Omron CJ2H-CPU64-EIP, CJ2H-CPU65-EIP, CJ2H-CPU67-EIP, CJ2H-CPU66-EIP, CJ2H-CPU68-EIP DATASHEET

0 (0)

SYSMAC CJ-series CJ2H (Built-in EtherNet/IP) CPU Units

CJ2H-CPU6@-EIP

CSM_CJ2H-CPU-EIP_DS_E_2_1

Flagship PLCs with Built-in

Multifunctional Ethernet Port

Small, Fast, Flexible:

The CJ2 CPU Units inherit and improve CJ1 features while also adding EtherNet/IP as a standard feature for high-speed, high-capacity Ethernet-based networking.

CJ2H-CPU6@-EIP

Features

High-speed, high-capacity EtherNet/IP is built into every model.

The CIP communications protocol is supported for direct access to multivendor devices.

Tag memory provided for easy access from host PCs and PTs.

Even more program memory and data memory.

Superior high-speed control performance: LOAD instructions execute in 16 ns, SINE instructions in 0.59 μs.

1

Omron CJ2H-CPU64-EIP, CJ2H-CPU65-EIP, CJ2H-CPU67-EIP, CJ2H-CPU66-EIP, CJ2H-CPU68-EIP DATASHEET

CJ2H-CPU6@-EIP

Ordering Information

CJ2H (Built-in EtherNet/IP) CPU Units

 

 

Specifications

 

Current

 

 

 

 

 

consumption (A)

 

 

 

 

 

 

 

 

 

Product

 

 

 

LD

 

 

Model

Standards

name

I/O capacity/Mountable

Program

 

instruction

 

 

Data memory capacity

5 V

24 V

 

 

 

Units (Expansion Racks)

capacity

execution

 

 

 

 

 

 

 

 

 

 

 

 

time

 

 

 

 

 

 

 

832K words

 

 

 

CJ2H-CPU68-EIP

 

 

 

400K steps

DM: 32K words

 

 

 

 

 

 

 

EM: 32K words × 25 banks

 

 

 

 

 

CJ2H

 

 

512K words

 

 

 

 

 

(Built-in

 

 

 

 

 

CJ2H-CPU67-EIP

 

 

250K steps

DM: 32K words

 

 

 

 

EtherNet/IP)

 

 

 

 

 

 

 

EM: 32K words × 15 banks

 

 

 

 

 

CPU Units

 

 

 

 

 

 

 

 

 

352K words

 

0.82

 

 

 

 

2,560 points / 40 Units

 

0.016 μs

CJ2H-CPU66-EIP

UC1, N, L,

 

150K steps

DM: 32K words

(See

 

(3 Expansion Racks max.)

CE

 

 

EM: 32K words × 10 banks

 

note.)

 

 

 

 

 

 

 

 

 

 

 

 

160K words

 

 

 

CJ2H-CPU65-EIP

 

 

 

100K steps

DM: 32K words

 

 

 

 

 

 

 

EM: 32K words × 4 banks

 

 

 

 

 

 

 

 

160K words

 

 

 

CJ2H-CPU64-EIP

 

 

 

50K steps

DM: 32K words

 

 

 

 

 

 

 

EM: 32K words × 4 banks

 

 

 

 

 

Note: Add 0.15 A per Adapter when using NT-AL001 RS-232C/RS-232A Adapters.

Add 0.04 A per Adapter when using CJ1W-CIF11 RS-422A Adapters.

International Standards

The standards indicated in the "Standards" column are those current for UL, CSA, cULus, NK, and Lloyd standards and EC Directives as of the end of April 2008. The standards are abbreviated as follows: U: UL, U1: UL (Class I Division 2 Products for Hazardous Locations), C: CSA, UC: cULus, UC1: cULus (Class I Division 2 Products for Hazardous Locations), CU: cUL, N: NK, L: Lloyd, and CE: EC Directives

Ask your OMRON representative for the conditions under which the standards were met.

Accessories

The following accessories come with CPU Unit:

Item

Specification

Battery

CJ1W-BAT01

End Cover

CJ1W-TER01 (necessary to be mouned at the right end of CPU Rack)

End Plate

PFP-M (2 pcs)

Serial Port (RS-232C) Connector

Connector set for serial port connection (D-SUB 9-pin male connector)

 

 

2

CJ2H-CPU6@-EIP

General Specifications

 

Item

 

 

 

 

CJ2H-

 

 

 

 

CPU64-EIP

 

CPU65-EIP

 

CPU66-EIP

 

CPU67-EIP

 

CPU68-EIP

 

 

 

 

 

 

Enclosure

Mounted in a panel

 

 

 

 

 

 

 

Grounding

Less than 100 Ω

 

 

 

 

 

 

 

CPU Rack Dimensions

90 mm × 65 mm × 80 mm (H × D × W)

 

 

 

 

 

Weight

280 g or less

 

 

 

 

 

 

 

Current Consumption

5 VDC, 0.82 A

 

 

 

 

 

 

 

 

Ambient Operating Temperature

0 to 55°C

 

 

 

 

 

 

 

 

Ambient Operating Humidity

10% to 90%

 

 

 

 

 

 

 

 

Atmosphere

Must be free from corrosive gases.

 

 

 

 

 

 

Ambient Storage Temperature

−20 to 70°C (excluding battery)

 

 

 

 

 

 

Altitude

2,000 m or less

 

 

 

 

 

 

 

 

Pollution Degree

2 or less: Conforms to JIS B3502 and IEC 61131-2.

 

 

 

Use Environment

Noise Immunity

2 kV on power supply line (Conforms to IEC 61000-4-4.)

 

 

 

Overvoltage Category

Category II: Conforms to JIS B3502 and IEC 61131-2.

 

 

 

 

 

 

 

 

EMC Immunity Level

Zone B

 

 

 

 

 

 

 

 

 

Conforms to JIS C60068-2-6.

 

 

 

 

 

 

Vibration Resistance

5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz

 

 

 

 

Acceleration of 9.8 m/s2 for 100 min in X, Y, and Z directions (10 sweeps of 10 min each =

 

 

 

 

100 min total)

 

 

 

 

 

 

 

 

Shock Resistance

Conforms to JIS C60068-2-27.

 

 

 

 

 

 

147 m/s2, 3 times in X, Y, and Z directions (100 m/s2 for Relay Output Units)

 

 

 

 

Battery

Life

5 years at 25°C

 

 

 

 

 

 

 

Model

CJ1W-BAT01

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Applicable Standards

Conforms to cULus and EC Directives.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

CJ2H-CPU6@-EIP

Performance Specifications

 

Items

 

 

 

CJ2H-

 

 

 

 

 

 

 

 

 

 

 

CPU64-EIP

 

CPU65-EIP

CPU66-EIP

 

CPU67-EIP

CPU68-EIP

 

 

 

 

 

User Memory

 

 

50K steps

 

100K steps

150K steps

 

250K steps

400K steps

I/O Bits

 

 

2,560 bits

 

 

 

 

 

 

 

 

 

Normal Mode: 200 μs

 

 

 

 

 

Overhead Processing Time

(If tag data links are used with EtherNet/IP, add the following to the above time: 100 μs + Number of transferred

 

words × (0.33 μs or 0.87 μs *))

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* When High-speed interrupt function is used

 

 

 

Execution Time

Basic Instructions: 0.016 μs min.;

 

 

 

 

Processing

Special Instructions: 0.048 μs min.

 

 

 

 

 

 

 

 

 

 

Speed

 

I/O Interrupts and

Start time of interrupt task : 26 μs or 17 μs * (30 μs in unit Ver.1.0)

 

 

 

Return time to cyclic task : 11 μs or 8 μs * (15 μs in unit Ver.1.0)

 

 

 

 

External Interrupts

 

 

 

 

* When High-speed interrupt function is used

 

 

 

Interrupts

 

 

 

 

Scheduled

Start time of interrupt task : 22 μs or 13 μs * (27 μs in unit Ver.1.0)

 

 

 

 

 

 

Return time to cyclic task : 11 μs or 8 μs * (15 μs in unit Ver.1.0)

 

 

 

 

Interrupts

 

 

 

 

* When High-speed interrupt function is used

 

 

 

 

 

 

 

Maximum Number of Connectable Units

Total per CPU Rack or Expansion Rack: 10 Units max.;

 

 

Total per PLC: 40 Units max.

 

 

 

 

 

 

 

 

 

 

 

Maximum Number of Expansion Racks

3 max.

 

 

 

 

 

 

 

I/O Area

2,560 bits (160 words): Words CIO 0000 to CIO 0159

 

 

 

Link Area

3,200 bits (200 words): Words CIO 1000 to CIO 1199

 

 

 

CPU Bus Unit Area

6,400 bits (400 words): Words CIO 1500 to CIO 1899

 

 

CIO Area

Special I/O Unit Area

15,360 bits (960 words): Words CIO 2000 to CIO 2959

 

 

 

DeviceNet Area

9,600 bits (600 words): Words CIO 3200 to CIO 3799

 

 

 

Internal I/O Area

3,200 bits (200 words): Words CIO 1300 to CIO 1499

 

 

 

37,504 bits (2,344 words): Words CIO 3800 to CIO 6143

 

 

 

 

 

Cannot be used for external I/O.

 

 

 

 

Work Area

 

 

8,192 bits (512 words): Words W000 to W511

 

 

 

 

Cannot be used for external I/O.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8,192 bits (512 words): Words H000 to H511

 

 

Holding Area

 

 

Bits in this area maintain their ON/OFF status when PLC is turned OFF or operating mode is changed.

 

 

Words H512 to H1535: These words can be used only for function blocks. They can be used only for function

 

 

 

 

 

 

block instances (i.e., they are allocated only for internal variables in function blocks).

 

 

 

 

Read-only: 31,744 bits (1,984 words)

 

 

 

 

Auxiliary Area

 

 

• 7,168 bits (448 words): Words A0 to A447

 

 

 

 

• 24,576 bits (1,536 words): Words A10000 to A11535

 

 

 

 

 

 

 

 

 

 

Read/write: 16,384 bits (1,024 words) in words A448 to A1471

 

 

Temporary Area

 

 

16 bits: TR0 to TR15

 

 

 

 

Timer Area

 

 

4,096 timer numbers (T0000 to T4095 (separate from counters))

 

 

Counter Area

 

 

4,096 counter numbers (C0000 to C4095 (separate from timers))

 

 

 

 

 

32k words (Bits in the DM Area can be addressed either by bit or by word.)

 

DM Area

 

 

DM Area words for Special I/O Units: D20000 to D29599 (100 words × 96 Units)

 

 

 

 

DM Area words for CPU Bus Units: D30000 to D31599 (100 words × 16 Units)

 

 

 

 

32k words/bank × 25 banks max.: E00_00000 to E18_32767 max.

 

 

EM Area

 

 

(Bits in the EM Area can be addressed either by bit or by word.)

 

 

 

 

 

 

 

 

 

 

 

 

 

32K words × 4

 

32K words × 4

32K words × 10

 

32K words × 15

32K words × 25

 

 

 

 

 

 

 

 

banks

 

banks

banks

 

banks

banks

 

 

Force-set/reset

EM3

 

EM3

EM6 to EM9

 

EM7 to EME

EM11 to EM18

 

 

Enabled Banks

Force-setting/resetting is enabled only for areas specified for automatic address allocation.

Index Registers

 

 

IR0 to IR15

 

 

 

 

 

 

 

 

These are special registers for storing PLC memory addresses for indirect addressing. (Index Registers can

 

 

 

be set so that they are unique in each task or so that they are shared by all tasks.)

 

Cyclic Task Flag Area

128 flags

 

 

 

 

 

 

Memory Card

 

 

128 MB, 256 MB, or 512 MB

 

 

 

 

 

 

 

PROGRAM Mode: Programs are not executed. Preparations can be executed prior to program execution in

Operating Modes

 

this mode.

 

 

 

 

MONITOR Mode: Programs are executed, and some operations, such as online editing, and changes to

 

 

 

 

present values in I/O memory, are enabled in this mode.

 

 

 

 

RUN Mode:

Programs are executed. This is the normal operating mode.

 

Execution Mode

 

 

Normal Mode

 

 

 

 

 

 

 

 

 

Ladder Logic (LD),

 

 

 

 

 

 

Programming Languages

Sequential Function Charts (SFC),

 

 

 

 

Structured Text (ST), and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Instruction Lists (IL)

 

 

 

 

Function

Maximum number of definitions

2,048

 

 

 

 

 

 

Blocks

Maximum number of instances

2,048

 

 

 

 

 

 

 

Type of Tasks

Cyclic tasks

 

 

 

 

 

 

 

Interrupt tasks (Power OFF interrupt tasks, scheduled interrupt tasks, I/O interrupt tasks, and external interrupt

 

 

 

tasks)

 

 

 

 

 

 

Tasks

 

 

Cyclic tasks: 128

 

 

 

 

 

 

 

Number of Tasks

Interrupt tasks: 256

 

 

 

 

 

(Interrupt tasks can be defined as cyclic tasks to create extra cyclic tasks. Therefore, the total number of cyclic

 

 

 

 

 

 

tasks is actually 384 max.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

CJ2H-CPU6@-EIP

 

Items

 

 

 

 

CJ2H-

 

 

 

 

 

 

 

 

 

 

 

 

 

CPU64-EIP

 

CPU65-EIP

 

CPU66-EIP

CPU67-EIP

 

CPU68-EIP

 

 

 

 

 

 

 

• Local symbols: Can be used only within a single task in the PLC.

 

 

Type of Symbols

• Global symbols: Can be used in all tasks in the PLC.

 

 

 

 

• Network symbols (tags): I/O memory in the CPU Unit can be externally accessed using symbols, depending

 

 

 

 

on parameter settings.

 

 

 

 

 

 

 

 

• BOOL (bit)

 

 

 

 

 

 

 

 

• UINT (one-word unsigned binary)

 

 

 

 

 

 

• UDINT (two-word unsigned binary)

 

 

 

 

 

 

• ULINT (four-word unsigned binary)

 

 

 

 

 

 

• INT (one-word signed binary)

 

 

 

 

 

 

• DINT (two-word signed binary)

 

 

 

 

 

 

• LINT (four-word signed binary)

 

 

 

 

 

 

• UINT BCD (one-word unsigned BCD) *1

 

 

 

 

 

 

• UDINT BCD (two-word unsigned BCD) *1

 

 

 

 

 

• ULINT BCD (four-word unsigned BCD) *1

 

 

 

 

Data Type of Symbols

• REAL (two-word floating-point)

 

 

 

 

 

• LREAL (four-word floating-point)

 

 

 

 

 

 

 

 

 

 

 

 

• CHANNEL (word) *1

 

 

 

 

 

 

Symbols

 

• NUMBER (constant or number) *1

 

 

 

 

 

• WORD (one-word hexadecimal)

 

 

 

 

(Variables)

 

 

 

 

 

 

• DWORD (two-word hexadecimal)

 

 

 

 

 

 

 

 

 

 

 

 

• LWORD (four-word hexadecimal)

 

 

 

 

 

 

• STRING (1 to 255 ASCII characters)

 

 

 

 

 

 

• TIMER (timer) *2

 

 

 

 

 

 

 

 

• COUNTER (counter) *2

 

 

 

 

 

 

*1. Cannot be used in Function blocks

 

 

 

 

 

 

*2. Can be used only in Function blocks

 

 

 

 

 

Maximum Size of Symbol

32k words

 

 

 

 

 

 

 

Array Symbols (Array Variables)

One-dimensional arrays

 

 

 

 

 

 

 

Number of Array Elements

32,000 elements max.

 

 

 

 

 

 

 

Number of Registrable Network

20,000 max.

 

 

 

 

 

 

 

Symbols (Tags)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Length of Network Symbol (Tag)

255 bytes max.

 

 

 

 

 

 

 

Name

 

 

 

 

 

 

 

 

 

Encoding of Network Symbols

UTF-8

 

 

 

 

 

 

 

(Tags)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Memory Capacity

8,000 words

 

 

16,000 words

32,000 words

 

 

 

 

 

 

 

 

 

 

 

(Up to 32k words × 25 banks when EM is specified in CX-Programmer)

 

 

 

 

 

Number of Samplings

Bits = 31, one-word data =16, two-word data = 8, four-word data = 4

 

 

Sampling Cycle

1 to 2,550 ms (Unit: 1 ms)

 

 

 

 

 

 

Data Tracing

 

ON/OFF of specified bit

 

 

 

 

 

 

 

Trigger Conditions

Data comparison of specified word

 

 

 

 

 

Data size: 1 word, 2 words, 4 words

 

 

 

 

 

 

Comparison Method: Equals (=), Greater Than (>), Greater Than or Equals (≥), Less Than (<), Less Than or

 

 

Equals (≤), Not Equal (≠)

 

 

 

 

 

 

 

Delay Value

−32,768 to +32,767 ms

 

 

 

 

 

 

File Memory

 

Memory Card (128, 256, or 512 Mbytes) (Use the Memory Cards provided by OMRON.)

 

 

EM file memory (Part of the EM Area can be converted for use as file memory.)

 

 

 

 

Source/

Function block program

 

 

 

 

 

 

 

 

Comment

memory, comment file, program

Capacity: 3.5 Mbytes

 

 

 

 

 

 

Memory

index file, symbol tables

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5