Actuators for three point control with stroke limitation (SL)

AMV 20 SL, AMV 30 SL

AMV 23 SL - with EN 14597 certified safety function

Description

AMV 20 SL, AMV 30 SL

AMV 23 SL

The actuators for 3-point controls with or without safety function are suitable to be used with VS2, VM2, VB2 and AVQM valves.

The safety function on AMV 23 SL is activated automatically in case of power failure or if the power supply is switched off by the safety thermostat. This function provides safety shut off on power failure.

In addition to basic function such as manual control and position indication, the actuators are also equipped with force sensitive switch-off to ensure that actuators and valves are not exposed to overload. This function automatically ensures the self-adjustment of the end positions on the valve.

Actuators are also equipped with stroke limitation that can limit flow in valves. Limitation of stroke is designed with switch that can be

set in any desirable position (stroke limit from 0 to 100%).

Features:

The advanced design incorporates load related ‘switch-off’ to ensure that actuators and valves are not exposed to overload.

Digital feedback end position indication signal for valve end position is available by terminal 4 or 13.

Low weight and robust.

Main data:

Nominal voltage:

-24 Vac and 230 Vac (AMV 20 SL, AMV 23 SL)

-230 Vac (AMV 30 SL)

Control input signal: 3 point

Force: 450 N

Speed:

- AMV 20 SL, AMV 23 SL ..........................

15 s/mm

- AMV 30 SL ................................................

3 s/mm

Max. medium tempetrature: 150 °C

Safety function: EN 14597

Stroke limitation (SL)

Ordering

 

 

 

Type

Supply voltage

Code No.

 

AMV 20 SL

230 V~

082G3035

 

 

 

 

 

AMV 20 SL

24 V~

082G3036

 

 

 

 

 

AMV 30 SL

230 V~

082G3055

 

 

 

 

 

Spring return function - EN 14597 approval

 

 

 

 

 

Type

Supply voltage

Code No.

 

 

 

 

 

AMV 23 SL

230 V~

082G3037

 

 

 

 

 

AMV 23 SL

24 V~

082G3038

 

 

 

 

© Danfoss | 2018.12

VD.AE.H7.02 | 1

Danfoss AMV 20 SL, AMV 30 SL, AMV 23 SL Data sheet

Data sheet

Actuators for three point control AMV 20 SL / 23 SL / 30 SL

 

 

Technical data

Type

 

AMV 20 SL

AMV 23 SL

AMV 30 SL

Power supply

Vac

24~, 230~; +10 to –15 %

230~; +10 to –15 %

Power consumption

VA

2.15

7

7

Frequency

Hz

 

50/60

 

Safety function

 

-

yes

-

Control input

 

 

3-point

 

Closing force

N

 

450

 

Spindle travel

mm

 

10

 

Spindle speed

s/mm

 

15

3

Max. medium temperature inside the pipe

 

 

150

 

Ambient temperature

°C

 

0 ... 55

 

Storage and transport temperature

 

 

−40 ... 70

 

Ambient humidity

 

 

5-95 % r.h., non-condensing

 

Protection Class

 

 

I (230 V); III (24 V)

 

Grade of enclosure

 

 

IP 54

 

Weight

kg

1.4

1.45

1.4

 

 

Low Voltage Directive (LVD) 2014/35/EU: EN 60730-1, EN 60730-2-14

- marking in accordance with standards

Electromagnetic Compatibility Directive (EMC) 2014/30/EU: EN 61000-6-2,

 

 

EN 61000-6-3

 

 

Stroke limitation

Installation

AMV 20 SL, AMV 30 SL

AMV 23 SL

Mechanical

The actuator should be mounted with the valve stem in either horizontal position or pointing upwards.

The actuator is fixed to the valve body by means of a mounting ring, which requires no tools for mounting. The ring should be tightened by hand.

Electrical

Important: It is strongly recommended that the mechanical installation is completed before the electrical installation.

Note: Two cable entries are provided for M 16×1.5 cable glands. One entry is provided with a rubber grommet. Note that in order to maintain the enclosure’s IP rating, appropriate cable glands must be used.

Disposal

The actuator must be dismantled and the

 

elements sorted into various material groups

 

before disposal.

 

 