Bosch D344-RT Installation Manual

5 (1)
Bosch D344-RT Installation Manual

Installation Instructions

for the

D344-RT Remote Test Kit

1.0Overview

Use the D344-RT Remote Test Kit with the D340 Series Duct (D340, D341, D342, and D343) Smoke Detector Housings.

The D344-RT includes:

Test coil with wiring harness (1)

Mounting screws (4 for the D307 Remote Test Indicator Plate, 1 for the test coil)

D307 Remote Test Indicator Plate (1). This plate contains LED indicators to determine the detector’s status and condition. The D307 also has a keyswitch to remotely test and reset the detector, and an indicator to read and test the sensitivity voltage. Refer to Figure 1.

Figure 1: D307 Remote Test Indicator Plate

1

2

3

1

1

4

1 - Mounting holes (4)

2 - LED status and condition indicators

3 - Normal, test, and reset keyswitch

4 - Sensitivity voltage indicators

2.0Installation

1.Ensure the D340 Series Housing you are using is installed according to the appropriate installation instructions:

D340 Installation Instructions (P/N: 48188)

D341/D342 Installation Instructions (P/N: 48196)

D343 Installation Instructions (P/N: 48199)

2.Ensure the detector is in proper working order.

3.Insert the test coil under the smoke detector base, rotating the coil into position as shown in Figure 2 on page 2.

4.Using one of the mounting screws, attach the test coil to the smoke detector base (refer to Figure 3 on page 2).

5.Install the smoke detector head.

6.Connect the wiring harness.

a.Attach the connector with three wires to the smaller connector from the D340 Series Power Card (refer to Figure 4 on page 2).

b.Attach the connector with one wire to the connector located on the side of the detector head.

7.Connect the D307 according to the D307 Installation Instructions (P/N: 32071).

3.0Specifications

Table 1: Specifications

 

 

Voltage Requirements

24 VDC

 

 

Current Draw

10 mA at 24 VDC, Standby

 

20 mA at 24 VDC, Alarm

 

140 mA at 24 VDC, Test Mode

Operating Temperature

-22°F to +130°F (-30°C to +54°C)

Range

For UL Listed requirements, the operating

 

temperature range is +32°F to +100°F

 

(0C° to +38°C).