GE Industrial Solutions EntelliGuard 800–2000 A Frames User Manual

0 (0)

DEH203

R02

g

EntelliGuard™ Power Circuit Breakers

800–2000 A Frames, 240–600 Vac

Maintenance Manual

DEH203

WARNINGS, CAUTIONS, AND NOTES

AS USED IN THIS PUBLICATION

WARNINGS

Warning notices are used in this publication to emphasize that hazardous voltages, currents, or other conditions that could cause personal injury are present in this equipment or may be associated with its use.

Warning notices are also used for situations in which inattention or lack of equipment knowledge could cause either personal injury or damage to equipment.

CAUTIONS

Caution notices are used for situations in which equipment might be damaged if care is not taken.

NOTES

Notes call attention to information that is especially significant to understanding and operating the equipment.

This document is based on information available at the time of its publication. While efforts have been made to ensure accuracy, the information contained herein does not cover all details or variations in hardware and software, nor does it provide for every possible contingency in connection with installation, operation, and maintenance. Features may be described herein that are not present in all hardware and software systems. GE Consumer & Industrial assumes no obligation of notice to holders of this document with respect to changes subsequently made.

GE Consumer & Industrial makes no representation or warranty, expressed, implied, or statutory, with respect to, and assumes no responsibility for the accuracy, completeness, sufficiency, or usefulness of the information contained herein. No warrantees of merchantability or fitness for purpose shall apply.

The following are trademarks of GE Company:

EntelliGuard™, EntelliGuard Messenger™, Entellisys™

© Copyright 2005 GE Company

All Rights Reserved

i

EntelliGuard™ 800–2000 A Power Circuit Breakers

Table of Contents

Chapter 1. Introduction

 

1.1

Overview...................................................................................................................................................

1

1.2 Inspection and Maintenance ..................................................................................................................

1

1.3

Renewal Parts...........................................................................................................................................

1

Chapter 2. Description

 

2.1

Introduction ............................................................................................................................................

3

2.2

Frame Sizes ..............................................................................................................................................

3

2.3 Operation ................................................................................................................................................

3

2.4 Fused Models ...........................................................................................................................................

3

2.5 Mounting .................................................................................................................................................

3

2.6

Trip Units ................................................................................................................................................

3

2.7

Interruption Ratings ...............................................................................................................................

3

Chapter 3. Storage, Safety, and Maintenance

 

3.1

Storage .....................................................................................................................................................

5

3.2

Safety ........................................................................................................................................................

5

3.3 Maintenance............................................................................................................................................

5

Chapter 4. Breaker Operation

 

4.1

Operating Instructions ............................................................................................................................

7

 

Sequence of Operations ..................................................................................................................

7

 

Operation of the Breaker ................................................................................................................

7

 

Padlock Operation...........................................................................................................................

8

4.2

Control Wiring ........................................................................................................................................

8

4.3

Breaker Interlocks ...................................................................................................................................

8

 

Drawout Interlock............................................................................................................................

8

 

Contact Interlock .............................................................................................................................

8

 

Spring Discharge Interlock .............................................................................................................

8

4.4

Equipment Interlocks..............................................................................................................................

8

Chapter 5. Breaker Maintenance

 

5.1

Lubrication ............................................................................................................................................

11

5.2

Removing and Reinstalling the Breaker ..............................................................................................

11

 

Removing the Breaker...................................................................................................................

11

 

Installing the Breaker ....................................................................................................................

11

5.3

Slow Closing the Breaker ......................................................................................................................

13

5.4 Separation and Reconnection of Front and Back Frames...................................................................

13

 

Separation of Front and Back Frames for EGS08, EGF08, and EGH08 ......................................

13

 

Reconnection of Front and Back Frames for EGS08, EGF08, and EGH08 .................................

14

 

Separation of Front and Back Frames for EGX08, EGS16, EGF16, EGH16, EGS20, and

 

 

EGF20.............................................................................................................................................

16

 

Reconnection of Front and Back Frames for EGX08, EGS16, EGF16, EGH16, EGS20, and

 

 

EGF20.............................................................................................................................................

16

 

ii

 

EntelliGuard™ 800–2000 A Power Circuit Breakers

Table of Contents

5.5 Breaker Mechanism Operation and Adjustment .................................................................................

18

Trip Latch Adjustment ..................................................................................................................

19

Chapter 6. Contact Maintenance

 

6.1 Introduction ..........................................................................................................................................

20

6.2 Arc Chute Removal and Replacement .................................................................................................

20

Arc Chutes in EGS08, EGF08, and EGH08 Breakers....................................................................

20

Arc Chutes in EGX08, EGS16, EGF16, EGH16, EGS20, and EGF20 Breakers ............................

20

6.3 Back Frame Assembly ............................................................................................................................

21

6.4 Replacement of Contacts ......................................................................................................................

21

Contact Replacement on EGS08, EGF08, and EGH08 Breakers .................................................

21

Contact Replacement on EGX08, EGS16, EGF16, EGH16, EGS20, and EGF20 Breakers..........

24

6.5 Adjusting the Contacts ..........................................................................................................................

26

Contact Adjustment on EGS08, EGF08, and EGH08 Breakers ....................................................

26

Contact Adjustment on EGX08, EGS16, EGF16, EGH16, EGS20, and EGF20 Breakers ............

26

Chapter 7. Maintenance of Standard Parts and Assemblies

 

7.1 Primary Disconnects ..............................................................................................................................

28

Primary Disconnect Replacement on EGS08, EGF08, and EGH08 Breakers..............................

28

Primary Disconnect Removal on EGX08, EGS16, EGF16, EGH16, EGS20, and EGF20

 

Breakers..........................................................................................................................................

28

Primary Disconnect Installation on EGX08, EGS16, EGF16, EGH16, EGS20, and EGF20

 

Breakers..........................................................................................................................................

29

7.2 Secondary Disconnect ...........................................................................................................................

31

Secondary Disconnect Removal ....................................................................................................

31

Secondary Disconnect Installation................................................................................................

31

7.3 Flux Shifter ............................................................................................................................................

32

Flux Shifter Adjustment.................................................................................................................

32

Removing the Flux Shifter ............................................................................................................

32

Installing the Flux Shifter..............................................................................................................

32

7.4 Draw-Out Mechanism............................................................................................................................

34

Draw-Out Mechanism Removal ....................................................................................................

34

Draw-Out Mechanism Installation ................................................................................................

34

Draw-Out Mechanism Adjustment................................................................................................

34

7.5 Escutcheon.............................................................................................................................................

36

Escutcheon Removal .....................................................................................................................

36

Escutcheon Installation .................................................................................................................

36

7.6 Charging Handle...................................................................................................................................

36

Removing the Charging Handle...................................................................................................

36

Installing the Charging Handle ....................................................................................................

36

Chapter 8. Accessory Maintenance

 

8.1 Bell Alarm with Lockout........................................................................................................................

38

Removing the Bell Alarm with Lockout........................................................................................

38

Installing the Bell Alarm with Lockout .........................................................................................

39

8.2 Shunt Trip .............................................................................................................................................

39

iii

 

EntelliGuard™ 800–2000 A Power Circuit Breakers

 

Table of Contents

 

Removing the Shunt Trip .............................................................................................................

40

Installing the Shunt Trip ..............................................................................................................

40

8.3 Charging Motor.....................................................................................................................................

41

Removing the Charging Motor.....................................................................................................

41

Installing the Charging Motor ......................................................................................................

41

Removing the Motor Cut-Off Switch ............................................................................................

41

Installing the Motor Cut-Off Switch..............................................................................................

41

Adjusting the Motor Cut-Off Switch .............................................................................................

43

8.4 Remote Close .........................................................................................................................................

43

Removing the Remote Close .........................................................................................................

44

Installing the Remote Close ..........................................................................................................

44

8.5 Open-Fuse Lockout ...............................................................................................................................

45

Removing the Open-Fuse Lockout, 800 A and 1600 A Breakers..................................................

45

Installing the Open-Fuse Lockout, 800 A and 1600 A Breakers...................................................

45

Removing the Open-Fuse Lockout, 2000 A Breakers ...................................................................

45

Installing the Open-Fuse Lockout, 2000 A Breakers ....................................................................

46

8.6 Remote Charge-Indication Switch........................................................................................................

47

Removing the Remote Charge-Indication Switch........................................................................

47

Installing the Remote Charge-Indication Switch .........................................................................

47

8.7 Network Interlock ..................................................................................................................................

48

iv

EntelliGuard™ 800–2000 A Power Circuit Breakers

List of Figures

1.

Front of the EntelliGuard circuit breaker, showing the locations of standard and optional

 

 

features.......................................................................................................................................................

2

2.

Elementary diagram of the breaker control circuits. ...............................................................................

9

3.

Location of the secondary disconnect ......................................................................................................

9

4.

Installing the breaker into the compartment.........................................................................................

12

5.

Disconnecting the closing spring assembly. ...........................................................................................

13

6.

Removing or installing the secondary disconnect .................................................................................

14

7.

Movable contact connection to the breaker main shaft on EGS08, EGF08, and EGH08 breakers. .....

14

8.

Separating the front and back frames on EGS08, EGF08, and EGH08 breakers..................................

15

9.

Movable contact connection to the breaker main shaft on EGX08, EGS16, EGF16, EGH16,

 

 

EGS20, and EGF20 breakers. ..................................................................................................................

16

10.

Separating the front and back frames on EGX08, EGS16, EGF16, EGH16, EGS20, and EGF20

 

 

breakers....................................................................................................................................................

17

11.

Breaker mechanism in the CLOSED position. ......................................................................................

18

12.

Breaker mechanism in the TRIPPED position. .....................................................................................

18

13.

Breaker mechanism in the RESET position...........................................................................................

18

14.

Adjusting the trip latch. ..........................................................................................................................

19

15.

Typical back frame assembly, EGS08, EGF08, and EGH08. ..................................................................

21

16.

Typical back frame assembly, EGX08, EGS16, EGF16, EGH16, EGS20, and EGF20............................

21

17.

Upper (stationary) contact assembly for EGS08, EGF08, and EGH08 breakers. ..................................

22

18.

Lower (movable) contact assembly for EGS08, EGF08, and EGH08 breakers......................................

22

19.

Removal and installation of contact assemblies on EGS08, EGF08, and EGH08 breakers ..................

23

20.

Removal and installation of contact assemblies on EGX08, EGS16, EGF16, EGH16, EGS20, and

 

 

EGF20 breakers........................................................................................................................................

25

21.

Stationary main and intermediate contact styles. ..................................................................................

25

22.

Replacement of stationary arcing contacts.............................................................................................

25

23.

Contact adjustment on EGS08, EGF08, and EGH08 breakers...............................................................

26

24.

Contact adjustment on EGX08, EGS16, EGF16, EGH16, EGS20, EGF20 breakers. .............................

27

25.

Primary disconnect assembly for EGS08, EGF08, and EGH08 breakers ...............................................

28

26.

Primary disconnect assembly for EGX08, EGS16, EGF16, EGH16, EGS20, and EGF20 breakers........

28

27.

Primary disconnect removal and installation on EGS08, EGF08, and EGH08 breakers ......................

29

28.

Primary disconnect removal and installation on EGX08, EGS16, EGF16, EGH16, EGS20, and

 

 

EGF20 breakers........................................................................................................................................

30

29.

Primary disconnect adjustment on EGX08, EGS16, EGF16, EGH16, EGS20 and EGF20 breakers. ....

30

30.

Secondary disconnect..............................................................................................................................

31

31.

Secondary disconnect terminal numbering. ..........................................................................................

31

32.

Removing or installing the secondary disconnect. ................................................................................

31

33.

Flux shifter ...............................................................................................................................................

32

34.

Flux shifter adjustment............................................................................................................................

32

35.

Removal or installation of a flux shifter .................................................................................................

33

36.

Draw-out racking mechanism. ................................................................................................................

34

 

v

 

EntelliGuard™ 800–2000 A Power Circuit Breakers

 

List of Figures

 

37.

Draw-out mechanism adjustment ............................................................................................................

34

38.

Draw-out racking mechanism removal and installation.........................................................................

35

39.

Escutcheon kit and related parts. ............................................................................................................

36

40.

Charging handle ......................................................................................................................................

37

41.

Charging handle removal and installation. ............................................................................................

37

42.

Charging handle mounting detail ..........................................................................................................

37

43.

Bell Alarm with Lockout connections on the secondary disconnect. ....................................................

38

44.

Bell Alarm with Lockout accessory kit. ....................................................................................................

38

45.

Bell Alarm with Lockout installation or removal. ...................................................................................

38

46.

Front view of the Bell Alarm with Lockout installation, showing the breaker mechanism tab

 

 

engaging the mounting plate slot............................................................................................................

39

47.

Orientation of the label on the Bell Alarm module for installation. .....................................................

39

48.

Shunt Trip connections to the auxiliary switch and secondary disconnect. .........................................

40

49.

Shunt Trip accessory kit...........................................................................................................................

40

50.

Shunt Trip module removal and installation. ........................................................................................

40

51.

Charging Motor and cut-off switch..........................................................................................................

41

52.

Removal and installation of the Charging Motor and cut-off switch.....................................................

42

53.

Cut-off switch adjustment.........................................................................................................................

43

54.

Remote Close accessory kit.......................................................................................................................

43

55.

Remote Close installation and removal...................................................................................................

44

56.

Open-Fuse Lockout accessory ..................................................................................................................

45

57.

Open-Fuse Lockout connections to the secondary disconnect for EGF-20 breakers. ............................

45

58.

Open-Fuse Lockout installation and removal .........................................................................................

46

59.

Remote charge-indication switch. ...........................................................................................................

47

60.

Remote charge-indication switch removal and installation. ..................................................................

47

61.

Remote charge-indication switch side view.............................................................................................

47

62.

Network Interlock connections to the secondary disconnect. ................................................................

48

63.

Network Interlock assembly mounting to the circuit breaker bottom frame .........................................

49

64.

Network Interlock module fastening to the mounting plate. .................................................................

49

65.

Manual reset assembly mounting. ...........................................................................................................

49

66. Trip paddle and set lever gap calibration .............................................................................................

49

vi

EntelliGuard™ 800–2000 A Power Circuit Breakers

List of Tables

1.

Recommended service intervals, in number of ON-OFF operations, for EntelliGuard breakers.

.......... 1

2.

Breaker interruption ratings. ....................................................................................................................

4

3.

Sequence of operations that may be performed with the EntelliGuard circuit breaker.........................

7

4.

Secondary disconnect terminals with standard and optional connections. .........................................

10

5.

Key to numbered parts in Figure 11, Figure 12, and Figure 13 .............................................................

18

6.

Bell Alarm with Lockout wires and corresponding secondary disconnect terminals. ..........................

39

7.

Catalog number and operating voltage for the Shunt Trip accessory. .................................................

40

8.

Catalog number and operating voltage for the Charging Motor accessory ..........................................

41

9.

Catalog number and operating voltage for the Remote Close accessory. .............................................

43

vii

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 1. Introduction

1.1 Overview

These instructions describe the procedures for maintenance and operation of EntelliGuard 800-2000 ampere low-voltage power circuit breakers. Figure 1 is a front view of the breaker, with key features indicated.

The proper use, care, and maintenance of these breakers is important both from the safety aspect of protecting personnel and for minimizing equipment damage when faults occur. Persons who apply, use, and service these breakers should be familiar with the information presented in this publication.

WARNING: Before inspecting or beginning any maintenance work on a circuit breaker, the breaker must be in the OPEN position and disconnected from all voltage sources, both power and control.

AVERTISSEMENT: Avant d’inspecter ou de débuter tout travail de maintenance d’un disjoncteur, celui-ci dout être en position OPEN et débranché de toutes les sources de voltage, à la fois de puissance et de contrôle.

Source of

800 A Frame

1600 and

Recommendation

2000 A Frames

ANSI

1750

500

EntelliGuard, no

3500

1000

load

 

 

EntelliGuard, at

2800

800

frame rating

 

 

Table 1. Recommended service intervals, in number of ON-OFF operations, for EntelliGuard breakers.

If a breaker is installed in an area of high humidity or a dusty atmosphere, it should be inspected more often. Monthly inspections might be warranted for a breaker operated under severe conditions.

Always inspect the breaker after it has interrupted a short circuit or ground fault.

A standard inspection should consist of the following steps:

1.Visual Check – Look for dirt, grease, or other foreign material on all breaker parts. Check insulating surfaces for conditions that could degrade insulating properties, such as cracks or evidence of overheating. Check for foreign objects on the bottom of the breaker compartment. Check for loose or damaged control wiring and for similar problems.

1.2 Inspection and Maintenance

Circuit breakers should be maintained under a systematic program. Take each breaker out of service periodically for inspection and maintenance to help establish high reliability in service. This policy is facilitated by keeping one or more spare breakers to install in place of breakers requiring maintenance. Keeping a stock of recommended renewal parts ensures that maintenance work can be done quickly.

The frequency at which an individual breaker should be inspected depends on the circumstances of its use. Table 1 lists the ANSI-recommended service interval with the GErecommended interval for EntelliGuard breakers. EntelliGuard breakers should be inspected after every short circuit interruption, after every number of ON-OFF operations given in Table 1, or every two years, whichever comes first. EntelliGuard breakers have been built and tested to operate reliably with inspections at twice the ANSI interval, thus saving time and money by reducing breaker downtime.

2.Operation – Observe a few close-open operations using the operating handle. If a breaker is seldom operated, such that it remains open or closed for six months or more, open and close the breaker several times in succession.

3.Interlocks – During the operational check, verify that the safety interlocks are working properly.

4.Arc Chutes and Contacts – Inspect the arc chutes and contacts for excessive burning or breakage. Check the amount of contact depression or wipe when the breaker is closed.

5.Accessories – Verify that the various accessories are working properly.

1.3Renewal Parts

Many of the parts and assemblies contained in EntelliGuard breakers are available as replacement parts. See DEF004 for a complete listing.

1

GE Industrial Solutions EntelliGuard 800–2000 A Frames User Manual

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 1. Introduction

G

H

J

A

B

C

D

E

F

K

Figure 1. Front of the EntelliGuard circuit breaker, showing the locations of standard and optional features.

A Indicator: DISC (white) TEST (white) CONN (white)

B Indicator: CHARGED (yellow)

DISCHARGED (white)

C Indicator: CLOSED (red) OPEN (green)

D CLOSE button (black)

EOPEN button (red)

FPadlock provision

GCatalog number, rating, and date code nameplate

HManual charging handle

JBell Alarm with Lockout target/RESET button

KDraw-out racking screw (behind cover)

2

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 2. Description

2.1 Introduction

breaker, and a Shunt Trip to open the breaker. External

EntelliGuard low-voltage power circuit breakers control

control power is required to energize the motor and its

control circuit. All breakers are equipped with a manual

and protect power circuits up to 600 volts. They will safely

charging handle so that the closing springs can be

switch loads and automatically clear circuits during abnor-

charged without motor control power.

mal conditions when used with the EntelliGuard

 

Messenger™. These include short circuits, sustained

2.4 Fused Models

overloads, and ground faults.

EntelliGuard breakers contain a “quick-make, quick-

Internally fused breakers are available in 800and 1600-

break” mechanism, which stores energy in a closing spring

ampere frame sizes. They are not interchangeable with

for quick release. During closing, some energy is

unfused breakers, since fused breakers require deeper

transferred to an opening spring to be used subsequently

compartments to accommodate the fuses.

for fast tripping.

 

The three main functional components of the breaker are

2.5 Mounting

its mechanism, an assembly consisting of the conductive

components, and the interrupter.

EntelliGuard breakers are designed for draw-out

The mechanism is designed to receive energy, store it, and

mounting. Draw-out breakers are easily installed into or

later deliver it to close the breaker contacts. It must be able

removed from their switchgear cubicle. They are

to reverse the closing operation at any point upon receipt

equipped with a racking mechanism, which is used to

of a trip signal from the EntelliGuard Messenger (that is,

insert or withdraw the breaker, and primary and

it must be “trip-free”). Finally, it must also open a closed

secondary disconnects, which connect and disconnect

breaker quickly enough to minimize contact erosion and

automatically.

to effectively transfer the arc to the arc chutes.

 

The current-carrying components are assembled on the back frame, which provides the required mechanical support and insulating structure. The conductive components are the studs for external connections, the movable and stationary contact sets, and the pivots for the movable contacts.

The interrupter components are the arcing contacts, the arc runners mounted on the back base, and the removable arc chute assemblies.

In addition to these basic components, a breaker may be equipped with a combination of accessories and interlocking devices.

2.2 Frame Sizes

The EntelliGuard breakers covered in this manual are available in 800-ampere, 1600-ampere, and 2000-ampere frame sizes. These values represent the maximum continuous-current rating of each frame. In addition, each breaker carries a specific rating that is determined by the current sensor ampere rating or the maximum setting of the EntelliGuard Messenger™ with which it is used.

2.6 EntelliGuard Messenger™

EntelliGuard low-voltage power circuit breakers are intended for use in Entellisys™ Low-Voltage Switchgear only. The breaker frames do not contain trip units or current transformers. Thus, the EntelliGuard circuit breaker must be used in concert with the EntelliGuard Messenger and the current transformers mounted within the switchgear cubicle. For installation and operation of the EntelliGuard Messenger, see DEH231 and DEH234.

2.7 Interruption Ratings

Table 2 lists the short-circuit current that each breaker type is rated to interrupt for each maximum rated voltage.

2.3 Operation

EntelliGuard breakers are available with either manual or electric operation. The mechanism closing springs of manually operated breakers are charged by operating the charging handle on the front of the breaker.

Electrically operated breakers contain an electric Charging Motor that charges the closing springs, a Remote Close accessory with antipump to close the

3

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 2. Description

Rated AC

 

Short-Circuit RMS Symmetrical kA

 

 

 

 

Voltage,

 

 

 

 

Nominal

Breaker

Short-Time

With

Without

(max)

Type

Withstand

Inst. Trip

Inst. Trip

 

 

 

 

 

 

EGS-08

30

30

30

 

EGH-08

42

42

42

600

EGX-08

50

50

50

(635)

EGS-16

42

42

42

 

EGH-16

65

65

65

 

EGS-20

65

65

65

 

EGS-08

30

30

30

 

EGH-08

42

42

42

480

EGX-08

65

65

65

(508)

EGS-16

50

50

50

 

EGH-16

65

65

65

 

EGS-20

65

65

65

 

EGS-08

30

42

30

 

EGH-08

42

50

42

240

EGX-08

65

65

65

(254)

EGS-16

50

65

50

 

EGH-16

65

65

65

 

EGS-20

65

65

65

Table 2. Breaker interruption ratings. (EGF-08/16/20 rated at 200kA).

4

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 3. Storage, Safety, and Maintenance

3.1 Storage

 

 

associated personnel carefully apply a thorough

The breaker should be put into service immediately in its

understanding of the specific equipment with

regard to its purpose, its construction, its operation,

permanent location. If this is not possible, the following

and situations that could be dangerous.

precautions must be taken to ensure proper storage of the

3. All personnel associated with installation, operation,

breaker

 

 

 

 

and maintenance of electrical equipment, such as

• Protect the breaker against condensation, preferably

power circuit breakers and other power-handling

by storing it in a warm, dry room, since water absorp-

equipment, must be thoroughly instructed, with

tion has an adverse effect on the insulating parts.

periodic retraining, about power equipment in gen-

• Store the breaker in a clean location free from corro-

eral and the specific equipment with which they will

sive gases or fumes. It is particularly important to

be working in particular. Instruction books, actual

protect the equipment from moisture and cement

devices, and appropriate safety and maintenance

dust, as this combination is corrosive to many parts.

procedures, such as OSHA publications, the

 

 

 

 

National Electrical Safety Code (ANSI C2), the

 

CAUTION: If the breaker is stored for any

 

National Electrical Code, and NFPA 7 OB Electrical

 

length of time, inspect it periodically to ensure

 

Equipment Maintenance, must be closely studied

 

that steel parts have not begun to rust and to

 

and followed. During actual work, supervisors

 

ensure good mechanical condition. If the

 

should audit procedures to ensure conformance.

 

breaker has been stored under unfavorable

 

4. Excellent maintenance is essential for reliability and

 

atmospheric conditions, it must be cleaned and

 

safety of all electrical equipment. Industry publica-

 

dried before being placed in service.

 

tions of recommended maintenance practices, such

 

 

 

 

as ANSI/NFPA 70B, Electrical Equipment Maintenance,

 

ATTENTION: Si le disjoncteur est remisé pour

 

are readily available.

 

peu importe la période de temps, inspectez-le

 

 

 

périodiquement afin de vous assurer que les

 

3.3 Maintenance

 

pièces d’acier n’ont pas commencé à rouiller et

 

 

de vous assurer

de leur bonne condition

 

Both longand short-term maintenance of all electrical

 

mécanique. Si le disjoncteur a été remisé à des

 

 

 

equipment is essential for reliability and safety. Mainte-

 

conditions atmosphériques défavorables, il doit

 

 

 

nance programs must be well-planned and carried out

 

être nettoyé et séché avant d’être mis en service.

 

 

 

consistently with both industry experience and the manu-

 

 

 

 

facturer’s recommendations. The local environment must

3.2 Safety

 

 

always be considered such programs, including such

 

 

variables as ambient temperature, extreme moisture,

 

 

 

 

number of operations, corrosive atmosphere, significant

Each facility must maintain a safety program for the pro-

insect problems, and any other unusual or abusive condi-

tection of personnel, as well as other equipment, from the

tion of the application.

hazards associated with electrical equipment.

One of the critical service activities, sometimes neglected,

 

 

 

 

The following requirements are intended to augment a

is the calibration of various control devices. These moni-

facility’s safety program, not

to supplant local responsibil-

tor conditions in the primary and secondary circuits,

ity for devising a complete safety program. The following

sometimes initiating emergency corrective action, such as

basic industry-accepted safety requirements are applicable

opening or closing circuit breakers. In view of the vital

to all major electrical equipment, such as switchgear and

roles of these devices, it is important to follow a periodic

switchboards. General Electric neither condones nor

test program.

assumes any responsibility for practices that deviate from

General Electric recognizes that the interval between peri-

these requirements.

 

 

 

 

odic checks will vary, depending on the environment, the

1. All conductors must be assumed to be energized

type of device, and the customer’s experience. GE recom-

unless their potential has been measured as ground

mends that, until the customer has accumulated sufficient

and suitable grounding conductors have been

experience to select a test interval best suited to the local

applied to prevent energizing. Many accidents have

requirements, all significant calibrations be checked at

been caused by back feeds from various sources.

oneto two-year intervals.

2. Although interlocks are provided to reduce some of

Operation and maintenance guides supplied by manufac-

the risks, each individual’s actions are essential to

turers normally address components that require service

prevent accidents when performing service or main-

or maintenance during the useful life of the equipment.

tenance. Each person’s knowledge, mental aware-

However, they cannot include every possible part that

ness, and planned and executed actions often

could require attention, particularly over a long service

determine if an accident will occur. The most

period or under adverse conditions. Maintenance

important principle for avoiding accidents is that all

personnel must be alert to deterioration of any part of the

 

 

 

 

5

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 3. Storage, Safety, and Maintenance

supplied switchgear, taking such action as necessary to restore it to serviceable status.

If additional assistance is required in the planning and performance of maintenance, contact GE Installation and Field Service (1-888-434SERV / 1-888-434-7378) to undertake the maintenance or to provide technical assistance, such as the latest publications.

The performance and safety of this equipment may be compromised by the modification or supplied parts or their replacement by non-identical substitutes. All such design changes must be qualified to ANSI/IEEE Standard C37.59.

Each customer should methodically keep written maintenance records as an aid in future service planning and equipment reliability improvement. Unusual experiences should be promptly reported to General Electric (1-888- GER-ESOLve).

6

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 4. Breaker Operation

4.1 Operating Instructions

Sequence of Operations

The sequence of operations that may be performed on the circuit breaker are listed in Table 3.

Closing the Breaker

Close the breaker contacts with any of the following methods:

Depress the CLOSE button on the front of the breaker.

Close the breaker using the Entellisys™ HMI.

Operation of the Breaker

Manually Charging the Closing Springs

Pull the operating handle down about 90° (until it stops) six times to fully charge the closing springs. This will not close the breaker contacts. The charge indicator will show CHARGED on a yellow background.

NOTE: The breaker cannot be closed unless the springs are fully charged and the handle is stored fully in.

NOTE: Le disjoncteur ne peut être fermé à moins que les ressorts ne soient pleinement chargés et que la poignée ne soit pleinement rentrée.

Electrically Charging the Closing Springs

If the breaker is equipped with the (optional) Charging Motor, the closing springs may also be charged with any the following methods:

With the breaker in the TEST position, install the motor fuse in the fuse holder in the upper left corner of the breaker compartment.

Operate the Charging Motor by applying the rated voltage to secondary disconnect terminals 8 and 17. Power to the motor is removed automatically by a cutoff switch when the springs are fully charged.

If power is lost during the charging cycle, finish charging the springs by cycling the charging handle until the indicator shows CHARGED on a yellow background.

The closing springs will automatically recharge after closing if control power is maintained at terminals 8 and 17.

Energize the (optional) Remote Close accessory by applying the rated voltage to secondary disconnect terminals 9 and 18.

If the breaker is closed electrically and the closing voltage is maintained, an antipump device prevents a second closing operation on the breaker in the event it is tripped OPEN. The closing impulse must be released for 1 to 2.5 seconds and reapplied before a second closing operation can occur.

If the closing voltage is applied while the closing springs are not fully charged, the Remote Close coil energizes, but operation of the closing mechanism is blocked. The closing voltage must be removed and reapplied when the springs are fully charged to close the breaker.

A mechanical interlock prevents the closing springs from discharging if an attempt is made to close an already CLOSED breaker.

NOTE: The main breaker contacts cannot be closed if any of the following conditions apply:

The draw-out mechanism is in any position other than TEST or CONN, as displayed on the breaker position indicator.

The (optional) Bell Alarm with Lockout was not reset after an overcurrent lockout.

The (optional) Open Fuse Lockout was not reset after replacement of a blown fuse.

The (optional) Network Interlock was not reset after a set operation.

These conditions must be corrected before the breaker can be closed. Attempts to close the breaker before these conditions are corrected may result in discharge of the closing springs without closing the main contacts.

Open/Closed

Main Breaker

Charge

Condition of Close

Next Permissible

Indicator

Contacts

Indicator

Springs

Operating Function

 

 

 

 

 

OPEN

Open

DISCHARGED

Discharged

Mechanism may be charged

OPEN

Open

CHARGED

Charged

Contacts may be closed

CLOSED

Closed

DISCHARGED

Discharged

Mechanism may be recharged or

Contacts may be opened

 

 

 

 

CLOSED

Closed

CHARGED

Charged

Contacts may be opened

Table 3. Sequence of operations that may be performed with the EntelliGuard circuit breaker

7

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 4. Breaker Operation

NOTE: Les contacts principaux du disjoncteur ne peuvent être fermés si l’une ou l’autre des conditions suivantes s’appliquent:

Le mécanisme de retrait du ressort est en tout autre position que: TEST ou DISC, tel que montré à la position indicatrice du disjoncteur.

L’alarme optionnelle avec cloche n’a pas été remise en place après un blocage par surintensité de courant.

Le mécanisme optionnel de déclenchement par sous voltage n’a pas été enclenché.

Le verrouillage réciproque optionnel de réseaun'était pas réenclenché après une opération d'enclenchement.

Il faut que ces situations soient corrigées avant de procéder à la fermeture du disjoncteur.

Opening the Breaker

Open the breaker contacts with any of the following methods:

Depress the OPEN button on the front of the breaker.

Open or trip the breaker using the Entellisys™ HMI.

Energize the (optional) Shunt Trip accessory by applying the rated voltage to secondary disconnect terminals 5 and 7.

Padlock Operation

The padlock provision prevents the breaker from closing by holding the trip latch in the tripped position. Up to three padlocks with 1/4" or 3/8" diameter shanks, or scis- sor-type safety lockout hasps may be inserted at one time. To install a padlock, use the following procedure:

WARNING: Be sure to test for proper operation of the mechanism, as described in step 1, before using it to secure the breaker.

AVERTISSEMENT: Assurez-vous de tester que le mécanisme opère correctement, tel que décrit à l'étape 1, avant de l'utiliser pour fixer le disjoncteur.

1.To check for proper installation of the padlock

mechanism, hold in the OPEN button, pull out the padlock slide, insert a 1/8" rod or #10 gage solid

wire, and attempt to close the breaker.

The breaker must not close.

2.While holding the OPEN button in, slide the padlock plate out and hold it in place.

3.Put the padlock or safety lockout hasp into one of the three holes in the padlock plate; this will

prevent the plate from returning to its unlocked position and prevent the breaker from closing.

4.2 Control Wiring

Figure 2 is the wiring diagram for the breaker control circuits. Table 4 lists the secondary disconnect terminals and the items connected to each. The location of the secondary disconnect is illustrated in Figure 3.

4.3 Breaker Interlocks

EntelliGuard breakers are equipped with a number of safety interlocks to prevent improper operation of the breaker.

Draw-Out Interlock

The draw-out interlock prevents the breaker from being closed when the breaker is in neither the CONN or TEST position, but is between these positions. A pin on the side of the breaker engages a ramped cam in the switchgear cubicle. When the pin is lifted 3/8" the breaker is held tripfree.

An additional interlock holds the breaker trip-free whenever the access door to the racking mechanism is open.

Contact Interlock

The contact interlock keeps the door to the draw-out mechanism racking screw closed whenever the breaker contacts are CLOSED. This prevents changes to the breaker’s position with the main contacts CLOSED.

Spring Discharge Interlock

The spring discharge interlock functions in conjunction with the circuit breaker’s draw-out interlock and a compartment-mounted cam to discharge the closing and opening springs before the breaker can be withdrawn from the compartment.

4.4 Equipment Interlocks

Additional optional interlocks may be furnished with the breaker enclosure. The Key Interlock prevents the breaker from closing when the interlock is engaged and requires one or more keys to operate. The Door Interlock prevents opening of the enclosure door when the breaker is in the CONN position. It can be defeated for authorized access. The door can be opened by racking the breaker to the TEST or DISC position.

8

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 4. Breaker Operation

Figure 2. Elementary diagram of the breaker control circuits.

Figure 3. Location of the secondary disconnect (top view of the breaker).

9

EntelliGuard™ 800–2000 A Power Circuit Breakers

Chapter 4. Breaker Operation

10Aux Switch (NO contact) 1 Aux Switch

2 Aux Switch

11Aux Switch (NC contact)

13 Flux Shifter

12 Flux Shifter common

5 Shunt Trip

7 Shunt Trip common

9 Close Circuit

18 Close Circuit common

8 Closing Spring Charging Motor

17 Closing Spring Charging Motor common

3Remote Charge Indicator

4Remote Charge Indicator

14 Bell Alarm Trip

6 Bell Alarm Trip Common

16 Bell Alarm Status

19Bell Alarm Status Comon OR

15Network Interlock SET

20Network Interlock RESET

21Network Interlock SET/RESET common

16Network Interlock Status

19 Network Interlock Status common

22OFLO (phase A)

23OFLO (phase A)

24OFLO (phase B)

25OFLO (phase B)

26OFLO (phase C)

27OFLO (phase C)

28Spare

29Spare

30Spare

31Spare

32Spare

33Spare

34Spare

35Spare

36Spare

Table 4. Secondary disconnect terminals with standard and optional connections.

10

Loading...
+ 44 hidden pages