Schneider Electric TAC Xenta 280, TAC Xenta 300, TAC Xenta 401 Users Manual

4 (1)

TAC Vista

TAC Pangaea

WorkStation

TAC Xenta 280/300/401

Product Manual

TAC Vista

TAC Xenta 280/300/401

Product Manual

Copyright © 2007-2011 Schneider Electric Buildings AB. All rights reserved.

This document, as well as the product it refers to, is only intended for licensed users. Schneider Electric Buildings AB owns the copyright of this document and reserves the right to make changes, additions or deletions. Schneider Electric Buildings AB assumes no responsibility for possible mistakes or errors that might appear in this document.

Do not use the product for other purposes than those indicated in this document.

Only licensed users of the product and the document are permitted to use the document or any information therein. Distribution, disclosure, copying, storing or use of the product, the information or the illustrations in the document on the part of non-licensed users, in electronic or mechanical form, as a recording or by other means, including photo copying or information storage and retrieval systems, without the express written permission of Schneider Electric Buildings AB, will be regarded as a violation of copyright laws and is strictly prohibited.

Trademarks and registered trademarks are the property of their respective owners.

TAC Xenta, TAC Xenta 280/300/401

Contents

 

 

Contents

INTRODUCTION

1 About this Manual

9

1.1

Structure .....................................................................................................................

9

1.2

Typographic Conventions ..........................................................................................

10

1.3

Prerequisites ...............................................................................................................

10

REFERENCE

2 TAC Xenta Components

13

2.1

Hardware Units ..........................................................................................................

13

2.2

Configurations............................................................................................................

14

2.3

Communications ........................................................................................................

15

3 Technical Description

17

3.1

The TAC Xenta 280 Controller..................................................................................

17

3.1.1

Terminals....................................................................................................................

17

3.1.2

Jacks ...........................................................................................................................

18

3.1.3

LED Indicators and Service pin .................................................................................

19

3.1.4

Technical Data TAC Xenta 280.................................................................................

20

3.2

The TAC Xenta 300 Controller..................................................................................

21

3.2.1

Terminals....................................................................................................................

21

3.2.2

Jacks ...........................................................................................................................

23

3.2.3

LED Indicators and Service pin .................................................................................

23

3.2.4

Technical Data TAC Xenta 300.................................................................................

24

3.3

The TAC Xenta 401 Controller..................................................................................

25

3.3.1

Terminals....................................................................................................................

25

3.3.2

Jacks ...........................................................................................................................

25

3.3.3

LED Indicators and Service pin .................................................................................

26

3.3.4

Technical Data TAC Xenta 401.................................................................................

27

4 Installation

29

4.1

Mounting the Controller.............................................................................................

29

4.2

Electrical Installation .................................................................................................

30

4.2.1

General Considerations ..............................................................................................

30

4.2.2

Cabinet Connections ..................................................................................................

32

4.2.3

Cables.........................................................................................................................

34

4.3

Terminations ..............................................................................................................

39

4.3.1

The TAC Xenta OP Operator Panel...........................................................................

42

5 Configuring your System

45

5.1

Overview ....................................................................................................................

45

Schneider Electric Buildings AB, June 2011

5 (74)

04-00067-02-en

 

Contents

 

TAC Xenta, TAC Xenta 280/300/401

 

 

 

 

 

5.2

A Single TAC Xenta 280/300/401 Controller............................................................

46

 

5.2.1

Initial Check ...............................................................................................................

46

 

5.2.2

OP Panel Activities.....................................................................................................

47

 

5.3

Two or more TAC Xenta 280/300/401 Units.............................................................

47

 

5.3.1

Initial Check ...............................................................................................................

47

 

5.3.2

Device Configuration .................................................................................................

47

 

5.3.3

OP Panel Activities.....................................................................................................

48

 

5.4

Additional I/O Units ...................................................................................................

48

 

5.4.1

Selecting I/O Modules................................................................................................

48

 

5.4.2

Initial Check ...............................................................................................................

49

 

5.4.3

I/O Module Configuration..........................................................................................

49

 

5.5

Setting the Date and Time ..........................................................................................

50

 

5.6

Clearing the Xenta Application ..................................................................................

51

 

5.7

Lock a Xenta OP to a specific TAC Xenta Controller ...............................................

51

 

5.7.1

Creating the PVI-block in the Xenta ..........................................................................

51

 

5.7.2

Enabling the function in TAC Xenta OP....................................................................

52

6

The TAC Xenta Service Menu

53

 

6.1

Accessing the Service Menu ......................................................................................

53

 

6.2

Submenus 1-8 .............................................................................................................

54

 

6.2.1

Submenu 6: Test dial ..................................................................................................

57

APPENDIX

 

 

A

Appendix A Restart Values

63

B

Appendix B Restart Sequences

67

Index

 

71

6 (74)

Schneider Electric Buildings AB, June 2011

 

04-00067-02-en

INTRODUCTION

1 About this Manual

TAC Xenta, TAC Xenta 280/300/401

1 About this Manual

 

 

1 About this Manual

This manual describes a particular process. For information on certain products, we refer you to the manual or the Help for the product in question.

For information on how to install software, we refer you to the instructions delivered with the software.

For information on third party products, we refer you to the instructions delivered with the third party product.

If you discover errors and/or unclear descriptions in this manual, please contact your Schneider Electric representative.

Note

We are continuously improving and correcting our documentation. This manual may have been updated.

Please check our Docnet site at www.tac.com for the latest version.

1.1Structure

The manual is divided into the following parts:

Introduction

The Introduction section contains information on how this manual is structured and how it should be used to find information in the most efficient way.

Reference

The Reference section contains more comprehensive information about various parts of the Getting Started section. It also provides you with information on alternative solutions not covered by the Getting Started section.

Schneider Electric Buildings AB, June 2011

9 (74)

04-00067-02-en

 

1 About this Manual

TAC Xenta, TAC Xenta 280/300/401

 

 

1.2Typographic Conventions

Throughout the manual the following specially marked texts may occur.

!Warning

Alerts you that failure to take, or avoid, a specific action might result in physical harm to you or to the hardware.

Caution

Alerts you to possible data loss, breaches of security, or other more serious problems.

Important

Alerts you to supplementary information that is essential to the completion of a task.

Note

Alerts you to supplementary information.

Tip

Alerts you to supplementary information that is not essential to the completion of the task at hand.

Advanced

Alerts you that the following information applies to complex tasks or tasks restricted by access.

1.3Prerequisites

To be able to profit from the contents in this manual, it is recommended that you read the following documents:

TAC Xenta 280 Programmable Controller datasheet

TAC Xenta 300 Programmable Controller datasheet

TAC Xenta 400 Controller, freely programmable datasheet

10 (74)

Schneider Electric Buildings AB, June 2011

 

04-00067-02-en

REFERENCE

2TAC Xenta Components

3Technical Description

4Installation

5Configuring your System

6The TAC Xenta Service Menu

TAC Xenta, TAC Xenta 280/300/401

2 TAC Xenta Components

 

 

2 TAC Xenta Components

2.1Hardware Units

The TAC Xenta 280/300/400 family consists of the following units:

The TAC Xenta 280/300/401 controller. The controller contains the database of the inputs and outputs of the TAC Xenta system. It also contains the system and application software for all the functions that are to be performed by the controller and the connected peripheral units.

TAC Xenta OP. The operator panel includes control buttons while a screen displays the values and menus. TAC Xenta OP can be connected to any controller in the network.

I/O expansion modules. These can be used to extend the number of inputs and outputs on a TAC Xenta 300/401 controller.

The I/O modules are described in a separate manual, TAC Xenta 400 I/ O Modules.

TAC Xenta 280 or 300 controller

12 13 14 15 16

17 18

20

 

 

 

TAC Xenta 401 controller

Operator panel

12 13 14 15 16 17 18

20

 

 

I/O expansion module

Fig. 2.1: The basic units of the TAC Xenta: the controller, the operator panel, and an I/O expansion module

Schneider Electric Buildings AB, June 2011

13 (74)

04-00067-02-en

 

2 TAC Xenta Components

TAC Xenta, TAC Xenta 280/300/401

 

 

 

 

Inputs

Outputs

I/O Modules

See section

 

 

 

 

 

 

TAC Xenta 280

 

 

 

 

3.1

 

TAC Xenta 281

6

6

none

 

 

TAC Xenta 282

8

8

none

 

 

TAC Xenta 283

6

6

none

 

TAC Xenta 300

 

 

 

 

3.2

 

TAC Xenta 301

12

8

up to 2

 

 

TAC Xenta 302

12

8

up to 2

 

TAC Xenta 401

 

none

none

up to 10

3.3

 

 

 

 

 

 

A number of controllers and I/O modules can form a local network and exchange data.

The TAC Xenta OP operator panel allows the user to:

Obtain access to certain parameters

Monitor the system status

Adjust setpoints and time channels

Display alarms (without communicating with a central system) Up to two OPs may be connected to each controller.

2.2Configurations

The TAC Xenta controllers can be used in different configurations, for example:

As stand-alone units (for a TAC Xenta 401 with at least one I/O module).

With controllers and OPs in a network, with extra I/O modules as required (no I/O modules for the TAC Xenta 280).

With controllers, OPs, I/O modules and other equipment in a full network with suitable adapters, possibly with connections to a TAC Vista Central System.

14 (74)

Schneider Electric Buildings AB, June 2011

 

04-00067-02-en

TAC Xenta, TAC Xenta 280/300/401

2 TAC Xenta Components

 

 

 

TAC

TAC

Web

Management

Vista

Vista

Browser

 

 

 

level

 

 

IP Network

PCLTA

or

 

 

card

 

 

 

 

 

 

TAC Xenta 901

TP/FT-10

TAC Xenta 511

Automation

 

 

level

 

 

 

TAC Xenta OP

 

TAC Xenta OP

 

TAC Xenta 401

I/O Module I/O Module

TAC Xenta 281 TAC Xenta 301

Field

 

+

-

level

 

Fig. 2.2: A TAC Xenta network example

2.3Communications

The TAC Xenta units communicate with each other in a network using a common bus, Echelon® LONWORKS® Free Topology 78 kbps (FTT10). Additional I/O units also connect to the network and may be added as required. An I/O unit can only be associated with one controller.

Explicit LONTALK® messages are used in communications between the operator panel and the controller.

The LONTALK protocol makes it possible to use Network Variables, defined on foreign equipment.

The Functional Block applications are modeled as true LONMARK Controller Objects.

The Network Variable interface (including the Standard Network Variable Types, SNVTs) can be customized, and External Interface Files (XIFs) can be generated in the field using the TAC Menta tool. Available SNVTs are listed in an appendix to the Engineering Applications in TAC Menta manual.

When connected to a TAC Vista Central System, the operating conditions of equipment such as fans, pumps, and recovery units can be displayed as graphs on the monitor and printed as reports. All temperatures and alarms may be read, while setpoints and time settings may be altered as required

TAC Xenta controllers can be reached from TAC Vista in many ways. Using LonWorks in the Xenta controller, some examples are:

From a PCLTA card in some form, directly on the PC.

Schneider Electric Buildings AB, June 2011

15 (74)

04-00067-02-en

 

2 TAC Xenta Components

TAC Xenta, TAC Xenta 280/300/401

 

 

Via the LTA function in the TAC Xenta 911.

Via the LTA function in the TAC Xenta 511.

Using the TAC Xenta 901.

Via an Ethernet/LON gateway.

Using the serial channel in the Xenta controller, for example:

Directly connected to a PC serial channel.

Connected to a PC serial channel via a telephone modem.

Connected to a PC serial channel via the IP modem function of the TAC Xenta 911.

Starting from v 3.1, application programs generated in TAC Menta may be downloaded from TAC Vista via the network.

The TAC Xenta 280/300/401 can communicate as follows:

It can send alarm and trend logging (versions 3.2 and higher) messages.

It can answer requests for the status of inputs and outputs.

It can send/ any of the parameters/variables in the program which are freely available (“Public signal”).

It can communicate with other TAC Xenta controllers to exchange data.

It can communicate with the Operator Panel, the I/O-modules, and TAC Vista.

For further details, please consult the TAC Vista IV, Engineering Classic/LNS Network manuals.

RS232

The TAC Xenta 280/300/401 controller has an RS232 port that can be used to:

Load the system software.

Load the application software from the TAC Menta programming tool.

Connect to TAC Menta when used as a commissioning tool.

Connect a specific controller directly to TAC Vista or via a modem (modem connection not available with TAC Xenta 280).

Retrieve the “System Error Log File” using the “Xenta System Error Log Viewer”.

16 (74)

Schneider Electric Buildings AB, June 2011

 

04-00067-02-en

TAC Xenta, TAC Xenta 280/300/401

3 Technical Description

 

 

3 Technical Description

3.1The TAC Xenta 280 Controller

Fig. 3.1: The TAC Xenta 280 controller

3.1.1Terminals

The TAC Xenta 281, 282 and 283

The TAC Xenta 280 has three I/O configurations, called the TAC Xenta 281, 282, and 283.

No external TAC Xenta 400 I/O modules can be used.

 

Digital

Thermistor

Univer-

Relay

TRIAC

Analog

 

inputs

inputs

sal inputs

outputs

outputs

outputs

 

 

 

 

 

 

 

Term. notation

X

B

U

K

V

Y

TAC Xenta 281

2

-

4

3

-

3

TAC Xenta 282

2

2

4

4

-

4

TAC Xenta 283

2

4

-

-

6

-

 

 

 

 

 

 

 

Schneider Electric Buildings AB, June 2011

17 (74)

04-00067-02-en

 

3 Technical Description

TAC Xenta, TAC Xenta 280/300/401

 

 

<![if ! IE]>

<![endif]>Comm

 

 

 

 

max 230 V AC

 

 

20

40

 

 

 

 

M

19

39

 

 

 

 

 

18

38

KC2

 

 

 

X2

17

37

K3

 

 

 

M

16

36

K2

 

 

 

X1

15

35

KC1

 

 

 

 

14

34

K1

 

 

 

 

13

33

 

 

 

 

 

12

32

 

 

 

 

 

11

31

 

 

 

 

 

10

30

 

 

 

 

 

9

29

 

 

 

 

U4

8

28

 

 

 

 

M

7

27

M

 

 

 

U3

6

26

Y3

 

 

 

U2

5

25

Y2

 

 

 

M

4

24

M

 

 

{

U1

3

23

Y1

0

24 V

C2

2

22

G0

C1

1

21

G

~

}AC/DC

<![if ! IE]>

<![endif]>Comm

M

X2

M

X1

M

B2

M

B1

U4

M

U3

U2

M

U1 { C2C1

 

 

max 230 V AC

20

40

 

 

 

19

39

K4

 

 

18

38

KC2

 

 

17

37

K3

 

 

16

36

K2

 

 

15

35

KC1

 

 

14

34

K1

 

 

13

33

 

 

 

12

32

 

 

 

11

31

 

 

 

10

30

 

 

 

9

29

 

 

 

8

28

Y4

 

 

7

27

M

 

 

6

26

Y3

 

 

5

25

Y2

 

 

4

24

M

 

 

3

23

Y1

0

24 V

2

22

G0

1

21

G

~

}AC/DC

<![if ! IE]>

<![endif]>Comm

 

 

 

 

 

 

24 V AC

 

 

20

40

VC

 

 

 

M

19

39

V4

 

 

 

 

18

38

 

 

 

 

X2

17

37

V3

 

 

 

M

16

36

V2

 

 

 

X1

15

35

 

 

 

 

B4

14

34

V1

 

 

 

M

13

33

V6

 

 

 

B3

12

32

 

 

 

 

B2

11

31

V5

 

 

 

M

10

30

 

 

 

 

B1

9

29

 

 

 

 

 

8

28

 

 

 

 

M

7

27

 

 

 

 

 

6

26

 

 

 

 

 

5

25

 

 

 

 

M

4

24

 

 

 

{

 

3

23

 

0

24 V

C2

2

22

G0

C1

1

21

G

~

}AC/DC

TAC Xenta 281

TAC Xenta 282

TAC Xenta 283

Fig. 3.2: The terminals of the TAC Xenta 281, 282, and 283

Inputs

All TAC Xenta 280 controllers have digital inputs (X).

The TAC Xenta 281 and 282 have universal (analog or digital, U) inputs. The universal inputs can be used for three types of signals:

TAC thermistor 1.8 kohm at 25 °C (the same as the thermistor inputs)

Voltage input 0–10V

open/closed contact (the same as the digital inputs).

The TAC Xenta 282 also has thermistor inputs (labeled B) for 1.8 kohm.

The TAC Xenta 283 has thermistor inputs (labelled B) that can be used with either 1.8 kohm or 10 kohm thermistors.

All controller inputs are protected from transients, in compliance with the EN 50082-1 norm.

Outputs

The TAC Xenta 281 and 282 have the following outputs;

Analog (Y) — 0–10V DC outputs

Digital (K) — relay potential-free outputs

While the TAC Xenta 283 has TRIAC (V) — outputs capable of supplying inductive loads.

3.1.2Jacks

The TAC Xenta 280 has two modular jacks–one for the TAC Xenta OP operator panel and one for an RS232 connection with TAC Menta.

The socket for the operator panel provides it with 24V AC or DC, depending on the supply.

18 (74)

Schneider Electric Buildings AB, June 2011

 

04-00067-02-en

TAC Xenta, TAC Xenta 280/300/401

3 Technical Description

 

 

At distances greater than 10 m (32 ft.) between the TAC Xenta controller and the OP, an external power supply should be used. In addition, the communications connection has to follow the same rules as for other nodes.

Jack for the

Jack for the

RS232/modem

Operator panel

Fig. 3.3: Location of jacks on the TAC Xenta 280 controller

3.1.3LED Indicators and Service pin

The Service pin can be activated through a small hole on the front. Also on the front, there are two LED indicators–one red and one green.

Service pin

Red service diode indicates a non-configured node or a hardware fault

Green status diode indicates that the program is running

Fig. 3.4: LED Indicators and Service Pin

The red service diode is primarily an error indication. It also lights up if the Service pin is activated.

The green status diode blinks once per second to indicate that the program is running.

Schneider Electric Buildings AB, June 2011

19 (74)

04-00067-02-en

 

3 Technical Description

TAC Xenta, TAC Xenta 280/300/401

 

 

3.1.4Technical Data TAC Xenta 280

Note

For a complete list of updated technical data for the Xenta 280 controller, see the TAC Xenta 280 Programmable Controller datasheet (003-2248).

Program cycle time

min. 1 s

Universal inputs (TAC Xenta 281, 282: U1–U4):

A/D-resolution

12 bits

–as Thermistor Inputs

 

Supply voltage

0.6V DC

Thermistor inputs (B1–B2, only TAC Xenta 282):

A/D-resolution

12 bits

Accuracy (Measuring range):

 

–50 °C to –30 °C (–58 °F to –22 °F)

±4 °C (±7.2 °F)

–30 °C to –10 °C (–22 °F to +14 °F)

±2 °C (±3.6 °F)

–10 °C to +10 °C (14 °F to 50 °F)

±1 °C (±1.8 °F)

+10 °C to +30 °C (50 °F to 86 °F)

±0.5 °C (±0.9 °F)

+30 °C to +60 °C (86 °F to 140 °F)

±1 °C (±1.8 °F)

+60 °C to +120 °C (140 °F to 248 °F)

±2 °C (±3.6 °F)

+120 °C to +150 °C (248 °F to 302 °F)

±4 °C (±7.2 °F)

Thermistor inputs (B1–B4, only TAC Xenta 283):

A/D-resolution

10 bits

Accuracy (Measuring range):

 

–20 °C to –10 °C (–4 °F to +14 °F)

±2 °C (±3.6 °F)

–10 °C to +10 °C (14 °F to 50 °F)

±1 °C (±1.8 °F)

+10 °C to +30 °C (50 °F to 86 °F)

±0,5 °C (±0.9 °F

+30 °C to +60 °C (86 °F to 140 °F)

±1 °C (±1.8 °F)

+60 °C to +90 °C (140 °F to 194 °F)

±2 °C (±3.6 °F)

+90 °C to +120 °C (194 °F to 248 °F)

±4 °C (±7.2 °F

TRIAC outputs (TAC Xenta 283 only, V1–V6)a:

Load may require auxiliary power

 

(term. 40) of up to

72 VA

Pulse length (TAC Menta DOPU

 

block)

min. 0.5 s

Analog outputs (TAC Xenta 281: Y1–Y3, TAC Xenta 282: Y1–

Y4):

D/A-resolution 12 bits

20 (74)

Schneider Electric Buildings AB, June 2011

 

04-00067-02-en

TAC Xenta, TAC Xenta 280/300/401

3 Technical Description

 

 

a.If the active sensor (0–10V), analog actuators and the TAC Xenta controller itself are supplied by the same transformer, the following restrictions will ensure the specified accuracy (for thermistor inputs, universal inputs, and analog outputs):

Cable length from controller to: Transformer: 3 m (10 ft.)

Active sensor/actuator: 20 m (65 ft.) Number of active sensors: max. 4 Number of actuators: max.6

Network communication (C1–C2, polarity insensitive):

Protocol

FTT-10, LONTALK®

Communication speed

78 kbits/s

 

 

Other communication:

 

 

 

TAC Menta

RS232, up to 9600 bits/

 

s, RJ45

TAC Vista (version IV or higher required), also for appl.pgm download

TP/FT-10, screw term.

TAC Xenta OP

TP/FT-10, modular

 

jack

3.2The TAC Xenta 300 Controller.

Fig. 3.5: The TAC Xenta 300 controller

3.2.1Terminals

TAC Xenta 301 and 302

TAC Xenta 300 has two I/O configurations: TAC Xenta 301 and TAC

Xenta 302.

 

Digital

Thermistor

Universal

Relay

Analog

 

inputs

inputs

inputs

outputs

outputs

 

 

 

 

 

 

Term. notation

X

B

U

K

Y

 

 

 

 

 

 

Schneider Electric Buildings AB, June 2011

21 (74)

04-00067-02-en

 

Schneider Electric TAC Xenta 280, TAC Xenta 300, TAC Xenta 401 Users Manual

3 Technical Description TAC Xenta, TAC Xenta 280/300/401

 

 

 

 

Digital

Thermistor

Universal

Relay

 

Analog

 

 

 

 

inputs

 

inputs

inputs

 

outputs

 

outputs

 

TAC Xenta 301

 

4

 

4

 

4

 

6

 

 

2

 

TAC Xenta 302

 

4

 

4

 

4

 

4

 

 

4

 

 

 

 

max 230 V AC

 

 

 

 

 

max 230 V AC

 

 

 

 

 

 

 

 

 

 

 

 

 

X4

20

40

 

 

 

 

 

X4

20

40

 

 

 

 

M

19

39

K4

 

 

 

 

M

19

39

K4

 

 

 

X3

18

38

KC2

 

 

 

 

X3

18

38

KC2

 

 

 

X2

17

37

K3

 

 

 

 

X2

17

37

K3

 

 

 

M

16

36

K2

 

 

 

 

M

16

36

K2

 

 

 

X1

15

35

KC1

 

 

 

 

X1

15

35

KC1

 

 

 

B4

14

34

K1

 

 

 

 

B4

14

34

K1

 

 

 

M

13

33

K6

 

 

 

 

M

13

33

 

 

 

 

B3

12

32

KC3

 

 

 

 

B3

12

32

 

 

 

 

B2

11

31

K5

 

 

 

 

B2

11

31

 

 

 

 

M

10

30

 

 

 

 

 

M

10

30

 

 

 

 

B1

9

29

 

 

 

 

 

B1

9

29

 

 

 

 

U4

8

28

 

 

 

 

 

U4

8

28

Y4

 

 

 

M

7

27

 

 

 

 

 

M

7

27

M

 

 

 

U3

6

26

 

 

 

 

 

U3

6

26

Y3

 

 

 

U2

5

25

Y2

 

 

 

 

U2

5

25

Y2

 

 

 

M

4

24

M

 

 

 

 

M

4

24

M

 

 

Comm{

U1

3

23

Y1

0

24 V AC or

 

Comm{

U1

3

23

Y1

0

 

C2

2

22

G0

 

C2

2

22

G0

24 V AC or

C1

1

21

G

~ }

19-40 V DC

 

C1

1

21

G

~

} 19-40 V DC

 

 

TAC Xenta 301

 

 

 

 

 

 

TAC Xenta 302

 

 

 

Fig. 3.6: The terminals of the TAC Xenta 301 and 302

Inputs

The TAC Xenta 300 controllers have twelve inputs:

Four thermistor inputs (labeled B1–B4)

Four universal (analog or digital, U1–U4)

Four digital (X1–X4).

The universal inputs can be used for three types of signals:

TAC thermistor 1.8 kohm at 25 °C (the same as the thermistor inputs)

Voltage input 0–10V

Open/closed contact (the same as the digital inputs)

All controller inputs are protected from transients, in compliance with the EN 50082-1 norm.

Outputs

The TAC Xenta 300 controllers have eight outputs:

Analog — 0–10V DC outputs

Digital — relay potential-free outputs

22 (74)

Schneider Electric Buildings AB, June 2011

 

04-00067-02-en

TAC Xenta, TAC Xenta 280/300/401

3 Technical Description

 

 

3.2.2Jacks

The TAC Xenta 300 has two modular jacks–one for the TAC Xenta OP operator panel and one for an RS232 connection with TAC Menta.

The socket for the operator panel provides it with 24V AC or DC, depending on the supply.

At distances greater than 10 m (32 ft.) between the TAC Xenta controller and the OP, an external power supply should be used. In addition, the communications connection has to follow the same rules as for other nodes.

Jack for the

Jack for the

RS232/modem

Operator panel

Fig. 3.7: Location of jacks on the TAC Xenta 280 controller

3.2.3LED Indicators and Service pin

The Service pin can be activated through a small hole on the front. Also on the front are two LED indicators–one red and one green.

Service pin

Red service diode indicates a non-configured node or a hardware fault

Green status diode indicates that the program is running

Fig. 3.8: LED Indicators and Service Pin

The red service diode is primarily an error indication. It also lights up if the Service pin is activated.

The green status diode blinks once per second to indicate that the program is running.

Schneider Electric Buildings AB, June 2011

23 (74)

04-00067-02-en

 

Loading...
+ 53 hidden pages