Data sheet
Actuators for three point control
AMV 130, AMV 140, AMV 130H, AMV 140H
Description |
|
AMV 130/140 and AMV 130H/140H actuators are |
|
|
|||
|
|
used with VZ, VZL and VRBZ valves. The actuator |
|
|
|
can be used with fan coil units, induction units, |
|
|
|
small reheaters, recoolers and zone applications |
|
|
|
in which hot/cold water is the controlled |
|
|
|
medium. |
|
|
|
Main data: |
|
|
|
• |
3-point versions |
|
|
• Force switch-o at stem down position |
|
|
|
|
prevents overload of actuator and valve |
|
|
• No tools required for mounting |
|
|
AMV 130, AMV 140 |
• Maintenance free during lifetime |
|
|
• |
Low noise operation |
|
|
|
||
|
|
• Supplied with 1.5 m cable |
AMV 130H, AMV 140H
Ordering |
Type |
Supply |
Speed |
Code No. |
Spare parts |
|
|
voltage |
Type |
Code No. |
|||
|
|
|
|
|||
|
AMV 130 |
|
24 s/mm |
082H8036 |
Cable (5m) - 24 V |
082H8052 |
|
AMV 140 |
|
12 s/mm |
082H8038 |
||
|
24 V~ |
Cable (5m) - 230 V |
082H8053 |
|||
|
AMV 130H |
24 s/mm |
082H8040 |
|||
|
|
|
||||
|
|
|
|
|||
|
AMV 140H |
|
12 s/mm |
082H8042 |
|
|
|
AMV 130 |
|
24 s/mm |
082H8037 |
|
|
|
AMV 140 |
230 V~ |
12 s/mm |
082H8039 |
|
|
|
AMV 130H |
24 s/mm |
082H8041 |
|
|
|
|
|
|
|
|||
|
AMV 140H |
|
12 s/mm |
082H8043 |
|
|
Technical data |
Type |
|
|
|
AMV 130, AMV 130H |
AMV 140, AMV 140H |
|
Power supply |
|
|
|
24 Vac, 230 Vac; +10 to –15% |
|
|
Power consumption |
|
|
1 VA - 24 Vac; 8 VA - 230 Vac |
|
|
|
Frequency |
|
|
|
50 Hz/60 Hz |
|
|
Close of force |
|
|
|
200 N |
|
|
Stroke |
|
|
|
5.5 mm |
|
|
Speed |
|
|
|
24 s/mm |
12 s/mm |
|
Max. medium temperature inside the pipe |
130 °C |
|
|||
|
Ambient temperature |
|
|
0 … 55 °C |
|
|
|
Storage and transport temperature |
|
–40 … +70 °C |
|
||
|
Protection code |
|
|
IP 42 |
|
|
|
Weight |
|
|
|
0.3 kg |
|
|
- marking in accordance with standards |
EMCDirective 89/336/EEC, 92/31/EEC, 93/68/EEC, |
||||
|
EN 61000-6-1 and EN 61000-6-3 |
|||||
|
|
|
|
|
||
|
|
|
|
|
Low Voltage Directive 73/23/EEC and 93/68/EEC, |
|
|
|
|
|
|
EN 60730-2-14 |
|
DH-SMT/SI |
VD.KG.Y1.02 © Danfoss 06/2006 |
1 |
Data sheet |
Actuators for three point control AMV 130, AMV 140, AMV 130H, AMV 140H |
Installation |
Mechanical |
|
The actuator should be mounted with the valve |
|
stem in either horizontal position or pointing |
|
upwards. |
|
The actuator is fixed to the valve body by means |
|
of a mounting ring which requires no tools for |
|
mounting.The ring should be tightened by hand. |
|
Electrical |
|
Important: It is strongly recommended that the |
|
mechanical installation is completed before the |
|
electrical installation. |
|
Each actuator is supplied with the connecting |
|
cable for the controller. |
Wiring
AMV 130/140, AMV 130H/140H - 24V
AMV 130/140, AMV 130H/140H - 230V
Disposal |
The actuator must be dismantled and the |
|
elements sorted into various material groups |
|
before disposal. |
|
|
Commissioning |
The factory setting of the spindle is the fully |
|
stem up position because of easier mechanical |
|
connection of the actuator on the valve. |
2 |
VD.KG.Y1.02 © Danfoss 06/2006 |
DH-SMT/SI |