Danfoss AMV 130, AMV 140, AMV 130H, AMV 140H Data sheet [nl]

0 (0)
Danfoss AMV 130, AMV 140, AMV 130H, AMV 140H Data sheet

Data sheet

Actuators for three point control

AMV 130, AMV 140, AMV 130H, AMV 140H

Description

 

AMV 130/140 and AMV 130H/140H actuators are

 

 

 

used with VZ, VZL and VRBZ valves. The actuator

 

 

can be used with fan coil units, induction units,

 

 

small reheaters, recoolers and zone applications

 

 

in which hot/cold water is the controlled

 

 

medium.

 

 

Main data:

 

 

3-point versions

 

 

Force switch-o at stem down position

 

 

 

prevents overload of actuator and valve

 

 

No tools required for mounting

 

AMV 130, AMV 140

Maintenance free during lifetime

 

Low noise operation

 

 

 

 

Supplied with 1.5 m cable

AMV 130H, AMV 140H

Ordering

Type

Supply

Speed

Code No.

Spare parts

 

 

voltage

Type

Code No.

 

 

 

 

 

AMV 130

 

24 s/mm

082H8036

Cable (5m) - 24 V

082H8052

 

AMV 140

 

12 s/mm

082H8038

 

24 V~

Cable (5m) - 230 V

082H8053

 

AMV 130H

24 s/mm

082H8040

 

 

 

 

 

 

 

 

AMV 140H

 

12 s/mm

082H8042

 

 

 

AMV 130

 

24 s/mm

082H8037

 

 

 

AMV 140

230 V~

12 s/mm

082H8039

 

 

 

AMV 130H

24 s/mm

082H8041

 

 

 

 

 

 

 

AMV 140H

 

12 s/mm

082H8043

 

 

Technical data

Type

 

 

 

AMV 130, AMV 130H

AMV 140, AMV 140H

 

Power supply

 

 

 

24 Vac, 230 Vac; +10 to –15%

 

 

Power consumption

 

 

1 VA - 24 Vac; 8 VA - 230 Vac

 

 

Frequency

 

 

 

50 Hz/60 Hz

 

 

Close of force

 

 

 

200 N

 

 

Stroke

 

 

 

5.5 mm

 

 

Speed

 

 

 

24 s/mm

12 s/mm

 

Max. medium temperature inside the pipe

130 °C

 

 

Ambient temperature

 

 

0 … 55 °C

 

 

Storage and transport temperature

 

–40 … +70 °C

 

 

Protection code

 

 

IP 42

 

 

Weight

 

 

 

0.3 kg

 

 

- marking in accordance with standards

EMCDirective 89/336/EEC, 92/31/EEC, 93/68/EEC,

 

EN 61000-6-1 and EN 61000-6-3

 

 

 

 

 

 

 

 

 

 

Low Voltage Directive 73/23/EEC and 93/68/EEC,

 

 

 

 

 

EN 60730-2-14

 

DH-SMT/SI

VD.KG.Y1.02 © Danfoss 06/2006

1

Data sheet

Actuators for three point control AMV 130, AMV 140, AMV 130H, AMV 140H

Installation

Mechanical

 

The actuator should be mounted with the valve

 

stem in either horizontal position or pointing

 

upwards.

 

The actuator is fixed to the valve body by means

 

of a mounting ring which requires no tools for

 

mounting.The ring should be tightened by hand.

 

Electrical

 

Important: It is strongly recommended that the

 

mechanical installation is completed before the

 

electrical installation.

 

Each actuator is supplied with the connecting

 

cable for the controller.

Wiring

AMV 130/140, AMV 130H/140H - 24V

AMV 130/140, AMV 130H/140H - 230V

Disposal

The actuator must be dismantled and the

 

elements sorted into various material groups

 

before disposal.

 

 

Commissioning

The factory setting of the spindle is the fully

 

stem up position because of easier mechanical

 

connection of the actuator on the valve.

2

VD.KG.Y1.02 © Danfoss 06/2006

DH-SMT/SI

Loading...