GE Industrial Solutions EntelliGuard G Spring charge Contact User Manual

0 (0)
GE Industrial Solutions EntelliGuard G Spring charge Contact User Manual

.

Introduction

Spring Charge Contact

All electrically operated (EO) ANSI/UL breakers are equipped with “Spring Charged” contacts for status indication.

Catalog Number: GSCC1

Table1. Parts List

Description

Quantity

Switch with harness

1

M3 screws

2

M3 washers

2

Spacer

1

Insulation sheet

1

DEH-41375 Installation Instructions

EntelliGuard ® G Circuit Breaker

Accessories

Spring charge Contact

WARNING: Before installing any accessories, turn the breaker OFF, disconnect it from all voltage sources, and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire, mettre le disjoncteur en position OFF, le déconnecter de toute tension d’alimentation , et décharger les resorts d’armement

Use the following procedure to install the Motor Operator accessory into the circuit breaker.

1.Check that the package contains all the parts listed in Table 1. If any components are missing, contact the Electrical Distribution Post Sales Service Team at 1-800-843-3742.

2.Turn the breaker off and discharge the closing springs by depressing the OFF and ON buttons in the sequence OFF-ON-OFF. Verify that the breaker OFF-ON indicator shows OFF on a green background and that the charge indicator shows DISCHARGE on a white background. If installing in a draw-out type breaker remove breaker from adaptor (cassette) before continuing.

3.Loosen the 6 screws on front cover (fascia) using a pozidrive screw driver as shown in Fig 1.B Rotate the charging handle down and slide the front cover over the handle to remove the front cover as shown in Fig. 1.C