Honeywell 5808W3 User Manual

4.3 (3)

5808W3 Photoelectronic Smoke/Temperature

Detector with Built-in Wireless Transmitter

INSTALLATION AND SETUP GUIDE

General Information

Table 1: Detector LED Modes

001R-2768-I56

Before installing detectors, please thoroughly read these installation instructions and Manual A05-1003-002, Guide for Proper Use of System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from Honeywell.

NOTICE: This manual should be left with the owner/user of this equipment.

IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. The detector should be cleaned at least once a year.

General Description

The 5808W3 photoelectronic smoke/heat detector with built-in wireless transmitter is intended for use with wireless alarm systems that support 5800 series devices. Refer to control/communicator installation instructions for compatibility. The 5808W3 smoke/heat detector can be used with any 5800 series wireless receiver/transceiver for residential installations. For commercial installations, the 5881ENHC or the 5883H receiver is required. The transmitter can send alarm, tamper, maintenance (when control panels are equipped to process maintenance signals), and battery condition messages to the system’s receiver. The maintenance signal fully complies with the sensitivity test requirement specified in NFPA 72, 7-2.2 and is approved by UL. Refer to the wireless system’s instructions for the maximum number of transmitters that can be supported.

The 5808W3 incorporates a state-of-the-art optical sensing chamber and an advanced microprocessor. The microprocessor allows the detector to automatically maintain proper operation at factory calibrated detection levels, even when sensitivity is altered due to the presence of contaminants settling into the unit’s smoke chamber. In order for this feature to work properly, the chamber must never be opened while power is applied to the smoke detector. This includes cleaning, maintenance or screen replacement. All models also feature a restorable, built-in, fixed temperature (135°F) thermal detector and is also capable of sensing a pre-freeze condition if the temperature is below 41°F.

The 5808W3 contains a piezoelectric horn which generates the ANSI S3.41 temporal pattern in an alarm condition. In alarm, a message is also sent to the wireless control panel and the smoke detector’s zone number is displayed at the console. The alarm message is transmitted every 4 seconds until the smoke or heat condition has cleared and the detector has reset. During an alarm condition, pressing the detector’s test switch will silence the piezoelectric horn for 5 minutes. Once the detector has reset, a RESTORE message is transmitted to the control panel and the transmitter’s zone number can be cleared from the panel. The builtin Drift Compensation algorithm automatically maintains the sensitivity of the detector. Once the detector reaches its limit of compensation, it transmits a maintenance signal to the panel. The mounting base installation is simplified by the incorporation of features compatible with drywall fasteners or other methods that provide a method for securing the detector in place.

Two LEDs and a sounder on the detector provide local visual and audible indication of the detector’s status:

 

Green LED

Red LED

Piezoelectric

 

 

 

Horn

 

 

 

 

Power-up

Blinks every

Blinks every

Off

 

5 sec

5 sec

 

 

 

 

 

Normal (standby)

Blinks every

Off

Off

 

10 sec

 

 

 

 

 

 

Out of sensitivity

Off

Blinks every

Off

 

 

5 sec

 

 

 

 

 

Freeze Trouble

Off

Blinks every

Off

 

 

10 sec

 

 

 

 

 

Smoke Alarm

Off

Blinks every

Temporal Pattern

 

 

1 sec

 

 

 

 

 

Thermal Alarm

Off

Blinks every

Temporal Pattern

 

 

4 sec

 

 

 

 

 

Low Battery

Off

Blinks every

Chirp every 45 sec

 

 

45 sec

after LED blinks for

 

 

 

7 days

 

 

 

 

During initial power-up, the red and green LEDs will blink synchronously once every 5 seconds. It will take approximately 20 seconds for the detector to finish the power-up cycle (see Table 1).

After power-up has completed and the detector is functioning normally within its listed sensitivity range, the green LED blinks once every 10 seconds. If the detector is in need of maintenance because its sensitivity has shifted outside the listed limits, the red LED blinks once every 5 seconds. When alarm has been activated by smoke, the red LED blinks every 1 second. During a thermal alarm condition (>135°F) the red LED blinks once every 4 seconds. The LED indication must not be used in place of the tests specified under Testing. In a freeze trouble condition, the red LED will blink once every 10 seconds (refer to Table 1). If the detector senses a low battery condition, the red LED blinks once every 45 seconds.

To measure the detector’s sensitivity, the i3 Series Model SENSRDR Infrared Sensitivity Reader tool (see Figure 4) should be used. Refer to instruction manual D100-98-00 for proper use of the SENSRDR.

Low Battery Detection

The 5808W3 is powered by a single 3-volt CR123A or DL123A Lithium battery (included). The detector checks for a low battery at least every 65 minutes. If a low battery is detected, the transmitter sends a low battery message to the control panel, which beeps and displays the detector’s zone number. In addition, the red LED of the 5808W3 will blink every 45 seconds and the test switch will be disabled. This condition will exist for a minimum of 7 days, and then the detector’s horn will “chirp” about every 45 seconds. Pressing the test switch during this time will silence the chirps for 12 hours. The battery should be replaced BEFORE the chirps begin. Be sure to replace the battery with a fresh one.

-1-

Honeywell 5808W3 User Manual

Battery Installation and Replacement

To replace the battery:

1.Remove the detector from its mounting base by twisting the detector counterclockwise. Remove the battery, and dispose properly.

2.To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new battery.

3.Install a new 3-volt CR123A Lithium battery in the battery compartment. Follow the polarity diagram inside the compartment.

4.Reinstall the smoke detector onto the mounting base by turning the detector clockwise.

5.Test the detector as described in the TESTING SIGNAL STRENGTH section of this manual. The green LED should blink about once every 10 seconds to indicate normal operation. If the battery is not installed correctly, the smoke detector will not operate and the battery may be damaged. If the detector does not appear to be sending a signal during any of the tests, check for correct battery installation and for a fully charged battery.

Test Switch

Green LED

Red LED

Figure 1. 5808W3 Wireless Smoke/Heat Detector

Programming

The smoke detector must be enrolled in the control panel before it can operate in the system. The 5808W3 smoke/heat protection zone must be enrolled as Loop 1 and “Input Type” 3 (supervised RF).

If programmed, this smoke detector is capable of monitoring the additional conditions of Maintenance (transmitted as Loop 2), and Low Temperature (transmitted as Loop 3). Tamper is transmitted as Loop 4, but does not require programming. To take advantage of the value added features of Maintenance and Low Temperature, you must program each loop as a separate zone in the 5800 series wireless compatible panel.

1.Enter the control’s Zone Programming mode.

2.Enter the zone number to be programmed.

3.Enter the applicable zone type when prompted. Program

Loop 1 (Heat/Smoke) as a Fire zone (type 9 or 16),

Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble zone (type 19), and

Loop 3 (Freeze Warning Sensor) as a 24-Hr. Aux. zone (type 8).

NOTE: Loop 2 High/Low Maintenance is supported only on commercial control panels such as the Vista-128FBP.

4.When prompted, enter Input Type 03 (3 on some controls)

– Supervised RF Transmitter.

5.When prompted for the serial number, transmit from the detector by activating the tamper switch. To do this, hold the base of the detector in one hand, and rotate the

- 2 -

detector counter-clockwise on the base until it snaps open. Then return to clockwise position until the detector snaps into place.

6.When the serial number is displayed, transmit from the detector a second time by activating the tamper switch again as described in Step 5. The current loop number (4) will begin to flash.

7.Manually change the loop number to the desired loop number for the zone (according to the application).

8.When programming for this zone is complete, program other zones for the transmitter as necessary (except for Tamper Loop 4, which does not require programming).

WARNING: The fire protection zone enrolled must always be Loop 1. Otherwise, fire annunciations will not be reported by the control.

9.Exit Programming mode when programming is complete, and test the detector. Refer to the Testing Section.

See the control unit’s installation instructions for further details.

Mounting

First, determine the best location for the smoke detector, one that provides a strong wireless transmission path and proper smoke detection. A GOOD TRANSMISSION PATH MUST BE

ESTABLISHED FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMANENTLY INSTALLING THE DETECTOR. To check, perform the test described in the TESTING SIGNAL STRENGTH section of this manual. Prior to mounting the detector to the mounting base, you must “enroll” the detector’s serial number into the system (see the PROGRAMMING section). To mount the detector, perform the following steps:

1.Once a suitable location has been determined, install the mounting base on the ceiling or on the wall (if local ordinances permit). Use the two screws and anchors provided.

2.Turn the detector in a clockwise direction in the mounting base until it clicks into place.

3.Test the detector immediately after completing the installation (as described in the TESTING section of this manual) and refer to the control system’s instructions for additional information concerning the use of wireless smoke detectors.

Direct Mount Holes

Tamper Resistant Tab (Cut off small tab to activate

Tamper tamper resist feature)

Release Tab

Figure 2. Detector Mounting Base

Figure 3. Mount Detector Across Ceiling Panel Support

!DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 3.

Loading...
+ 2 hidden pages