DPTM50D-5000D
3-WIRE DIFFERENTIAL PRESSURE TRANSMITTERS WITH DIGITAL DISPLAY AND CURRENT/VOLTAGE OUTPUT
GENERAL
The differential pressure transmitters of the DPTM series are used for measuring differential pressure, positive pressure, and vacuum. The transmitters are suitable for:
•air-conditioning,
•building automation,
•environmental protection,
•valve and flap control,
•filter and blower monitoring,
•fluid and level monitoring, and
•control of air flows.
Models
|
order no. |
|
pressure range |
|
overload |
|
burst |
|
|
|
|
1 (pre-set) |
2 |
|
capacity |
|
pressure |
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|||
|
DPTM50D |
|
-50...0...+50 Pa1) |
n.a. |
|
20 kPa |
|
40 kPa |
|
|
DPTM110D |
|
-100...0...+100 Pa1) |
n.a. |
|
20 kPa |
|
40 kPa |
|
|
DPTM550D |
|
-500...0...+500 Pa1) |
n.a. |
|
20 kPa |
|
40 kPa |
|
|
DPTM1100D |
|
-1 kPa...0...+1 kPa2) |
n.a. |
|
40 kPa |
|
70 kPa |
|
|
DPTM100D |
|
0...100 Pa1) |
0...250 Pa1) |
|
20 kPa |
|
40 kPa |
|
|
DPTM250D |
|
0...250 Pa1) |
0...500 Pa1) |
|
20 kPa |
|
40 kPa |
|
|
DPTM500D |
|
0...500 Pa1) |
0...1 kPa1) |
|
20 kPa |
|
40 kPa |
|
|
DPTM1000D |
|
0...1 kPa2) |
0...2.5 kPa2) |
|
40 kPa |
|
70 kPa |
|
|
DPTM5000D |
|
0...5 kPa3) |
0...10 kPa3) |
|
60 kPa |
|
120 kPa |
1) pressure displayed in Pa, temperature error at 0…50 °C ≤ ± 5% of full scale (FS)
2) pressure displayed in kPa, temperature error at 0…50 °C ≤ ± 2.5% of full scale (FS) 3) pressure displayed in kPa, temperature error at 0…50 °C ≤ ± 1% of full scale (FS)
SPECIFICATION DATA & MOUNTING INSTRUCTIONS
FEATURES
•Monitoring gaseous, non-aggressive media
•Piezo-resistive pressure transducer
•Up to 40 kPa (60 kPa) overload capacity
•Rugged design; protection class IP54
•Easy installation and wiring connection
•Measurement range adjustable by jumper
•Response time adjustable by jumper
•Output signal adjustable by jumper
•Red digital display
•Display of values > +1000 Pa in kPa
•Re-zeroing possible by pushbutton
NOTE: These sensors are not suitable for use in installations under periodic inspection by the U.S. Food and Drug Administration.
SPECIFICATION
Supply voltage |
18...30 Vac/dc, 50/60 Hz |
Output signal |
0...10 Vdc (factory setting) / |
|
4…20 mA |
Pressure medium |
Air, non-aggressive gases |
Working temperature |
0...50 °C |
Linearity and hysteresis error |
≤ ± 1.0% of FS |
Temperature error at 0...50°C |
See section "Models" |
Storage temperature |
-10...+70 °C |
Humidity |
0...95% rh, non-condensing |
Repetition accuracy |
≤ ± 0.2% of FS |
Response time |
1 s (factory setting) / 100 ms |
Process connection |
6 mm hose pipe |
Electrical connection |
Screw terminal block for wire |
|
up to 1.5 mm² |
Housing material |
ABS and POM |
Cable entry |
M20x1.5 (polyamide) |
Protection class |
IP54 as per EN60529 |
EMV |
EN60770, EN61326 |
Weight |
approx. 130 g |
® U.S. Registered Trademark |
|
EN0B-0616GE51 R1007 |