AQ2000 Series
AQUATROL THERMOSTAT WIRING
INSTALLATION INSTRUCTIONS
Aquatrol zoning modules are compatible with any digital thermostat. The AQ1000 digital communicating thermostats have been designed to enhance the Aquatrol system functionalities. Non-communicating dry-contact thermostats provide the needed heat signals for operation.
|
|
|
|
AQ1000TN2 and AQ1000TP2 |
Battery-powered/ |
|
24-VAC Thermostats |
Dry-contact Thermostats |
|
||
|
|
|
|
|
|
|
|
Connect TH terminals of the thermostat |
Connect Rh and W terminals of the |
1. |
If any, remove jumper between Rc |
to Rh and W terminals of the zone |
thermostat to Rh and W terminals of |
|
and R on thermostat. |
module (no polarity to observe). |
the zone module. |
2. |
Connect 24 VAC from transformer to |
|
|
|
C and Rc terminals of thermostat. |
|
|
3. |
Connect Rh and W terminals of the |
|
|
|
thermostat to Rh and W terminals of |
|
|
|
the zone module. |
|
|
|
|
Aquatrol zoning modules are compatible with any digital thermostat. The AS1000 digital communicating thermostats have been The AQ panels are equipped with a 38 VA transformer which leaves between 27 and 34 VA available (depending on the panel model) to power thermostats or valves. Honeywell's VisionPRO, FocusPRO and PRO thermostat lines draw less than 0.5 VA for each thermostat. Honeywell's Prestige HD thermostat draws 2.7 VA each under normal usage. If additional VA is needed for the system, use a second transformer.
69-2394—02