Data Sheet
Hermetic receiver filter drier
Type DMC and DCC
ELIMINATOR®, combined receivers and €lter driers used in small hermetic refrigeration systems
DMC and DCC are combined receivers and €lter driers for use in small hermetic refrigeration systems.
Under operating conditions where the condenser cannot contain the total quantity of refrigerant, a receiver might be necessary. This extra receiver capacity can be provided by using a DCC or a DMC combined receiver and €lter drier.
ELIMINATOR® type DMC driers are designed for applications requiring the highest moisture capacity and acid adsorption capacity.
Available with solder (cu-plated steel) connections.
AI192386433450en-000702
Hermetic receiver €lter drier, Type DMC and DCC
Features
The Core - Type DMC
•100% Molecular Sieve core
•High drying capacity minimizing the risk of acid formation (hydrolysis)
•Recommended for use with HFO, HC, HFC and HCFC refrigerants
•Will not deplete oil additives
The Core - Type DCC
•80% Molecular Sieve with 20% activated alumina
•Recommended for use with HFO, HC, HFC and HCFC refrigerants
•Perfect core blend for A/C systems that operate at high condensing temperatures and require high drying capacity
The Shell
•PED/UL approved for PS 42 bar
•Available with solder (cu-plated steel connectors)
•Corrosion resistant powder-painted €nish
The Filter
•Combination of €lter drier and receiver
•Available in sizes 4 – 40 cubic inches
•High drying capacity at high and low liquid temperatures
•Space-saving
•Fast installation
•25 μm (0.001 in.) €lter provides high retention with minimal pressure drop
•Thermally stable up to 120 °C
© Danfoss | Climate Solutions | 2021.07 |
AI192386433450en-000702 | 2 |
Hermetic receiver €lter drier, Type DMC and DCC
Product speci€cation
Design
Figure 1: DMC and DCC
3 |
5 |
1 |
|
<![if ! IE]> <![endif]>Danfoss 23Z7008.10 |
|
2 |
4 |
|
1.Inlet
2.Spring
3.Solid core
4.Polyester mat
5.Perforated plate
Technical Data
Table 1: Surface and volume
|
|
Solid core surface |
Solid core volume |
Filter drier volume |
Filter drier volume |
|
Filter |
(shell volume) |
(net volume) |
||
|
|
|
|||
|
|
[cm2] |
[cm3] |
[l] |
[l] |
|
DMC / DCC 04 |
83 |
53 |
0.14 |
0.09 |
|
DMC / DCC 07 |
83 |
53 |
0.19 |
0.14 |
|
DMC / DCC 20 |
83 |
53 |
0.35 |
0.30 |
|
DMC 40 |
220 |
234 |
0.77 |
0.54 |
|
|
|
|
|
|
Table 2: Acid capacity
|
Filter |
Acid capacity |
|
[g](1) |
|
|
|
|
|
DCC 04 |
0.71 |
|
DCC 07 |
0.71 |
|
DCC 20 |
0.71 |
|
|
|
(1) Adsorption capacity of oleic acid at 0.05 TAN (Total Acid Number).
Temperature range: -40 – 70 °C
Figure 2: Solder connection (cu-plated steel connectors)
© Danfoss | Climate Solutions | 2021.07 |