Danfoss CCMT 2, CCMT 8, CCMT 16, CCMT 24, CCMT 30 Installation guide

...
0 (0)

Installation guide

Electric regulating valves

Type CCMT 2 – CCMT 8 / CCMT 16 – CCMT 42

<![if ! IE]>

<![endif]>027R9803

Refrigerant:

Ambient temperature:

Fluid temperature:

 

 

Min. -40 °C / -40 °F

 

R744

Min. -40 °C / -40 °F

 

Max. 60 °C / 140 °F

 

For other refrigerants, contact Danfoss.

Max. 60 °C / 140 °F

 

 

 

Stepper motor type:

 

Max working pressure:

Total full steps

 

 

 

 

 

 

 

 

Bipolar

 

140 Bar / 2030 psig

CCMT 2 - CCMT 8 : 1100

 

 

 

 

 

 

 

 

 

CCMT 16 :

800

 

 

 

 

 

 

 

 

Phase Current:

 

Coil resistance:

 

 

 

CCMT 24 :

1400

 

CCMT 2 – CCMT 8:

100 mA RMS

CCMT 2 – CCMT 8:

52 Ohm

CCMT 30 :

2300

 

 

 

CCMT 16 – CCMT 42:

300 mA RMS

CCMT 16 – CCMT 42: 29 Ohm

CCMT 42 :

2200

 

 

 

 

 

 

 

 

 

 

 

 

Note!

 

CCMT 16 - CCMT 42.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CCMT valves are delivered in open position, ready for brazing.

Pressure transmitter, type MBS 8250

 

 

 

 

 

 

For CCMT 2 - CCMT 8, Filter with a maximum mesh of 100 μm

Connection

:

round packard metripack.

 

 

 

 

 

 

recommended to install on the inlet line that can resists articles size

Supply voltage

:

5 V DC ± 0.5 V

 

 

 

 

 

 

 

 

 

above 100 μm.

 

Output signal

:

10 – 90 % of supply voltage.

 

 

 

 

 

 

 

 

 

 

Pressure range

:

1 – 159 bar gauge / 14.5 – 2306 psi

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Warning! Do not connect directly to AC / DC power source. Connect valve to appropriate controller/driver only. Do not operate valve while assembling or disassembling.

Flow direction

Flow direction

CCMT 2 – CCMT 8

CCMT 16 – CCMT 42

<![if ! IE]>

<![endif]>Danfoss 27H253.10

Pressure transmitter measure at inlet A

A

Normal flow direction

Normal flow direction

For more language options and more information on the valve refer to the website.

ccmt.danfoss.com

<![if ! IE]>

<![endif]>027R9803

© Danfoss | DCS (js)| 2021.02

AN168586419953en-000601 | 1

Danfoss CCMT 2, CCMT 8, CCMT 16, CCMT 24, CCMT 30 Installation guide

Mounting direction CCMT 2 - CCMT 42

1

Warning!

 

• Do not disassemble the valve before brazing or welding.

• Valve must be open during brazing and welding.

<![if ! IE]>

<![endif]>Danfoss 27H254.10

Danfoss 27H341.10

Fully closed

Danfoss 27H340.10

Open

Brazing

3a

Welding

CCMT 2 - CCMT 42

CCMT 2 - CCMT 42

 

<![if ! IE]>

<![endif]>Danfoss27H300.11

N2

2 1

max. 75 °C / 167 °F

max. 700 °C / 1300 °F

Materials for brazing

3

Recommendation

Solder nozzle 4 - 6 mm

N (5/32 in - 15/64 in)

For CCMT 2 – CCMT 42

Materials used for brazing:

Flus: Metalli tenacity No. 5 Powder or Braze Tec special h paste.

Filler: Silver-Flo 55 (BS:AG 14/ DIN L-Ag55 Sn) or Silver-Flo 56 (AWS B Ag-7).

Warning!

Filler metals containing Phosphor i.e. BS: CP 1/ DIN L-Ag 15P or BS: CP 3/ DIN L-Ag P7 must not be used.

<![if ! IE]>

<![endif]>27H302.10

<![if ! IE]>

<![endif]>Danfoss

max. 75 °C / 167 °F

Recommendation for TIG welding

Power approximately 60 A.

Use Shield gas charge - Argon.

Material for welding - approximately 2 mm thick stainless steel alloy.

2

3b

© Danfoss | DCS (js)| 2021.02

AN168586419953en-000601 | 2

Loading...
+ 2 hidden pages