Data Sheet
Solenoid coil
Type BV
Coils are designed to be used with Danfoss solenoid valves
BV is a solenoid coil with ATEX EX zone 2 approval. The coils are designed to be used with Danfoss solenoid valves.
Features:
• Embedded coils with long lifetime even under extreme conditons
• Available with 1 m 3-core cable
• Safe mounting with screw-on system
• Standard coils from 24 V to 240 V AC
• Standard coils dimensioned to max. opening di•erential pressure (MOPD) up to 21 bar for AC
AI096886423275en-000201
Solenoid coil, type BV
Product speci€cation
Technical data
Figure 1: Type BV
<![if ! IE]> <![endif]>Danfoss |
<![if ! IE]> <![endif]>18Z62.10 |
Table 1: Technical data for type BV
Speci€cation |
Values |
|
|
|
Mode of operation |
|
|
|
|
Proctection against electrical shock |
|
|
|
|
Humidity |
0 - 100% RH |
|
|
|
Enclosure |
IP65 |
|
|
|
Pollution degree |
3 |
|
|
|
Max. altitude above sea level |
4000 m |
|
|
|
Permissible voltage variation |
11 W AC, 50 Hz: 10 to -15% |
|
|
|
|
11 W AC, 60 Hz: ±10% |
|
|
|
Rated impulse voltage |
? kV |
|
|
|
Over voltage category |
- |
|
|
|
Nominal current [A] |
Power consumption holding |
Inrush current |
|
|
|
||||
|
[W] |
[VA] |
[mA] |
[ms] |
|
11 |
21 |
44 |
- |
Duty rating |
100% |
|
|
|
|
|
|
||
Ambient temperature |
-20 °C to +50 °C |
|
|
|
Media temperature |
Max. 100 °C |
|
|
|
Insulation of coil windings |
|
|
|
|
Connection |
3-core cable |
|
|
|
|
The external thread of the cable entry is suitable for „exible steel hose or similar cable protection |
|||
Outside diameter sheet |
|
|
|
|
Size of fuse in front of the coil |
|
|
|
|
External earth core |
|
|
|
|
|
|
|
|
|
Table 2: Classi€cation EN 60079
Type |
Classi€cation |
Media |
|
Explosion proof area |
Zone 2 |
Product group |
II |
Product category |
3G |
Product niveau EPL |
Gc |
Explosion group |
IIC |
Temperature class |
T4 |
Type of protection |
nA |
Exposed to SUN/UV light |
No |
Impact height |
|
|
|
WARNING:
Always install a fuse ahead of the coil. It should not exceed 2 A for coils rated less than 50 V and it should not exceed 1 A for coils rated 50 V or more. Time log: Medium.
Use only for system in compliance with ATEX. Ignition risk is evaluated in accordance to ATEX.
© Danfoss | Climate Solutions | 2021.03 |
AI096886423275en-000201 | 2 |