Installation
Instructions
HumidiPRO H6062
Digital Humidity Control
When Installing this Product
Read these instructions carefully, failure to follow them could damage the product and cause a hazardous situation.
Check the ratings given in the instructions and on the product to make sure the product is suitable for your application
Installer must be a trained, experienced service technician.
After installation is complete, check out product operation as provided in these instructions.
Cautions
Electrical shock or equipment damage may occur.
Disconnect power supply before beginning installation.
2
Duct Installation (recommended) OR Remote Mount Installation
1.Choose a location on the RETURN duct.
1. Choose a location in the living area.
|
ALTERNATE |
|
|
LOCATION |
|
RETURN |
RETURN |
|
AIR |
AIR |
|
6 IN (152 MM) |
15 IN (381 MM) |
|
MINIMUM |
||
MINIMUM |
||
|
||
BEST |
|
|
LOCATION |
|
|
RETURN |
|
|
AIR DUCT |
M34579 |
NOTE: Select a location clear of drafts or excessive humidity. Avoid mounting near doors or windows, or in bathrooms or kitchens.
NO
YES
Warning: Product must be mounted |
|
on the RETURN side of the duct for |
|
proper RH% sensing. |
M34567 |
3
Duct-Mount Installation |
|||||
2. Separate wallplate from humidistat. |
|||||
|
|
|
|
|
05,, (%2% |
)NSIDE |
2EPLACE"ATT |
3ETTING |
|
||
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
(5-)$)49"//34 |
|
|
|
|
|
|
,IGHT |
3YSTEM |
|
|
|
|
!UTO |
.EXT!UTO |
|
|
|
|
|
|
|
||
|
|
|
|
|
- |
Caution: Electrical Hazard
Can cause electrical shock or equipment damage. Disconnect power before beginning installation.
3. Mark the duct-tube hole.
M34580
Hold the wallplate up to the desired location on the duct and make a mark inside the duct tube hole.
4
4. Drill the duct-tube hole.
M34581
Find your mark and drill a 1/2 in. hole in the duct. This is where the duct tube will be inserted to capture air.
5. Insert the duct tube.
Insert the duct tube through the wallplate before securing to the duct.
M34671
5
6. Secure the wallplate. |
7. Run wires through the back plate. |
M34582
Secure the wallplate to the duct with sheet metal screws (provided).
|
RUN WIRES |
|
THROUGH THE |
C |
TOP OR BOTTOM |
CHANNEL |
|
R |
|
U |
|
U |
|
S |
|
S |
|
|
M34610 |
Run wires through the top or bottom channel on the back plate when ductmounted. If installing like a thermostat on a wall, run the wires through the back.
6
Wiring the Humidistat
This humidity control is wired the same way a manual humidistat (H8908) is wired. The only difference is that you also wire in power (24 VAC) and an outdoor sensor.
TERMINAL DESIGNATION
C 24 VAC POWER FROM EQUIPMENT
R24 VAC POWER FROM EQUIPMENT
UHUMIDIFIER/DEHUMIDIFIER
UHUMIDIFIER/DEHUMIDIFIER
SOUTDOOR SENSOR
S OUTDOOR SENSOR
24 VAC (CONSTANT)
TO HUMIDIFIER OR DEHUMIDIFIER
OUTDOOR TEMPERATURE SENSOR
NOTES: C AND R MUST BE CONSTANT 24VAC! RECOMMENDED TO WIRE TO FURNACE/AIR HANDLER CONTROL BOARD.
DO NOT WIRE C AND R TO HUMIDIFIER TRANSFORMER!
C
R
U
U
S
S
M34569
7
Wiring HumidiPRO with Fan Interlock
FAN CONTROL |
TRANSFORMER |
L1
(HOT) POWER SUPPLY
L2
1FURNACE FAN
MOTOR
1PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
224 VAC WIRING.
C 24 VAC (CONSTANT)
R
U
U
SOUTDOOR SENSOR
S
2
HUMIDIFIER
M34570
8
Wiring HumidiPRO with Fan Interlock for 2 Speed Motor
|
FAN CONTROL |
TRANSFORMER |
L1 |
|
|
(HOT) POWER |
|
|
SUPPLY |
|
2 |
|
|
|
L2 |
DPST |
|
1 |
|
|
SWITCHING |
|
|
|
|
|
|
RELAY |
|
H |
L |
|
2-SPEED FAN MOTOR
C
C 24 VAC (CONSTANT)
R
U
U
SOUTDOOR SENSOR
S
HUMIDIFIER
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 24 VAC WIRING. |
M34571 |
9
Wiring HumidiPRO with Current Sensing Relay
|
C |
24 VAC (CONSTANT) |
|
||
|
R |
|
|||
|
|
|
|
|
|
|
U |
|
|
|
|
|
U |
|
|
|
|
|
S |
OUTDOOR SENSOR |
|
||
|
S |
|
|||
|
|
|
|
|
|
CURRENT |
|
LO |
|
|
|
|
|
L2 |
L1 |
1 |
|
SENSING |
C |
HI |
|||
RELAY |
|
|
|
(HOT) |
HUMIDIFIER
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M34572
10
Wiring HumidiPRO with Sail/Pressure Switch
AIR PRESSURE SWITCH/SAIL SWITCH
C 24 VAC (CONSTANT)
R
U
U
SOUTDOOR SENSOR
S
L2 L1 1 (HOT)
HUMIDIFIER
1 PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
M34573
11
Wiring HumidiPRO to FORCE FAN ON (Basic Humidifier)
R |
C |
24 VAC (CONSTANT) |
HUMIDIFIER |
|
C |
R |
|
|
|
|
|
|
||
W |
U |
|
|
|
Y |
U |
|
|
|
G |
S |
OUTDOOR SENSOR |
|
|
|
S |
|
|
|
|
|
|
|
|
|
DPST RELAY |
|
|
|
1 |
3 |
|
|
|
|
2 |
|
|
|
4 |
6 |
|
|
|
|
5 |
|
|
|
NOTES: USE DPST RELAY FOR HUMIDITY ON DEMAND |
L2 L1 |
1 |
||
WITH A BASIC HUMIDIFIER. |
|
|||
|
(HOT) |
|||
|
|
|
||
HUMIDIFIER MUST BE PLUMBED TO HOT WATER |
|
|||
WHEN FORCING FAN. |
|
|
|
|
HONEYWELL ADVANCED HUMIDIFIERS DO NOT |
|
|
||
NEED A RELAY TO FORCE FAN. |
M34574 |
12
Wiring HumidiPRO to TrueEASE Advanced Humidifier
with Fan Interlock (HE150/HE250/HE300)
HumidiPRO
HVAC |
C |
|
|
|
|
||
|
R |
|
|
|
U |
|
|
R C W Y G |
U |
|
|
S |
OUTDOOR |
||
|
|||
|
S |
SENSOR |
|
|
THERMOSTAT |
||
|
G “FAN” |
|
24VAC CONSTANT
POWER IN
NOT REQUIRED
ON HE300
NOTE: SEE TrueEASE INSTALL GUIDE FOR DETAILED WIRING INFORMATION. |
M34577 |
13
Wiring HumidiPRO to TrueSTEAM Advanced Humidifier
|
HumidiPRO |
|
|
|
|
|
|
|
|
C |
|
24V |
1 |
2 |
3 |
4 |
5 |
6 |
|
R |
|
24V |
|||||||
|
ON |
|
|
|
|
|
|||
U |
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|||
U |
|
HUM |
OFF |
|
|
|
|
|
|
S |
OUTDOOR SENSOR |
HUM |
|
|
|
|
|
||
|
|
|
|
|
|
||||
S |
AFS MONITOR RECOMMENDED |
||||||||
|
C |
||||||||
|
|
||||||||
|
|
|
|
|
|
|
|
||
HVAC |
|
GT |
|
|
|
|
|
|
|
R |
|
R |
|
|
|
|
|
|
|
C |
|
RT |
|
|
|
|
|
|
|
W |
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
||
Y |
|
GF |
|
|
|
|
|
|
|
G |
|
EXT |
|
|
|
|
|
|
|
|
THERMOSTAT |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
||
|
G “FAN” |
|
|
|
|
|
|
|
NOTE: SEE TrueSTEAM INSTALL GUIDE FOR DETAILED WIRING INFORMATION.
M34576
14
Wiring HumidiPRO to Dehumidifier
C |
24 VAC |
|
(CONSTANT) |
||
R |
||
|
||
U |
|
|
U |
|
|
S |
|
|
S |
|
Float DHUM R Fan C
M34595
15
Mounting the Outdoor Sensor
(Not required if window protection isn’t needed)
Location
Mount the sensor where:
•it cannot be tampered with.
•there is good air circulation.
•surface is flat.
•wire distance between sensor and humidistat is less than 200 feet.
•it can measure true outdoor ambient temperature.
Do NOT mount the sensor:
•in direct sunlight.
•where snow, ice or debris can cover it.
•where hot or cold air blows on the sensor. (For example, a discharge line from an outdoor compressor unit, vent or fan can cause inaccurate temperature readings.)
16
Steps to mount the sensor
1.Remove the sensor from the mounting clip.
2. Mark the area on the location selected for mounting the sensor mounting clip.
3. Mount the clip. Image on right shows typical locations for outdoor sensor.
M7514A
17
Wiring the sensor
Caution
Electrical Interference (Noise) Hazard. Can cause erratic system operation.
•Keep wiring at least one foot away from large inductive loads such as motors, line starters, lighting ballasts and large power distribution panels.
Use shielded cable to reduce interference when rerouting is not possible.
•Be sure wires have a cable separate from the thermostat cable.
•Do not route temperature sensor wiring with building power wiring, next to control contactors or near light dimming circuits, electric motors or welding equipment.
•Avoid poor wiring connections.
•Avoid intermittent or missing building earth ground.
18
Caution
Electrical Shock Hazard. Can cause electrical shock or equipment damage.
Disconnect power supply before connecting wiring.
Wiring must comply with applicable codes, ordinances and regulations:
1.Wire the C7089 Outdoor Sensor to the S terminals on the humidity control. If leadwire provided with C7089 is not long enough (60 in.), run a cable to a hole at C7089 location.
•Using color-coded, 18-gauge, shielded thermostat wire is recommended. For example of general wiring of C7089, see image at right.
•Pigtail wiring can be used.
2.Mount C7089 in its mounting clip.
3.Plug wiring hole using nonhardening caulk or putty.
1 |
WIRING HOLE |
|
|
C7089 |
THROUGH 2 |
|
STRUCTURE |
C
R
U
U
S
S
1USE APPROPRIATE MOUNTING MEANS FOR THE TYPE OF STRUCTURE.
2PLUG WIRING HOLE WITH NON-HARDENING
CAULK OR PUTTY. |
M34611 |
19
Mount Humidity Control
Align the 4 tabs on the wallplate with the slots on the back of the control, then push gently until the control snaps in place.
SLOTS ON
BACK OF
HumidiPRO
WALLPLATE TABS
M34583
20
Checkout
Allow C7089B Outdoor Sensor to absorb outdoor air for a minimum of twenty minutes before taking a reading.
With an accurate thermometer (±1°F [0.5°C]), measure the temperature at the sensor location, allowing time for the thermometer to stabilize before reading.
Then verify the sensor accuracy by going into installer Test #20. This will show you the outdoor temperature.
Calibration
The C7089 Outdoor Sensor is calibrated at the factory. However, you can offset the outdoor sensor reading using Function 35 in Installer Setup.
21
You’ve just installed your Humidity Controller!
This Humidity Control has been preprogrammed to the ideal settings for most homes.
If you installed this control with an outdoor sensor, the control will operate in AUTOMATIC MODE, which automatically adjusts humidity to help prevent window condensation.
If you installed this control without an outdoor sensor, the control will operate in MANUAL MODE, giving the homeowner simple, direct control of their humidifier (RH% Setting Only).
Advanced Installer Setup
See next page to customize feature operation.
Installer System Test
If Advanced Installer Setup is not required, skip to “Installer System Test/Checkout” on page 27.
22
Advanced Installer Setup
Honeywell has already programmed this control to work properly in most applications. However, you can adjust the advanced settings by following the steps below.
To begin, press and hold the p and LIGHT buttons until the display changes.
1 1
Done |
Next |
M29387A
Press p or q to change settings.
Press NEXT to advance to the next function.
Press DONE to exit and save settings.
23
|
Setting |
|
Function Number |
Displayed |
Description |
1 System Type |
1 |
Humidifier |
2 |
Dehumidifier |
|
4 Control Mode |
1 |
Automatic |
Automatic Mode is Default when Outdoor Sensor Detected |
2 |
Manual |
Manual Mode is Default when NO Outdoor Sensor Detected |
||
5 Automatic Mode RH% (Hum) |
Range: 20%-60% |
|
This is the humidity setpoint (RH%) the control will operate to. |
||
The homeowner does not change this and will only need to set |
Default = 35% |
|
the appropriate window protection setting. |
|
|
|
|
|
11 Automatic Mode Humidity Boost |
0 |
OFF |
Increases Preset RH% (#5) when user sets window protection |
5% |
5% |
to 11. |
10% |
10% |
17 Automatic Mode High Temp Shut-Off |
Range: |
40° - 90° |
Turns humidifier OFF when Outdoor Temperature is greater |
0 = OFF |
|
than selected setting. |
Default = 65° |
|
|
Range: 10% - 90% |
|
19 High Hum Limit |
Default = 60% |
24
|
Setting |
|
Function Number |
Displayed |
Description |
|
Range: |
10% - 90% |
20 Low Hum Limit |
Default = 10% |
|
|
Range: 10% - 90% |
|
21 High Dehum Limit |
Default = 80% |
|
|
Range: 10% - 90% |
|
23 Low Dehum Limit |
Default = 40% |
|
25 Dehumidifier Compressor Lockout |
0 - 5 Minutes |
|
Default = 0 Minutes |
||
|
(OFF) |
|
|
Range: -9% to +9% |
|
30 Humidity Sensing Calibration |
Default = 0 (Displays |
|
This feature will offset the sensed indoor humidity. |
Actual RH%) |
|
35 Outdoor Temperature Sensor Calibration |
Range: -9° to +9° |
|
This feature will offset the sensed outdoor temperature if |
Default = 0 (Displays |
|
needed. |
Actual Outdoor Temp) |
25
Honeywell HumidiPROTM Frost Index
Frost Index
|
|
|
|
|
Outdoor Temp |
|
|
|
|
|
||
|
-10°F |
0°F |
10°F |
20°F |
30°F |
40°F |
||||||
1 |
10 |
10 |
10 |
10 |
11 |
11 |
17 |
17 |
25 |
25 |
35 |
36 |
2 |
10 |
10 |
10 |
10 |
15 |
15 |
21 |
21 |
29 |
29 |
35 |
39 |
3 |
10 |
10 |
14 |
14 |
19 |
19 |
26 |
26 |
34 |
34 |
35 |
46 |
4 |
15 |
15 |
19 |
19 |
25 |
25 |
32 |
32 |
35 |
39 |
35 |
52 |
5 |
21 |
21 |
26 |
26 |
32 |
32 |
35 |
38 |
35 |
48 |
35 |
58 |
6 |
29 |
29 |
34 |
34 |
35 |
39 |
35 |
48 |
35 |
56 |
35 |
60 |
7 |
35 |
39 |
35 |
46 |
35 |
52 |
35 |
58 |
35 |
60 |
35 |
60 |
8* |
35 |
56 |
35 |
60 |
35 |
60 |
35 |
60 |
35 |
60 |
35 |
60 |
9 |
35 |
60 |
35 |
60 |
35 |
60 |
35 |
60 |
35 |
60 |
35 |
60 |
10 |
35 |
60 |
35 |
60 |
35 |
60 |
35 |
60 |
35 |
60 |
35 |
60 |
*Black Numbers show highest humidity allowed when Default RH% (35%) is Selected.
Note: Smaller grey numbers show highest humidity allowed when Maximum RH% (60%) is selected.
26
Installer System Test/Checkout
Test number |
System status |
10 0
M29388A
To begin, press and hold the p and q buttons until the display changes.
Press p / q to turn system on/off. Press NEXT to advance to next test. Press DONE to terminate system test.
|
|
Setting |
|
|
|
|
|
Function Number |
Number |
|
Description |
|
|
|
|
10 System Test |
0 |
|
OFF |
|
|
|
|
1 |
|
ON |
|
|
|
||
|
|
|
|
20 View Outdoor Temperature |
Shows Outdoor Temperature |
||
|
|
|
|
27
Installer System Test/Checkout (continued)
NOTE: Most humidifiers require airflow in the system to operate. Make sure to turn on the system fan when testing humidifier operation.
Caution: If running a dehumidifier, compressor protection is bypassed during testing; avoid cycling the compressor too quickly.
Note: Some dehumidifiers may already have built in compressor protection.
Specifications
Humidity Ranges:
Humidify:
•Default: 10% to 60%
•Total Range Available: 10% to 90% Dehumidify:
•Default: 40% to 80%
• Total Range Available: 10% to 90%
Operating Ambient Temperature
• 32° to 120°F (0° to 48.9°C)
Operating Relative Humidity
• 5% to 90% (non-condensing)
28
Troubleshooting
If you have difficulty with your humidity control, please try the following suggestions. Most problems can be corrected quickly and easily.
Display is blank
Humidity settings do not change
•Check circuit breaker and reset if necessary.
•Check for 24VAC between R and C at the wall plate.
•Make sure power switch at heating and cooling system is on.
•Make sure furnace door is closed securely.
Make sure the humidity is set to an acceptable range:
•Check current range stop settings in Installer Setup.
•Auto Mode: 1–10 (up to 11 if Humidity Boost is enabled)
•Manual Mode: 20%–60%
•Dehumidification Mode: 40%–80%
29