Danfoss DCC 04, DCC 07, DCC 20, DMC 04, DMC 07 Data sheet

...
0 (0)

Data Sheet

Hermetic receiver filter drier

Type DMC and DCC

ELIMINATOR®, combined receivers and €lter driers used in small hermetic refrigeration systems

DMC and DCC are combined receivers and €lter driers for use in small hermetic refrigeration systems.

Under operating conditions where the condenser cannot contain the total quantity of refrigerant, a receiver might be necessary. This extra receiver capacity can be provided by using a DCC or a DMC combined receiver and €lter drier.

ELIMINATOR® type DMC driers are designed for applications requiring the highest moisture capacity and acid adsorption capacity.

Available with solder (cu-plated steel) connections.

AI192386433450en-000702

Hermetic receiver €lter drier, Type DMC and DCC

Features

The Core - Type DMC

100% Molecular Sieve core

High drying capacity minimizing the risk of acid formation (hydrolysis)

Recommended for use with HFO, HC, HFC and HCFC refrigerants

Will not deplete oil additives

The Core - Type DCC

80% Molecular Sieve with 20% activated alumina

Recommended for use with HFO, HC, HFC and HCFC refrigerants

Perfect core blend for A/C systems that operate at high condensing temperatures and require high drying capacity

The Shell

PED/UL approved for PS 42 bar

Available with solder (cu-plated steel connectors)

Corrosion resistant powder-painted €nish

The Filter

Combination of €lter drier and receiver

Available in sizes 4 – 40 cubic inches

High drying capacity at high and low liquid temperatures

Space-saving

Fast installation

25 μm (0.001 in.) €lter provides high retention with minimal pressure drop

Thermally stable up to 120 °C

© Danfoss | Climate Solutions | 2021.07

AI192386433450en-000702 | 2

Danfoss DCC 04, DCC 07, DCC 20, DMC 04, DMC 07 Data sheet

Hermetic receiver €lter drier, Type DMC and DCC

Product speci€cation

Design

Figure 1: DMC and DCC

3

5

1

 

<![if ! IE]>

<![endif]>Danfoss 23Z7008.10

 

2

4

 

1.Inlet

2.Spring

3.Solid core

4.Polyester mat

5.Perforated plate

Technical Data

Table 1: Surface and volume

 

 

Solid core surface

Solid core volume

Filter drier volume

Filter drier volume

 

Filter

(shell volume)

(net volume)

 

 

 

 

 

[cm2]

[cm3]

[l]

[l]

 

DMC / DCC 04

83

53

0.14

0.09

 

DMC / DCC 07

83

53

0.19

0.14

 

DMC / DCC 20

83

53

0.35

0.30

 

DMC 40

220

234

0.77

0.54

 

 

 

 

 

 

Table 2: Acid capacity

 

Filter

Acid capacity

 

[g](1)

 

 

 

DCC 04

0.71

 

DCC 07

0.71

 

DCC 20

0.71

 

 

 

(1) Adsorption capacity of oleic acid at 0.05 TAN (Total Acid Number).

Temperature range: -40 – 70 °C

Figure 2: Solder connection (cu-plated steel connectors)

© Danfoss | Climate Solutions | 2021.07

AI192386433450en-000702 | 3

Loading...