)Humidité ambiante

(3)température programmée

ON

état ventilateurs. Le voyant clignotant indique

 

 

l’arrêt des ventilateurs dans l’attente d’un appel du

 

 

thermostat. Le symbole allumé fixe indique que les

 

 

ventilateurs sont en fonction

 

OFF

état ventilateurs. Ventilateurs à l’arrêt car la vites-

 

 

se sélectionnée est sur Off ou la commande est

 

 

désactivée

 

AUTO

logique de ventilation automatique

 

 

vitesse ventilateur

 

 

modalités de fonctionnement Rafraîchissement Le

 

 

voyant clignotant indique l’absence de signal eau

 

 

de fonctionnement de la ventilation.

 

 

modalités de fonctionnement Chauffage Le voyant

 

 

clignotant indique l’absence de signal eau de

 

 

fonctionnement de la ventilation.

 

 

Déshumidification. Le symbole clignotant indique

 

 

l’absence de signal de déshumidification. Le

 

 

 

 

 

 

symbole allumé fixe indique par contre que cette

 

 

 

fonction est activée.

 

 

 

option Economy activée

 

 

 

présence d’alarme

 

 

 

contrôloe Température minimum

 

 

 

ouverture vanne

 

 

 

résistance électrique Le symbole clignotant indique

 

 

 

 

que la résistance est en fonction. Le symbole allumé

 

 

fixe indique uniquement la résistance sélectionnée.

 

 

communicationsérielleactive.Lesymboleclignotant

 

 

indique que la commande est maître

 

CLAVIER (VOIR FIGURE 3)

Touche On/Off: allumage /extinction thermostat Durantlaprocéduredemodificationdesmaramètres permet de revenir au fonctionnement normal

TouchesUpetDown:modificationdelatempérature de réglage du thermostat (Chauffage:[5.0-30.0°C], rafraîchissement: [10.0-35.0°C]). Durant la procédure de modification des paramètres ces touches sont utilisées pour sélectionner les paramètres ou modifier leur valeur

ToucheSEL:danslamodalitéChauffage,sélectionne la résistance électrique comme fonction auxiliaire

ToucheMode:sélectiondesmodalitésdefonctionnement

Chauffage / Rafraîchissement

Touche Fan: sélection de la vitesse de fonctionnement

Touche EC: sélection de la modalité Economy

FWEC2

Manuel d'installation et d'utilisation

Advanced electronic controller

1

FC66002764

COMBINAISONS DE TOUCHES ACTIVES

Thermostat sur Off: allumé sur la procédure de configuration des paramètres

Thermostat sur On: affichage momentané de la température de l’eau

Sélection de la fonction de Température minimum air

Sélection Déshumidification

CONFIGURATION DE LA CARTE

La carte est configurable en fonction du type d’unité terminale/installation à contrôler, en modifiant des paramètres donnés.

LISTE DES PARAMÈTRES

P00 = configuration commande (voir “Configurations Prévues”) pour sélectionner le type d’unité terminale à contrôler.

P01 = type d’installation de la commande -000: sur l’appareil

-001: murale

P02 = adresse Modbus [pour valider la modifica-

tion

de ce

paramètre (sauf le

cas de

passa-

ge

inter ne

entre valeurs] il

faut

couper

l’alimentation et remettre sous tension à la fin de la programmation)

-0: communication sérielle désactivée -1-247: Secondaire

-255: Master

P03=zoneneutre[20-50°C/10];paramètreutiliséencasdecon- figurationa avec sélection automatique Rafraîchissement/ Chauffage en fonction de la température de l’air.

P04 = sonde eau -0: non prévue -1: prévue

Selon la valeur programmée, seront contrôlées l’alarme sonde et l’activation de la résistance électrique

P05 = Logique de configuration – utilisation entrées nu-

 

mériques 1 et 2:

 

-

0:

DIN1 = -

DIN2 = -

-

1:

DIN1 = -

DIN2 = OnOff

 

-

2:

DIN1 = Été/Hiv

DIN2 = -

 

-

3:

DIN1 = Eco

DIN2 = -

 

-

4:

DIN1 = Été/Hiv

DIN2 = On/Off

 

-

5:

DIN1 = Eco

DIN2 = On/Off

 

-

6:

DIN1 = Été/Hiv

DIN2 = Eco

P06 = logique d’utilisation – entrée numérique 1:

-0: [ouvert/fermé] = [Rafraîch./Chauff.] = [-/ECO]

-1: [ouvert/fermé] = [Chauff./Rafraîch.] = [ECO/-]

P07 = logique d’utilisation – entrée numérique 2:

-0: [ouvert/fermé] = [Off/On] = [-/ECO]

-1: [ouvert/fermé] = [On/Off] = [ECO/-]

P08 = sonde humidité éloignée:

-0 : non prévue

-1 : prévue

Selon la valeur programmée, sera contrôlée l’alarme sonde correspondante.

PROCEDURE DE CONFIGURATION DES

PARAMÈTRES

■ Porter le thermostat sur OFF

■ Enfoncer simultanément les touches

Indication niveau: 001= saisie MdP

Utiliser les touches pour modifier la valeur du moniteur jusqu’à la valeur du MdP 10, puis enforcer S’il est correct, on aura accès aux paramètres

Valeur paramètre

 

 

sélectionné

 

 

 

Indication niveau:

 

 

 

 

 

 

Paramètre sélec-

 

 

 

002= sélection

 

 

 

paramètre

tionné: P...

 

 

 

Utiliser les touches pour faire défiler les différents paramètres (voir “List des paramètres, ci-dessus)

Appuyer sur pour activer la modification du paramètre (la valeur affichée commence à clignoter)

Indication niveau:

003 = modification paramètre

Utiliser les touches pour modifier la valeur

Appuyer sur pour sauvegarder la nouvelle valeur ou sur pour annuler la modification

Une fois la modification des paramètres terminée, appuyer

sur la touche

pour quitter la procédure

NB: la procédure de la procedura de paramétrisation a une durée limitée. À l’échéance de la période prévue (2 min. env.) le thermostat revient à l’état de OFF et ne conserve que les modifications sauvegardées.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manuel d'installation et d'utilisation

FWEC2

 

 

 

 

 

 

 

2

Advanced electronic controller

 

 

 

 

 

 

 

FC66002764

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Loading...
+ 102 hidden pages