Daikin RBLQ05 07CAV3, RDLQ05 07CAV3, RKCB07CAV3, RK2CB07CAV3, RKMBUHCA3V3 Installer reference guide

...
5 (1)

Installer reference guide

ROTEX HPSU low temperature monobloc

RBLQ05+07CAV3

RDLQ05+07CAV3

RKCB07CAV3

RK2CB07CAV3

RKMBUHCA3V3

Installer reference guide

English

RKMBUHCA9W1

ROTEX HPSU low temperature monobloc

 

Table of Contents

Table of Contents

5.6.2

Power limitation activated by digital inputs ..................

23

5.6.3

Power limitation process ..............................................

23

5.7 Setting up an external temperature sensor ................................

24

6 Preparation

24

1 General safety precautions

4

1.1

About the documentation ..........................................................

4

 

1.1.1 Meaning of warnings and symbols..............................

4

1.2

For the installer..........................................................................

4

 

1.2.1

General .......................................................................

4

 

1.2.2

Installation site ............................................................

4

 

1.2.3

Refrigerant ..................................................................

5

 

1.2.4

Brine............................................................................

5

 

1.2.5

Water ..........................................................................

5

 

1.2.6

Electrical .....................................................................

6

2

About the documentation

6

 

2.1

About this document..................................................................

6

 

2.2

Installer reference guide at a glance .........................................

7

3

About the box

7

 

3.1

Overview: About the box ...........................................................

7

 

3.2

Outdoor unit...............................................................................

7

 

 

3.2.1

To unpack the outdoor unit .........................................

7

 

 

3.2.2

To remove the accessories from the outdoor unit.......

8

 

3.3

Control box ................................................................................

8

 

 

3.3.1

To unpack the control box...........................................

8

 

 

3.3.2

To remove the accessories from the control box ........

8

 

3.4

Option box .................................................................................

8

 

 

3.4.1

To unpack the option box............................................

8

 

 

3.4.2

To remove the accessories from the option box .........

9

 

3.5

Backup heater ...........................................................................

9

 

 

3.5.1

To unpack the backup heater .....................................

9

 

 

3.5.2

To remove the accessories from the backup heater...

9

4 About the units and options

9

 

4.1

Overview: About the units and options......................................

9

 

4.2

Identification ..............................................................................

9

 

 

4.2.1

Identification label: Outdoor unit .................................

10

 

 

4.2.2

Identification label: Control box...................................

10

 

 

4.2.3

Identification label: Option box....................................

10

 

 

4.2.4

Identification label: Backup heater ..............................

10

 

4.3

Combining units and options .....................................................

10

 

 

4.3.1

Possible combinations of outdoor unit and options.....

10

 

 

4.3.2

Possible options for the outdoor unit...........................

11

 

 

4.3.3

Possible options for the control box ............................

12

 

 

4.3.4

Possible options for the option box .............................

12

4.3.5Possible combinations of outdoor unit and domestic

 

 

 

hot water tank .............................................................

12

 

5 Application guidelines

13

5.1

Overview: Application guidelines...............................................

13

5.2

Setting up the space heating/cooling system ............................

13

 

 

5.2.1

Single room.................................................................

13

 

 

5.2.2

Multiple rooms – One LWT zone ................................

15

 

 

5.2.3

Multiple rooms – Two LWT zones...............................

17

5.3

Setting up an auxiliary heat source for space heating...............

18

5.4

Setting up the domestic hot water tank .....................................

19

 

 

5.4.1

System layout – Standalone DHW tank......................

19

 

 

5.4.2

Selecting the volume and desired temperature for

 

 

 

 

the DHW tank..............................................................

19

 

 

5.4.3

Setup and configuration – DHW tank..........................

20

 

 

5.4.4

DHW pump for instant hot water.................................

20

 

 

5.4.5

DHW pump for disinfection .........................................

20

5.5

Setting up the energy metering .................................................

21

 

 

5.5.1

Produced heat.............................................................

21

 

 

5.5.2

Consumed energy.......................................................

21

 

 

5.5.3

Normal kWh rate power supply...................................

21

 

 

5.5.4

Preferential kWh rate power supply

22

 

 

 

5.6

Setting up the power consumption control ................................

22

 

 

5.6.1

Permanent power limitation ........................................

22

 

 

 

 

 

6.1

Overview: Preparation................................................................

24

6.2

Preparing installation site ...........................................................

24

 

6.2.1

Installation site requirements of the outdoor unit .........

24

6.2.2Additional installation site requirements of the

 

 

outdoor unit in cold climates ........................................

25

 

6.2.3

Installation site requirements of the control box...........

25

 

6.2.4

Installation site requirements of the option box............

26

 

6.2.5

Installation site requirements of the backup heater .....

26

6.3

Preparing water piping ...............................................................

26

 

6.3.1

Water circuit requirements ...........................................

26

6.3.2Formula to calculate the expansion vessel pre-

 

 

pressure .......................................................................

28

 

6.3.3

To check the water volume and flow rate ....................

28

 

6.3.4

Changing the pre-pressure of the expansion vessel....

29

 

6.3.5

To check the water volume: Examples ........................

29

6.4

Preparing electrical wiring ..........................................................

29

 

6.4.1

About preparing electrical wiring..................................

29

 

6.4.2

About preferential kWh rate power supply ...................

29

6.4.3Overview of electrical connections except external

actuators ......................................................................

29

6.4.4Overview of electrical connections for external and

 

 

internal actuators .........................................................

30

7 Installation

31

7.1

Overview: Installation .................................................................

31

7.2

Opening the units .......................................................................

32

 

7.2.1

About opening the units ...............................................

32

 

7.2.2

To open the outdoor unit..............................................

32

 

7.2.3

To open the switch box cover of the outdoor unit ........

32

 

7.2.4

To open the control box ...............................................

32

 

7.2.5

To open the option box ................................................

32

 

7.2.6

To open the backup heater ..........................................

33

 

7.2.7

To open the switch box cover of the backup heater ....

33

7.3

Mounting the outdoor unit...........................................................

33

 

7.3.1

About mounting the outdoor unit..................................

33

 

7.3.2

Precautions when mounting the outdoor unit...............

33

 

7.3.3

To provide the installation structure .............................

33

 

7.3.4

To install the outdoor unit.............................................

34

 

7.3.5

To provide drainage .....................................................

35

 

7.3.6

To prevent the outdoor unit from falling over ...............

35

7.4

Mounting the control box ............................................................

36

 

7.4.1

About mounting the control box ...................................

36

 

7.4.2

Precautions when mounting the control box ................

36

 

7.4.3

To install the control box ..............................................

36

7.5

Mounting the option box .............................................................

36

 

7.5.1

About mounting the option box ....................................

36

 

7.5.2

Precautions when mounting the option box .................

36

 

7.5.3

To install the option box ...............................................

36

7.6

Mounting the backup heater.......................................................

36

 

7.6.1

About mounting the backup heater ..............................

36

 

7.6.2

Precautions when mounting the backup heater...........

36

 

7.6.3

To install the backup heater.........................................

36

7.7

Connecting the water piping.......................................................

37

 

7.7.1

About connecting the water piping...............................

37

 

7.7.2

Precautions when connecting the water piping............

37

 

7.7.3

To connect the water piping.........................................

37

 

7.7.4

To connect the water piping to the backup heater .......

38

 

7.7.5

About the valve kit........................................................

38

 

7.7.6

To protect the water circuit against freezing ................

39

 

7.7.7

To fill the water circuit ..................................................

40

 

7.7.8

To fill the domestic hot water tank ...............................

41

 

7.7.9

To insulate the water piping .........................................

41

7.8

Connecting the electrical wiring..................................................

41

 

7.8.1

About connecting the electrical wiring..........................

41

 

7.8.2

Precautions when connecting the electrical wiring ......

41

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

2

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

Table of Contents

7.8.3

Guidelines when connecting the electrical wiring .......

41

7.8.4

To connect the electrical wiring on the outdoor unit....

41

7.8.5

To connect the main power supply .............................

42

7.8.6

To connect the user interface .....................................

43

7.8.7

To connect the shut-off valve......................................

44

7.8.8

To connect the domestic hot water pump ...................

45

7.8.9

To connect the electrical wiring on the control box .....

45

7.8.10

To connect the control box power supply ...................

45

7.8.11To connect the interconnection cable between

 

control box and outdoor unit .......................................

45

7.8.12

To connect the electrical wiring on the option box ......

46

7.8.13

To connect the option box power supply ....................

46

7.8.14To connect the interconnection cable between option

 

 

 

box and control box.....................................................

46

 

 

7.8.15

To connect the electrical meters .................................

46

 

 

7.8.16

To connect the power consumption digital inputs .......

47

 

 

7.8.17

To connect the alarm output .......................................

47

 

 

7.8.18

To connect the space cooling/heating ON/OFF

 

 

 

 

output ..........................................................................

47

 

 

7.8.19

To connect the changeover to external heat source...

47

 

 

7.8.20

To connect the electrical wiring on the backup heater

48

 

 

7.8.21

To connect the backup heater power supply ..............

48

 

 

7.8.22

To connect the backup heater kit to the control box ...

49

 

 

7.8.23

To connect the valve kit ..............................................

49

 

7.9

Finishing the outdoor unit installation ........................................

50

 

 

7.9.1

To close the outdoor unit ............................................

50

 

7.10

Finishing the control box installation .........................................

50

 

 

7.10.1

To close the control box..............................................

50

 

7.11

Finishing the option box installation ..........................................

50

 

 

7.11.1

To close the option box...............................................

50

 

7.12

Finishing the backup heater installation ....................................

50

 

 

7.12.1

To close the backup heater.........................................

50

8

Configuration

51

 

8.1

Overview: Configuration ............................................................

51

 

 

8.1.1

To connect the PC cable to the switch box.................

51

 

 

8.1.2

To access the most used commands .........................

51

 

 

8.1.3

To copy the system settings from the first to the

 

 

 

 

second user interface..................................................

52

 

 

8.1.4

To copy the language set from the first to the second

 

 

 

 

user interface ..............................................................

53

 

 

8.1.5

Quick wizard: Set the system layout after first power

 

 

 

 

ON...............................................................................

53

 

8.2

Basic configuration ....................................................................

53

 

 

8.2.1

Quick wizard: Language / time and date.....................

53

 

 

8.2.2

Quick wizard: Standard...............................................

53

 

 

8.2.3

Quick wizard: Options .................................................

55

 

 

8.2.4

Quick wizard: Capacities (energy metering) ...............

57

 

 

8.2.5

Space heating/cooling control.....................................

57

 

 

8.2.6

Domestic hot water control .........................................

61

 

 

8.2.7

Contact/helpdesk number ...........................................

62

 

8.3

Advanced configuration/optimization.........................................

62

 

 

8.3.1

Space heating/cooling operation: advanced ...............

62

 

 

8.3.2

Domestic hot water control: advanced........................

66

 

 

8.3.3

Heat source settings ...................................................

70

 

 

8.3.4

System settings...........................................................

71

 

8.4

Menu structure: Overview user settings ....................................

76

 

8.5

Menu structure: Overview installer settings...............................

77

9

Commissioning

78

 

9.1

Overview: Commissioning.........................................................

78

 

9.2

Precautions when commissioning .............................................

78

 

9.3

Checklist before commissioning................................................

78

 

9.4

Checklist during commissioning ................................................

78

 

 

9.4.1

To check the minimum flow rate .................................

78

 

 

9.4.2

Air purge function........................................................

79

 

 

9.4.3

To perform a test run ..................................................

80

 

 

9.4.4

To perform an actuator test run ..................................

80

 

 

9.4.5

Underfloor heating screed dryout................................

80

10.1 About locking and unlocking.......................................................

82

Possible function locks ...............................................................

82

To check if locking is active........................................................

82

To activate or deactivate a function lock ....................................

82

To activate or deactivate button lock..........................................

82

11 Maintenance and service

82

11.1

Overview: Maintenance and service ..........................................

82

11.2

Maintenance safety precautions.................................................

82

 

11.2.1 Opening the outdoor unit .............................................

83

 

11.2.2 Opening the control box...............................................

83

 

11.2.3 Opening the option box................................................

83

 

11.2.4 Opening the backup heater..........................................

83

11.3

Checklist for yearly maintenance of the outdoor unit .................

83

12 Troubleshooting

83

12.1

Overview: Troubleshooting.........................................................

83

12.2

Precautions when troubleshooting .............................................

84

12.3 Solving problems based on symptoms.......................................

84

 

12.3.1

Symptom: The unit is NOT heating or cooling as

 

 

 

expected ......................................................................

84

 

12.3.2

Symptom: The compressor does NOT start (space

 

 

 

heating or domestic water heating)..............................

84

 

12.3.3

Symptom: The pump is making noise (cavitation) .......

84

 

12.3.4

Symptom: The pressure relief valve opens..................

85

 

12.3.5

Symptom: The water pressure relief valve leaks .........

85

 

12.3.6

Symptom: The space is NOT sufficiently heated at

 

 

 

low outdoor temperatures ............................................

85

 

12.3.7

Symptom: The pressure at the tapping point is

 

 

 

temporarily unusual high..............................................

86

 

12.3.8

Symptom: Decoration panels are pushed away due

 

 

 

to a swollen tank ..........................................................

86

 

12.3.9

Symptom: Tank disinfection function is NOT

 

 

 

completed correctly (AH-error).....................................

86

 

12.3.10

Symptom: The energy metering (produced heat) is

 

 

 

NOT working correctly .................................................

86

12.4 Solving problems based on error codes.....................................

86

 

12.4.1

Error codes: Overview .................................................

86

13 Disposal

89

13.1

Overview: Disposal.....................................................................

89

13.2

To pump down............................................................................

89

13.3

To start and stop forced cooling .................................................

89

14 Technical data

90

14.1

Overview: Technical data ...........................................................

90

14.2

Dimensions and service space...................................................

90

 

14.2.1 Dimensions and service space: Outdoor unit ..............

90

 

14.2.2 Dimensions and service space: Options......................

91

14.3

Center of gravity .........................................................................

93

 

14.3.1 Center of gravity: Outdoor unit.....................................

93

 

14.3.2 Center of gravity: Options ............................................

94

14.4

Components ...............................................................................

95

 

14.4.1

Components: Outdoor unit...........................................

95

 

14.4.2 Components: Switch box (outdoor unit).......................

96

 

14.4.3

Components: Options ..................................................

97

 

14.4.4 Components: Switch box (options) ..............................

99

14.5

Piping diagram ...........................................................................

100

 

14.5.1 Piping diagram: Outdoor unit .......................................

100

14.6

Wiring diagram ...........................................................................

101

 

14.6.1 Wiring diagram: Outdoor unit .......................................

101

14.7

Operation range .........................................................................

109

 

14.7.1

Valve kit necessity .......................................................

109

14.8

ESP curve ..................................................................................

110

 

14.8.1 ESP curve: Outdoor unit ..............................................

110

15 Glossary

 

111

16 Field settings table

112

10 Hand-over to the user

82

 

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

3

1 General safety precautions

1 General safety precautions

1.1About the documentation

The original documentation is written in English. All other languages are translations.

The precautions described in this document cover very important topics, follow them carefully.

The installation of the system, and all activities described in the installation manual and the installer reference guide must be performed by an authorized installer.

1.1.1Meaning of warnings and symbols

DANGER

Indicates a situation that results in death or serious injury.

DANGER: RISK OF ELECTROCUTION

Indicates a situation that could result in electrocution.

DANGER: RISK OF BURNING

Indicates a situation that could result in burning because of extreme hot or cold temperatures.

WARNING: FLAMMABLE MATERIAL

WARNING

Indicates a situation that could result in death or serious injury.

CAUTION

Indicates a situation that could result in minor or moderate injury.

NOTICE

Indicates a situation that could result in equipment or property damage.

INFORMATION

Indicates useful tips or additional information.

WARNING

Tear apart and throw away plastic packaging bags so that nobody, especially children, can play with them. Possible risk: suffocation.

DANGER: RISK OF BURNING

Do NOT touch the refrigerant piping, water piping or internal parts during and immediately after operation. It could be too hot or too cold. Give it time to return to normal temperature. If you must touch it, wear protective gloves.

Do NOT touch any accidental leaking refrigerant.

WARNING

Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.

CAUTION

Do NOT touch the air inlet or aluminum fins of the unit.

NOTICE

Do NOT place any objects or equipment on top of the unit.

Do NOT sit, climb or stand on the unit.

NOTICE

Works executed on the outdoor unit are best done under dry weather conditions to avoid water ingress.

In accordance with the applicable legislation, it might be necessary to provide a logbook with the product containing at least: information on maintenance, repair work, results of tests, stand-by periods,…

Also, at least, following information must be provided at an accessible place at the product:

Instructions for shutting down the system in case of an emergency

Name and address of fire department, police and hospital

Name, address and day and night telephone numbers for obtaining service

In Europe, EN378 provides the necessary guidance for this logbook.

1.2For the installer

1.2.1General

If you are not sure how to install or operate the unit, contact your dealer.

NOTICE

Improper installation or attachment of equipment or accessories could result in electric shock, short-circuit, leaks, fire or other damage to the equipment. Only use accessories, optional equipment and spare parts made or approved by ROTEX.

WARNING

Make sure installation, testing and applied materials comply with applicable legislation (on top of the instructions described in the ROTEX documentation).

CAUTION

Wear adequate personal protective equipment (protective gloves, safety glasses,…) when installing, maintaining or servicing the system.

1.2.2Installation site

Provide sufficient space around the unit for servicing and air circulation.

Make sure the installation site withstands the unit's weight and vibration.

Make sure the area is well ventilated. Do NOT block any ventilation openings.

Make sure the unit is level.

Do NOT install the unit in the following places:

In potentially explosive atmospheres.

In places where there is machinery that emits electromagnetic waves. Electromagnetic waves may disturb the control system, and cause malfunction of the equipment.

In places where there is a risk of fire due to the leakage of flammable gases (example: thinner or gasoline), carbon fibre, ignitable dust.

In places where corrosive gas (example: sulphurous acid gas) is produced. Corrosion of copper pipes or soldered parts may cause the refrigerant to leak.

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

4

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

1 General safety precautions

1.2.3Refrigerant

If applicable. See the installation manual or installer reference guide of your application for more information.

NOTICE

Make sure refrigerant piping installation complies with applicable legislation. In Europe, EN378 is the applicable standard.

NOTICE

Make sure the field piping and connections are not subjected to stress.

WARNING

During tests, NEVER pressurize the product with a pressure higher than the maximum allowable pressure (as indicated on the nameplate of the unit).

WARNING

Take sufficient precautions in case of refrigerant leakage. If refrigerant gas leaks, ventilate the area immediately. Possible risks:

Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency.

Toxic gas may be produced if refrigerant gas comes into contact with fire.

WARNING

Always recover the refrigerant. Do NOT release them directly into the environment. Use a vacuum pump to evacuate the installation.

NOTICE

After all the piping has been connected, make sure there is no gas leak. Use nitrogen to perform a gas leak detection.

NOTICE

To avoid compressor breakdown, do NOT charge more than the specified amount of refrigerant.

When the refrigerant system is to be opened, refrigerant must be treated according to the applicable legislation.

WARNING

Make sure there is no oxygen in the system. Refrigerant may only be charged after performing the leak test and the vacuum drying.

In case re-charge is required, refer to the nameplate of the unit. It states the type of refrigerant and necessary amount.

The unit is factory charged with refrigerant and depending on pipe sizes and pipe lengths some systems require additional charging of refrigerant.

Only use tools exclusively for the refrigerant type used in the system, this to ensure pressure resistance and prevent foreign materials from entering into the system.

Charge the liquid refrigerant as follows:

If

Then

A siphon tube is present

Charge with the cylinder upright.

(i.e., the cylinder is marked with "Liquid filling siphon attached")

If

Then

A siphon tube is NOT present

Charge with the cylinder upside

 

down.

 

 

 

 

 

 

 

 

Open refrigerant cylinders slowly.

Charge the refrigerant in liquid form. Adding it in gas form may prevent normal operation.

CAUTION

When the refrigerant charging procedure is done or when pausing, close the valve of the refrigerant tank immediately. If the valve is not closed immediately, remaining pressure might charge additional refrigerant.

Possible consequence: Incorrect refrigerant amount.

1.2.4Brine

If applicable. See the installation manual or installer reference guide of your application for more information.

WARNING

The selection of the brine MUST be in accordance with the applicable legislation.

WARNING

Take sufficient precautions in case of brine leakage. If brine leaks, ventilate the area immediately and contact your local dealer.

WARNING

The ambient temperature inside the unit can get much higher than that of the room, e.g. 70°C. In case of a brine leak, hot parts inside the unit can create a hazardous situation.

WARNING

The use and installation of the application MUST comply with the safety and environmental precautions specified in the applicable legislation.

1.2.5Water

If applicable. See the installation manual or installer reference guide of your application for more information.

NOTICE

Make sure water quality complies with EU directive

98/83 EC.

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

5

2 About the documentation

1.2.6Electrical

DANGER: RISK OF ELECTROCUTION

Turn OFF all power supply before removing the switch box cover, connecting electrical wiring or touching electrical parts.

Disconnect the power supply for more than 1 minute, and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.

Do NOT touch electrical components with wet hands.

Do NOT leave the unit unattended when the service cover is removed.

WARNING

If NOT factory installed, a main switch or other means for disconnection, having a contact separation in all poles providing full disconnection under overvoltage category III condition, shall be installed in the fixed wiring.

WARNING

ONLY use copper wires.

Make sure the field wiring complies with the applicable legislation.

All field wiring must be performed in accordance with the wiring diagram supplied with the product.

NEVER squeeze bundled cables and make sure they do not come in contact with the piping and sharp edges. Make sure no external pressure is applied to the terminal connections.

Make sure to install earth wiring. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earth may cause electrical shock.

Make sure to use a dedicated power circuit. NEVER use a power supply shared by another appliance.

Make sure to install the required fuses or circuit breakers.

Make sure to install an earth leakage protector. Failure to do so may cause electric shock or fire.

When installing the earth leakage protector, make sure it is compatible with the inverter (resistant to high frequency electric noise) to avoid unnecessary opening of the earth leakage protector.

NOTICE

Precautions when laying power wiring:

Do not connect wiring of different thicknesses to the power terminal block (slack in the power wiring may cause abnormal heat).

When connecting wiring which is the same thickness, do as shown in the figure below.

For wiring, use the designated power wire and connect firmly, then secure to prevent outside pressure being exerted on the terminal board.

Use an appropriate screwdriver for tightening the terminal screws. A screwdriver with a small head will damage the head and make proper tightening impossible.

Over-tightening the terminal screws may break them.

Install power cables at least 1 metre away from televisions or radios to prevent interference. Depending on the radio waves, a distance of 1 metre may not be sufficient.

WARNING

After finishing the electrical work, confirm that each electrical component and terminal inside the electrical components box is connected securely.

Make sure all covers are closed before starting up the unit.

NOTICE

Only applicable if the power supply is three phase, and the compressor has an ON/OFF starting method.

If there exists the possibility of reversed phase after a momentary black out and the power goes on and off while the product is operating, attach a reversed phase protection circuit locally. Running the product in reversed phase can break the compressor and other parts.

2 About the documentation

2.1About this document

Target audience

Authorised installers

Documentation set

This document is part of a documentation set. The complete set consists of:

General safety precautions:

Safety instructions that you must read before installing

Format: Paper (in the box of the outdoor unit)

Outdoor unit installation manual:

Installation instructions

Format: Paper (in the box of the outdoor unit)

Control box installation manual:

Installation instructions

Format: Paper (in the box of the control box)

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

6

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

3 About the box

Option box installation manual:

Installation instructions

Format: Paper (in the box of the option box)

Backup heater installation manual:

Installation instructions

Format: Paper (in the box of the backup heater)

Installer reference guide:

Preparation of the installation, technical specifications, good practices, reference data,…

Format: Digital files on the ROTEX homepage

Addendum book for optional equipment:

Additional info about how to install optional equipment

Format: Paper (in the box of the outdoor unit) + Digital files on the ROTEX homepage

Latest revisions of the supplied documentation may be available on the regional ROTEX website or via your dealer.

The original documentation is written in English. All other languages are translations.

3 About the box

3.1Overview: About the box

This chapter describes what you have to do after the boxes with the outdoor unit, control box, and/or backup heater are delivered on-site.

It contains information about:

Unpacking and handling the units

Removing the accessories from the units

Keep the following in mind:

At delivery, the unit must be checked for damage. Any damage must be reported immediately to the carrier's claims agent.

Bring the packed unit as close as possible to its final installation position to prevent damage during transport.

3.2Outdoor unit

3.2.1To unpack the outdoor unit

2.2Installer reference guide at a glance

Chapter

Description

 

 

General safety

Safety instructions that you must read

 

 

precautions

before installing

 

 

About the documentation

What documentation exists for the

 

 

 

installer

 

 

About the box

How to unpack the units and remove

 

 

 

their accessories

 

 

About the units and

▪ How to identify the units

 

 

options

▪ Possible combinations of units and

 

 

 

 

 

 

options

 

 

 

 

 

 

Application guidelines

Various installation setups of the system

 

 

Preparation

What to do and know before going

 

 

 

on site

 

 

Installation

What to do and know to install the

 

 

 

system

 

 

Configuration

What to do and know to configure the

 

 

 

system after it is installed

 

 

Commissioning

What to do and know to commission the

 

 

 

system after it is configured

 

 

Hand over to the user

What to give and explain to the user

 

 

 

 

 

 

Maintenance and service

How to maintain and service the units

 

 

Troubleshooting

What to do in case of problems

 

 

Disposal

How to dispose of the system

 

 

 

 

 

 

Technical data

Specifications of the system

 

 

Glossary

Definition of terms

 

 

 

 

 

 

Field settings table

Table to be filled in by the installer, and

 

 

 

kept for future reference

 

 

 

Note: There is also an installer settings

 

 

 

table in the user reference guide. This

 

 

 

table has to be filled in by the installer

 

 

 

and handed over to the user.

 

 

 

 

 

 

1

2

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

7

Daikin RBLQ05 07CAV3, RDLQ05 07CAV3, RKCB07CAV3, RK2CB07CAV3, RKMBUHCA3V3 Installer reference guide

3 About the box

3.2.2To remove the accessories from the outdoor unit

1 Open the outdoor unit.

2 Remove the accessories.

a

b

c

d

e

f

 

g

 

aGeneral safety precautions

bAddendum book for optional equipment

cOutdoor unit installation manual

dOperation manual

eSealing ring for shut-off valve

fShut-off valve

gUnit mounting plate

3.3Control box

NOTICE

Control box RKCB07CAV3 is an option and can only be

used in combination with outdoor units RDLQ05+07CAV3

and RBLQ05+07CAV3.

3.3.1To unpack the control box

1

2

3.3.2To remove the accessories from the control box

1 Open the control box.

2 Remove the accessories.

a

b

c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

aM4 bolts for user interface

bM4 nuts for user interface

cWires for domestic hot water booster heater relay

3.4Option box

NOTICE

Option box RK2CB07CAV3 is an option and can only be used in combination with outdoor units RDLQ05+07CAV3 and RBLQ05+07CAV3.

To be able to use the option box, it is required that optional control box RKCB07CAV3 is part of the system.

3.4.1To unpack the option box

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

 

 

 

 

 

8

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

 

 

4P415097-1A – 2016.02

4 About the units and options

2

3.4.2To remove the accessories from the option box

1 Open the option box.

2 Remove the accessories.

a

aConnectors for interconnection cable between the option box and control box RKCB07CAV3.

3.5Backup heater

NOTICE

The backup heater is an option and can only be used in combination with outdoor units RDLQ05+07CAV3 and

RBLQ05+07CAV3.

To be able to use the backup heater, it is required that optional control box RKCB07CAV3 is part of the system.

3.5.1To unpack the backup heater

1

2

3.5.2To remove the accessories from the backup heater

1 Remove the wall bracket from the box.

4 About the units and options

4.1Overview: About the units and options

This chapter contains information about:

Identifying the outdoor unit

Identifying the control box

Identifying the backup heater

Combining the outdoor unit with options

Combining the control box with options

Possible combinations of outdoor unit and control box

4.2Identification

NOTICE

When installing or servicing several units at the same time, make sure NOT to switch the service panels between different models.

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

9

4 About the units and options

4.2.1Identification label: Outdoor unit

Location

Model identification

Example: R B/D L Q 05 CA V3

Code

Explanation

R

Monobloc outdoor heat pump

 

 

B

B=Reversible (heating+cooling)

D

D=Heating only

 

 

L

Low water temperature – ambient zone: −10~

 

−25°C

Q

Refrigerant R410A

05

Capacity class

CA

Model series

 

 

V3

Power supply

4.2.2Identification label: Control box

Location

Model identification

Example: RK CB 07 CA V3

Code

Description

RK

ROTEX kit

 

 

CB

Control box

07

Capacity class

 

 

CA

Model series

 

 

V3

Power supply

4.2.3Identification label: Option box

Location

Code

Description

RK

ROTEX kit

 

 

2

Optional

CB

Control box

07

Capacity class

 

 

CA

Model series

V3

Power supply

 

 

4.2.4Identification label: Backup heater

Location

Model identification

Example: RK M BUH CA 3 V3

Code

Explanation

RK

ROTEX kit

 

 

M

Designed for Monobloc

BUH

Backup heater

 

 

CA

Model series

3

Capacity of heater kit (kW)

V3

Power supply

 

 

4.3Combining units and options

4.3.1Possible combinations of outdoor unit and options

f

g

i

a

b

c

d

e

d

 

 

 

 

 

FHL1

 

 

 

 

 

FHL2

FHL3

h

Model identification

Example: RK 2 CB 07 CA V3

aOutdoor unit (RBLQ05+07CAV3 or RDLQ05+07CAV3)

bRefrigerant part of the outdoor unit

cHydro part of the outdoor unit

dValve kit EKMBHBP1

eBackup heater kit (RKMBUHCA3V3 or RKMBUHCA9W1)

fControl box RKCB07CAV3

gOption box RK2CB07CAV3

hDomestic hot water tank

iSpace heating circuit

 

 

Option

System components required for that option

 

 

 

 

 

 

Outdoor unit

Control box

Option box

 

Valve kit EKMBHBP1

 

 

 

RBLQ05+07CAV3 or

RKCB07CAV3

RK2CB07CAV3

 

 

 

 

RDLQ05+07CAV3

 

 

 

 

 

 

 

 

 

Optional equipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installer reference guide

 

 

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

 

 

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

 

 

 

 

 

 

4P415097-1A – 2016.02

4 About the units and options

Option

System components required for that option

 

 

 

Outdoor unit

Control box

Option box

Valve kit EKMBHBP1

 

RBLQ05+07CAV3 or

RKCB07CAV3

RK2CB07CAV3

 

 

RDLQ05+07CAV3

 

 

 

User interface (RKRUCBL*)

O

 

 

 

(mandatory)

 

 

 

 

Domestic hot water tank

O

O

 

 

Remote outdoor sensor

O

 

 

 

(EKRSCA1)

 

 

 

 

PC configurator

O

 

 

 

(EKPCCAB)

 

 

 

 

Room thermostat

O

O

 

 

(RKRTWA, RKRTR1)

 

 

 

 

Remote sensor for wireless

O

O

 

 

thermostat (EKRTETS)

 

 

 

 

Heat pump convector

O

O

 

 

(RFWXV)

 

 

 

 

Backup heater kit

O

O

 

O(a)

(RKMBUHCA3V3,

 

 

 

 

RKMBUHCA9W1)

 

 

 

 

Remote indoor sensor

O

O

O

 

(KRCS01-1)

 

 

 

 

Field-supplied components

 

 

 

 

Space heating/cooling

O

 

 

 

operation control (or

 

 

 

 

shut off valve)

 

 

 

 

Preferential kWh rate

O

O

 

 

power supply (voltage free

 

 

 

 

contact)

 

 

 

 

Domestic hot water pump

O

O

 

 

 

 

 

 

 

Electric meter

O

O

O

 

Power consumption digital

O

O

O

 

inputs

 

 

 

 

Alarm output

O

O

O

 

Space cooling/heating ON/

O

O

O

 

OFF output

 

 

 

 

Changeover to external

O

O

O

 

heat source

 

 

 

 

(a)Only for RBLQ05+07CAV3.

4.3.2Possible options for the outdoor unit

User interface (RKRUCBL*)

The user interface and a possible additional user interface are available as an option.

The additional user interface can be connected:

To have both:

control close to the control box,

room thermostat functionality in the principal space to be heated.

To have an interface containing other languages.

Following user interfaces are available:

RKRUCBL1 contains following languages: German, French, Dutch, Italian.

RKRUCBL2 contains following languages: English, Swedish, Norwegian, Finnish.

RKRUCBL3 contains following languages: English, Spanish, Greek, Portuguese.

RKRUCBL4 contains following languages: English, Turkish, Polish, Romanian.

RKRUCBL5 contains following languages: German, Czech,

Slovenian, Slovakian.

RKRUCBL6 contains following languages: English, Croatian, Hungarian, Estonian.

RKRUCBL7 contains following languages: English, German,

Russian, Danish.

Languages on the user interface can be uploaded by PC software or copied from an user interface to the other.

For installation instructions, see "7.8.6 To connect the user interface" on page 43.

INFORMATION

If control box RKCB07CAV3 is NOT part of the system, connect the user interface directly to the outdoor unit.

If control box RKCB07CAV3 is part of the system, you can also connect the user interface to the control box.

Domestic hot water tank

For providing domestic hot water, a domestic hot water tank can be connected to the outdoor unit.

The following domestic hot water tanks are available:

Polypropylene tank (HYC)

There are 2 types available: 300 and 500 litre.

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

11

4 About the units and options

For installation instructions, see the installation manual of the domestic hot water tank and addendum book for optional equipment.

INFORMATION

The domestic hot water tank can only be connected if control box RKCB07CAV3 is part of the system.

The domestic hot water tank is connected to the hydro part of the outdoor unit, and wired to control box RKCB07CAV3.

Remote outdoor sensor (EKRSCA1)

By default the sensor inside the outdoor unit will be used to measure the outdoor temperature.

As an option the remote outdoor sensor can be installed to measure the outdoor temperature on another location (e.g. to avoid direct sunlight) to have an improved system behaviour.

For installation instructions, see the installation manual of the remote outdoor sensor and the addendum book for optional equipment.

Heat pump convector (RFWXV)

For providing space heating/cooling, it is possible to use heat pump convectors (RFWXV).

For installation instructions, refer to the installation manual of the heat pump convectors, and the addendum book for optional equipment.

Room thermostat (RKRTWA, RKRTR1, RTRNETA)

You can connect an optional room thermostat to control box RKCB07CAV3.This thermostat can either be wired (RKRTWA) or wireless (RKRTR1and RTRNETA). Thermostat RTRNETA can only be used in heating-only systems.

For installation instructions, see the installation manual of the room thermostat and addendum book for optional equipment.

Remote sensor for wireless thermostat (EKRTETS)

You can use a wireless indoor temperature sensor (EKRTETS) only in combination with the wireless thermostat (RKRTR1).

For installation intructions, see the installation manual of the room thermostat and addendum book for optional equipment.

PC configurator (EKPCCAB)

The PC cable makes a connection between the switch box of the outdoor unit (or that of control box RKCB07CAV3) and a PC. It gives the possibility to upload different language files to the user interface, and parameters to the outdoor unit. For the available language files, contact your local dealer.

The software and corresponding operating instructions are available on the ROTEX homepage.

For installation instructions, see the installation manual of the PC cable, the "8 Configuration" on page 51 chapter, and the addendum book for optional equipment.

4.3.3Possible options for the control box

User interface (RKRUCBL*)

The user interface and a possible additional user interface are available as an option.

The additional user interface can be connected:

To have both:

control close to the control box,

room thermostat functionality in the principal space to be heated.

To have an interface containing other languages.

Following user interfaces are available:

RKRUCBL1 contains following languages: German, French, Dutch, Italian.

RKRUCBL2 contains following languages: English, Swedish, Norwegian, Finnish.

RKRUCBL3 contains following languages: English, Spanish, Greek, Portuguese.

RKRUCBL4 contains following languages: English, Turkish, Polish, Romanian.

RKRUCBL5 contains following languages: German, Czech,

Slovenian, Slovakian.

RKRUCBL6 contains following languages: English, Croatian, Hungarian, Estonian.

RKRUCBL7 contains following languages: English, German,

Russian, Danish.

Languages on the user interface can be uploaded by PC software or copied from an user interface to the other.

For installation instructions, see "7.8.6 To connect the user interface" on page 43.

INFORMATION

If control box RKCB07CAV3 is NOT part of the system, connect the user interface directly to the outdoor unit.

If control box RKCB07CAV3 is part of the system, you can also connect the user interface to the control box.

4.3.4Possible options for the option box

Remote indoor sensor (KRCS01-1)

By default the internal user interface sensor will be used as room temperature sensor.

As an option the remote indoor sensor can be installed to measure the room temperature on another location.

The remote indoor sensor is connected to option box RK2CB07CAV3. For installation instructions, see the installation manual of the remote indoor sensor and the addendum book for optional equipment.

INFORMATION

The remote indoor sensor can only be used in case the user interface is configured with room thermostat functionality.

You can only connect either the remote indoor sensor or the remote outdoor sensor.

4.3.5Possible combinations of outdoor unit and domestic hot water tank

Outdoor unit

Domestic hot water tank

 

HYC 343/19/0-DB

HYC 544/32/0-DB

RBLQ05CAV3

O

O

 

 

 

RBLQ07CAV3

O

O

RDLQ05CAV3

O

O

 

 

 

RDLQ07CAV3

O

O

 

 

 

INFORMATION

The domestic hot water tank can only be connected if control box RKCB07CAV3 is part of the system.

The domestic hot water tank is connected to the hydro part of the outdoor unit, and wired to control box

RKCB07CAV3.

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

12

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

5 Application guidelines

5 Application guidelines

5.1Overview: Application guidelines

The purpose of the application guidelines is to give a glance of the possibilities of the ROTEX heat pump system.

NOTICE

The illustrations in the application guidelines are meant for reference only, and are NOT to be used as detailed hydraulic diagrams. The detailed hydraulic dimensioning and balancing are NOT shown, and are the responsibility of the installer.

For more information about the configuration settings to optimize heat pump operation, see "8 Configuration" on page 51.

This chapter contains application guidelines for:

Setting up the space heating/cooling system

Setting up an auxiliary heat source for space heating

Setting up the domestic hot water tank

Setting up the energy metering

Setting up the power consumption

Setting up an external temperature sensor

5.2Setting up the space heating/ cooling system

The heat pump system supplies leaving water to heat emitters in one or more rooms.

Because the system offers a wide flexibility to control the temperature in each room, you need to answer the following questions first:

▪ How many rooms are heated (or cooled) by the ROTEX heat pump system?

Which heat emitter types are used in each room and what is their design leaving water temperature?

Once the space heating/cooling requirements are clear, ROTEX recommends to follow the setup guidelines below.

NOTICE

If an external room thermostat is used, the external room thermostat will control the room frost protection. However, the room frost protection is only possible if the leaving water temperature control on the unit's user interface is turned ON.

INFORMATION

In case an external room thermostat is used and room frost protection needs to be guaranteed in all conditions, then you have to set auto emergency [A.5.1.2] to 1.

5.2.1Single room

Under floor heating or radiators – Wired room thermostat

Setup

A

B

c

b

a

AMain leaving water temperature zone

BOne single room

aUser interface used as room thermostat

bControl box

cBackup heater (option)

The under floor heating or radiators are directly connected to the outdoor unit – or to the backup heater, if there is one.

The room temperature is controlled by the user interface, that is connected to control box RKCB07CAV3. Possible installations:

Control box RKCB07CAV3 is installed in the room and the user interface is used as room thermostat.

Control box RKCB07CAV3 is installed indoors, close to the outdoor unit + user interface installed in the room and used as room thermostat.

Configuration

 

Setting

 

Value

Unit temperature control:

2

(RT control): Unit operation is

#: [A.2.1.7]

decided based on the ambient

temperature of the user interface.

Code: [C-07]

 

 

Number of water temperature

0

(1 LWT zone): Main

zones:

 

 

#: [A.2.1.8]

Code: [7-02]

Benefits

Cost effective. You do NOT need an additional external room thermostat.

Highest comfort and efficiency. The smart room thermostat functionality can decrease or increase the desired leaving water temperature based on the actual room temperature (modulation).

This results in:

Stable room temperature matching the desired temperature

(higher comfort)

Less ON/OFF cycles (more quiet, higher comfort and higher efficiency)

Lowest possible leaving water temperature (higher efficiency)

Easy. You can easily set the desired room temperature via the user interface:

For your daily needs, you can use preset values and schedules.

To deviate from your daily needs, you can temporarily overrule the preset values and schedules, use the holiday mode…

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

13

5 Application guidelines

Under floor heating or radiators – Wireless room thermostat

Setup

 

A

 

B

c

 

b

d

 

a

e

AMain leaving water temperature zone

BOne single room

aUser interface

bControl box

cBackup heater (option)

dReceiver for wireless external room thermostat

eWireless external room thermostat

The under floor heating or radiators are directly connected to the outdoor unit – or to the backup heater, if there is one.

The room temperature is controlled by the wireless external room thermostat (optional equipment RKRTR1).

Configuration

Heat pump convectors

Setup

A

B

c

b

d a

AMain leaving water temperature zone

BOne single room

aUser interface

bControl box

cBackup heater (option)

dRemote controller of the heat pump convectors

The under floor heating or radiators are directly connected to the outdoor unit – or to the backup heater, if there is one.

The desired room temperature is set via the remote controller of the heat pump convectors.

The space heating/cooling demand signal is sent to one digital input on control box RKCB07CAV3 (X2M/1 and X2M/2).

 

Setting

 

Value

Unit temperature control:

1

(Ext RT control): Unit operation

#: [A.2.1.7]

is decided by the external

thermostat.

Code: [C-07]

 

 

Number of water temperature

0

(1 LWT zone): Main

zones:

 

 

#: [A.2.1.8]

Code: [7-02]

External room thermostat for the

1 (Thermo ON/OFF): When the

main zone:

used external room thermostat or

#: [A.2.2.E.5]

heat pump convector can only

send a thermo ON/OFF

Code: [C-05]

condition.

Benefits

Wireless. The ROTEX external room thermostat is available in a wireless version.

Efficiency. Although the external room thermostat only sends ON/ OFF signals, it is specifically designed for the heat pump system.

Comfort. In case of under floor heating, the wireless external room thermostat prevents condensation on the floor during cooling operation by measuring the room humidity.

The space operation mode is sent to the heat pump convectors by one digital output on control box RKCB07CAV3 (X8M/6 and

X8M/7).

INFORMATION

When using multiple heat pump convectors, make sure each one receives the infrared signal from the remote controller of the heat pump convectors.

Configuration

 

Setting

 

Value

Unit temperature control:

1

(Ext RT control): Unit operation

#: [A.2.1.7]

is decided by the external

thermostat.

Code: [C-07]

 

 

 

 

 

Number of water temperature

0

(1 LWT zone): Main

zones:

 

 

#: [A.2.1.8]

Code: [7-02]

External room thermostat for the

1 (Thermo ON/OFF): When the

main zone:

used external room thermostat or

#: [A.2.2.E.5]

heat pump convector can only

send a thermo ON/OFF

Code: [C-05]

condition.

Benefits

Cooling. The heat pump convector offers, besides heating capacity, also excellent cooling capacity.

Efficiency. Optimal energy efficiency because of the interlink function.

Stylish.

Combination: Under floor heating + Heat pump convectors

Space heating is provided by:

The under floor heating

The heat pump convectors

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

14

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

5 Application guidelines

Space cooling is provided by the heat pump convectors only. The under floor heating is shut off by the shut-off valve.

Setup

5.2.2Multiple rooms – One LWT zone

If only one leaving water temperature zone is needed because the design leaving water temperature of all heat emitters is the same, you do NOT need a mixing valve station (cost effective).

Example: If the heat pump system is used to heat up one floor where all the rooms have the same heat emitters.

A

B

c

M1

b

d

a

Under floor heating or radiators – Thermostatic valves

If you are heating up rooms with under floor heating or radiators, a very common way is to control the temperature of the main room by using a thermostat (this can either be the user interface connected to control box RKCB07CAV3, or an external room thermostat), while the other rooms are controlled by so-called thermostatic valves (field supply), which open or close depending on the room temperature.

Setup

AMain leaving water temperature zone

BOne single room

aUser interface

bControl box

cBackup heater (option)

dRemote controller of the heat pump convectors

The heat pump convectors are directly connected to the outdoor unit – or to the backup heater, if there is one.

A shut-off valve (field supply) is installed before the under floor heating to prevent condensation on the floor during cooling operation.

The desired room temperature is set via the remote controller of the heat pump convectors.

The space heating/cooling demand signal is sent to one digital input on control box RKCB07CAV3 (X2M/1 and X2M/2)

The space operation mode is sent by one digital output (X8M/6 and X8M/7) on control box RKCB07CAV3 to:

The heat pump convectors

The shut-off valve

Configuration

 

Setting

 

Value

Unit temperature control:

1

(Ext RT control): Unit operation

#: [A.2.1.7]

is decided by the external

thermostat.

Code: [C-07]

 

 

Number of water temperature

0

(1 LWT zone): Main

zones:

 

 

#: [A.2.1.8]

Code: [7-02]

External room thermostat for the

1 (Thermo ON/OFF): When the

main zone:

used external room thermostat or

#: [A.2.2.E.5]

heat pump convector can only

send a thermo ON/OFF

Code: [C-05]

condition.

Benefits

Cooling. Heat pump convectors provide, besides heating capacity, also excellent cooling capacity.

Efficiency. Under floor heating has the best performance with

ROTEX HPSU.

Comfort. The combination of the two heat emitter types provides: ▪ The excellent heating comfort of the under floor heating

A

B C

c

T

b a

AMain leaving water temperature zone

BRoom 1

CRoom 2

aUser interface

bControl box

cBackup heater (option)

The under floor heating of the main room is directly connected to the outdoor unit – or to the backup heater, if there is one.

The room temperature of the main room is controlled by the user interface used as thermostat.

A thermostatic valve is installed before the under floor heating in each of the other rooms.

INFORMATION

Mind situations where the main room can be heated by another heating source. Example: Fireplaces.

Configuration

 

Setting

 

Value

Unit temperature control:

2

(RT control): Unit operation is

#: [A.2.1.7]

decided based on the ambient

temperature of the user interface.

Code: [C-07]

 

 

Number of water temperature

0

(1 LWT zone): Main

zones:

 

 

#: [A.2.1.8]

Code: [7-02]

Benefits

Cost effective.

Easy. Same installation as for one room, but with thermostatic valves.

Under floor heating or radiators – Multiple external

▪ The excellent cooling comfort of the heat pump convectors

room thermostats

Setup

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

15

5 Application guidelines

 

 

A

 

 

 

 

B

C

 

c

 

M1

M2

d

 

 

 

b

a

e

 

e

 

 

 

 

 

AMain leaving water temperature zone

BRoom 1

CRoom 2

aUser interface

bControl box

cBackup heater (option)

dBypass valve

eExternal room thermostat

For each room, a shut-off valve (field supplied) is installed to avoid leaving water supply when there is no heating or cooling demand.

A bypass valve must be installed to make water recirculation possible when all shut-off valves are closed. To guarantee reliable operation, provide a minimum water flow as described in table "To check the water volume and flow rate" in "6.3 Preparing water piping" on page 26.

The main user interface (connected to control box RKCB07CAV3) decides the space operation mode. Mind that the space operation mode of the additional user interfaces (used as room thermostat) must be set to match that of the main user interface.

The room thermostats are connected to the shut-off valves, and do NOT have to be connected to the outdoor unit. The outdoor unit will supply leaving water all the time, with the possibility to program a leaving water schedule.

Configuration

 

Setting

Value

Unit temperature control:

0 (LWT control): Unit operation is

#: [A.2.1.7]

decided based on the leaving

water temperature.

Code: [C-07]

 

Number of water temperature

0 (1 LWT zone): Main

zones:

 

#: [A.2.1.8]

 

Code: [7-02]

 

Benefits

Compared with under floor heating or radiators for one room:

Comfort. You can set the desired room temperature, including schedules, for each room via the room thermostats.

Heat pump convectors

Setup

A

C

B

c

 

b

 

d

d

a

 

AMain leaving water temperature zone

BRoom 1

C Room 2

aUser interface

bControl box

cBackup heater (option)

dRemote controller of the heat pump convectors

The desired room temperature is set via the remote controller of the heat pump convectors.

The main user interface (connected to control box RKCB07CAV3) decides the space operation mode.

The heating demand signals of each heat pump convector are connected in parallel to the digital input on control box RKCB07CAV3 (X2M/1 and X2M/2). The outdoor unit will only supply leaving water temperature when there is an actual demand.

INFORMATION

To increase comfort and performance, ROTEX recommends to install the valve kit option EKVKHPC on each heat pump convector.

Configuration

 

Setting

 

Value

Unit temperature control:

1

(Ext RT control): Unit operation

#: [A.2.1.7]

is decided by the external

thermostat.

Code: [C-07]

 

 

Number of water temperature

0

(1 LWT zone): Main

zones:

 

 

#: [A.2.1.8]

Code: [7-02]

Benefits

Compared with heat pump convectors for one room:

Comfort. You can set the desired room temperature, including schedules, for each room via the remote controller of the heat pump convectors.

Combination: Under floor heating + Heat pump convectors

Setup

A

 

B

C

c

 

M1

 

M1

 

 

e

b

d

a

AMain leaving water temperature zone

BRoom 1

CRoom 2

aUser interface

bControl box

cBackup heater (option)

dExternal room thermostat

eRemote controller of the heat pump convectors

For each room with heat pump convectors: The heat pump convectors are directly connected to the outdoor unit – or to the backup heater, if there is one.

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

16

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

5 Application guidelines

For each room with under floor heating: Two shut-off valves (field supply) are installed before the under floor heating:

A shut-off valve to prevent hot water supply when the room has no heating demand

A shut-off valve to prevent condensation on the floor during cooling operation of the rooms with heat pump convectors.

For each room with heat pump convectors: The desired room temperature is set via the remote controller of the heat pump convectors.

For each room with under floor heating: The desired room temperature is set via the external room thermostat (wired or wireless).

The main user interface (connected to control box RKCB07CAV3) decides the space operation mode. Mind that the operation mode of each external room thermostat and heat pump convector remote controller must be set to match that of the main user interface.

INFORMATION

To increase comfort and performance, ROTEX recommends to install the valve kit option EKVKHPC on each heat pump convector.

Configuration

 

Setting

 

Value

Unit temperature control:

0

(LWT control): Unit operation is

#: [A.2.1.7]

decided based on the leaving

water temperature.

Code: [C-07]

 

 

Number of water temperature

0

(1 LWT zone): Main

zones:

 

 

#: [A.2.1.8]

Code: [7-02]

5.2.3Multiple rooms – Two LWT zones

If the heat emitters selected for each room are designed for different leaving water temperatures, you can use different leaving water temperature zones (maximum 2).

In this document:

Main zone = Zone with the lowest design temperature in heating, and the highest design temperature in cooling

Additional zone = The other zone

NOTICE

If there are two leaving water temperature zones, and an external room thermostat is used, then cooling operation is NOT possible.

CAUTION

When there is more than one leaving water zone, you must

ALWAYS install a mixing valve station in the main zone to decrease (in heating)/increase (in cooling) the leaving water temperature when the additional zone has demand.

Typical example:

Room (zone)

Heat emitters: Design

 

 

 

temperature

 

 

Living room (main zone)

Under floor heating: 35°C

 

 

 

 

 

 

Bed rooms (additional zone)

Heat pump convectors: 45°C

 

 

 

 

 

 

Setup

A

B C

f

f

 

e

D

d

E

 

 

c

 

 

b

 

 

a

AAdditional leaving water temperature zone

BRoom 1

CRoom 2

DMain leaving water temperature zone

ERoom 3

aUser interface

bControl box

cBackup heater (option)

dPressure-regulating valve

eMixing valve station

fRemote controller of the heat pump convectors

INFORMATION

A pressure regulating valve should be implemented before the mixing valve station. This is to guarantee the correct water flow balance between the main leaving water temperature zone and the additional leaving water temperature zone in relation to the required capacity of both water temperature zones.

For the main zone:

A mixing valve station is installed before the under floor heating.

The room temperature is controlled by the user interface, which is used as room thermostat.

NOTICE

ROTEX is NOT responsible for the operation of the mixing valve station pump. It is the responsibility of the installer to guarantee pump operation.

For the additional zone:

The heat pump convectors are directly connected to the outdoor unit – or to the backup heater, if there is one.

The desired room temperature is set via the remote controller of the heat pump convectors for each room.

The heating or cooling demand signals of each heat pump convector are connected in parallel to the digital input on control box RKCB07CAV3 (X2M/1 and X2M/2). The outdoor unit will only supply the desired additional leaving water temperature when there is an actual demand.

The main user interface (connected to control box RKCB07CAV3) decides the space operation mode. Mind that the operation mode of each heat pump convector remote controller must be set to match that of the main user interface.

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

17

5 Application guidelines

Configuration

 

Setting

Value

Unit temperature control:

2 (RT control): Unit operation is

#: [A.2.1.7]

decided based on the ambient

temperature of the user interface.

Code: [C-07]

Note:

 

 

 

 

▪ Main room = user interface

 

 

used as room thermostat

 

 

functionality

 

 

▪ Other rooms = external room

 

 

thermostat functionality

Number of water temperature

1 (2 LWT zones): Main +

zones:

additional

#: [A.2.1.8]

Code: [7-02]

In case of heat pump convectors:

1 (Thermo ON/OFF): When the

External room thermostat for the

used external room thermostat or

additional zone:

heat pump convector can only

send a thermo ON/OFF

#: [A.2.2.5]

condition. No separation between

Code: [C-06]

heating or cooling demand.

 

 

 

Shut off valve

If the main zone must be shut off

 

 

during cooling mode to prevent

 

 

condensation on the floor, set it

 

 

accordingly.

At the mixing valve station

Set the desired main leaving

 

 

water temperature for heating

 

 

and/or cooling.

Benefits

Comfort.

The smart room thermostat functionality can decrease or increase the desired leaving water temperature based on the actual room temperature (modulation).

The combination of the two heat emitter systems provides the excellent heating comfort of the under floor heating, and the excellent cooling comfort of the heat pump convectors.

Efficiency.

Depending on the demand, the outdoor unit supplies different leaving water temperature matching the design temperature of the different heat emitters.

Under floor heating has the best performance with ROTEX

HPSU.

5.3Setting up an auxiliary heat source for space heating

Space heating can be done by:

The outdoor unit

An auxiliary boiler (field supply) connected to the system

When the room thermostat requests heating, the outdoor unit or the auxiliary boiler starts operating depending on the outdoor temperature (status of the changeover to external heat source).

When the permission is given to the auxiliary boiler, the space heating by the outdoor unit is turned OFF.

Bivalent operation is only possible for space heating, NOT for domestic hot water production. Domestic hot water is always produced by the DHW tank connected to the outdoor unit.

INFORMATION

For bivalent operation to be possible, the system requires control box RK2CB07CAV3.

INFORMATION

▪ During heating operation of the heat pump, the heat pump operates to achieve the desired temperature set via the user interface. When weatherdependent operation is active, the water temperature is determined automatically depending on the outdoor temperature.

During heating operation of the auxiliary boiler, the auxiliary boiler operates to achieve the desired water temperature set via the auxiliary boiler controller.

Setup

▪ Integrate the boiler as follows:

a

b

c

i

j

l

 

 

d

M

 

 

 

 

 

 

 

 

 

d

e

j

 

 

 

 

 

 

 

 

 

k

 

 

 

f

h

m

 

 

 

 

 

 

 

 

 

n

k

 

 

 

 

 

 

g

p

 

FHL1

 

FHL2

o

FHL3

 

aOutdoor unit

bHeat exchanger

cPump

dShut off valve

eBackup heater (option)

fControl box

gUser interface

hOption box

iMotorised 3 way valve (delivered with the domestic hot water tank)

jNon return valve (field supply)

kShut off valve (field supply)

lCollector (field supply)

mAuxiliary boiler (field supply)

nAquastat valve (field supply)

oDomestic hot water tank (option)

pHeat exchanger coil

FHL1...3 Under floor heating

NOTICE

Make sure the auxiliary boiler and its integration in the system complies with applicable legislation.

ROTEX is NOT responsible for incorrect or unsafe situations in the auxiliary boiler system.

Make sure the return water to the heat pump does NOT exceed 55°C. To do so:

Set the desired water temperature via the auxiliary boiler controller to maximum 55°C.

▪ Install an aquastat valve in the return water flow of the heat pump.

Set the aquastat valve to close above 55°C and to open below 55°C.

Install non-return valves.

Make sure to only have one expansion vessel in the water circuit.

An expansion vessel is already pre-mounted in the outdoor unit.

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

18

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

5 Application guidelines

Install control box RKCB07CAV3 and option box RK2CB07CAV3.

Connect X8M/3 and X8M/4 (changeover to external heat source) on option box RK2CB07CAV3 to the auxiliary boiler thermostat.

To setup the heat emitters, see "5.2 Setting up the space heating/ cooling system" on page 13.

Configuration

Via the user interface (quick wizard):

Set the use of a bivalent system as external heat source.

Set the bivalent temperature and hysteresis.

NOTICE

Make sure the bivalent hysteresis has enough differential to prevent frequent changeover between outdoor unit and auxiliary boiler.

Because the outdoor temperature is measured by the outdoor unit air thermistor, install the outdoor unit in the shadow so that it is NOT influenced or turned ON/OFF by direct sunlight.

Frequent changeover may cause corrosion of the auxiliary boiler. Contact the manufacturer of the auxiliary boiler for more information.

Changeover to external heat source decided by an auxiliary contact

Only possible in external room thermostat control AND one leaving water temperature zone (see "5.2 Setting up the space heating/cooling system" on page 13).

The auxiliary contact can be:

▪ An outdoor temperature thermostat

5.4Setting up the domestic hot water tank

5.4.1System layout – Standalone DHW tank

a

b

c

 

h

k

 

 

 

d

M

 

 

 

 

 

 

 

 

 

d

e

 

 

 

 

 

 

 

 

 

 

FHL1

FHL2

 

 

 

 

j

 

 

 

 

FHL3

f

i

g

aOutdoor unit

bHeat exchanger

cPump

dShut off valve

eBackup heater (option)

fControl box

gUser interface

hMotorised 3 way valve

iDomestic hot water tank

jHeat exchanger coil

kCollector (field supply) FHL1...3 Under floor heating

An electricity tariff contact

A manually operated contact

Setup: Connect the following field wiring:

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

 

 

Com

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control box

 

 

 

 

 

 

Outdoor/Auto/Boiler

 

 

 

 

 

 

 

 

 

BTI

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X2M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

4

 

 

X

Y

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K1A

 

K2A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

K1A

 

 

K2A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BTI

Boiler thermostat input

 

 

 

 

 

 

A

Auxiliary contact (normal closed)

 

 

 

 

 

 

H

Heating demand room thermostat (optional)

K1A

Auxiliary relay for activation of outdoor unit (field supply)

K2A

Auxiliary relay for activation of boiler (field supply)

Outdoor

Outdoor unit

 

 

 

 

 

 

Auto

Automatic

 

 

 

 

 

 

Boiler

Boiler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control box

Control box

 

 

 

 

 

 

NOTICE

Make sure the auxiliary contact has enough differential or time delay to prevent frequent changeover between outdoor unit and auxiliary boiler.

If the auxiliary contact is an outdoor temperature thermostat, install the thermostat in the shadow so that it is NOT influenced or turned ON/OFF by direct sunlight.

Frequent changeover may cause corrosion of the auxiliary boiler. Contact the manufacturer of the auxiliary boiler for more information.

5.4.2Selecting the volume and desired temperature for the DHW tank

People experience water as hot when its temperature is 40°C. Therefore, the DHW consumption is always expressed as equivalent hot water volume at 40°C. However, you can set the DHW tank temperature at a higher temperature (example: 53°C), which is then mixed with cold water (example: 15°C).

Selecting the volume and desired temperature for the DHW tank consists of:

1Determining the DHW consumption (equivalent hot water volume at 40°C).

2Determining the volume and desired temperature for the DHW tank.

Possible DHW tank volumes

Type

 

Possible volumes

Standalone DHW tank

300 l

 

500 l

Energy saving tips

If the DHW consumption differs from day to day, you can program a weekly schedule with different desired DHW tank temperatures for each day.

The lower the desired DHW tank temperature, the more cost effective. By selecting a larger DHW tank, you can lower the desired DHW tank temperature.

The heat pump itself can produce domestic hot water of maximum

55°C (50°C if outdoor temperature is low). The electrical resistance integrated in the heat pump can increase this temperature. However, this consumes more energy. ROTEX recommends to set the desired DHW tank temperature below 55°C to avoid using the electrical resistance.

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

19

5 Application guidelines

The higher the outdoor temperature, the better the performance of the heat pump.

If energy prices are the same during the day and the night, ROTEX recommends to heat up the DHW tank during the day.

If energy prices are lower during the night, ROTEX recommends to heat up the DHW tank during the night.

When the heat pump produces domestic hot water, it cannot heat up a space. When you need domestic hot water and space heating at the same, ROTEX recommends to produce the domestic hot water during the night when there is lower space heating demand.

Determining the DHW consumption

Answer the following questions and calculate the DHW consumption

(equivalent hot water volume at 40°C) using the typical water volumes:

Question

Typical water volume

How many showers are needed

1 shower = 10 min×10 l/min =

per day?

100 l

How many baths are needed per 1 bath = 150 l day?

How much water is needed at the 1 sink = 2 min×5 l/min = 10 l kitchen sink per day?

Are there any other domestic hot — water needs?

Example: If the DHW consumption of a family (4 persons) per day is as follows:

3 showers

1 bath

3 sink volumes

Then the DHW consumption = (3×100 l)+(1×150 l)+(3×10 l)=480 l

Determining the volume and desired temperature for the DHW tank

 

Formula

 

Example

V1=V2+V2×(T2−40)/(40−T1)

If:

 

 

 

V2=180 l

 

 

T2=54°C

 

 

T1=15°C

 

 

Then V1=280 l

V2=V1×(40−T1)/(T2−T1)

If:

 

 

 

V1=480 l

 

 

T2=54°C

 

 

T1=15°C

 

 

Then V2=307 l

V1

DHW consumption (equivalent hot water volume at 40°C)

V2

Required DHW tank volume if only heated once

T2

DHW tank temperature

 

 

T1

Cold water temperature

 

 

5.4.3Setup and configuration – DHW tank

For large DHW consumptions, you can heat up the DHW tank several times during the day.

To heat up the DHW tank to the desired DHW tank temperature, you can use the following energy sources:

Thermodynamic cycle of the heat pump

Electrical booster heater

For more information about:

Optimizing the energy consumption for producing domestic hot water, see "8 Configuration" on page 51.

Connecting the electrical wiring of the domestic hot water tank to control box RKCB07CAV3, see the installation manual of the domestic hot water tank.

Connecting the water piping of the domestic hot water tank to the outdoor unit, see the installation manual of the domestic hot water tank.

5.4.4DHW pump for instant hot water

Setup

d

g

 

b

c

a

 

 

e

 

h

f

aOutdoor unit

bDomestic hot water tank

cDomestic hot water pump

dControl box

eShower

fCold water

gDomestic hot water OUT

hRecirculation connection

By connecting a DHW pump, instant hot water can be available at the tap.

The DHW pump and the installation are field supply and the responsibility of the installer.

For more information about the recirculation connection, see

"7.8.8 To connect the domestic hot water pump" on page 45, and the installation manual of the domestic hot water tank.

Configuration

For more information, see "8 Configuration" on page 51.

You can program a schedule to control the DHW pump via the user interface. For more information, see the user reference guide.

5.4.5DHW pump for disinfection

Setup

h

h

 

 

b

c

 

a

 

 

 

d

f

 

 

 

i

e

g

aOutdoor unit

bDomestic hot water tank

cDomestic hot water pump (field supply)

dHeater element (field supply)

eNon return valve (field supply)

fShower (field supply)

gCold water

hControl box

iDomestic hot water OUT

jRecirculation connection

The DHW pump is field-supplied and its installation is the responsibility of the installer.

The temperature of the DHW tank can be set to maximum 70°C. If the applicable legislation requires a higher temperature for disinfection, you can connect a DHW pump and heater element as shown above.

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

20

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

5 Application guidelines

If applicable legislation requires disinfection of the water piping until the tapping point, you can connect a DHW pump and heater element (if needed) as shown above.

For more information about the recirculation connection, see "7.8.8 To connect the domestic hot water pump" on page 45, and the installation manual of the domestic hot water tank.

Configuration

The outdoor unit can control DHW pump operation. For more information, see "8 Configuration" on page 51.

5.5Setting up the energy metering

Via the user interface, you can read out the following energy data:

Produced heat

Consumed energy

You can read out the energy data:

For space heating

For space cooling

For domestic hot water production

You can read out the energy data:

Per month

Per year

INFORMATION

The calculated produced heat and consumed energy are an estimation, the accuracy cannot be guaranteed.

5.5.1Produced heat

INFORMATION

The sensors used to calculate the produced heat are calibrated automatically.

INFORMATION

If glycol is present in the system ([E 0D]=1]), then the produced heat will NOT be calculated, nor will it be displayed on the user interface.

Applicable for all models.

The produced heat is calculated internally based on:

The leaving and entering water temperature

The flow rate

The power consumption of the booster heater (if applicable) in the domestic hot water tank

Setup and configuration:

No additional equipment needed.

Only in case a booster heater is present in the system, measure its capacity (resistance measurement) and set the capacity via the user interface. Example: If you measure a booster heater resistance of 17.1Ω, the capacity of the heater at 230 V is 3100 W.

5.5.2Consumed energy

You can use the following methods to determine the consumed energy:

Calculating

Measuring

INFORMATION

You cannot combine calculating the consumed energy (example: for backup heater) and measuring the consumed energy (example: for outdoor unit). If you do so, the energy data will be invalid.

Calculating the consumed energy

The consumed energy is calculated internally based on:

The actual power input of the outdoor unit

The set capacity of the booster heater and the optional backup heater

The voltage

Setup and configuration: To get accurate energy data, measure the capacity (resistance measurement) and set the capacity via the user interface for:

The optional backup heater (step 1 and step 2)

The booster heater

Measuring the consumed energy

Preferred method because of higher accuracy.

Setup and configuration:

Requires option box RK2CB07CAV3.

Requires external power meters.

For the specifications of each type of meter, see "14 Technical data" on page 90.

When using electrical power meters, set the number of pulses/ kWh for each power meter via the user interface.

INFORMATION

When measuring the electrical power consumption, make sure ALL power input of the system is covered by the electrical power meters.

5.5.3Normal kWh rate power supply

General rule

One power meter that covers the entire system is sufficient.

Setup

Install control box RKCB07CAV3 and option box RK2CB07CAV3.

Connect the power meter to X2M/7 and X2M/8 of option box RK2CB07CAV3.

Power meter type

 

In case of…

Use a… power meter

 

 

 

Backup heater supplied from a

Single-phase

 

 

 

single-phase grid (i.e. the backup

 

 

 

 

heater model is *3V or *9W

 

 

 

 

connected to a single-phase grid)

 

 

 

 

In other cases (i.e. a *9W backup

Three-phase

 

 

 

heater model connected to a

 

 

 

 

three-phase grid)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

21

5 Application guidelines

Example

Single-phase power meter

Three-phase power meter

 

 

a

 

 

 

 

a

 

 

 

b

 

 

 

 

 

b

 

 

c

 

c

 

 

c

c

 

 

d

d

e

f

g

h

e

f

g

h

i

A

B

C

D

E

A

B

C

D

E

A Outdoor unit

A Outdoor unit

B Control box

B Control box

C DHW tank

C DHW tank

D Option box

D Option box

E Backup heater kit

E Backup heater kit

a Electrical cabinet (L1/N)

a Electrical cabinet (L1/L2/L3/N)

b Power meter (L1/N)

b Power meter (L1/L2/L3/N)

c Fuse (L1/N)

c Fuse (L1/N)

d Outdoor unit (L1/N)

d Fuse (L1/L2/L3/N)

e Control box (L1/N)

e Outdoor unit (L1/N)

f Booster heater (L1/N)

f Control box (L1/N)

g Option box (L1/N)

g Booster heater (L1/N)

h Backup heater (L1/N)

h Option box (L1/N)

 

i Backup heater (L1/L2/L3/N)

Exception

You can use a second power meter if:

The power range of one meter is insufficient.

The electrical meter cannot easily be installed in the electrical cabinet.

Connect power meter 2 to X2M/9 and X2M/10 of option box RK2CB07CAV3.

Power meter types

Power meter 1: Single-phase power meter.

Power meter 2:

In case of a single-phase backup heater configuration, use a single-phase power meter.

In other cases, use a three-phase power meter.

Example

Three-phase backup heater:

 

 

a

 

b

 

 

c

 

d

e

e

 

 

f

g

h

i

j

k

A

B

C

D

E

AOutdoor unit

BControl box

CDomestic hot water tank

DOption box

EBackup heater kit

aElectrical cabinet (L1/N): Preferential kWh rate power supply

bElectrical cabinet (L1/L2/L3/N): Normal kWh rate power supply

cPower meter (L1/N)

dPower meter (L1/L2/L3/N)

eFuse (L1/N)

fFuse (L1/L2/L3/N)

gOutdoor unit (L1/N)

hControl box (L1/N)

iBooster heater (L1/N)

jOption box (L1/N)

kBackup heater (L1/L2/L3/N)

230 V and 400 V three-phase grids are combined (very uncommon), because of technical limitations of power meters.

Connection and setup:

Connect the second power meter to X2M/9 and X2M/10 of option box RK2CB07CAV3.

In the software the power consumption data of both meters is added so you do NOT have to set which meter covers which power consumption. You only need to set the number of pulses of each power meter.

See "5.5.4 Preferential kWh rate power supply" on page 22 for an example with two power meters.

5.5.4Preferential kWh rate power supply

General rule

Power meter 1: Measures the refrigerant part of the outdoor unit.

Power meter 2: Measures the rest (i.e. the hydro part of the outdoor unit, control box RKCB07CAV3, option box

RK2CB07CAV3, the backup heater kit, and the optional booster heater).

Setup

Connect power meter 1 to X2M/7 and X2M/8 of option box RK2CB07CAV3.

5.6Setting up the power consumption control

The power consumption control:

Allows you to limit the power consumption of the entire system (sum of the outdoor unit, control box RKCB07CAV3, option box RK2CB07CAV3, the backup heater kit, and the optional booster heater).

Configuration: Set the power limitation level and how it has to be achieved via the user interface.

The power limitation level can be expressed as:

Maximum running current (in A)

Maximum power input (in kW)

The power limitation level can be activated:

Permanently

By digital inputs

5.6.1Permanent power limitation

Permanent power limitation is useful to assure a maximum power or current input of the system. In some countries, legislation limits the maximum power consumption for space heating and DHW production.

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

22

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

5 Application guidelines

Pi

a

DI

b

t

Pi Power input t Time

DI Digital input (power limitation level)

aPower limitation active

bActual power input

Setup and configuration

bBackup heater

cBooster heater

Pi

a

 

DI1

 

 

 

 

 

DI3

 

 

 

DI4

 

 

b

 

 

 

 

 

Pi

t

 

 

 

 

Power input

 

 

t

Time

DI Digital inputs (power limitation levels)

aPower limitation active

bActual power input

No additional equipment needed.

Set the power consumption control settings in [A.6.3.1] via the

user interface (for the description of all settings, see

"8 Configuration" on page 51):

Select full time limitation mode

Select the type of limitation (power in kW or current in A)

Set the desired power limitation level

NOTICE

Mind the following guidelines when selecting the desired power limitation level:

Set a minimum power consumption of ±3.6 kW to guarantee defrost operation. Otherwise, if defrosting is interrupted several times, the heat exchanger will freeze up.

Set a minimum power consumption of ±3 kW to guarantee space heating and DHW production by allowing at least one electrical heater (backup heater step 1 or booster heater).

5.6.2Power limitation activated by digital inputs

Power limitation is also useful in combination with an energy management system.

The power or current of the entire ROTEX system is limited dynamically by digital inputs (maximum four steps). Each power limitation level is set via the user interface by limiting one of the following:

Current (in A)

Power input (in kW)

The energy management system (field supply) decides the activation of a certain power limitation level. Example: To limit the maximum power of the entire house (lighting, domestic appliances, space heating…).

A

B

C

D

E

X2M

b c

a

F

AOutdoor unit

BControl box

COption box

DBackup heater kit

EDomestic hot water tank

FEnergy management system

a Power limitation activation (4 digital inputs)

Setup

Install control box RKCB07CAV3 and option box RK2CB07CAV3.

Maximum four digital inputs are used to activate the corresponding power limitation level:

DI1 = weakest limitation (highest energy consumption)

DI4 = strongest limitation (lowest energy consumption)

For the specifications of the digital inputs, and for where to connect them, refer to the wiring diagram.

Configuration

Set the power consumption control settings in [A.6.3.1] via the user interface (for the description of all settings, see "8 Configuration" on page 51):

Select activation by digital inputs.

Select the type of limitation (power in kW or current in A).

Set the desired power limitation level corresponding to each digital input.

INFORMATION

In case more than 1 digital input is closed (at the same time), the digital input priority is fixed: DI4 priority>…>DI1.

5.6.3Power limitation process

The outdoor unit has better efficiency than the electrical heaters. Therefore, the electrical heaters are limited and turned OFF first. The system limits power consumption in the following order:

1 Limits certain electrical heaters.

If… has priority

Then set the heater priority

 

via the user interface to…

Domestic hot water production

Booster heater.

 

Result: The backup heater will

 

be turned OFF first.

Space heating

Backup heater.

 

Result: The booster heater will

 

be turned OFF first.

2Turns OFF all electrical heaters.

3Limits the outdoor unit.

4Turns OFF the outdoor unit.

Example

If the configuration is as follows:

Power limitation level does NOT allow operation of both booster heater and backup heater (step 1 and step 2).

Heater priority = Booster heater.

Then power consumption is limited as follows:

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

23

6 Preparation

Ph

e d

c

b

a

A B C Ce

6.2Preparing installation site

Do NOT install the unit in places often used as work place. In case of construction works (e.g. grinding works) where a lot of dust is created, the unit must be covered.

Choose the installation location with sufficient place for carrying the unit in and out of the site.

6.2.1Installation site requirements of the

Ph

Produced heat

Ce

Consumed energy

AOutdoor unit

BBooster heater

CBackup heater

aLimited outdoor unit operation

bFull outdoor unit operation

cBooster heater turned ON

dBackup heater step 1 turned ON

eBackup heater step 2 turned ON

5.7Setting up an external temperature sensor

You can connect one external temperature sensor. It can measure the outdoor ambient temperature. ROTEX recommends to use an external temperature sensor in the following cases:

Outdoor ambient temperature

In the outdoor unit, the outdoor ambient temperature is measured.

Therefore, the outdoor unit must be installed on a location:

At the north side of the house or at the side of the house where the most heat emitters are located

That is NOT exposed to direct sunlight

If this is NOT possible, ROTEX recommends to connect a remote outdoor sensor (option EKRSCA1).

Setup: For installation instructions, see the installation manual of the remote outdoor sensor and the addendum book for optional equipment.

Configuration: Select outdoor sensor [A.2.2.B].

During suspend (see "8 Configuration" on page 51), the outdoor unit is turned down to reduce the standby energy losses. As a result, the outdoor ambient temperature is NOT read out.

If the desired leaving water temperature is weather dependent, the full time outdoor temperature measurement is important. This is another reason to install the optional outdoor ambient temperature sensor.

INFORMATION

The external outdoor ambient sensor data (either averaged or instantaneous) is used in the weather-dependent control curves and in the automatic heating/cooling changeover logic. To protect the outdoor unit, the internal sensor of the outdoor unit is always used.

outdoor unit

INFORMATION

Also read the precautions and requirements in the

"General safety precautions" chapter.

Mind the following spacing guidelines:

 

>250/400

>350

<![if ! IE]>

<![endif]>≤1200

b

 

 

a

 

 

 

(mm)

 

 

a

Air outlet

 

b

Air inlet

 

b

>250

a

 

 

(mm)

INFORMATION

If shut-off valves are installed on the unit, provide a minimum space of 400 mm at the air inlet side. If shut off valves are NOT installed on the unit, provide a minimum space of 250 mm.

If the system contains a domestic hot water tank, meet the following requirements:

Maximum allowable distance

Distance

between outdoor unit and …

 

domestic hot water tank

10 m

 

 

3 way valve

10 m

See "14.2 Dimensions and service space" on page 90 for more detailed information about spacing guidelines.

NOTICE

Do NOT stack the units on each other.

Do NOT hang the unit on a ceiling.

Strong winds (≥18 km/h) blowing against the outdoor unit’s air outlet causes short circuit (suction of discharge air). This may result in:

deterioration of the operational capacity;

frequent frost acceleration in heating operation;

disruption of operation due to decrease of low pressure or increase of high pressure;

6 Preparation

6.1Overview: Preparation

This chapter describes what you have to do and know before going on-site.

It contains information about:

Preparing the installation site

Preparing the water piping

Preparing the electrical wiring

a broken fan (if a strong wind blows continuously on the fan, it may start rotating very fast, until it breaks).

It is recommended to install a baffle plate when the air outlet is exposed to wind.

It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind.

Do NOT install the unit in the following places:

Sound sensitive areas (e.g. near a bedroom and the like), so that the operation noise will cause no trouble.

In places where a mineral oil mist, spray or vapour may be present in the atmosphere. Plastic parts may deteriorate and fall off or cause water leakage.

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

24

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

It is NOT recommended to install the unit in the following places because it may shorten the life of the unit:

Where the voltage fluctuates a lot

In vehicles or vessels

Where acidic or alkaline vapour is present

Seaside installation. Make sure the outdoor unit is NOT directly exposed to sea winds. This is to prevent corrosion caused by high levels of salt in the air, which might shorten the life of the unit.

Install the outdoor unit away from direct sea winds.

Example: Behind the building.

b

a

c

If the outdoor unit is exposed to direct sea winds, install a windbreaker.

Height of windbreaker≥1.5×height of outdoor unit

Mind the service space requirements when installing the windbreaker.

d c

b

a

d c

aSea wind

bBuilding

cOutdoor unit

dWindbreaker

The outdoor unit is designed for outdoor installation only, and for ambient temperatures ranging 10~43°C in cooling mode, –25~25°C in space heating mode, and –25~35°C in domestic hot water operation mode.

6.2.2Additional installation site requirements of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the

outdoor unit is NEVER snowed up.

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

6 Preparation

a

c

b

d

c

aSnow cover or shed

bPedestal

cPrevailing wind direction

dAir outlet

In any case, provide at least 300 mm of free space below the unit. Additionally, make sure the unit is positioned at least 100 mm above the maximum expected level of snow. See "7.3 Mounting the outdoor unit" on page 33 for more details.

In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is NOT affected by the snow. If necessary, install a snow cover or shed and a pedestal.

6.2.3Installation site requirements of the control box

INFORMATION

Also read the precautions and requirements in the "General safety precautions" chapter.

▪ Mind the measurement guidelines:

Maximum distance between control box and

 

 

 

 

20 m

outdoor unit

 

 

 

 

 

Maximum distance between control box and backup

10 m

heater kit

 

 

 

 

 

Maximum distance between control box and

 

 

 

 

10 m

domestic hot water tank

 

 

 

 

 

▪ Mind the following spacing installation guidelines:

 

<![if ! IE]>

<![endif]>50

 

 

<![if ! IE]>

<![endif]>50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

50

600

<![if ! IE]>

<![endif]>100

 

 

(mm)

The control box is designed to be wall-mounted in indoor locations only. Make sure the installation surface is a flat and vertical noncombustible wall.

The control box is designed to operate in ambient temperatures ranging from 5~35°C.

Do NOT install the control box in the following places:

Installer reference guide

25

6 Preparation

Sound sensitive areas (e.g. near a bedroom and the like), so that the operation noise will cause no trouble.

In places with high humidity (max. RH=85%), for example a bathroom.

In places where frost is possible.

6.2.4Installation site requirements of the option box

INFORMATION

Also read the precautions and requirements in the "General safety precautions" chapter.

Mind the measurement guidelines:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Maximum distance between the option box and

 

 

 

 

3 m

control box RKCB07CAV3

 

 

 

 

 

Mind the following spacing installation guidelines:

 

<![if ! IE]>

<![endif]>50

 

 

<![if ! IE]>

<![endif]>50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

50

600

<![if ! IE]>

<![endif]>100

 

 

(mm)

The option box is designed to be wall-mounted in indoor locations only. Make sure the installation surface is a flat and vertical noncombustible wall.

The option box is designed to operate in ambient temperatures ranging from 5~35°C.

Do NOT install the option box in the following places:

Sound sensitive areas (e.g. near a bedroom and the like), so that the operation noise will cause no trouble.

In places with high humidity (max. RH=85%), for example a bathroom.

In places where frost is possible.

6.2.5Installation site requirements of the backup heater

INFORMATION

Also read the precautions and requirements in the

"General safety precautions" chapter.

 

 

Mind the measurement guidelines:

 

 

 

 

 

 

 

Maximum distance between the backup heater and

10 m

 

 

the outdoor unit

 

 

 

Mind the following spacing installation guidelines:

 

 

 

 

 

 

 

 

 

 

 

Installer reference guide

26

 

<![if ! IE]>

<![endif]>>200

 

>50

>50

>500

 

<![if ! IE]>

<![endif]>>350

 

 

INFORMATION

 

If the backup heater is installed in a reversible system

(RBLQ05+07CAV3) and valve kit EKMBHBP1 is part of the system, it may be required to provide more space under the backup heater than indicated above. For more information, refer to "7.7.5 About the valve kit" on page 38.

The backup heater is designed to be wall-mounted in indoor locations only. Make sure the installation surface is a flat and vertical non-combustible wall.

The backup heater is designed to operate in ambient temperatures ranging from 5~30°C.

Do NOT install the backup heater in the following places:

Sound sensitive areas (e.g. near a bedroom and the like), so that the operation noise will cause no trouble.

In places with high humidity (max. RH=85%), for example a bathroom.

In places where frost is possible.

6.3Preparing water piping

6.3.1Water circuit requirements

INFORMATION

Also read the precautions and requirements in the

"General safety precautions" chapter.

Connecting piping – Legislation. Make all piping connections in accordance with the applicable legislation and the instructions in the "Installation" chapter, respecting the water inlet and outlet.

Connecting piping – Force. Do NOT use excessive force when connecting the piping. Deformation of the piping can cause malfunctioning of the unit.

Connecting piping – Tools. Only use appropriate tooling to handle brass, which is a soft material. If NOT, pipes will get damaged.

Connecting piping – Air, moisture, dust. If air, moisture or dust gets into the circuit, problems may occur. To prevent this:

Only use clean pipes

Hold the pipe end downwards when removing burrs.

Cover the pipe end when inserting it through a wall, to prevent dust and/or particles entering the pipe.

Use a decent thread sealant to seal connections.

NOTICE

If glycol is present in the system, make sure the thread sealant used is resistant to glycol.

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc 4P415097-1A – 2016.02

6 Preparation

Closed circuit. Use the outdoor unit ONLY in a closed water system. Using the system in an open water system will lead to excessive corrosion.

Piping length. It is recommended to avoid long runs of piping between the domestic hot water tank and the hot water end point

(shower, bath,…) and to avoid dead ends.

Piping diameter. Select the water piping diameter in relation to the required water flow and the available external static pressure of the pump. See "14 Technical data" on page 90 for the external static pressure curves of the outdoor unit.

Water flow. It is required to guarantee a minimum flow of 12 l/min.

When the flow is lower, the system will stop operation and display error 7H.

Minimum required flow rate

05+07 models

12 l/min

 

 

Field supply components – Water and glycol. Only use materials that are compatible with the water (and, if applicable, glycol) used in the system, and with the materials used in the outdoor unit.

Field supply components – Water pressure and temperature.

Check that all components in the field piping can withstand the water pressure and water temperature.

Water pressure. The maximum water pressure is 3 bar. Provide adequate safeguards in the water circuit to ensure that the maximum pressure is NOT exceeded.

Water temperature. All installed piping and piping accessories (valve, connections,…) MUST withstand the following temperatures:

INFORMATION

FHL1...3 Floor heating loop (field supply)

Drainage – Low points. Provide drain taps at all low points of the system in order to allow complete drainage of the water circuit.

Drainage – Pressure relief valve. Provide a proper drain for the pressure relief valve to avoid water coming into contact with electrical parts.

Air vents. Provide air vents at all high points of the system, which must also be easily accessible for servicing. The outdoor unit has a manual air purge valve. The backup heater (option) has an automatic air purge valve. Check that automatic air purge valves are NOT tightened too much, so that the automatic release of air from the water circuit is possible.

Zn-coated parts. Never use Zn-coated parts in the water circuit. Because the unit's internal water circuit uses copper piping, excessive corrosion may occur.

Non-brass metallic piping. When using non-brass metallic piping, insulate the brass and non-brass properly so that they do NOT make contact with each other. This to prevent galvanic corrosion.

Valve – Separating circuits. When using a 3-way valve in the water circuit make sure that the domestic hot water circuit and the floor heating circuit is fully separated.

Valve – Change over time. When using a 2-way valve or a 3-way valve in the water circuit, the maximum change-over time of the valve must be 60 seconds.

Filter. It is strongly recommended to install an additional filter on the heating water circuit. Especially to remove metallic particles from foul heating piping, it is recommended to use a magnetic or cyclone filter, which can remove small particles. Small particles may damage the unit and will NOT be removed by the standard filter of the heat pump system.

The following illustration is an example and might NOT match your system layout.

65°C

h

 

 

 

 

 

 

 

 

 

 

 

 

h

 

a

b

c

d

e

f

 

g

FCU1

 

 

 

 

 

 

 

 

 

 

FCU2

 

 

 

 

 

M

 

M

h

FCU3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

h

 

 

 

 

d

 

 

 

 

 

 

 

 

 

 

 

k

j

 

FHL1 FHL2

 

 

 

 

 

 

 

 

 

FHL3

 

 

 

 

 

 

 

 

 

89°C

 

 

 

 

 

 

 

 

i

 

aOutdoor unit

bHeat exchanger

cPump

dShut off valve

eBackup heater

fMotorised 3 way valve (supplied with the domestic hot water tank)

gMotorised 2 way valve (field supply)

hCollector

iDomestic hot water tank

jHeat exchanger coil

kBooster heater

FCU1...3 Fan coil unit (optional) (field supply)

Domestic hot water tank – Capacity. To avoid stagnation of water, it is important that the storage capacity of the domestic hot water tank meets the daily consumption of domestic hot water.

Domestic hot water tank – After installation. Immediately after installation, the domestic hot water tank must be flushed with fresh water. This procedure must be repeated at least once a day the first 5 consecutive days after installation.

Domestic hot water tank – Standstills. In cases where during longer periods of time there is no consumption of hot water, the equipment MUST be flushed with fresh water before usage.

Domestic hot water tank – Disinfection. For the disinfection function of the domestic hot water tank, see "8.3.2 Domestic hot water control: advanced" on page 66.

Thermostatic mixing valves. In accordance with the applicable legislation, it may be necessary to install thermostatic mixing valves.

Hygienic measures. The installation must be in compliance with the applicable legislation and may require additional hygienic installation measures.

Recirculation pump. In accordance with the applicable legislation, it may be required to connect a recirculation pump in between the hot water end point and the recirculation connection of the domestic hot water tank.

a

b

c

d

 

 

aRecirculation connection

bHot water connection

cShower

dRecirculation pump

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

27

6 Preparation

6.3.2Formula to calculate the expansion vessel pre-pressure

The pre-pressure (Pg) of the vessel depends on the installation height difference (H):

Pg=0.3+(H/10) (bar)

6.3.3To check the water volume and flow rate

The outdoor unit has an expansion vessel of 7 litre with a factory-set pre-pressure of 1 bar

To make sure that the unit operates properly:

You must check the minimum and maximum water volume.

You might need to adjust the pre-pressure of the expansion vessel.

Minimum water volume

If

Then

The system contains a backup

The minimum water volume is

heater

10 l(a)

The system does NOT contain a

The minimum water volume is

backup heater

20 l(a)

(a)The internal water volume of the outdoor unit NOT included.

INFORMATION

In critical processes, or in rooms with a high heat load, extra water might be required.

NOTICE

When circulation in each space heating loop is controlled by remotely controlled valves, it is important that the minimum water volume is guaranteed, even if all of the valves are closed.

a

b

c

d

e

f

g

 

 

 

 

T1

T2

T3

 

 

 

 

M1

M2

M3

 

 

 

d

 

 

 

 

 

 

 

FHL1

 

 

 

 

 

 

 

FHL2

 

 

 

 

 

 

 

FHL3

aOutdoor unit

bHeat exchanger

cPump

dShut off valve

eBackup heater kit (optional)

fCollector (field supply)

gBy pass valve (field supply) FHL1...3 Floor heating loop (field supply)

T1...3 Individual room thermostat (optional)

M1...3 Individual motorised valve to control loop FHL1...3 (field

supply)

Maximum water volume

NOTICE

The maximum water volume depends on whether glycol is added to the water circuit. For more information on the addition of glycol, refer to "7.7.6 To protect the water circuit against freezing" on page 39.

Use the following graph to determine the maximum water volume for the calculated pre-pressure.

A 2,4

 

 

 

 

 

 

 

2,1

 

 

 

 

 

 

 

1,8

 

 

 

 

 

 

 

1,5

 

 

 

 

 

 

 

1,2

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

0,9

 

 

 

 

 

 

 

0,6

 

 

 

 

 

 

 

0,3

20

70

105 120

150

170 185

220

270

 

 

 

 

 

 

 

B

APre-pressure (bar)

BMaximum water volume (l) Water

Water + glycol

Example: Maximum water volume and expansion vessel pre-

pressure

Installation

 

 

 

Water volume

 

 

height

 

≤185/105 l(b)

 

>185/105 l(b)

 

difference(a)

 

 

 

 

 

 

 

 

≤7 m

No pre-pressure

 

Do the following:

 

 

adjustment is required.

▪ Decrease

the

pre-

 

 

 

 

 

 

 

 

 

 

 

 

pressure.

 

 

 

 

 

 

 

 

▪ Check if the water

 

 

 

 

 

 

volume

does

NOT

 

 

 

 

 

 

exceed the maximum

 

 

 

 

 

 

allowed water volume.

>7 m

Do the following:

 

The expansion vessel of

 

Increase

 

the

pre-

the outdoor unit is too

 

 

pressure.

 

 

small for the installation.

 

 

 

 

In this case, it is

 

 

Check

if

the

water

 

 

recommended to install

 

 

volume

does

NOT

an extra vessel outside

 

 

exceed

the

maximum

the unit.

 

 

 

 

allowed water volume.

 

 

 

(a)This is the height difference (m) between the highest point of the water circuit and the outdoor unit. If the outdoor unit is at the highest point of the installation, the installation height is 0 m.

(b)The maximum water volume is 185 l in case the circuit is only filled with water, and 105 l in case the circuit is filled with water and glycol.

Minimum flow rate

Check that the minimum flow rate (required during defrost/backup heater operation) in the installation is guaranteed in all conditions.

NOTICE

If glycol was added to the water circuit, and the temperature of the water circuit is low, the flow rate will NOT be displayed on the user interface. In this case, the minimum flow rate can be checked by way of the pump test (check that the user interface does NOT display error 7H).

NOTICE

When circulation in each or certain space heating loops is controlled by remotely controlled valves, it is important that the minimum flow rate is guaranteed, even if all valves are closed. In case the minimum flow rate cannot be reached, a flow error 7H will be generated (no heating/operation).

Minimum required flow rate

05+07 models

12 l/min

 

 

See the recommended procedure as described in "9.4 Checklist during commissioning" on page 78.

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

28

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

4P415097-1A – 2016.02

6 Preparation

6.3.4Changing the pre-pressure of the expansion vessel

NOTICE

Only a licensed installer may adjust the pre-pressure of the expansion vessel.

When changing the default pre-pressure of the expansion vessel (1 bar) is required, take following guidelines into account:

Only use dry nitrogen to set the expansion vessel pre-pressure.

Inappropriate setting of the expansion vessel pre-pressure will lead to malfunction of the system.

Changing the pre-pressure of the expansion vessel should be done by releasing or increasing nitrogen pressure through the schräder valve of the expansion vessel.

a

a Schräder valve

WARNING

If the power supply has a missing or wrong N-phase, equipment might break down.

Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth.

Incomplete earthing may cause electrical shock.

Install the required fuses or circuit breakers.

Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.

Do NOT use taped wires, stranded conductor wires, extension cords, or connections from a star system.

They can cause overheating, electrical shock or fire.

Do NOT install a phase advancing capacitor, because this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.

WARNING

All wiring must be performed by an authorized electrician and must comply with the applicable legislation.

Make electrical connections to the fixed wiring.

All components procured on the site and all electrical construction must comply with the applicable legislation.

WARNING

The backup heater should have a dedicated power supply.

6.3.5

To check the water volume: Examples

WARNING

ALWAYS use multicore cable for power supply cables.

Example 1

 

 

The outdoor unit is installed 5 m below the highest point in the water circuit. The total water volume in the water circuit is 100 l.

No actions or adjustments are required.

6.4.2About preferential kWh rate power supply

Electricity companies throughout the world work hard to provide reliable electric service at competitive prices and are often authorized to bill clients at benefit rates. E.g. time-of-use rates, seasonal rates, Wärmepumpentarif in Germany and Austria, ...

Example 2

The outdoor unit is installed at the highest point in the water circuit. The total water volume in the water circuit is 350 l. The concentration of propylene glycol is 35%.

Actions:

Because the total water volume (350 l) is more than the default water volume (105 l), the pre-pressure must be decreased.

The required pre-pressure is:

Pg = (0.3+(H/10)) bar = (0.3+(0/10)) bar=0.3 bar.

The corresponding maximum water volume at 0.3 bar is 150 l.

(See the graph in the chapter above).

Because 350 l is more than 150 l, the expansion vessel is NOT appropriate for the installation. Therefore the system requires an external expansion vessel.

6.4Preparing electrical wiring

6.4.1About preparing electrical wiring

INFORMATION

Also read the precautions and requirements in the

"General safety precautions" chapter.

This equipment allows for connection to such preferential kWh rate power supply delivery systems.

Consult with the electricity company acting as provider at the site where this equipment is to be installed to know whether it is appropriate to connect the equipment in one of the preferential kWh rate power supply delivery systems available, if any.

When the equipment is connected to such preferential kWh rate power supply, the electricity company is allowed to:

interrupt power supply to the equipment for certain periods of time;

demand that the equipment only consumes a limited amount of electricity during certain periods of time.

Control box RKCB07CAV3 is designed to receive an input signal by which it switches the outdoor unit into forced-off mode. At that moment, the compressor will not operate.

Whether the power supply is interrupted or not, the wiring to the unit is different.

6.4.3Overview of electrical connections except external actuators

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 + RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1 ROTEX HPSU low temperature monobloc

4P415097-1A – 2016.02

Installer reference guide

29

6 Preparation

Normal power

Preferential kWh rate power supply

supply

Power supply is

Power supply is

 

NOT interrupted

 

interrupted

a

b

a

b

 

 

 

 

 

 

 

 

 

5

4

 

7

1

 

5

4

 

1

 

 

5

 

1

 

 

 

 

 

 

 

 

 

 

4

 

3

 

6

 

 

 

 

 

 

 

 

3

6

2

 

 

 

 

 

 

2

 

 

 

f

e

2

c

d

 

 

 

 

f

e

f

3 e

 

d

c

 

d

c

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During preferential

During preferential

kWh rate power

kWh rate power

supply activation,

supply activation,

power supply is

power supply is NOT

interrupted

interrupted. The

immediately or after

outdoor unit is turned

some time by the

off by the control.

electricity company.

Remark: The

In this case, the

electricity company

hydro part of the

must always allow the

outdoor unit (and the

power consumption

control box, if part of

of the hydro part of

the system) must be

the outdoor unit (and

powered by a

of the control box, if

separate normal

part of the system).

power supply.

aNormal power supply

bPreferential kWh rate power supply

cHydro part of the outdoor unit

dRefrigerant part of the outdoor unit

eControl box

fBackup heater kit

1Power supply for outdoor unit

2Interconnection cable to control box

3Interconnection cable to backup heater kit

4Power supply for control box

5Power supply for backup heater kit

6Preferential kWh rate power supply (voltage free contact)

7Normal kWh rate power supply (to power the hydro part of the outdoor unit in the event of a power supply interruption of the preferential kWh rate power supply)

6.4.4Overview of electrical connections for external and internal actuators

The following illustration shows the required field wiring.

INFORMATION

The following illustration is an example and might NOT match your system layout.

 

1

 

 

 

c 4

 

 

2

 

 

 

 

 

13

 

 

 

 

 

 

5

 

 

 

3

 

 

21

 

 

 

 

M

 

 

 

 

 

11 9

10

7

8

12

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

14

 

 

 

 

 

 

18

 

 

 

 

 

 

a

 

 

 

d

 

b

 

 

 

 

 

22

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

f

17

 

 

 

e

28

 

19

 

 

 

 

 

 

 

 

30

M

16

 

 

 

27

29

 

 

 

 

24

26

 

 

 

 

 

 

6

 

 

 

23

 

 

 

 

25

aBackup heater power supply

bBackup heater kit

cOutdoor unit

dControl box

eOption box

fDomestic hot water tank

Outdoor unit

Item

Description

Wires

Maximum

 

 

 

running

 

 

 

current

Power supply

 

 

1

Power supply for

2+GND

(a)

 

 

outdoor unit

 

 

2

Normal kWh rate power

2

6.3 A

 

supply

 

 

User interface

 

 

3

User interface

2

(b)

 

 

 

 

 

Optional equipment

 

 

4

Remote outdoor sensor

2

(c)

 

Field-supplied components

 

 

5

Space heating/cooling

2

(c)

 

 

operation control (or

 

 

 

shut off valve)

 

 

(a)Refer to name plate on outdoor unit.

(b)Cable section 0.75 mm² till 1.25 mm²; maximum length: 500 m. Applicable for both single user interface and dual user interface connection.

(c)Minimum cable section 0.75 mm².

Control box

Item

Description

Wires

Maximum

 

 

 

running

 

 

 

current

Power supply

 

 

6

Power supply for

2+GND

(a)

 

 

control box

 

 

 

 

 

 

Interconnection cable

 

 

7

Interconnection cable

2

(b)

 

 

between outdoor unit

 

 

 

and control box

 

 

8

Interconnection cable

2

(c)

 

 

for the user interface

 

 

 

(between outdoor unit

 

 

 

and control box)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installer reference guide

 

 

 

RBLQ05+07CAV3 + RDLQ05+07CAV3 + RKCB07CAV3 +

 

 

 

 

 

 

 

30

 

 

 

RK2CB07CAV3 + RKMBUHCA3V3 + RKMBUHCA9W1

 

 

 

ROTEX HPSU low temperature monobloc

 

 

 

 

 

 

4P415097-1A – 2016.02

Loading...
+ 90 hidden pages