Temperature Controllers
E5CSV
CSM_E5CSV_DS_E_7_1
Easy Setting Using DIP Switch and Simple Functions in DIN 48 × 48 mm-size
Temperature Controllers
•Easy setting using DIP switch.
•Models with two alarms added to Series, ideal for temperature alarm applications.
•Universal-input (thermocouple/platinum resistance thermometer) models also available.
•Clearly visible digital display with character height of 13.5 mm.
•Models available with black in addition to white cases.
•RoHS compliant.
Model Number Structure
Refer to Safety Precautions for All Temperature Controllers.
Refer to E5CS/E5CSV Operation for operating procedures.
■ Model Number Legend
Models with Terminal Blocks
E5CSV-@@@@-@
|
|
1 |
2 |
3 |
4 |
5 |
|
|
|
|
|
1. |
Control Outputs |
|
|
3. Input |
4. |
Power Supply Voltage |
|||||
|
R: Relay |
|
|
|
|
KJ: Thermocouple |
|
Blank: 100 to 240 VAC |
|||
|
Q: Voltage for driving SSR |
P: |
Platinum resistance thermometer |
|
D: |
24 VAC/VDC |
|||||
2. |
Alarm Outputs |
|
|
T: |
Thermocouple/platinum resistance |
5. |
Case Color |
||||
|
Blank: No alarm |
|
|
|
thermometer (universal-input) |
|
Blank: Black |
||||
|
1: |
1 alarm |
|
|
|
|
|
|
W: |
Light gray |
2:2 alarms
Note: A functional explanation is provided here for illustration, but models are not necessarily available for all possible combinations. Refer to
Ordering Information when ordering.
Examples
•Relay control output, without alarm, thermocouple input, light gray case: E5CSV-RKJ-W
•Relay control output, one alarm output, platinum resistance thermometer input, black case: E5CSV-R1P-W
1
E5CSV
Ordering Information
■ List of Models
Case Color: Light Gray, Thermocouple or Platinum Resistance Thermometer, Power Supply Voltage: 100 to 240 VAC
Size |
Type |
Control |
Alarms |
Outputs |
Model with |
Model with platinum |
|
|
modes |
|
|
thermocouple |
resistance |
|
|
|
|
|
|
thermometer |
E5CSV |
Terminal block |
ON/OFF or |
1 |
Relay |
E5CSV-R1KJ-W |
E5CSV-R1P-W |
48 × 48mm |
|
PID |
|
|
|
|
|
|
Voltage (for driving SSR) |
E5CSV-Q1KJ-W |
E5CSV-Q1P-W |
||
|
|
|
|
|
|
|
Case Color: Light Gray, Thermocouple, Power Supply Voltage: 24 VAC/VDC
Size |
Type |
Control |
Alarms |
Outputs |
Model with |
|
|
modes |
|
|
thermocouple |
E5CSV |
Terminal block |
ON/OFF or |
1 |
Relay |
E5CSV-R1KJD-W |
48 × 48mm |
|
PID |
|
|
|
Case Color: Light Gray, Universal-input, Power Supply Voltage: 100 to 240 VAC
Size |
Type |
Control |
Alarms |
Outputs |
Model with universal- |
|
|
modes |
|
|
input (thermocouple |
|
|
|
|
|
or platinum resistance |
|
|
|
|
|
thermometer) |
E5CSV |
Terminal block |
ON/OFF or |
0 |
Relay |
E5CSV-RT |
48 × 48mm |
|
PID |
|
|
|
|
|
Voltage (for driving SSR) |
E5CSV-QT |
||
|
|
|
|
|
|
|
|
|
1 |
Relay |
E5CSV-R1T |
|
|
|
|
|
|
|
|
|
|
Voltage (for driving SSR) |
E5CSV-Q1T |
|
|
|
|
|
|
|
|
|
2 (See note.) |
Relay |
E5CSV-R2T |
|
|
|
|
|
|
|
|
|
|
Voltage (for driving SSR) |
E5CSV-Q2T |
|
|
|
|
|
|
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting, change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller User’s Manual” (Cat. No. H140-E1-01).
Case Color: Black, Universal-input, Power Supply Voltage: 24 VAC/VDC
Size |
Type |
Control |
Alarms |
Outputs |
Model with universal- |
|
|
modes |
|
|
input (thermocouple |
|
|
|
|
|
or platinum resistance |
|
|
|
|
|
thermometer) |
E5CSV |
Terminal block |
ON/OFF or |
0 |
Relay |
E5CSV-RTD |
48 × 48mm |
|
PID |
|
|
|
|
|
Voltage (for driving SSR) |
E5CSV-QTD |
||
|
|
|
|
|
|
|
|
|
1 |
Relay |
E5CSV-R1TD |
|
|
|
|
|
|
|
|
|
|
Voltage (for driving SSR) |
E5CSV-Q1TD |
|
|
|
|
|
|
|
|
|
2 (See note.) |
Relay |
E5CSV-R2TD |
|
|
|
|
|
|
|
|
|
|
Voltage (for driving SSR) |
E5CSV-Q2TD |
|
|
|
|
|
|
Note: There is no alarm output 2 mode switch. The default setting for alarm output 2 is for the upper limit alarm mode. To change the setting, change the alarm type for alarm output 2 in initial setting level 5. For details, refer to the “E5CSV/E5CS-U Digital Temperature Controller User’s Manual” (Cat. No. H140-E1-01).
■ Accessories (Order Separately)
Protective Cover
Type |
Model |
Hard Protective Cover |
Y92A-48B |
|
|
Terminal Cover
Model
E53-COV10
Terminal Cover
(For Controllers after the design change scheduled for October 2010)
Model
E53-COV17
Note: The E53-COV10 Terminal Cover cannot be mounted to Controllers that are manufactured after the design change scheduled for October 2010
Rubber Packing
Model
Y92S-29
Note: The Rubber Packing is provided with the Digital Controller.
2
E5CSV
Specifications
■ Ratings
Supply voltage |
100 to 240 VAC, 50/60 Hz |
|
||
|
|
24 VAC, 50/60 Hz; 24 VDC |
|
|
|
|
|
||
Operating voltage range |
85% to 110% of rated supply voltage |
|
||
|
|
|
||
Power consumption |
100 to 240 VAC: 5 VA |
|
||
|
|
24 VAC: 3 VA, 24 VDC: 2 W |
|
|
Sensor input |
Thermocouple input type: |
K, J, L |
||
|
|
Platinum resistance thermometer input type: |
Pt100, JPt100 |
|
|
|
Universal-input (thermocouple/platinum resistance thermometer) type: K, J, L, T, U, N, R, Pt100, JPt100 |
||
Control |
Relay output |
SPST-NO, 250 VAC, 3A (resistive load) |
|
|
output |
|
|
|
|
Voltage output (for driving the SSR) |
12 VDC, 21 mA (with short-circuit protection circuit) |
|
||
|
|
|||
|
|
|
|
|
Control method |
ON/OFF or 2-PID (with auto-tuning) |
|
||
|
|
|
||
Alarm output |
SPST-NO, 250 VAC, 1A (resistive load) |
|
||
|
|
|
||
Setting method |
Digital setting using front panel keys |
|
||
|
|
|||
Indication method |
7-segment digital display (character height: 13.5 mm) and deviation indicators |
|||
|
|
|
||
Other functions |
• Setting change prohibit (key protection) |
|
||
|
|
• |
Input shift |
|
|
|
• |
Temperature unit change (°C/°F) |
|
|
|
• |
Direct/reverse operation |
|
|
|
• |
Temperature range, Sensor switching (K/J/L, Pt100/JPt100) |
|
|
|
• |
Switching is performed between a thermocouple and platinum resistance thermometer for universal-input models. |
|
|
|
• |
Control period switching |
|
|
|
• |
8-mode alarm output |
|
|
|
• |
Sensor error detection |
|
Ambient operating temperature |
−10 to 55°C (with no condensation or icing); with 3-year guarantee: −10 to 50°C |
|||
Ambient operating humidity |
25% to 85% |
|
||
|
|
|
||
Storage temperature |
−25 to 65°C (with no condensation or icing) |
|
Note: 1. Do not use an inverter output as the power supply. (Refer to Safety Precautions for All Temperature Controllers.)
2.Models for 24 VAC/DC can also be manufactured.
■Characteristics
Setting accuracy |
|
Thermocouple (See note 1.): |
|
(±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max. |
|||
|
|
|
Platinum resistance thermometer (See note 2.): (±0.5% of indication value or ±1°C, whichever is greater) ±1 digit max. |
||||
Indication accuracy |
|
||||||
(ambient temperature of 23°C) |
|
|
|
|
|
||
Influence of temperature |
R thermocouple inputs: |
(±1% of PV or ±10°C, whichever is greater) ±1 digit max. |
|||||
|
|
|
Other thermocouple inputs: |
(±1% of PV or ±4°C, whichever is greater) ±1 digit max. |
|||
Influence of voltage |
|
||||||
|
Platinum resistance thermometer inputs: (±1% of PV or ±2°C, whichever is greater) ±1 digit max. |
||||||
|
|
|
|||||
|
|
||||||
Hysteresis (for ON/OFF control) |
0.2% FS (0.1% FS for universal-input (thermocouple/platinum resistance thermometer) models) |
||||||
|
|
|
|||||
Proportional band (P) |
1 to 999°C (automatic adjustment using auto-tuning/self-tuning) |
|
|||||
Integral time (I) |
|
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning |
|
||||
|
|
|
|
||||
Derivative time (D) |
|
1 to 1,999 s (automatic adjustment using auto-tuning/self-tuning) |
|
||||
|
|
|
|
||||
Alarm output range |
|
Absolute-value alarm: Same as the control range |
|
||||
|
|
|
Other: |
0 to input setting range full scale (°C or °F) |
|
||
|
|
|
Alarm hysteresis: |
0.2°C or °F (fixed) |
|
|
|
Control period |
|
2/20 s |
|
|
|
|
|
|
|
|
|
|
|
|
|
Sampling period |
|
500 ms |
|
|
|
|
|
|
|
|
|
|
|
||
Insulation resistance |
|
20 MΩ min. (at 500 VDC) |
|
|
|
||
Dielectric strength |
|
2,000 VAC, 50/60 Hz for 1 min between current-carrying terminals of different polarity |
|
||||
|
|
|
|
||||
Vibration |
|
Malfunction |
10 to 55 Hz, 20 m/s2 for 10 min each in X, Y, and Z directions |
|
|||
resistance |
|
|
|
|
|
|
|
|
Destruction |
10 to 55 Hz, 0.75-mm single amplitude for 2 hr each in X, Y, and Z directions |
|
||||
|
|
|
|||||
|
|
|
|
|
|
||
Shock resistance |
|
Malfunction |
100 m/s2 min., 3 times each in 6 directions |
|
|
||
|
|
Destruction |
300 m/s2 min., 3 times each in 6 directions |
|
|
||
Life expectancy |
|
Electrical |
100,000 operations min. (relay output models) |
|
|||
|
|
|
|
|
|
|
|
Weight |
|
Approx. 120 g (Controller only) |
|
|
|
||
|
|
|
|
||||
Degree of protection |
|
Front panel: Equivalent to IP66; Rear case: IP20; Terminals: IP00 |
|
||||
|
|
|
|
||||
Memory protection |
|
EEPROM (non-volatile memory) (number of writes: 1,000,000) |
|
||||
|
|
|
|
|
|
|
|
EMC |
|
EMI Radiated: |
|
|
EN 55011 Group 1 Class A |
|
|
|
|
|
EMI Conducted: |
|
|
EN 55011 Group 1 Class A |
|
|
|
|
ESD Immunity: |
|
|
EN 61000-4-2: 4 kV contact discharge (level 2) |
|
|
|
|
|
|
|
8 kV air discharge (level 3) |
|
|
|
|
Radiated Electromagnetic Field Immunity: |
EN 61000-4-3: 10 V/m (80-1000 MHz, 1.4-2.0 GHz amplitude modulated) (level 3) |
|||
|
|
|
|
|
|
10 V/m (900 MHz pulse modulated) |
|
|
|
|
Conducted Disturbance Immunity: |
|
EN 61000-4-6: 3 V (0.15 to 80 MHz) (level 2) |
||
|
|
|
Noise Immunity (First Transient Burst Noise): EN 61000-4-4 |
|
|||
|
|
|
Burst Immunity: |
|
|
2 kV power-line (level 3), 1 kV I/O signal-line (level 3) |
|
|
|
|
Surge Immunity: |
|
|
EN 61000-4-5: Power line: |
Normal mode 1 kV; Common mode 2 kV |
|
|
|
|
|
|
Output line (relay output): Normal mode 1 kV; Common mode 2 kV |
|
|
|
|
Voltage Dip/Interrupting Immunity: |
|
EN 61000-4-11 0.5 cycle, 100% (rated voltage) |
||
|
|
|
|
|
|
|
|
Approved standards |
|
UL 61010-1 (listing) |
|
|
|
|
|
|
|
|
CSA C22.2 No.1010-1 |
|
|
|
|
Conformed standards |
EN 61326, EN 61010-1, IEC 61010-1 |
|
|
|
|||
|
|
|
VDE 0106 Part 100 (finger protection), when the terminal cover is mounted. |
|
|||
Note: 1. The following exceptions apply to thermocouples. |
|
|
|
|
|||
• U, L: ±2°C ±1 digit max. |
|
|
|
|
|
||
• R: ±3°C ±1 digit max. at 200°C or less |
|
|
|
|
|||
2. The following exceptions apply to platinum resistance thermometers. |
|
|
|
||||
Input set values 0, 1, 2, 3 for E5CSV: 0.5% FS ±1 digit max. |
|
|
|
3