D8129
Installation and Operation Guide
EN Octo-relay Module
D8129 | Installation and Operation Guide | 1.0 G Series Control Panels |
EN | 2 |
|
|
1.0G Series Control Panels
Use the D8129 Octo-relay Module to add programmable relay outputs to the system in groups of eight to the
G Series Control Panels (D9412GV4, D7412GV4, D7212GV4, D9412GV3, D7412GV3, D7212GV3, D9412GV2, D7412GV2, D7212GV2, D9412G, D7412G, D7212G), the D9124 control panel, and the new
G Series control panels (B9512G, B8512G).
The new G Series panels (B9512G, B8512G) require the B600 Retrofit (ZONEX) Module to use the B8129.
On the B9512G, D9412GV4, D9412GV3, D9412GV2, and D9412G, you can add up to 128 Octo-relay outputs (relay numbers 1 to 128) to the system using 16 D8129 Modules. The B8512G, D7412GV4, D7412GV3, D7412GV2, and D7412G allow up to 64 relay outputs. Review the control panel installation and compliance documents to determine the number of D8129 modules each panel can support and any power requirements and limitations.
The D7212GV4, D7212GV3, D7212GV2, and D7212G support up to 24 output relays (3 D8129 Modules).
The D8129 Modules for relay numbers 1 to 64 connect to ZONEX 1. The D8129 Modules for relay numbers 65 to 128 connect to ZONEX 2. Refer to Figure 1 and Figure 2 on page 3.
The D8129 outputs can be assigned functions individually. Functions include alarm, auxiliary relay, sensor reset, arming status, and point status. Review the control panel installation or programming documents, or RPS help for complete programming details.
The D8129 relay outputs are not supervised and cannot be used for the primary indication device
in commercial fire applications.
It is possible for relay outputs to activate while setting the D8129 switches, or changing the control panel programming. You can disconnect the equipment connected to relay
outputs when performing these functions.
1.1Specifications
Table 1: Specifications
|
|
|
|
|
|
|
|
Voltage |
|
Nominal 12 VDC |
|
||
|
Current |
|
130 mA maximum |
|
||
|
|
|
|
|
|
|
|
Wiring |
|
UL864 Control Panel Wiring Connection |
|||
|
|
|
Requirements |
|
||
|
|
|
Maximum Wire Resistance: 0.1 Ω |
|||
|
|
|
Maximum Distance |
|
Wire Size |
|
|
|
|
5 ft |
|
22 AWG |
|
|
|
|
5 ft |
|
18 AWG |
|
|
|
|
1.5 m |
|
0.6 mm |
|
|
|
|
1.5 m |
|
1.0 mm |
|
|
|
|
Non-UL864 Control |
Panel Wiring |
||
|
|
|
Connection Requirements |
|||
|
|
|
Maximum Wire Resistance: 4 Ω |
|||
|
|
|
Maximum Distance |
|
Wire Size |
|
|
|
|
200 ft |
|
22 AWG |
|
|
|
|
200 ft |
|
18 AWG |
|
|
|
|
60 m |
|
0.6 mm |
|
|
|
|
60 m |
|
1.0 mm |
|
|
Relay |
|
Resistive Load |
Voltage |
‒ 5-24 VDC |
|
|
Output |
|
Maximums |
|
|
|
|
(Form |
|
|
Current ‒ 1 mA - 1 Amp |
||
|
“C” dry |
|
|
|
|
|
|
contact) |
|
During pulsed |
operation, the relay will maintain |
||
|
|
|
closure for minimum of 1 sec. |
|
1.2Configuration
Five D8129 switches determine the relay numbers for the eight relay outputs. Table 2 shows the switch settings.
Table 2: DIP Switch Settings
|
|
|
|
|
|
|
|
Relay |
|
DIP Switch Setting |
|
Control Panel or |
|
|
Number |
|
|
B600 Connection |
|
|
|
|
|
|
|
||
|
1 to 8 |
|
OFF-ON-ON-ON-ON |
|
ZONEX 1 |
|
|
9 to 16 |
|
ON-OFF-ON-ON-ON |
|
ZONEX 1 |
|
|
17 to 24 |
|
OFF-OFF-ON-ON-ON |
|
ZONEX 1 |
|
|
25 to 32 |
|
ON-ON-OFF-ON-ON |
|
ZONEX 1 |
|
|
33 to 40 |
|
OFF-ON-OFF-ON-ON |
|
ZONEX 1 |
|
|
41 to 48 |
|
ON-OFF-OFF-ON-ON |
|
ZONEX 1 |
|
|
49 to 56 |
|
OFF-OFF-OFF-ON-ON |
|
ZONEX 1 |
|
|
57 to 64 |
|
ON-ON-ON-OFF-ON |
|
ZONEX 1 |
|
|
65 to 72 |
|
OFF-ON-ON-ON-ON |
|
ZONEX 2 |
|
|
73 to 80 |
|
ON-OFF-ON-ON-ON |
|
ZONEX 2 |
|
|
81 to 88 |
|
OFF-OFF-ON-ON-ON |
|
ZONEX 2 |
|
|
89 to 96 |
|
ON-ON-OFF-ON-ON |
|
ZONEX 2 |
|
|
97 to 104 |
|
OFF-ON-OFF-ON-ON |
|
ZONEX 2 |
|
|
105 to 112 |
|
ON-OFF-OFF-ON-ON |
|
ZONEX 2 |
|
|
113 to 120 |
OFF-OFF-OFF-ON-ON |
|
ZONEX 2 |
|
|
|
121 to 128 |
|
ON-ON-ON-OFF-ON |
|
ZONEX 2 |
|
Bosch Security Systems, Inc. | 11/15 | F01U036302-09
D8129 | Installation and Operation Guide | 1.0 G Series Control Panels |
EN | 3 |
|
|
Figure 1: D8129 Connections to the D9412GV2, D9412G, D9124
|
|
|
|
Reset Pin |
4 |
|
|
|
|
|
|
|
|
|
|
|
Disable All Except Battery |
|
|
GND |
|
|
|
|
2 |
||
|
|
|
Charging And Programming |
|
|
|
|
|
|
||||
|
|
|
PERIPHERAL DEVICE CONNECTIONS |
|
|
AU |
|
|
|
|
|||
|
|
|
RED |
POWER + |
32 |
|
|
DATA |
|
|
|
|
|
|
|
|
YELLOW |
DATA BUS A |
31 |
4 |
1 |
2 |
3 |
4 |
5 |
6 |
7 8 |
|
|
|
GREEN |
DATA BUS B |
30 |
||||||||
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
BLACK |
COMMON 29 |
|
|
|
|
|
|
|
|
|
|
|
|
N.F.P.A. |
ZONEX OUT 1 |
28 |
|
4 |
|
|
|
|
|
|
|
|
|
Style 3.5 |
|
|
|
|
|
|
|
|||
|
|
|
Signaling |
|
|
|
|
|
|
|
|
|
|
|
|
|
Line |
|
27 |
|
|
|
|
|
|
|
|
|
|
|
Circuits |
ZONEX IN 1 |
|
|
|
|
|
|
|
|
|
|
1 |
|
|
ZONEX OUT 2 26 |
|
|
|
|
|
|
|
|
|
|
|
|
ZONEX IN 2 25 |
|
Note: Do not loop wires |
|
|
|
|||||
|
|
|
|
ZONEX POWER + 24 |
|
|
around the terminals. |
|
|
||||
|
|
|
|
ZONEX COMMON 23 |
|
|
|
|
|
|
|
|
|
|
|
|
Detect |
Monitor Normal Ringing |
PROG |
|
|
|
|
|
|
|
|
|
|
|
Point 8 |
|
4 |
|
|
|
|
|
|
|
|
|
|
GND FAULT |
|
CONN |
|
|
|
|
|
|
3 |
||
|
|
A |
S |
Operation When When |
|
|
GND |
|
|
|
|
||
|
|
E |
DI |
|
|
|
|
|
|
|
|||
|
|
B |
A |
|
|
|
AU |
|
|
|
|
|
|
|
|
N |
|
GRN PulsesFlickers |
|
|
|
DATA |
|
|
|
|
|
21 |
22 |
E |
L |
|
|
|
|
|
|
|
|
||
|
|
L |
B |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 8 |
1 - Control Panel |
4 - Power limited |
2 - ZONEX 1 Connection (Relays 1 to 64) - connect multiple D8129 modules in parallel.
3 - ZONEX 2 Connection (Relays 65 to 128) - connect multiple
D8129 modules in parallel.
Figure 2: D8129 Connections to the D7412GV2, D7212GV2, D7412G, D7212G
RED |
Low Battery |
1 |
|
Pin |
Battery |
||||
|
|
|
amming |
|
|
|
|
E CONNECTIONS |
|
1 |
CLASS 2 TRANS |
POWER + |
32 |
|
16.5 VAC 40 VAC |
||||
|
Part No. D1640 |
|
|
|
|
Internally Fuse |
|
|
31 |
2 |
Requires Unsw |
DATA BUS A |
||
Do Not Share |
|
|||
3 |
+ AUX PO |
|
DATA BUS B |
30 |
4 |
BATTERY N |
|
COMMON 29 |
|
|
Maximum Charging |
|
|
|
|
Current 1.4 Amps. |
ZONEX OUT 1 28 |
||
5 |
BATTERY POSITIVE ONLY |
|||
6 |
RELAY A |
PR |
ZONEX IN 1 27 |
|
AL |
||||
7 |
RELAY B |
Re |
|
|
|
|
|
|
8RELAY C
9COMMON
10 EARTH GRO
GROUND FAUL
PROG
CONN
3
3
3
|
GND |
|
|
|
|
2 |
|
AU |
|
|
|
|
|
|
DATA |
|
|
|
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 8 |
1 - |
Control Panel |
3 - Power limited |
2 - |
ZONEX 1 Connection for Relays 1 to 64 (1 to 24 for |
|
|
D7212GV2/D7212G). Connect multiple D8129 modules in |
|
|
parallel. |
|
Bosch Security Systems, Inc. | 11/15 | F01U036302-09