Honeywell F300E User Manual

0 (0)

F300E Electronic Air Cleaner

with Enhanced Filtration

PRODUCT DATA

APPLICATION

The F300E Electronic Air Cleaner is mounted in the return air duct of a forced air heating, cooling, or ventilating system. It captures a significant amount of the airborne particles 0.3 micron and larger from air circulated through it.

FEATURES

Media postfilters provide enhanced filtration.

Available in four sizes to fit most ducts; adapts to airflow from either side.

Capacity varies from 1200 cfm (2040 m3/hr) to 2000 cfm (3400 m3/hr), depending on size.

Solid state power supply is self-regulating and maintains peak efficiency during a wide range of cell dirt loading conditions.

Low pressure drop.

Optional W8600F Air Cleaner Monitor indicates air cleaner performance, reminds homeowner when filter and cell maintenance are due and when to check the system.

Optional wireless W8600A AIRWATCH™ LCD indicator provides reminder when air cleaner electronic cells need washing, when media postfilters need replacing, when UV lamps need replacing and when humidifier pad needs replacing.

Galvanized cabinet protects against rust.

Neon light next to on-off switch tells if air cleaner is powered and if high voltage is present.

Prefilter screens protect cells from large dirt particles.

Test button checks system operation.

 

Contents

Application/Features..........................................................

1

Specifications/Ordering Information ..................................

2

Installation .........................................................................

7

Operation...........................................................................

10

Checkout ...........................................................................

10

Service ..............................................................................

11

Replacement Parts/Exploded View ...................................

15

® U.S. Registered Trademark

 

Copyright © 2003 Honeywell International Inc. All Rights Reserved

68-0240EF-3

 

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

SPECIFICATIONS

IMPORTANT

The specifications given in this publication do not include normal manufacturing tolerances. Therefore, this unit may not exactly match the listed specifications. This product is tested and calibrated under closely controlled conditions, and some minor differences in performance can be expected if those conditions are changed.

Model:

Electronic Air Cleaner: Includes cabinet, access door, solid state power supply, two electronic cells, two metal mesh prefilters, and two media postfilters.

Electrical Ratings:

Voltage and Frequency: Models available for 120V, 60 Hz. Can be converted in the field to 240V, 60 Hz or 220/240V, 50 Hz with the 203365A Conversion Kit.

Power Consumption: 36W maximum. Current Draw: See Table 1.

Ionizer Voltage: 8150 Vdc.

Collector Voltage: 4075 Vdc.

Table 1. Current Draw.

 

 

 

 

 

 

 

Size

No.

Max Current (A)

 

 

 

 

 

in.

 

mm

Cells

120V

220/240V

 

 

 

 

 

 

 

 

 

 

 

 

16 x 25

 

406 x 635

2

0.4

0.2

 

 

 

 

 

 

20 x 25

 

508 x 635

2

0.4

0.2

 

 

 

 

 

 

16 x 20

 

406 x 508

2

0.4

0.2

 

 

 

 

 

 

20 x 20

 

508 x 508

2

0.4

0.2

 

 

 

 

 

 

Fractional Efficiency:

Efficiency ratings are based on American Society of Heating, Refrigerating and Air-Conditioning Engineers Standard 52.2-1999. Efficiency ranges are defined for small particles, E1 =.3 to 1.0 micron; medium particles, E2 = 1.0 to 3.0 microns; and large particles, E3 = 3.0 to 10.0 microns.

E1 = Up to 81% at 492 fpm. E2 = Up to 93% at 492 fpm. E3 = Up to 99% at 492 fpm.

Pressure Drop Vs. Airflow:

Velocity (fpm)

Pressure Drop (in.wc)

123.0

0.030

246.0

0.086

 

 

295.0

0.112

 

 

369.0

0.165

 

 

492.0

0.266

 

 

615.0

0. 402

 

 

Temperature Ratings:

Operating Ambient: 40° to 125°F (4° to 52°C). Temperature of Airflow Through Cells: 40° to 125°F

(4° to 52°C).

Maximum Cell Washing Temperature: 220°F (140°C). Storage and Shipping Ambient: Minus 40°F to plus 140°F

(minus 40°C to plus 60°C).

Mounting:

Mounts in the return air duct of a forced air heating, cooling, or ventilating system. Mount upstream from an atomizing humidifier. See Planning the Installation section.

Weight:

See Table 2.

Dimensions:

See Fig. 1.

Approvals:

Underwriters Laboratories Inc. Listed: File E30954.

ORDERING INFORMATION

When purchasing replacement and modernization products from your Total Comfort System wholesaler or distributor, refer to the Total Comfort System catalog or price sheets for complete ordering number or specify:

1.Order number.

2.Voltage and frequency.

3.Dimensions: 16 x 20 in. (406 x 508 mm), 16 x 25 in. (406 x 635 mm), 20 x 20 in. (508 x 508 mm) and 20 x 25 in. ( 508 x 635 mm),

4.Conversion Kit for changing two-cell 120V, 60 Hz models to 240V, 60 Hz or 220/240V, 50 Hz.

5.W8600F Air Cleaner Monitor, if desired.

6.W8600A AIRWATCH™ Indicator, if desired.

7.Additional F300 Electronic Air Cleaner Media Postfilters, as needed.

If you have additional questions, need further information, or would like to comment on our products or services, please:

1.Write: Automation and Control Solutions Customer Response, 1985 Douglas Drive N, Golden Valley, MN 55422-4386.

2.Visit our web site: www.honeywell.com/yourhome.

68-0240EF—3

2

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

Accessories:

 

 

 

 

 

 

Repair Parts:

 

 

 

 

203365A Conversion Kit for changing 120V, 60 Hz power

 

 

See Replacement Parts/Exploded View section.

 

supply to 240V, 60 Hz or 220/240V, 50 Hz.

 

 

 

 

 

 

 

 

W8600F Air Cleaner Monitor.

 

 

 

 

 

 

 

 

 

 

 

 

W8600A AIRWATCH™ Indicator.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 2. Shipping and Installed Weight.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Weight

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16 x 20 in.

 

 

16 x 25 in.

 

20x 20 in.

20 x 25 in.

 

 

(406 x 508 mm)

 

(406 x 635 mm)

 

(508x 508 mm)

(508 x 635 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

lb

 

kg

 

lb

 

kg

 

lb

kg

lb

kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Electronic Cell (each)

 

5

 

2.25

 

6

 

2.7

 

6-3/16

2.8

7-1/2

3.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shipping Weight

 

30

 

13.6

 

33

 

15.0

 

33

15.0

38

17.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installed Weight

 

26

 

11.6

 

28

 

12.7

 

29

13.2

33

15.0

(Cells included)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

68-0240EF—3

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

6

3

 

 

 

8 (162)

 

 

 

ELECTRONIC AIR CLEANER

DIM. E

 

 

 

 

(SEE TABLE)

 

 

 

DIM. A

 

 

 

 

(SEE TABLE)

 

 

3

7

5

 

 

8

DIM. C (SEE TABLE)

 

6 4

8

 

(22)

(172)

(16)

DIM. D (SEE TABLE)

 

 

 

 

F300E SIZE

DIM. A

 

DIM. B

 

DIM. C

 

DIM. D

 

DIM. E

 

IN.

MM

IN.

MM

IN.

MM

IN.

MM

IN.

MM

IN.

MM

16 X 25

406 X 635

14-7/16

367

16-3/16

411

23-1/4

591

25-1/2

648

2-3/4

70

20 X 25

508 X 635

18-7/16

468

20-3/16

513

23-1/4

591

25-1/2

648

2-3/4

70

16 X 20

406 X 508

14-7/16

367

16-3/16

411

18-1/4

457

20-1/2

521

2-3/4

70

20 X 20

508 X 508

18-7/16

468

20-3/16

513

18-1/4

457

20-1/2

521

2-3/4

70

DIM. B

(SEE TABLE)

7

8

(22)

M19776

Fig. 1. Electronic Air Cleaner installation dimensions in in. (mm).

PLANNING THE INSTALLATION

Application

The F300E Electronic Air Cleaner is used in a forced air heating, cooling, or ventilating system. It removes airborne particles from the air circulated through it. All models have an internal air flow switch that automatically energizes the air cleaner cells when the system blower is on.

IMPORTANT

Do not mount in the discharge air duct.

For most efficient air cleaning, airflow must be spread evenly across the face of the air cleaner. If the duct is a different size than the air cleaner cabinet, gradual transitions are recommended. If the duct turns sharply just before the air cleaner, turning vanes are recommended.

Applications with Air Conditioning

Review Installation Requirements

The air cleaner should be installed where all the air passing through the system circulates through it. The best location is in the return air duct next to the blower compartment so the air cleaner can help keep the blower motor and evaporator coils clean.

The air cleaner should be installed upstream from the evaporator coil. The air cleaner will help keep the coil clean, reducing maintenance.

68-0240EF—3

4

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

Applications with a Humidifier

An evaporative humidifier can be mounted upstream from the air cleaner. An atomizing humidifier should be mounted downstream from the air cleaner, even though hard water salts will be blown into the living space and deposited as dust. If an atomizing humidifier must be mounted upstream from the air cleaner:

1.Mount it as far as possible upstream from the air cleaner.

2.Install a standard disposable furnace filter between the humidifier and the air cleaner to trap water droplets and hard water salts.

3.Frequently clean the air cleaner to prevent a hard water salt buildup.

NOTE: The volume of water that passes through an atomizing humidifier can overload the air cleaner, resulting in hard water salts being deposited as dust in the living space.

Applications with Outdoor Air Intake

Return air temperature must be at least 40°F (4°C). Lower temperatures can cause ionizer wire failure. If outdoor air is used, warm it upstream from the air cleaner by:

Making sure the outdoor intake is far enough upstream from the air cleaner so the return and outdoor air is thoroughly mixed. Stratified air can dump a stream of very cold air into one section of the air cleaner.

Adding baffles upstream from the air cleaner to force thorough air mixing.

Installing a Honeywell Perfect Window™ Fresh Air Ventilation System that transfers up to 80 percent of the heat from the exhaust air to the incoming outside air. This keeps the incoming air above 40°F (4°C) and reduces energy usage.

Installing a preheater if large amounts of outdoor air are used. The preheater, which could be an electric strip heater or hot water coil, should be controlled by a thermostat. Hot water or steam coils should be protected by a freeze-up control.

Optional W8600F Air Cleaner Monitor

The W8600F Air Cleaner Monitor can be mounted in the living area or in the furnace room. It should be located in a convenient location to observe the display.

The W8600F Air Cleaner Monitor is furnished with all the connectors needed for easy installation. Follow the installation instructions provided with the W8600F.

Optional W8600A AIRWATCH™ Indicator

The W8600A can be mounted next to the thermostat or in any other location in the living area of the home where the display can be conveniently observed. No wiring is necessary.

Choose Location

Choose a location that is readily accessible for regular inspection and cleaning. Allow at least 13 in. (330 mm) in front of the access door for removing the metal mesh prefilter, media postfilter and electronic cell. Allow enough room above the power supply so it can be serviced without removing pipes, ducts, or other heating system components.

The air cleaner must be installed where the temperature is between 40° to 125°F (4° to 52°C).

Choose Mounting Position

WARNING

Heavy Equipment Hazard.

Can cause injury or equipment damage.

Do not mount air cleaner with access door facing down because the latch may not hold and the cell, postfilter and prefilter can fall unexpectedly.

NOTE: Nothing holds the cell, postfilter, and prefilter in place when the access door is opened.

IMPORTANT

UV light can damage media postfilters. Avoid installing UV lamp downstream of F300 in location where UV light illuminates postfilter.

The air cleaner can be mounted in any position except with the access door facing down. A list of air cleaner mounting positions for a variety of furnace installations follows.

NOTE: At least 13 in. (330 mm) clearance is required between the access door and any obstructions for cell, postfilter and prefilter maintenance.

Upflow Highboy furnace: Side installation; air cleaner is mounted vertically where return enters side inlet of furnace. See Fig. 2A.

Upflow Highboy furnace: Installation beneath furnace (air cleaner cabinet can easily support weight of furnace and air conditioner coil). Air cleaner is mounted horizontally where return enters from below. See Fig. 2B.

Upflow Highboy furnace: Closet installation. Air cleaner is mounted vertically on furnace between furnace and louvered return air opening in closet door. See Fig. 2C.

Lowboy furnace: Air cleaner is mounted horizontally in return plenum just above furnace, opposite of supply plenum. See Fig. 2D.

Downflow Counterflow furnace: Air cleaner is mounted horizontally in return duct or plenum just above furnace. See Fig. 2E.

High capacity system: Two or more air cleaners can be used together. See Fig. 2F.

Horizontal furnace: Air cleaner is mounted vertically where return enters. See Fig. 2G.

5

68-0240EF—3

Honeywell F300E User Manual

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

A

B

D

C

E

F G

M19777

Fig. 2. Mounting positions with variety of furnace installations.

Determine Duct Design Requirements

The air cleaner is adaptable to all new or existing forced air heating, cooling and ventilating systems used in residential applications. Transitions, turning vanes, or offsets may be needed in some applications for effective operation.

Transitions

Transitions are needed when the duct is a different size than the air cleaner cabinet. Gradual transitions reduce air turbulence and increase efficiency. Limit expansion to no more than 20 degrees or about 4 in. per running foot (100 mm per 300 linear mm) on each side of a transition fitting.

See Fig. 3.

CHANGE DUCT SIZE GRADUALLY TO MINIMIZE TURBULENCE.

20 DEGREE EXPANSION PER SIDE PER FITTING (4 in. PER LINEAR FOOT

[100 mm PER 300 LINEAR mm]).

RETURN

AIR DUCT

TRANSITION FITTING

ELECTRONIC AIR CLEANER CABINET

M5626A

Fig. 3. Change duct size gradually to minimize turbulence.

Turning Vanes

If the air cleaner is installed close to an elbow or angle fitting, install turning vanes inside the angle to distribute airflow more evenly across the face of the cell. See Fig. 4.

68-0240EF—3

6

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

Offsets

If the duct connection to the furnace in a side installation allows less than 7 in. (178 mm) for mounting the air cleaner cabinet, add an offset to the elbow. See Fig. 4.

TYPICAL USE OF DUCT OFFSET TO ALLOW

SPACE FOR ELECTRONIC AIR CLEANER.

OFFSET

LESS

THAN 7 in.

[178 mm]

AT LEAST 1 7 in.

[178 mm]

1 TURNING VANES HELP DISTRIBUTE AIRFLOW EVENLY.

M5627A

Fig. 4. Typical use of duct offset to allow space for electronic air cleaner.

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After installation is complete, check out product operation as provided in these instructions.

WARNING

Electric Shock Hazard.

Can cause electrical shock or equipment damage.

Do not connect to power before installation is complete.

Unpack Electronic Air Cleaner

Check that all components are included. The electronic air cleaner is shipped assembled. The unit consists of a galvanized steel cabinet, power supply with On-Off switch and neon light, two electronic cells, two metal mesh prefilters, two media postfilters, access door and product data literature

Order W8600F (optional) including mounting hardware and installation literature separately.

Order W8600A (optional) including mounting hardware, batteries, and literature separately.

Clean Blower Compartment

Remove and discard the existing furnace filter.

Thoroughly clean the blower compartment.

If possible, power vacuum the ductwork to remove accumulated dust in an existing home, or construction dirt in a new home. The electronic air cleaner cannot remove dust that has settled in the blower compartment and distribution ducts.

Check the edges of the furnace fan blades for dirt buildup and clean as necessary. The fan will not deliver the rated cfm if the blades are dirty.

Fasten Cabinet To Furnace

NOTE: This procedure shows a side installation on a typical highboy furnace. You may need to alter the procedure to fit your application.

Remove and set aside the access door, electronic cells metal mesh prefilters and media postfilters.

Align the cabinet with the return air opening.

Create opening in furnace to match air cleaner cabinet opening.

Install a transition when the furnace and air cleaner openings are different sizes. See Fig. 3.

Place blocks under the cabinet so the unit is firmly supported and level. The 5/8 in. (16 mm) mounting foot on the cabinet hinge plate provides the minimum clearance required for the access door hinge.

Attach the cabinet securely to the furnace. The unit can be attached directly, as shown, or a starting collar can first be fitted in the furnace opening. Either drill holes and fasten with sheet metal screws or rivets, or use slip joints. See Fig. 5.

M20804

Fig. 5. Fasten cabinet to furnace.

7

68-0240EF—3

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

Install Turning Vanes

Mount turning vanes inside the elbow or angle fitting that is directly against the air cleaner cabinet. See Fig. 6.

Fasten Cabinet To Ductwork

Install a transition when the opening in the air cleaner cabinet and the duct are different sizes. See Fig. 3.

Fasten the other side of the cabinet to the elbow using sheet metal screws, rivets, or slip joints as appropriate. If drilling holes, use locking pliers to help hold the unit in place during drilling. See Fig. 6.

TURNING

VANES

LOCKING

PLIERS

M20815

Fig. 6. Connect ductwork to air cleaner. (Note turning vanes. Locking pliers hold duct to air cleaner cabinet during installation.)

 

DOWNSTREAM

 

 

AIRFLOW

 

 

CELL KEY

 

CELL

SCREW

CELL KEY

KEY

 

 

 

PREFILTER GUIDES

 

 

 

 

ALTERNATE

 

 

HOLES FOR

M5639

 

KEY

Fig. 7. Position of cell key determines orientation of cell (arrow on key must point downstream).

3.Turn the key around and place it over the opposite holes. The tab on the bottom fits into the larger hole, and the screw fits into the smaller hole. Make sure the arrow on the key points in the direction of the air flow (downstream).

4.Tighten the screw into the new hole.

5.Insert the electronic cell. The ionizer section will now be on the air-entering (upstream) side of the cabinet.

Attach Cell Handles

Cell handles included with the air cleaner must be installed on the end of the cell closest to the access door. To install:

1.Orient the cell as it will be when installed. The gray contact board must be up and the airflow arrow stamped into the cell must point downstream.

2.Hold the handle sideways and insert the solid tab on the back of the handle into the slot in the cell. Turn the handle 90 degrees clockwise to align the divided tab with the square hole. See Fig. 8.

Seal Joints

Seal all joints in the return air system between the air cleaner and the furnace to prevent dust from entering the clean airstream. Use optional air cleaner cabinet gasket kit (part no. 32002109-001), mastic or foil tape.

Position Cell Key

The electronic cell must always be installed so the ionizer section is on the upstream side. A factory-installed cell key on the bottom of the cabinet allows the cell to be inserted in only one direction. If the arrow molded into the plastic key points in the same direction as the airflow, the ionizer is always on the upstream side.

If position of the key must be reversed, proceed as follows:

1.Remove the electronic cell.

2.Remove the screw holding the cell key in place. See Fig. 7.

INSTALL HANDLE ON END OF CELL

CLOSEST TO ACCESS DOOR

ROTATE 90

DEGREES

FOLD TAB

TO LOCK

HANDLE

IN PLACE

M6047A

Fig. 8. Install the handle on the end of the cell closest to the access door.

3.Insert the divided tab into the square hole.

4.Fold up the wedge and insert it into the divided tab to lock the handle in place. If necessary, press with a blunt instrument like the end of a pliers.

68-0240EF—3

8

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

Reassemble Air Cleaner

Insert the electronic cells with the gray contact board toward the power supply and the airflow arrow pointing downstream. If the cell does not slide easily into the cabinet, check the orientation of the cell key.

Insert the metal mesh prefilters on the upstream side of the cabinet in the guide provided.

Insert the media postfilters on the downstream side of the cabinet in the guide provided.

Replace the access door. Insert the tab on the bottom of the door into the slot in the cabinet, then swing it closed and press into place. The door must be firmly in place or the air cleaner will not operate.

Complete Wiring

WARNING

Electric Shock Hazard.

Can cause personal injury.

Do not use an extension cord.

Assure all wiring complies with local codes and ordinances.

The line voltage power source must match the voltage and frequency printed on the label inside the access door.

When the System fan comes on, the Air Flow Switch (AFS) senses the negative pressure in the duct and turns on the power supply. If power to the air cleaner is controlled by another switch, the AFS can be disabled by cutting the jumper on the back of the AFS circuit board. See Fig. 9.

Plug the electronic air cleaner directly into the correct voltage and frequency outlet. See Fig. 9 for internal schematic. The air cleaner operates correctly with any fan when wired with conduit or plugged in.

NOTE: To reduce the risk of electric shock, this product has a grounding type plug that has a third (grounding) pin. This plug only fits into a grounding type power outlet. If the plug does not fit into the outlet, contact a qualified electrician to install the proper outlet. Do not change the plug in any way.

 

 

 

BLACK COLLECTOR

 

 

 

 

 

RED IONIZER

 

TEST

 

 

 

RED

BUTTON

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

CONTACT

 

 

 

 

 

 

 

 

 

 

BOARD

5

 

P3

 

BLACK

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

P4

 

 

 

 

 

 

POWER

 

 

 

 

J4

SUPPLY

 

 

 

 

 

 

 

 

2

J5

 

 

 

 

 

 

 

 

 

 

J3

BROWN

 

 

 

 

P2

 

 

 

 

J1

 

 

 

 

P1

 

 

 

 

 

BLACK

 

 

 

ORANGE

 

GRAY

 

1

 

VIOLET

 

BLACK

1 INTERLOCK SWITCH.

BLACK

2 SHORTING BAR.

W4 W2 W1 W3

3 AIRFLOW SWITCH DISABLE JUMPER.

3

4 NEON LIGHT.

AIRFLOW SWITCH BOARD

BLACK

WHITE

GREEN

BLACK

M20830

Fig. 9. Internal schematic for electronic air cleaner with W8600F.

9

68-0240EF—3

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

Alternatively, the electronic air cleaner can be wired with conduit.

1.Open access door.

2.Remove and retain the two screws from the front of the power box and the two screws from the sides of the power box. See Fig. 10.

3.In the power box, remove and retain two wire nuts that connect the line cord leads to the power box wiring.

4.Remove the power cord green lead from the green grounding screw on the wiring compartment barrier.

5.Remove the power cord and the strain relief.

6.Install the plug (provided with the literature pack) in the hole left by the power cord.

7.Attach conduit through a power box side knockout.

8.Wire the air cleaner directly to line voltage using wire nuts. See Fig. 11. Secure ground connection to the green ground screw on the wiring compartment barrier.

9.Replace power supply cover and access door.

 

WIRING

 

 

COMPARTMENT

 

ELECTRONIC

 

2

AIR CLEANER

BLACK

L1 (HOT)

 

 

 

BROWN

1

 

L2

 

 

1POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2THE AIR CLEANER CAN BE COMPLETELY ISOLATED FROM THE ELECTRICAL CIRCUIT OF THE HVAC SYSTEM UNLESS REQUIRED BY LOCAL CODE TO USE SAME CIRCUIT. ANY CONVENIENT HOUSE CIRCUIT CAN POWER AIR CLEANER, REGARDLESS OF ELECTRICAL RATING OF HVAC SYSTEM.

M5707

Fig. 11. Conduit connection for electronic air cleaner.

REMOVING COVER

FROM POWER BOX.

2

1

3

M20806

Fig. 10. Removing cover from power box.

OPERATION

Large particles (lint, hair) are caught by the prefilter. As the dirty air passes through the intense high voltage electric field surrounding the ionizer wires, all particles are given an electrical charge.

The air then moves through the collector part of the cell where alternate parallel plates are charged positively and negatively, creating a uniform electrostatic field. The charged particles are attracted to and collect on the plates that have the opposite electrical charge.

The air then passes through media postfilters, removing additional particles from the air stream. The air leaving the air cleaner has fewer particles. Each time the air circulates through the electronic air cleaner, more particles are removed.

CHECKOUT

Inspect the Installation

Make sure:

Turning vanes and transitions, as needed, are correctly installed.

Sheet metal joints between air cleaner and furnace are sealed.

All sheet metal connections are complete.

Original furnace filter has been removed and the blower compartment cleaned.

If atomizing humidifier is installed upstream from the air cleaner, a disposable furnace filter is installed between the humidifier and the air cleaner.

Outside air, if used, is mixed with return air or heated, as necessary, before it can reach the air cleaner.

Airflow arrows on the electronic cell point downstream.

Metal mesh prefilter is on the upstream side and media postfilter is on downstream side of the cell.

Cell handle faces outward.

Electronic cell and prefilter are clean and dry.

W8600F wiring connections are correctly made.

68-0240EF—3

10

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

Check Air Cleaner Operation

With all components in place, turn on air cleaner switch and energize system blower. Check following points of operation:

1.The neon light next to the On-Off switch is on. The neon light shows that the air cleaner is energized and the high voltage power supply is working correctly. If a W8600F is part of the installation, also check the wall panel and make sure the On indicator is lit. The W8600F Fault indicator comes on if there is a problem with the high voltage power supply.

2.Turn off the system blower. The neon light should go off after a few seconds.

3.Turn on the system blower. With the air cleaner energized, push the test button. A snapping sound indicates that the collector voltage is present on the cell.

4.With a multispeed blower, repeat steps 1 through 3 for each fan speed.

SERVICE

CAUTION

Sharp Edges.

Can cause personal injury.

Carefully handle the cell(s) or wear protective gloves to avoid cuts from the sharp metal edges.

Cleaning the Cells and Prefilters

To assure optimum performance from the air cleaner, the cells and prefilters must be cleaned regularly and the postfilters replaced regularly—every one to six months. Washing frequency varies, depending on the number of family members, pets, activities (such as cooking or woodworking) and smoking habits. Use the Service Reminder Schedule at the end of this document to help establish and maintain a regular cleaning schedule. Keep your Service Reminder Schedule in a convenient location.

NOTE: Media postfilters should be replaced rather than cleaned. See Replacing Media Postfilters section.

If the air cleaner has a W8600F Air Cleaner Monitor, the SERVICE indicator activates to indicate filter and cell maintenance are due. The time between activation of the SERVICE indicator is based on air cleaner run time that is selected by the installer at installation.

If the air cleaner has a W8600A AIRWATCH Indicator, the Air Cleaner LCD arrow blinks to indicate it is time to service the cells and prefilters. The time between activations of the Air Cleaner LCD is based on calendar time that is selected at installation.

NOTE: To let the heating or air conditioning system operate normally while the cells are being washed, simply turn off the air cleaner switch.

IMPORTANT

Vacuum the prefilter or brush or soak it in a tub. Do not wash the prefilter in the dishwasher or car wash.

Automatic Dishwasher

CAUTION

Burn Hazard.

Can cause personal injury.

Allow cells to cool completely in dishwasher at end of wash cycle or wear protective gloves to avoid burns. Hot water can accumulate in the tubes supporting collector plates; tip cells so tubes drain.

IMPORTANT

Check the dishwasher owner's manual. Some manufacturers do not recommend washing electronic cells in their dishwashers.

If the dishwasher has upper and lower arms, position the cells carefully to allow good water circulation.

Be careful to avoid damaging the cells when placing them in the dishwasher. Broken ionizer wires or bent collector plates are not included in the warranty.

Very dirty cells, especially from tobacco or cooking smoke, can discolor the plastic parts and the lining of some dishwashers. This discoloration is not harmful. To minimize it, wash the cells more frequently or try a different brand of detergent.

Do not allow the dishwasher to run through the dry cycle. This bakes on any contaminants not removed during the wash cycle and reduces air cleaner efficiency.

1.Put the cells on the lower rack of the dishwasher with the airflow arrow pointing up. It may be necessary to remove the upper rack. Do not block water flow to the upper arm.

HINT: Lay a few large water glasses between the spikes on the lower rack and rest the cell(s) on them so the spikes do not damage the aluminum collector blades.

2.Using regular dishwasher detergent, allow the dishwasher to run through the complete wash and rinse cycle. Do not use the dry cycle. To avoid burns, let the cells cool completely before removing, or wear protective gloves when removing the cells. Remember that water may be trapped inside the cells. Tip the cells so the tubes can drain.

3.Wipe ionizer wires and contact board on the end of the cell using thumb and forefinger with a small, damp cloth.

4.Inspect the dishwasher. Rerun wash and/or rinse cycle with the dishwasher empty if there is dirt or residue from washing the cells. If dirt or residue seems excessive, wash cells more often or try a different detergent.

11

68-0240EF—3

F300E ELECTRONIC AIR CLEANER WITH ENHANCED FILTRATION

Washing Cells in a Container

CAUTION

Hazardous Chemical.

Can cause personal injury.

Do not splash detergent solution in eyes. Wear rubber gloves to avoid prolonged detergent contact with skin. Keep detergent and solution out of reach of children.

NOTE: Always wash the cells first, then the prefilters, to keep heavy prefilter lint from getting caught in the cells.

1.Use a large enough container, such as a laundry tub or trash container, to hold one or both cells.

NOTE: Sharp corners on cells can scratch surface of bathtub.

2.Dissolve about 3/4 cup of automatic dishwasher detergent per cell in enough hot water to cover the cells. If detergent does not dissolve readily, or forms a scum on the water, try another brand, or use softened water

3.After detergent has completely dissolved, place cells in the container and let soak for 15 to 20 minutes. Agitate up and down a few times and remove. See Fig. 12.

WEAR GLOVES

TO PROTECT

HANDS FROM

DETERGENT

SOLUTION.

M922A

Fig. 12. Washing cells in container.

4.Next, wash the prefilters the same way. Empty and rinse the wash container.

5.Rinse the cells and prefilters with a hard spray of very hot water; rinse the tub clean, then fill the tub with clean hot water and soak for 5 to 15 minutes. Rinse until the water draining from the cells and prefilters no longer feel slippery.

6.Soak cells and prefilters in a final clear water rinse for ten minutes.

7.Wipe ionizer wires and contact board on end of cell using your thumb and forefinger with a small, damp cloth.

Washing Cells at the Car Wash

Use the hand sprayer at a coin-operated do-it-yourself car wash to clean the cells. Hold the nozzle at least two feet away from the unit to avoid damage (such as broken ionizer wires or bent collector plates) from the high pressure stream of water. See Fig. 13. Follow the same sequence of wash and rinse as recommended for cars. However, do not wax the cells. Be sure to rinse until the water draining from the cells no longer feel slippery.

HIGH VELOCITY

DETERGENT SPRAY

STEAM

M20831

Fig. 13. Washing cells at car wash.

Reinstall the Cells and Prefilters

1.Inspect the cells for broken ionizer wires and bent collector plates. Repair as necessary or take to a Honeywell Authorized Air Cleaner Repair Station.

2.Slide the prefilters into the upstream prefilter guides.

3.Slide in the air cleaner cells so the airflow arrow points downstream and the handles faces outward.

4.Firmly close the access door.

5.Turn on the air cleaner. If the cells and prefilters are wet, the neon light may not come on and you may hear arcing. If the arcing is annoying, simply turn off the air cleaner for two to three hours or until the cells are dry.

Replacing Media Postfilters

To maximize the filtration efficiency of the media postfilters, replace them every six months. Replacement filters are available in the same size and configuration as the original unit. Contact your local Honeywell distributor to purchase replacement filters. Install the replacement filters exactly as the filters provided with the equipment. Use the Service Reminder Schedule at the end of this document to help you establish and maintain a regular replacement schedule. Keep your Service Reminder Schedule in a convenient location.

68-0240EF—3

12

Loading...
+ 28 hidden pages