Honeywell H46C, H46E Installation Manual

0 (0)
H46C,E Humidity Controllers
INSTALLATION INSTRUCTIONS

APPLICATION

The H46C,E Humidity Controllers are used with portable and central unit dehumidifiers to maintain relative humidity. The H46 has an spst, snap-acting switch designed for line voltage circuits. The H46C has two leadwires for switch box mounting. The H46E has an electric cord with an interrupter plug.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow them could damage the product or cause a hazard­ous condition.
2. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.
3. Installer must be a trained, experienced service technician.
4. After installation is complete, check out product operation as provided in these instructions.
CAUTION
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.

Location

Select a location about 5 ft (1.5 m) above the floor in an area with good circulation at average temperature and humidity for the area to be controlled. Avoid locations near hot or cold air ducts and discharge air from the controlled equipment.

Mounting H46C

1. Remove the setting knob.
2. Pull the cover forward from the device to remove.
3. Install a 2 in. x 3 in. (51 mm x 76 mm) vertical
switch box at the selected location.
4. Using the two screws provided, fasten the adapter plate to the switch box as shown. See Fig. 1.
5. Pull the wires from the switch box through the opening in the adapter plate and connect to the H46 leadwires with the solderless connectors (provided). See Fig. 4-6 for typical hookups.
6. Push the wires back into the switch box.
7. Place the H46 against the adapter plate, making
certain the tab at the bottom of the plate fits into the notch on the H46.
8. Fasten the H46 to the adapter plate by tightening the captive screw.
9. Replace the cover and the setting knob.

Mounting H46E

1. At the selected location, insert the two wood screws (provided) into the wall 2 in. (51 mm) vertically apart and protruding 1/16 in. (2 mm) from the wall. See Fig. 2.
2. Position the H46 on the screws and slide it down until the screws are in the slots.
3. Insert the dehumidifier plug into the end of the interrupter plug. See Fig. 3.
4. Insert the interrupter plug into the electrical outlet.
NOTE: H46E has a 3-prong plug. When connecting to
the 2-prong receptacle, use the converter plug (not included) and connect the pigtail lead to the ground screw.
® U.S. Registered Trademark Copyright © 2003 Honeywell International Inc. • • All Rights Reserved
69-1000B-1
H46C,E HUMIDITY CONTROLLERS
2 X 3 IN.
S
F
(COVER ON)
P S
PROTECTION AS REQUIRED.
H46C,E
R
N R
ADAPTER PLATE
H46 (COVER OFF)
NYLON ELEMENT
SCREWS (2)
H46 CAPTIVE MOUNTING SCREW
SWITCH BOX
ADAPTER PLATE
PLATE TAB
H46 LEADWIRES (2)
WALL SURFACE
Fig. 1. Mounting H46C on vertical switch box.
WOOD SCREW
2 IN.
KEYHOLES IN BACK O CASE (2)
WALL SURFACE
H46
CORD
M7908
Fig. 2. Mounting H46E with two screws.
M7907
STANDARD WALL OUTLET OR EXTENSION CORD
TO H46E
H46E PLUG
DEHUMIDIFIER PLUG
TO DEHUMIDIFIER
M7909
Fig. 3. Connecting H46E interrupter plug.

WIRING

Disconnect power supply before connecting wiring to avoid electrical shock or equipment damage. All wiring must comply with local codes and ordinances. Do not exceed contact and coil ratings when wiring into the system.

Connections and Operation

A dehumidistat in combination with the thermostat can be used to run the air conditioner to control relative humidity levels. The H46C dehumidistat and thermostat can be wired in parallel or in series.
Wiring in parallel allows the dehumidistat to indepen­dently control the humidity level, but could cause overcooling of the home. During unoccupied times, the homeowner should set the thermostat to a relatively high setting and control moisture using the dehumidistat.
Wiring in series prevents overcooling but the air conditioner runs only when both the thermostat and dehumidistat are calling. During unoccupied times, the homeowner should set the thermostat to a relatively low setting and control moisture using the dehumidistat.
HUMIDITY
CONTROLLER
RISE
L1 (HOT)
OWER
1
UPPLY
L2
PROVIDE DISCONNECT MEANS AND OVERLOAD
1
DEHUMIDIFIE EXHAUST FA OR AIR CONDITIONE
M7915
69-1000B-1 2
Fig. 4. Typical wiring diagram for H46C,E.
H46C,E HUMIDITY CONTROLLERS
3
H46C
FILTER LIGHT
HEAT OFF FANAUTO ONCOOL
3 2
1
PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED.
HEATING DAMPER MOTOR, IF USED.
2 3
CLOGGED FILTER SWITCH OR COOLING PANEL CONNECTION.
Fig. 5. Typical parallel wiring hookup for H46C with T87F/Q539A combination for dehumidification
T87F/Q539A INTERNALSCHEMATIC
R1
BX O
and mildew control.
T87F
TEMPERATURE FALL
W1 Y1
HEAT OFF COOL
W Y
HEATING RELAY OR VALVE COIL
COOLING CONTACTOR COIL
FIXED COOL ANTICIPATOR
G RHR
FAN RELAY COIL
ADJUSTABLE HEAT ANTICIPATOR
1
M791
3 69-1000B-1
Loading...
+ 5 hidden pages