Danfoss BV024A, BV, BV110A, BV230A, BV240A Data sheet

...
0 (0)

Data Sheet

Solenoid coil

Type BV

Coils are designed to be used with Danfoss solenoid valves

BV is a solenoid coil with ATEX EX zone 2 approval. The coils are designed to be used with Danfoss solenoid valves.

Features:

• Embedded coils with long lifetime even under extreme conditons

• Available with 1 m 3-core cable

• Safe mounting with screw-on system

• Standard coils from 24 V to 240 V AC

• Standard coils dimensioned to max. opening di•erential pressure (MOPD) up to 21 bar for AC

AI096886423275en-000201

Danfoss BV024A, BV, BV110A, BV230A, BV240A Data sheet

Solenoid coil, type BV

Product speci€cation

Technical data

Figure 1: Type BV

<![if ! IE]>

<![endif]>Danfoss

<![if ! IE]>

<![endif]>18Z62.10

Table 1: Technical data for type BV

Speci€cation

Values

 

 

 

Mode of operation

 

 

 

 

Proctection against electrical shock

 

 

 

 

Humidity

0 - 100% RH

 

 

 

Enclosure

IP65

 

 

 

Pollution degree

3

 

 

 

Max. altitude above sea level

4000 m

 

 

 

Permissible voltage variation

11 W AC, 50 Hz: 10 to -15%

 

 

 

 

11 W AC, 60 Hz: ±10%

 

 

 

Rated impulse voltage

? kV

 

 

 

Over voltage category

-

 

 

 

Nominal current [A]

Power consumption holding

Inrush current

 

 

 

[W]

[VA]

[mA]

[ms]

 

11

21

44

-

Duty rating

100%

 

 

 

 

 

 

Ambient temperature

-20 °C to +50 °C

 

 

 

Media temperature

Max. 100 °C

 

 

 

Insulation of coil windings

 

 

 

 

Connection

3-core cable

 

 

 

 

The external thread of the cable entry is suitable for „exible steel hose or similar cable protection

Outside diameter sheet

 

 

 

 

Size of fuse in front of the coil

 

 

 

 

External earth core

 

 

 

 

 

 

 

 

 

Table 2: Classi€cation EN 60079

Type

Classi€cation

Media

 

Explosion proof area

Zone 2

Product group

II

Product category

3G

Product niveau EPL

Gc

Explosion group

IIC

Temperature class

T4

Type of protection

nA

Exposed to SUN/UV light

No

Impact height

 

 

 

WARNING:

Always install a fuse ahead of the coil. It should not exceed 2 A for coils rated less than 50 V and it should not exceed 1 A for coils rated 50 V or more. Time log: Medium.

Use only for system in compliance with ATEX. Ignition risk is evaluated in accordance to ATEX.

© Danfoss | Climate Solutions | 2021.03