H46C Humidity Controller

APPLICATION

 

INSTALLATION INSTRUCTIONS

5.

opening in the adapter plate and connect to the

 

Pull the wires from the switch box through the

The H46C Humidity Controller is used with portable and

 

H46 leadwires with the solderless connectors

6.

provided. See Fig. 2 and 3 for typical hookup.

central unit dehumidifiers to maintain relative humidity.

Push the wires back into the switch box.

The H46 has an spst, snap-acting switch designed for

7.

Place the H46 against the adapter plate, making

line voltage circuits and two leadwires for switch box

 

certain the tab at the bottom of the plate fits into the

mounting.

8.

notch on the H46.

 

 

Fasten the H46 to the adapter plate by tightening

INSTALLATION

9.

the captive screw.

 

Replace the cover and the setting knob.

When Installing this Product...

 

 

SWITCH BOX

 

 

 

2 X 3 IN.

1. Read these instructions carefully. Failure to follow

 

ADAPTER PLATE

 

 

SCREWS (2)

 

them could damage the product or cause a

H46 CAPTIVE

 

hazardous condition.

MOUNTING SCREW

 

2. Check the ratings in the instructions and on the

H46

 

 

product to make sure the product is suitable for

(COVER OFF)

 

your application.

 

 

 

3. Installer must be a trained, experienced service

 

 

 

technician.

 

 

 

4.After installation is complete, check out product operation as provided in these instructions.

CAUTION

Electrical Shock Hazard.

Can cause electrical shock or equipment damage.

Disconnect power supply before connecting wiring.

Location

Select a location about 5 ft (1.5m) above the floor in an area with good circulation at average temperature and humidity for the area to be controlled. Avoid locations near hot or cold air ducts and discharged air from the controlled equipment.

WALL SURFACE

 

ADAPTER PLATE

 

 

PLATE TAB

 

NYLON

H46 LEADWIRES (2)

M7907

ELEMENT

 

Fig. 1. Mounting H46C on vertical switch box.

Wiring

Mounting

1.Remove the setting knob.

2.To remove cover, pull cover forward from device.

3.Install a 2 in. x 3 in. (51 mm x 76 mm) vertical switch box at the selected location.

4.Using the two screws provided, fasten the adapter plate to the switch box, as shown.

Disconnect power supply before connecting wiring to avoid electrical shock or equipment damage. All wiring must comply with local codes or equipment damage. All wiring must comply with local codes and ordinances. Do not exceed contact and coil ratings when wiring into system. See Fig. 2.

® U.S. Registered Trademark

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Copyright © 2003 Honeywell International Inc. •

• All Rights Reserved

95-5367-4

 

 

Honeywell H46C User Manual

H46C HUMIDITY CONTROLLER

 

HUMIDITY

H46C

 

CONTROLLER

 

RISE

DEHUMIDIFIER

 

 

 

L1

EXHAUST FAN

POWER

(HOT)

OR AIR

SUPPLY 1

CONDITIONER

 

 

 

L2

 

 

 

 

1 PROVIDE DISCONNECT MEANS AND OVERLOAD

M7923

PROTECTION AS REQUIRED.

 

Fig. 2. Typical H46C wiring diagram.

Connections and Operation

A dehumidistat in combination with the thermostat can be used to run the air conditioner to control relative humidity levels. The dehumidistat and thermostat can be wired in parallel or in series.

Wiring in parallel allows the dehumidistat to indepen­ dently control the humidity level, but could cause overcooling of the home. During unoccupied times, the homeowner should set the thermostat to a relatively high setting and control moisture using the dehumidistat.

Wiring in series prevents overcooling but the air conditioner runs only when both the thermostat and dehumidistat are calling. During unoccupied times, the homeowner should set the thermostat to a relatively low setting and control moisture using the dehumidistat.

SETTING AND ADJUSTMENT

The H46 makes contact on a relative humidity rise to the setpoint to start the dehumidifier. On a decrease in relative humidity to the setpoint (minus the differential), the switch breaks contact to stop the dehumidifier. Turn the knob clockwise to the setting stop to place the H46 in the On position. Turn the knob counterclockwise to the setting stop to place the H46 in the Off position.

CHECKOUT

After completing all mounting and wiring, turn on the power supply. Place the system into operation by turning the setting knob toward the low end of the scale until the dehumidifier motor starts. Turn the setting knob slowly toward the high end of the scale until the dehumidifier motor stops.

H46C

T87F/Q539A INTERNALSCHEMATIC

 

 

 

 

 

 

T87F

 

FIXED

 

 

 

 

 

R1

 

 

 

 

 

 

 

FILTER

 

 

 

COOL

 

 

 

 

 

 

 

TEMPERATURE

ANTICIPATOR

 

 

 

LIGHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FALL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADJUSTABLE

 

 

 

 

 

 

 

 

HEAT

 

 

 

 

 

 

 

 

ANTICIPATOR

 

 

 

 

 

W1

 

Y1

 

 

 

 

 

HEAT

OFF COOL

 

 

AUTO

FAN

ON

 

 

 

 

 

HEAT

OFF

COOL

 

 

 

 

3

2

 

 

 

 

 

 

R

H

X

B

O

W

 

Y

G

R

 

 

 

 

 

HEATING

 

 

 

 

 

 

 

 

 

RELAY OR

 

 

 

 

 

 

 

 

VALVE COIL

 

 

 

1PROVIDE OVERLOAD PROTECTION AND DISCONNECT MEANS AS REQUIRED.

2HEATING DAMPER MOTOR, IF USED.

3CLOGGED FILTER SWITCH OR COOLING PANEL CONNECTION.

COOLING

CONTACTOR

FAN RELAY

COIL

COIL

1

M7913

Fig. 3. Typical parallel wiring hookup for H46C with T87F/Q539A combination for dehumidification and mildew control.

95-5367-4