Honeywell 50027910-001 Installation Manual

0 (0)
Honeywell 50027910-001 Installation Manual

50027910-001

Differential Pressure Switch

APPLICATION

The Honeywell differential pressure switch senses changes in duct air pressure to confirm air movement, providing a safeguard that airflow is present during the operation of installed IAQ equipment, including the TrueSTEAM Humidification System.

 

M27300

Fig. 1. Pressure switch.

 

Table 1. Parts Included.

 

Item

Quantity

Rubber Grommet

2

 

M27302

 

Tubing Fitting Elbow

2

 

M27323

 

Tubing, 1/4 in. ID

10 ft

Differential Pressure Switch (Fig. 1)

1

Screws, #8 x 3/4 in. sheet metal

2

Terminal Adaptor

2

INSTALLATION INSTRUCTIONS

SPECIFICATIONS

SPST: normally open, snap-acting contacts

Pressure setpoint contacts: change at 0.04 in. W.C.

Electrical

5 amp resistive @ 24VAC

One common (C), One Normally Open (NO) quick-con- nect terminals

Operating Temperature: -40F to 190F (-40C to 88C)

Pressure Sample Taps

Black positive pressure tap. 1/4 in. outside diameter Grey negative pressure tap. 1/4 in. outside diameter Use with 1/4 in. inside diameter tubing (10 ft provided)

4-13/64 (107)

3-13/16 (97)

5/64

(2)

FULL

R

3/16

(5)

Ø3-1/4 (83)

[2] 1/2 (13)

[2] 1/4 (6)

 

C

1

ASSEMBLED MEXICOIN

 

1

 

 

 

2

 

3

2

3

 

 

2-1/64 (51) 1-19/32 (41)

Ø3/16

(5)

3-15/16

(100)

NEGATIVE

 

PRESSURE

27/32

PORT

(21)

POSITIVE

PRESSURE

PORT

COMMON (C) TERMINAL 1/4 (6) X 1/32 (1) THICK QUICK CONNECT

2

3

NO

NC

+ PI

NORMALLY OPEN (NO)

TERMINAL 1/4 (6) X 1/32 (1)

 

THICK QUICK CONNECT

M27301

Fig. 2. Pressure switch dimensions.

Mounting position: mount vertically (upright) with Honeywell logo right-side up.

Approvals

Underwriters Laboratories Inc. Approved: MP2168 Canadian Underwriter Laboratories Inc. Approved:

MP2168

69-2205-01

50027910-001 DIFFERENTIAL PRESSURE SWITCH

INSTALLATION

Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition. This control must be installed in accordance with the local code and regulations.

Check ratings and descriptions given in the Specifications section to ensure the product is suitable for your application.

Installer must be a trained, experienced service technician.

IMPORTANT

Do not install the switch in an area where temperature exceeds rating of -40F to 190F (-40C to 88C)

1.Disconnect power from the TrueSTEAM before installing.

2.Mount the switch vertically with pressure connectors facing down, using provided self-tapping screws to secure the switch to the duct.

IMPORTANT

Calibration accuracy requires that the switch be mounted vertically (as pictured in Fig. 3).

M27300

Fig. 3. Pressure switch—oriented vertically.

3.The return duct is recommended, however the switch can also be mounted to the supply duct.

A

B

SUPPLY DUCT INSTALL - AIR LINE ONLY TO TAP A,

CONNECTED TO THE + PORT ON THE AIR FLOW SWITCH

RETURN DUCT INSTALL - AIR LINE ONLY TO TAP B,

CONNECTED TO THE – PORT ON THE AIR FLOW SWITCH

SUPPLY/RETURN DUCT INSTALL - AIR LINE CONNECTED

TO BOTH THE + AND – PORTS ON THE AIR FLOW SWITCH

M27303

Fig. 4. Mounting the pressure switch.

4.Cut a 3/4-in. diameter hole in the duct within 10 feet of the switch to ensure the provided tubing reaches the pressure tap elbow.

5.Insert the grommet into the duct hole, then insert the tube elbow into the grommet.

6.Connect the tubing to the elbow fitting and the other end to the applicable pressure connection on the switch:

a.Black connection if installed on the supply

b.Grey connection if installed on the return

IMPORTANT

With low-speed airflow or variable speed systems it is recommended to run tubing to both the supply and return ducts.

INSIDE

OF DUCT

1

1CONNECT TUBING TO + CONNECTION IF PRESSURE TAP IS MOUNTED TO SUPPLY DUCT. CONNECT TO – IF PRESSURE

TAP IS MOUNTED TO RETURN DUCT.

M27304

Fig. 5. Install tubing.

NOTE: You may cut the tubing to fit the connection length between the elbow fitting and switch. It is also recommended to secure the hose to existing structures to avoid accidental disconnection.

69-2205—01

2

Loading...
+ 2 hidden pages