Honeywell DS06-100-SUS-LF, DS06-101-SUS-LF, DS06-102-SUS-LF, DS06-103-SUS-LF, DS06-104-SUS-LF Installation Manual

...
5 (1)

DS06 Low Lead Content

Dial Set Pressure Regulating

Valves

 

INSTALLATION INSTRUCTIONS

APPLICATION

to 60° C).

 

Ambient Temperature Range: 33° F to 140° F (1° C

The Honeywell DS06 Dial Set® Pressure Regulating

Pipe Sizes Available: 1/2 in., 3/4 in., 1 in., 1-1/4 in.,

Valve is a high quality pressure regulating valve that

1-1/2 in. and 2 in. available.

maintains a constant outlet pressure over a wide

Connections:

range of inlet supply pressures. It is suitable for

potable water and irrigation applications. The

Can be configured as female thread-by-thread,

downstream pressure adjustment dial eliminates the

singleor double-union, NPT threaded or sweat.

need for a pressure gauge when adjusting the

Low Lead Content: < 0.25% Lead.

pressure setting (static pressure only).

 

Gauge Tap: 1/4" NPT.

SPECIFICATIONS

Model: DS06 Dial Set Pressure Regulating Valves.

Construction Materials:

Body: Brass.

Internal Parts: Stainless steel and engineered plastics.

Regulator Mechanism: Fabric-reinforced diaphragm.

Seat Design: Balanced single seat construction.

Inlet Pressure (Maximum): 250 psi maximum.

Reduced Pressure Range:

25 to 90 psi (1/2 in. to 2 in.).

Outlet Pressure: Factory set at 60 psi (414 kPa).

Dial Calibration: ± 4 psi.

Differential: 14.5 psi minimum (inlet to outlet).

Fluid Temperature (Maximum):

Water: 140° F (60° C).

Approvals:

ASSE 1003 Listed

CSA Certified

IAPMO/UPC Listed

NSF 61 Compliant

INSTALLATION

When Installing this Product...

1.Read these instructions carefully. Failure to follow them could damage the product or cause a hazardous condition.

2.Check the ratings given in these instructions and on the product to make sure the product is suitable for your application.

3.Installer must be a trained, experienced service technician.

4.After installation is complete, check out the product operation as provided in these instructions.

33-00014EF-07

DS06 LOW LEAD CONTENT DIAL SET PRESSURE REGULATING VALVES

Water Capacities

The suitability of a given regulator size is dependent on the pressure requirements where it will operate. For the pressure regulator valve size required for a specific installation, determine the following:

1.Pressure differential between inlet and outlet pressure in pounds per square inch (psi),

2.Capacity in gallons per minute, and

3.Allowable reduced pressure falloff in psi. Given these variables, use Table 1 to determine the proper size pressure regulator valve for your application.

Example: An installation has 135 psi inlet pressure, 60 psi outlet pressure (75 psi pressure differential). If a 15 gpm capacity is required with only 10 psi falloff allowable, a 3/4 in. DS06 is required.

Table 1. Water Capacities.

 

 

 

 

 

 

 

 

Pressure Differential Between Inlet and Outlet

 

 

 

 

 

100 psi or

Pressure

Reduced

25 psi

50 psi

75 psi

more

Regulator

Pressure

Flow Capacity

Flow Capacity

Flow Capacity

Flow Capacity

Valve Size

Falloff (PSI)

(US gpm)

(US gpm)

(US gpm)

(US gpm)

1/2"

6

7.26

8.15

7.44

6.47

 

 

 

 

 

 

 

10

10.7

10.66

9.69

8.85

 

 

 

 

 

 

 

15

14.27

15.72

14.49

13.96

 

 

 

 

 

 

 

20

17.74

19.59

18.98

18.1

 

 

 

 

 

 

3/4"

6

11.98

14.44

14.53

14.97

 

 

 

 

 

 

 

10

17.17

21.05

25.23

26.33

 

 

 

 

 

 

 

15

19.86

25.14

29.32

32.85

 

 

 

 

 

 

 

20

21.27

26.42

30.42

33.82

 

 

 

 

 

 

1"

6

11.18

11.23

9.51

9.11

 

 

 

 

 

 

 

10

18.01

18.98

17.39

16.78

 

 

 

 

 

 

 

15

25.67

28.14

28.71

26.9

 

 

 

 

 

 

 

20

30.69

34.7

36.19

35.05

 

 

 

 

 

 

1-1/4"

6

7.53

6.34

7.26

7.13

 

 

 

 

 

 

 

10

20.25

17.88

15.15

14

 

 

 

 

 

 

 

15

33.02

34.87

32.63

29.68

 

 

 

 

 

 

 

20

40.07

44.29

46.01

34.61

 

 

 

 

 

 

1-1/2"

6

29.81

32.27

30.87

26.81

 

 

 

 

 

 

 

10

46.14

50.02

49.89

47.82

 

 

 

 

 

 

 

15

66.22

78.42

86.74

84.14

 

 

 

 

 

 

 

20

77.14

92.29

103.82

109.68

 

 

 

 

 

 

2"

6

27.34

25.8

24.48

18.01

 

 

 

 

 

 

 

10

64.81

97.61

78.15

90.09

 

 

 

 

 

 

 

15

82.82

105.14

119.94

129.62

 

 

 

 

 

 

 

20

87.66

107.83

120.95

132.09

 

 

 

 

 

 

DSO6 Fixture Unit

Flow rates based on submittal sheet DS06, based on flush tank systems with a 15 psi fall-off defined by IAPMO/ANSI UPC 1-2009.

Table 2.

 

 

 

 

 

 

 

Fixture

Size

I/s

GPM

Units

1/2”

0.99

15.72

21

 

 

 

 

3/4”

1.58

25.14

40

 

 

 

 

1”

1.77

28.14

48

 

 

 

 

1-1/4”

2.19

34.87

70

 

 

 

 

1-1/2”

4.93

78.42

270

 

 

 

 

2”

6.61

105.14

400

 

 

 

 

Capacities are based on a 100 psi supply pressure and a difference of 50 psi or more between the initial supply pressure and the reduced no-flow pressure.

Check local water pressures before selection.

Procedure

1.Flush the system clear of sediment or debris.

2.Close the supply valve and downstream isolating valve (if one is installed).

3.Install the DS06 with the arrow on the body pointing in the direction of water flow. Install, preferably, in horizontal pipework with filter bowl downwards - vertical installation also possible.

The DS06 can be installed directly onto the pipe by using the female NPT threads on each end. If space limitations restrict turning the DS06, install singleor double-unions.

33-00014EF—07

2

Honeywell DS06-100-SUS-LF, DS06-101-SUS-LF, DS06-102-SUS-LF, DS06-103-SUS-LF, DS06-104-SUS-LF Installation Manual

DS06 LOW LEAD CONTENT DIAL SET PRESSURE REGULATING VALVES

NOTE: Heat from soldering can damage internal parts of the DS06. Always solder the tailpieces separately from the DS06.

8.Remove cartridge using a pliers as a lever.

9.Reassemble bonnet in reverse order.

4.Open the supply valve slowly and check for leakage and proper operation of the DS06.

Changing the Downstream

Pressure (See Fig. 1)

Remove the dust cap from the DS06. The DS06 is factory set to 60 psi.

To adjust the outlet pressure to a desired setting:

1.Loosen the locking screw by turning counter-

clockwise

! (Do not remove this screw.)

2.Turn the adjusting knob counter-clockwise to reduce pressure or clockwise to increase pressure.

3.Lock the setting by turning the locking screw clockwise .

4.Replace the dust cap over the dial.

LOOSEN LOCKING

SCREW ONE TURN

ADJUST SETPOINT AT THE DESIRED VALUE BY ACTUATING SELECTOR.

INLET PRESSURE (MAXIMUM): 250 PSI REDUCED PRESSURE RANGE:

25 TO 90PSI 1/2 IN. TO 2 IN. SIZE

NOTE: DO NOT DISMANTLE KNOB

SET-POINT READOUT HAS BEEN CALIBRATED

 

IN THE FACTORY AND SET AT 60 PSI.

 

DISMANTLING THE SELECTOR KNOB WILL

 

CANCEL THIS CALIBRATION. RECALIBRATE

 

USING A PRESSURE GAUGE. SEE RECALIBRATION.

M35046A

Fig. 1. Changing outlet pressure.

Replacing the Cartridge (Fig. 2)

The working parts of the DS06, including diaphragm, valve seat, strainer, and disk are all contained in a replaceable cartridge. To replace the cartridge:

1.Close shutoff valve on inlet.

2.Release pressure on outlet side (e.g. through water tap).

3.Close shutoff valve on outlet.

4.Loosen slotted screw (do not remove the screw).

CAUTION

To prevent injury and/or equipment damage, loosen locknut and turn adjusting screw counter-clockwise to remove spring tension.

5.Slacken tension in compression spring by turning counter clockwise until it does not move anymore.

6.Unscrew Bonnet.

7.Remove slip ring.

Recalibrate

If the dial knob assembly has been disassembled recalibration is necessary.

1. Close shutoff valve on inlet.

2. Release pressure on outlet side (e.g. through water tap).

3. Close shutoff valve on outlet.

4. Remove dust cap.

5. Loosen slotted screw (do not remove screw).

6. Fit pressure gauge.

7. Slowly open shutoff valve on inlet.

8. Set desired outlet pressure (e.g. 60 psi).

9. Align scale (e.g. 60 psi) in middle of viewing window.

10. Retighten slotted screw.

11. Slowly open shutoff valve on outlet.

1 LOOSEN THE SETPOINT DIAL LOCKING SCREW.

2 UNSTRESS THE PRESSURE SPRING

BY TURNING COUNTERCLOCKWISE .

3 UNSCREW THE BONNET WITH A 1-5/8" WRENCH.

1-5/8" WRENCH

4 REMOVE CARTRIDGE USING A PLIERS AS A LEVER.

5 WHEN REASSEMBLING, ENSURE O-RINGS AND WASHER ARE PROPERLY INSTALLED

WASHER (LIP UP)

O-RINGS

6 REASSEMBLE BONNET IN REVERSE ORDER.

M35634A

Fig. 2. Replacing the DS06 cartridge.

3

33-00014EF—07

DS06 LOW LEAD CONTENT DIAL SET PRESSURE REGULATING VALVES

Cleaning

1.Close shutoff valve on inlet.

2.Release pressure on outlet (e.g. through water tap).

3.Close shutoff valve on outlet.

4.Unscrew filter bowl using a 1-5/8" wrench.

5.Remove filter, clean and reinsert.

6.Place O-ring onto filter bowl.

7.Screw in filter cup hand-tight.

8.Slowly open shutoff valve on inlet.

9.Slowly open shutoff valve on outlets.

DUST CAP (BLACK)

LOCKING SCREW

ADJUSTING

KNOB

DIAL RING

BONNET

SPINDLE

SPRING

WASHER

CARTRIDGE

GASKETS (2)

TAILPIECES (2)

NUTS

(2)

PLUGS (2)

REPLACEMENT

FILTER

O-RING SET

FOR DO6F

OPERATION

DS06 is a spring loaded pressure reducing valve that operates by means of force equalizing system. The force of a diaphragm operates against the force of an adjustment spring. If the outlet pressure and therefore diaphragm force fall because water is dawn, the then greater force of the spring causes the valve to open. The outlet pressure then increases until the forces between the diaphragm and the spring are equal again. The inlet pressure has no influence in either opening or closing the valve. Because of this, inlet pressure fluctuation does not influence the outlet pressure, thus providing inlet pressure balancing. See Fig. 4 for the internal construction of the DS06.

NOTE: Minimum ambient rating is 33° F (1° C).

4

M35052

Fig. 4. Internal construction of DS06.

M35053A

Fig. 3. DS06 exploded view.

33-00014EF—07

4

Loading...
+ 8 hidden pages