Danfoss AMV 01, AMV 02, AMV-H 01, AMV-H 02 Data sheet [nl]

0 (0)

Data sheet

Actuators for three point control AMV 01, AMV 02, AMV-H 01, AMV-H 02

Description

AMV 01, AMV 02

AMV-H 01, AMV-H 02

AMV 01/02 and AMV-H 01/02 actuators are used withVZ,VZL,VRBZ or with AB-QM valves (AMV version only).The actuator can be used with fan coil units, induction units, small reheaters, recoolers, and zone applications in which hot/ cold water is the controlled medium.

Main data:

3-point versions

The advanced design incorporates no-force switch-o at stem up position, which enables use of the actuator on valves with di erent nominal strokes and improves the controller response

Force switch-o at stem down position prevents overload of actuator and valve

No tools required for mounting

Maintenance free during the lifetime

Low noise operation

Supplied with 1.5 m cable.

Ordering

 

 

 

 

 

Spare parts

 

Type

Supply

Speed

Code No.

 

 

 

 

 

 

voltage

 

Type

Code No.

 

 

 

 

 

 

 

 

 

 

 

 

AMV 01

 

24 s/mm

082H8001

 

 

 

 

 

 

1.5 m cable for AMV, AMV-H - 24 V

082H8007

 

 

 

 

 

 

 

AMV 02

 

12 s/mm

082H8004

 

 

 

 

24 V~

 

1.5 m cable for AMV, AMV-H - 230 V

082H8008

 

 

 

 

 

 

AMV-H 01

24 s/mm

082H8021

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AMV-H 02

 

12 s/mm

082H8024

 

 

 

 

 

 

 

 

 

 

 

 

AMV 01

 

24 s/mm

082H8002

 

 

 

 

 

 

 

 

 

 

 

 

AMV 02

230 V~

12 s/mm

082H8005

 

 

 

 

 

 

 

 

 

 

 

AMV-H 01

24 s/mm

082H8022

 

 

 

 

 

 

 

 

 

 

 

 

AMV-H 02

 

12 s/mm

082H8025

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Technical data

Type

AMV 01, AMV-H 01

AMV 02, AMV-H 02

 

 

Power supply

24 Vac, 230 Vac; +10 to –15%

 

 

Power consumption

1 VA - 24 Vac; 7 VA-230 Vac

 

 

Frequency

50 Hz/60 Hz

 

 

Close of force

200 N

 

 

Max. stroke

5.5 mm

 

 

Speed

24 s/mm

12 s/mm

 

Max. medium temperature inside the pipe

120 °C

 

 

Ambient temperature

0 to 55 °C

 

 

Storage and transport temperature

–40 to +70 °C

 

 

Protection code

IP 42

 

 

Weight

0.34 kg

 

 

- marking in accordance with standards

EMCDirective 89/336/EEC, 92/31/EEC, 93/68/EEC,

 

EN 50081-1 and EN 50082-1

 

 

 

 

 

 

Low voltage Directive 73/23/EEC and 93/68/EEC,

 

 

EN 60730/2/14

 

SIBC

VD.JC.M2.02 © Danfoss 08/05

1

Danfoss AMV 01, AMV 02, AMV-H 01, AMV-H 02 Data sheet

Data sheet

Actuators for three point control AMV 01, AMV 02, AMV-H 01, AMV-H 02

Installation

Mechanical

 

The actuator should be mounted with the valve

 

stem in either horizontal position or pointing

 

upwards.

 

The actuator is fixed to the valve body by means

 

of a mounting ring which requires no tools for

 

mounting.The ring should be tightened by hand.

 

Electrical

 

Important: It is strongly recommended that the

 

mechanical installation is completed before the

 

electrical installation.

 

Each actuator is supplied with the connecting

 

cable for the controller.

Wiring

AMV/AMV-H 01, AMV/AMV-H 02 - 24V

 

AMV/AMV-H 01, AMV/AMV-H 02 - 230V

 

 

 

 

Disposal

The actuator must be dismantled and the

 

elements sorted into various material groups

 

before disposal.

 

 

Commissioning

All actuators are factory tested prior to shipment.

 

The factory setting of the spindle is the fully

 

stem up position because of easier mechanical

 

connection of actuator on valve.

 

Important: Uninstalled actuator will operated

 

properly only in stem down direction!

 

If uninstalled actuator is tested than use Allen key

 

size 4 mm (or knob for AMV-H version) in order to

 

drive actuator on it's top position.

2

VD.JC.M2.02 © Danfoss 08/05

SIBC

Loading...
+ 4 hidden pages