D7052
Installation Instructions
EN Multiplex Dual Input
Module
D7052 | Installation Instructions | Notices
Notices
These instructions cover the installation of the D7052 Multiplex Dual Input Module in a fire system supervised by a D7024 or DS9400M Fire Alarm Control Panel (FACP) with firmware revision 2.0 or greater and a D7039 or DS9431 Multiplex Expansion Module.
Install, test, and maintain the D7052 according to these instructions, NFPA 72, local codes, and the Authority Having Jurisdiction (AHJ).
Follow the procedures in these instructions to avoid personal injury and damage to equipment. Failure to follow these instructions can cause the D7052 to not operate properly. Bosch is not responsible for improperly installed, tested, or maintained devices.
Test the FACP according to NFPA 72.
1.0Description
The D7052 (Figure 1) is a general purpose module that connects to the multiplex bus of the control panel. It provides two supervised Class “B” input zones or one Class “A” input zone. Use a jumper pin setting for a Class “A” or Class “B” wiring configuration.
All operating power for the D7052 is drawn from the control panel. Rotary switches provide convenient address setting.
An on-board Status LED, visible through the faceplate, indicates normal operation and communication with the control panel. The LED flash rates are:
•Fast: Approximately 4 sec indicating an alarm condition.
•Medium: Approximately 8 sec indicating a normal operation.
•Slow: Approximately 16 sec indicating a trouble condition.
The D7052 can be mounted in a standard double-gang or a 4 in. x 4 in. electrical box.
Figure 1: |
D7052 Features |
|
|
|||
|
|
|
|
1 |
|
|
|
|
|
|
|
|
2 |
4 |
|
|
|
|
|
3 |
|
0 1 |
A |
9 |
0 1 |
9 |
0 1 |
|
|
2 |
8 |
2 |
8 |
2 |
|
|
0 |
||||
|
2 1 |
7 |
3 |
7 |
3 |
|
|
B |
6 5 4 |
6 |
5 4 |
5
1 - Status LED
2 - Class “A” and Class “B” jumper pins
3 - MUX bus loop terminals
4 - Zone input terminals
5 - Rotary address switches
2.0Setting the Address
Set the D7052 address using a flat-blade screwdriver to position each rotary switch located on the front of the module (Figure 2). Note that the switches click when turned.
Figure 2: Setting the Address |
|
|
|
|||
|
0 1 A |
9 |
0 1 |
9 |
0 1 |
|
|
2 |
8 |
2 |
8 |
2 |
|
|
0 |
7 |
3 |
7 |
3 |
|
|
2 1 B |
6 5 4 |
6 5 4 |
|
||
|
1 |
|
2 |
|
3 |
|
1 - |
Hundreds |
2 - |
Tens |
|
3 - |
Ones |
|
A = D7024 FACP, B = DS9400M FACP |
|
||||
For example: |
|
|
|
|
|
|
0 hundreds, 9 tens, 5 ones = Address 095 on the |
||||||
|
|
|
D7024 FACP |
|
The valid address range is 9 to 255. Refer to the D7024 Operation and Installation Guide (P/N: 31499) or the
DS9400M Reference Guide (P/N: 44578) for additional address limitations.
The D7052 requires two program addresses. The address cannot be 8 or a multiple of 8, such as 16, 24, 32, and so on.
2 |
Bosch | 11/04 | 48709F |
|
|
|
|
D7052 | Installation Instructions | 3.0 |
Wiring |
||||||
|
The A address range works on the D7039 |
Figure 4: |
Class “B” Wiring Connections |
|
|||||||
|
Multiplex Expansion Module with the D7024 |
|
|
|
|
|
|
|
|
||
|
FACP. The B address range works on the |
|
|
|
|
|
|
|
|
||
|
DS9431 Multiplex Expansion Module with |
|
|
|
|
|
|
|
|
||
|
the DS9400M FACP. |
|
|
|
|
|
|
|
|
|
|
Figure 2 on page 2 shows the input address set at 095. |
|
|
|
|
|
4 |
|
|
|||
The second input address will be set to the next |
|
|
|
|
2 |
|
|
||||
|
|
|
|
|
|
|
|||||
consecutive address, 096. Because the hundreds address |
|
|
|
|
5 |
|
|
||||
|
1 |
|
|
|
|
|
|||||
is within the input address range, it works on the D7039 |
|
|
|
|
4 |
|
|
||||
with the D7024 FACP. |
|
|
|
|
|
3 |
|
|
|||
|
|
|
|
|
|
|
5 |
|
|
||
3.0 |
Wiring |
|
|
|
|
|
|
0 1 |
A |
||
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
0 |
|||
|
|
|
|
|
|
|
|
|
|
2 |
|
|
|
|
|
|
|
|
|
|
2 1 |
B |
|
|
Remove all power before making electrical |
|
|
|
|
|
|
|
|
||
|
connections. Failure to do so can result in |
|
|
|
|
|
|
|
|
||
|
personal injury and damage to the |
|
|
|
|
|
|
|
|
||
|
equipment. |
|
1 - |
2.21 kΩ end-of-line (EOL) resistor, UL Listed |
|||||||
|
|
|
|||||||||
|
Use normally-open (NO) contacts for |
|
(P/N: 25899) |
|
|
|
|||||
|
2 - |
Input Zone 1 |
|
|
|
||||||
|
Underwriters Laboratories, Inc. (UL) Listed |
|
|
|
|||||||
|
3 - |
Input Zone 2 |
|
|
|
||||||
|
fire installations. |
|
|
|
|
||||||
The wiring connections are made using the terminals on |
4 - |
Zone in |
|
(+) |
|
|
|
||||
5 - |
Zone in (-) |
|
|
|
|||||||
either side of the D7052 (refer to Figure 1 on page 2). All |
|
|
|
||||||||
Note: The maximum zone wire resistance = 100 Ω |
|
||||||||||
terminals can accommodate up to and including |
|
||||||||||
|
|
|
|
|
|
|
|
||||
12 AWG (2.3 mm) wire. Follow the wiring guidelines as |
Figure 5: |
Loop and Control Panel Wiring |
|
||||||||
specified by NFPA-70 and the local AHJ. |
|
||||||||||
All wiring is power limited and supervised. Refer to |
|
|
Connections |
|
|
|
|||||
|
|
|
|
|
|
|
|
||||
Figure 3 and Figure 4 for the two types of wiring |
|
|
|
|
1 |
2 |
3 |
|
|||
connections. |
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|||
Ensure the D7052 is correctly configured for Class “A” |
|
|
|
|
|
|
|
|
|||
or Class “B.” Refer to Figure 5 for jumper settings. |
|
|
|
|
|
|
|
|
|||
Figure 3: Class “A” Wiring Connections |
|
|
|
|
|
4 |
|
|
|||
|
|
|
|
|
|
|
|
6 |
|
||
|
|
|
|
|
|
|
|
5 |
|
||
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
4 |
7 |
|
|
|
|
|
|
|
|
|
|
5 |
|
||
|
|
|
|
|
9 |
0 |
1 |
|
|
||
|
|
|
|
|
8 |
|
2 |
|
|
|
|
|
1 |
|
|
|
7 |
|
3 |
|
|
|
|
|
|
|
|
6 5 4 |
|
|
|
||||
|
|
|
|
|
|
|
|
||||
|
2 |
|
|
|
|
|
|
|
|
|
|
|
1 |
|
|
|
|
|
|
|
|
|
|
|
2 |
0 1 A |
1 - |
Class “A” and Class “B” jumper pins |
|
||||||
|
|
|
|||||||||
|
|
2 |
2 - |
Class “B” |
|
|
|
||||
|
|
0 |
|
|
|
||||||
|
|
2 1 B |
|
|
|
||||||
|
|
|
3 - |
Class “A” |
|
|
|
||||
|
|
|
4 - |
MUX bus loop (+) |
|
|
|
||||
|
|
|
5 - |
MUX bus loop (-) |
|
|
|
||||
1 - |
Zone in (+) |
2 - Zone in (-) |
6 - |
To next device |
|
|
|
||||
7 - |
From previous device, the D7039, or the DS9431 |
||||||||||
Note: The maximum zone wire resistance = 100 Ω |
|||||||||||
|
|
|
|
|
|
|
|
Bosch | 11/04 | 48709F |