Omron E5CN-Q2MT-500-AC100-240, E5CSVQ1TF, E5CSVR1TF Data Sheet

0 (0)
Omron E5CN-Q2MT-500-AC100-240, E5CSVQ1TF, E5CSVR1TF Data Sheet

Temperature Controllers

E5CSV

CSM_E5CSV_DS_E_7_1

Easy Setting Using DIP Switch and Simple Functions in DIN 48 × 48 mm-size

Temperature Controllers

Easy setting using DIP switch.

Models with two alarms added to Series, ideal for temperature alarm applications.

Universal-input (thermocouple/platinum resistance thermometer) models also available.

Clearly visible digital display with character height of 13.5 mm.

Models available with black in addition to white cases.

RoHS compliant.

Model Number Structure

Refer to Safety Precautions for All Temperature Controllers.

Refer to E5CS/E5CSV Operation for operating procedures.

Model Number Legend

Models with Terminal Blocks

E5CSV-@@@@-@

 

 

1

2

3

4

5

 

 

 

 

 

1.

Control Outputs

 

 

3. Input

4.

Power Supply Voltage

 

R: Relay

 

 

 

 

KJ: Thermocouple

 

Blank: 100 to 240 VAC

 

Q: Voltage for driving SSR

P:

Platinum resistance thermometer

 

D:

24 VAC/VDC

2.

Alarm Outputs

 

 

T:

Thermocouple/platinum resistance

5.

Case Color

 

Blank: No alarm

 

 

 

thermometer (universal-input)

 

Blank: Black

 

1:

1 alarm

 

 

 

 

 

 

W:

Light gray

2:2 alarms

Note: A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to

Ordering Information when ordering.

Examples

Relay control output, without alarm, thermocouple input, light gray case: E5CSV-RKJ-W

Relay control output, one alarm output, platinum resistance thermometer input, black case: E5CSV-R1P-W

1

E5CSV

Ordering Information

List of Models

Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer, Power Supply Voltage: 100 to 240 VAC

Size

Type

Control

Alarms

Outputs

Model with

Model with platinum

 

 

modes

 

 

thermocouple

resistance

 

 

 

 

 

 

thermometer

E5CSV

Terminal block

ON/OFF or

1

Relay

E5CSV-R1KJ-W

E5CSV-R1P-W

48 × 48mm

 

PID

 

 

 

 

 

 

Voltage (for driving SSR)

E5CSV-Q1KJ-W

E5CSV-Q1P-W

 

 

 

 

 

 

 

Case Color: Light Gray, Thermocouple, Power Supply Voltage: 24 VAC/VDC

Size

Type

Control

Alarms

Outputs

Model with

 

 

modes

 

 

thermocouple

E5CSV

Terminal block

ON/OFF or

1

Relay

E5CSV-R1KJD-W

48 × 48mm

 

PID

 

 

 

Case Color: Light Gray, Universal-input, Power Supply Voltage: 100 to 240 VAC

Size

Type

Control

Alarms

Outputs

Model with universal-

 

 

modes

 

 

input (thermocouple

 

 

 

 

 

or platinum resistance

 

 

 

 

 

thermometer)

E5CSV

Terminal block

ON/OFF or

0

Relay

E5CSV-RT

48 × 48mm

 

PID

 

 

 

 

 

Voltage (for driving SSR)

E5CSV-QT

 

 

 

 

 

 

 

 

 

1

Relay

E5CSV-R1T

 

 

 

 

 

 

 

 

 

 

Voltage (for driving SSR)

E5CSV-Q1T

 

 

 

 

 

 

 

 

 

2 (See note.)

Relay

E5CSV-R2T

 

 

 

 

 

 

 

 

 

 

Voltage (for driving SSR)

E5CSV-Q2T

 

 

 

 

 

 

Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting, change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller User’s Manual” (Cat. No. H140-E1-01).

Case Color: Black, Universal-input, Power Supply Voltage: 24 VAC/VDC

Size

Type

Control

Alarms

Outputs

Model with universal-

 

 

modes

 

 

input (thermocouple

 

 

 

 

 

or platinum resistance

 

 

 

 

 

thermometer)

E5CSV

Terminal block

ON/OFF or

0

Relay

E5CSV-RTD

48 × 48mm

 

PID

 

 

 

 

 

Voltage (for driving SSR)

E5CSV-QTD

 

 

 

 

 

 

 

 

 

1

Relay

E5CSV-R1TD

 

 

 

 

 

 

 

 

 

 

Voltage (for driving SSR)

E5CSV-Q1TD

 

 

 

 

 

 

 

 

 

2 (See note.)

Relay

E5CSV-R2TD

 

 

 

 

 

 

 

 

 

 

Voltage (for driving SSR)

E5CSV-Q2TD

 

 

 

 

 

 

Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting, change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller User’s Manual” (Cat. No. H140-E1-01).

Accessories (Order Separately)

Protective Cover

Type

Model

Hard Protective Cover

Y92A-48B

 

 

Terminal Cover

Model

E53-COV10

Terminal Cover

(For Controllers after the design change scheduled for October 2010)

Model

E53-COV17

Note: The E53-COV10 Terminal Cover cannot be mounted to Controllers that are manufactured after the design change scheduled for October 2010

Rubber Packing

Model

Y92S-29

Note: The Rubber Packing is provided with the Digital Controller.

2

E5CSV

Specifications

Ratings

Supply voltage

100 to 240 VAC, 50/60 Hz

 

 

 

24 VAC, 50/60 Hz; 24 VDC

 

 

 

 

Operating voltage range

85% to 110% of rated supply voltage

 

 

 

 

Power consumption

100 to 240 VAC: 5 VA

 

 

 

24 VAC: 3 VA, 24 VDC: 2 W

 

Sensor input

Thermocouple input type:

K, J, L

 

 

Platinum resistance thermometer input type:

Pt100, JPt100

 

 

Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100

Control

Relay output

SPST-NO, 250 VAC, 3A (resistive load)

 

output

 

 

 

 

Voltage output (for driving the SSR)

12 VDC, 21 mA (with short-circuit protection circuit)

 

 

 

 

 

 

 

Control method

ON/OFF or 2-PID (with auto-tuning)

 

 

 

 

Alarm output

SPST-NO, 250 VAC, 1A (resistive load)

 

 

 

 

Setting method

Digital setting using front panel keys

 

 

 

Indication method

7-segment digital display (character height: 13.5 mm) and deviation indicators

 

 

 

Other functions

• Setting change prohibit (key protection)

 

 

 

Input shift

 

 

 

Temperature unit change (°C/°F)

 

 

 

Direct/reverse operation

 

 

 

Temperature range, Sensor switching (K/J/L, Pt100/JPt100)

 

 

 

Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models.

 

 

Control period switching

 

 

 

8-mode alarm output

 

 

 

Sensor error detection

 

Ambient operating temperature

−10 to 55°C (with no condensation or icing); with 3-year guarantee: −10 to 50°C

Ambient operating humidity

25% to 85%

 

 

 

 

Storage temperature

−25 to 65°C (with no condensation or icing)

 

Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)

2.Models for 24 VAC/DC can also be manufactured.

Characteristics

Setting accuracy

 

Thermocouple (See note 1.):

 

(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.

 

 

 

Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max.

Indication accuracy

 

(ambient temperature of 23°C)

 

 

 

 

 

Influence of temperature

R thermocouple inputs:

(±1% of PV or ±10°C, whichever is greater) ±1 digit max.

 

 

 

Other thermocouple inputs:

(±1% of PV or ±4°C, whichever is greater) ±1 digit max.

Influence of voltage

 

 

Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max.

 

 

 

 

 

Hysteresis (for ON/OFF control)

0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models)

 

 

 

Proportional band (P)

1 to 999°C (automatic adjustment using auto-tuning/self-tuning)

 

Integral time (I)

 

1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning

 

 

 

 

 

Derivative time (D)

 

1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning)

 

 

 

 

 

Alarm output range

 

Absolute-value alarm: Same as the control range

 

 

 

 

Other:

0 to input setting range full scale (°C or °F)

 

 

 

 

Alarm hysteresis:

0.2°C or °F (fixed)

 

 

 

Control period

 

2/20 s

 

 

 

 

 

 

 

 

 

 

 

Sampling period

 

500 ms

 

 

 

 

 

 

 

 

 

 

Insulation resistance

 

20 MΩ min. (at 500 VDC)

 

 

 

Dielectric strength

 

2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity

 

 

 

 

 

Vibration

 

Malfunction

10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions

 

resistance

 

 

 

 

 

 

 

 

Destruction

10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions

 

 

 

 

 

 

 

 

 

 

Shock resistance

 

Malfunction

100 m/s2 min., 3 times each in 6 directions

 

 

 

 

Destruction

300 m/s2 min., 3 times each in 6 directions

 

 

Life expectancy

 

Electrical

100,000 operations min. (relay output models)

 

 

 

 

 

 

 

 

Weight

 

Approx. 120 g (Controller only)

 

 

 

 

 

 

 

Degree of protection

 

Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00

 

 

 

 

 

Memory protection

 

EEPROM (non-volatile memory) (number of writes: 1,000,000)

 

 

 

 

 

 

 

 

EMC

 

EMI Radiated:

 

 

EN 55011 Group 1 Class A

 

 

 

 

EMI Conducted:

 

 

EN 55011 Group 1 Class A

 

 

 

 

ESD Immunity:

 

 

EN 61000-4-2: 4 kV contact discharge (level 2)

 

 

 

 

 

 

8 kV air discharge (level 3)

 

 

 

Radiated Electromagnetic Field Immunity:

EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3)

 

 

 

 

 

 

10 V/m (900 MHz pulse modulated)

 

 

 

Conducted Disturbance Immunity:

 

EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2)

 

 

 

Noise Immunity (First Transient Burst Noise): EN 61000-4-4

 

 

 

 

Burst Immunity:

 

 

2 kV power-line (level 3), 1 kV I/O signal-line (level 3)

 

 

 

Surge Immunity:

 

 

EN 61000-4-5: Power line:

Normal mode 1 kV; Common mode 2 kV

 

 

 

 

 

 

Output line (relay output): Normal mode 1 kV; Common mode 2 kV

 

 

 

Voltage Dip/Interrupting Immunity:

 

EN 61000-4-11 0.5 cycle, 100% (rated voltage)

 

 

 

 

 

 

 

Approved standards

 

UL 61010-1 (listing)

 

 

 

 

 

 

 

CSA C22.2 No.1010-1

 

 

 

 

Conformed standards

EN 61326, EN 61010-1, IEC 61010-1

 

 

 

 

 

 

VDE 0106 Part 100 (finger protection), when the terminal cover is mounted.

 

Note: 1. The following exceptions apply to thermocouples.

 

 

 

 

• U, L: ±2°C ±1 digit max.

 

 

 

 

 

• R: ±3°C ±1 digit max. at 200°C or less

 

 

 

 

2. The following exceptions apply to platinum resistance thermometers.

 

 

 

Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max.

 

 

 

3

Loading...
+ 5 hidden pages