Honeywell H6062 User Manual

0 (0)

Installation

Instructions

HumidiPRO H6062

Digital Humidity Control

When Installing this Product

Read these instructions carefully, failure to follow them could damage the product and cause a hazardous situation.

Check the ratings given in the instructions and on the product to make sure the product is suitable for your application

Installer must be a trained, experienced service technician.

After installation is complete, check out product operation as provided in these instructions.

Cautions

Electrical shock or equipment damage may occur.

Disconnect power supply before beginning installation.

2

Duct Installation (recommended) OR Remote Mount Installation

1.Choose a location on the RETURN duct.

1. Choose a location in the living area.

 

ALTERNATE

 

LOCATION

RETURN

RETURN

AIR

AIR

6 IN (152 MM)

15 IN (381 MM)

MINIMUM

MINIMUM

 

BEST

 

LOCATION

 

RETURN

 

AIR DUCT

M34579

NOTE: Select a location clear of drafts or excessive humidity. Avoid mounting near doors or windows, or in bathrooms or kitchens.

NO

YES

Warning: Product must be mounted

 

on the RETURN side of the duct for

 

proper RH% sensing.

M34567

3

Duct-Mount Installation

2. Separate wallplate from humidistat.

 

 

 

 

 

05,, (%2%

)NSIDE

2EPLACE"ATT

3ETTING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(5-)$)49"//34

 

 

 

 

 

,IGHT

3YSTEM

 

 

 

!UTO

.EXT!UTO

 

 

 

 

 

 

 

 

 

 

 

-

Caution: Electrical Hazard

Can cause electrical shock or equipment damage. Disconnect power before beginning installation.

3. Mark the duct-tube hole.

M34580

Hold the wallplate up to the desired location on the duct and make a mark inside the duct tube hole.

4

4. Drill the duct-tube hole.

M34581

Find your mark and drill a 1/2 in. hole in the duct. This is where the duct tube will be inserted to capture air.

5. Insert the duct tube.

Insert the duct tube through the wallplate before securing to the duct.

M34671

5

6. Secure the wallplate.

7. Run wires through the back plate.

M34582

Secure the wallplate to the duct with sheet metal screws (provided).

 

RUN WIRES

 

THROUGH THE

C

TOP OR BOTTOM

CHANNEL

R

 

U

 

U

 

S

 

S

 

 

M34610

Run wires through the top or bottom channel on the back plate when ductmounted. If installing like a thermostat on a wall, run the wires through the back.

6

Wiring the Humidistat

This humidity control is wired the same way a manual humidistat (H8908) is wired. The only difference is that you also wire in power (24 VAC) and an outdoor sensor.

TERMINAL DESIGNATION

C 24 VAC POWER FROM EQUIPMENT

R24 VAC POWER FROM EQUIPMENT

UHUMIDIFIER/DEHUMIDIFIER

UHUMIDIFIER/DEHUMIDIFIER

SOUTDOOR SENSOR

S OUTDOOR SENSOR

24 VAC (CONSTANT)

TO HUMIDIFIER OR DEHUMIDIFIER

OUTDOOR TEMPERATURE SENSOR

NOTES: C AND R MUST BE CONSTANT 24VAC! RECOMMENDED TO WIRE TO FURNACE/AIR HANDLER CONTROL BOARD.

DO NOT WIRE C AND R TO HUMIDIFIER TRANSFORMER!

C

R

U

U

S

S

M34569

7

Wiring HumidiPRO with Fan Interlock

FAN CONTROL

TRANSFORMER

L1

(HOT) POWER SUPPLY

L2

1FURNACE FAN

MOTOR

1PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

224 VAC WIRING.

C 24 VAC (CONSTANT)

R

U

U

SOUTDOOR SENSOR

S

2

HUMIDIFIER

M34570

8

Wiring HumidiPRO with Fan Interlock for 2 Speed Motor

 

FAN CONTROL

TRANSFORMER

L1

 

 

(HOT) POWER

 

 

SUPPLY

 

2

 

 

L2

DPST

 

1

 

SWITCHING

 

 

 

 

RELAY

 

H

L

 

2-SPEED FAN MOTOR

C

C 24 VAC (CONSTANT)

R

U

U

SOUTDOOR SENSOR

S

HUMIDIFIER

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

2 24 VAC WIRING.

M34571

9

Wiring HumidiPRO with Current Sensing Relay

 

C

24 VAC (CONSTANT)

 

 

R

 

 

 

 

 

 

 

U

 

 

 

 

 

U

 

 

 

 

 

S

OUTDOOR SENSOR

 

 

S

 

 

 

 

 

 

CURRENT

 

LO

 

 

 

 

 

L2

L1

1

SENSING

C

HI

RELAY

 

 

 

(HOT)

HUMIDIFIER

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M34572

10

Wiring HumidiPRO with Sail/Pressure Switch

AIR PRESSURE SWITCH/SAIL SWITCH

C 24 VAC (CONSTANT)

R

U

U

SOUTDOOR SENSOR

S

L2 L1 1 (HOT)

HUMIDIFIER

1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

M34573

11

Wiring HumidiPRO to FORCE FAN ON (Basic Humidifier)

R

C

24 VAC (CONSTANT)

HUMIDIFIER

 

C

R

 

 

 

 

 

W

U

 

 

 

Y

U

 

 

 

G

S

OUTDOOR SENSOR

 

 

 

S

 

 

 

 

 

 

 

DPST RELAY

 

 

 

1

3

 

 

 

 

2

 

 

 

4

6

 

 

 

 

5

 

 

 

NOTES: USE DPST RELAY FOR HUMIDITY ON DEMAND

L2 L1

1

WITH A BASIC HUMIDIFIER.

 

 

(HOT)

 

 

 

HUMIDIFIER MUST BE PLUMBED TO HOT WATER

 

WHEN FORCING FAN.

 

 

 

HONEYWELL ADVANCED HUMIDIFIERS DO NOT

 

 

NEED A RELAY TO FORCE FAN.

M34574

12

Wiring HumidiPRO to TrueEASE Advanced Humidifier

with Fan Interlock (HE150/HE250/HE300)

HumidiPRO

HVAC

C

 

 

 

 

R

 

 

U

 

R C W Y G

U

 

S

OUTDOOR

 

 

S

SENSOR

 

THERMOSTAT

 

G “FAN”

 

24VAC CONSTANT

POWER IN

NOT REQUIRED

ON HE300

NOTE: SEE TrueEASE INSTALL GUIDE FOR DETAILED WIRING INFORMATION.

M34577

13

Wiring HumidiPRO to TrueSTEAM Advanced Humidifier

 

HumidiPRO

 

 

 

 

 

 

 

C

 

24V

1

2

3

4

5

6

R

 

24V

 

ON

 

 

 

 

 

U

 

 

 

 

 

 

 

 

 

 

 

 

 

U

 

HUM

OFF

 

 

 

 

 

S

OUTDOOR SENSOR

HUM

 

 

 

 

 

 

 

 

 

 

 

S

AFS MONITOR RECOMMENDED

 

C

 

 

 

 

 

 

 

 

 

 

HVAC

 

GT

 

 

 

 

 

 

R

 

R

 

 

 

 

 

 

C

 

RT

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y

 

GF

 

 

 

 

 

 

G

 

EXT

 

 

 

 

 

 

 

THERMOSTAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

G “FAN”

 

 

 

 

 

 

 

NOTE: SEE TrueSTEAM INSTALL GUIDE FOR DETAILED WIRING INFORMATION.

M34576

14

Wiring HumidiPRO to Dehumidifier

C

24 VAC

(CONSTANT)

R

 

U

 

U

 

S

 

S

 

Float DHUM R Fan C

M34595

15

Mounting the Outdoor Sensor

(Not required if window protection isn’t needed)

Location

Mount the sensor where:

it cannot be tampered with.

there is good air circulation.

surface is flat.

wire distance between sensor and humidistat is less than 200 feet.

it can measure true outdoor ambient temperature.

Do NOT mount the sensor:

in direct sunlight.

where snow, ice or debris can cover it.

where hot or cold air blows on the sensor. (For example, a discharge line from an outdoor compressor unit, vent or fan can cause inaccurate temperature readings.)

16

Honeywell H6062 User Manual

Steps to mount the sensor

1.Remove the sensor from the mounting clip.

2. Mark the area on the location selected for mounting the sensor mounting clip.

3. Mount the clip. Image on right shows typical locations for outdoor sensor.

M7514A

17

Wiring the sensor

Caution

Electrical Interference (Noise) Hazard. Can cause erratic system operation.

Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels.

Use shielded cable to reduce interference when rerouting is not possible.

Be sure wires have a cable separate from the thermostat cable.

Do not route temperature sensor wiring with building power wiring, next to control contactors or near light dimming circuits, electric motors or welding equipment.

Avoid poor wiring connections.

Avoid intermittent or missing building earth ground.

18

Caution

Electrical Shock Hazard. Can cause electrical shock or equipment damage.

Disconnect power supply before connecting wiring.

Wiring must comply with applicable codes, ordinances and regulations:

1.Wire the C7089 Outdoor Sensor to the S terminals on the humidity control. If leadwire provided with C7089 is not long enough (60 in.), run a cable to a hole at C7089 location.

Using color-coded, 18-gauge, shielded thermostat wire is recommended. For example of general wiring of C7089, see image at right.

Pigtail wiring can be used.

2.Mount C7089 in its mounting clip.

3.Plug wiring hole using nonhardening caulk or putty.

1

WIRING HOLE

 

C7089

THROUGH 2

 

STRUCTURE

C

R

U

U

S

S

1USE APPROPRIATE MOUNTING MEANS FOR THE TYPE OF STRUCTURE.

2PLUG WIRING HOLE WITH NON-HARDENING

CAULK OR PUTTY.

M34611

19

Mount Humidity Control

Align the 4 tabs on the wallplate with the slots on the back of the control, then push gently until the control snaps in place.

SLOTS ON

BACK OF

HumidiPRO

WALLPLATE TABS

M34583

20

Checkout

Allow C7089B Outdoor Sensor to absorb outdoor air for a minimum of twenty minutes before taking a reading.

With an accurate thermometer (±1°F [0.5°C]), measure the temperature at the sensor location, allowing time for the thermometer to stabilize before reading.

Then verify the sensor accuracy by going into installer Test #20. This will show you the outdoor temperature.

Calibration

The C7089 Outdoor Sensor is calibrated at the factory. However, you can offset the outdoor sensor reading using Function 35 in Installer Setup.

21

You’ve just installed your Humidity Controller!

This Humidity Control has been preprogrammed to the ideal settings for most homes.

If you installed this control with an outdoor sensor, the control will operate in AUTOMATIC MODE, which automatically adjusts humidity to help prevent window condensation.

If you installed this control without an outdoor sensor, the control will operate in MANUAL MODE, giving the homeowner simple, direct control of their humidifier (RH% Setting Only).

Advanced Installer Setup

See next page to customize feature operation.

Installer System Test

If Advanced Installer Setup is not required, skip to “Installer System Test/Checkout” on page 27.

22

Advanced Installer Setup

Honeywell has already programmed this control to work properly in most applications. However, you can adjust the advanced settings by following the steps below.

To begin, press and hold the p and LIGHT buttons until the display changes.

1 1

Done

Next

M29387A

Press p or q to change settings.

Press NEXT to advance to the next function.

Press DONE to exit and save settings.

23

 

Setting

Function Number

Displayed

Description

1 System Type

1

Humidifier

2

Dehumidifier

4 Control Mode

1

Automatic

Automatic Mode is Default when Outdoor Sensor Detected

2

Manual

Manual Mode is Default when NO Outdoor Sensor Detected

5 Automatic Mode RH% (Hum)

Range: 20%-60%

This is the humidity setpoint (RH%) the control will operate to.

The homeowner does not change this and will only need to set

Default = 35%

the appropriate window protection setting.

 

 

 

 

 

11 Automatic Mode Humidity Boost

0

OFF

Increases Preset RH% (#5) when user sets window protection

5%

5%

to 11.

10%

10%

17 Automatic Mode High Temp Shut-Off

Range:

40° - 90°

Turns humidifier OFF when Outdoor Temperature is greater

0 = OFF

than selected setting.

Default = 65°

 

Range: 10% - 90%

19 High Hum Limit

Default = 60%

24

 

Setting

Function Number

Displayed

Description

 

Range:

10% - 90%

20 Low Hum Limit

Default = 10%

 

Range: 10% - 90%

21 High Dehum Limit

Default = 80%

 

Range: 10% - 90%

23 Low Dehum Limit

Default = 40%

25 Dehumidifier Compressor Lockout

0 - 5 Minutes

Default = 0 Minutes

 

(OFF)

 

Range: -9% to +9%

30 Humidity Sensing Calibration

Default = 0 (Displays

This feature will offset the sensed indoor humidity.

Actual RH%)

35 Outdoor Temperature Sensor Calibration

Range: -9° to +9°

This feature will offset the sensed outdoor temperature if

Default = 0 (Displays

needed.

Actual Outdoor Temp)

25

Honeywell HumidiPROTM Frost Index

Frost Index

 

 

 

 

 

Outdoor Temp

 

 

 

 

 

 

-10°F

0°F

10°F

20°F

30°F

40°F

1

10

10

10

10

11

11

17

17

25

25

35

36

2

10

10

10

10

15

15

21

21

29

29

35

39

3

10

10

14

14

19

19

26

26

34

34

35

46

4

15

15

19

19

25

25

32

32

35

39

35

52

5

21

21

26

26

32

32

35

38

35

48

35

58

6

29

29

34

34

35

39

35

48

35

56

35

60

7

35

39

35

46

35

52

35

58

35

60

35

60

8*

35

56

35

60

35

60

35

60

35

60

35

60

9

35

60

35

60

35

60

35

60

35

60

35

60

10

35

60

35

60

35

60

35

60

35

60

35

60

*Black Numbers show highest humidity allowed when Default RH% (35%) is Selected.

Note: Smaller grey numbers show highest humidity allowed when Maximum RH% (60%) is selected.

26

Installer System Test/Checkout

Test number

System status

10 0

M29388A

To begin, press and hold the p and q buttons until the display changes.

Press p / q to turn system on/off. Press NEXT to advance to next test. Press DONE to terminate system test.

 

 

Setting

 

 

 

 

Function Number

Number

 

Description

 

 

 

 

10 System Test

0

 

OFF

 

 

 

1

 

ON

 

 

 

 

 

20 View Outdoor Temperature

Shows Outdoor Temperature

 

 

 

 

27

Installer System Test/Checkout (continued)

NOTE: Most humidifiers require airflow in the system to operate. Make sure to turn on the system fan when testing humidifier operation.

Caution: If running a dehumidifier, compressor protection is bypassed during testing; avoid cycling the compressor too quickly.

Note: Some dehumidifiers may already have built in compressor protection.

Specifications

Humidity Ranges:

Humidify:

Default: 10% to 60%

Total Range Available: 10% to 90% Dehumidify:

Default: 40% to 80%

• Total Range Available: 10% to 90%

Operating Ambient Temperature

• 32° to 120°F (0° to 48.9°C)

Operating Relative Humidity

• 5% to 90% (non-condensing)

28

Troubleshooting

If you have difficulty with your humidity control, please try the following suggestions. Most problems can be corrected quickly and easily.

Display is blank

Humidity settings do not change

Check circuit breaker and reset if necessary.

Check for 24VAC between R and C at the wall plate.

Make sure power switch at heating and cooling system is on.

Make sure furnace door is closed securely.

Make sure the humidity is set to an acceptable range:

Check current range stop settings in Installer Setup.

Auto Mode: 1–10 (up to 11 if Humidity Boost is enabled)

Manual Mode: 20%–60%

Dehumidification Mode: 40%–80%

29

Loading...
+ 67 hidden pages