Omron CS1, C200HW-NC413, C200HS, C200HW-NC113, C200HW-NC213 DATASHEET

0 (0)

CS1 Series, C200HX/HG/HE, C200HS, C200H

C200HW-NC113, C200HW-NC213, and C200HW-NC413

Position Control Unit

Specification Sheets

Omron CS1, C200HW-NC413, C200HS, C200HW-NC113, C200HW-NC213 DATASHEET

Product Specifications

C200H Special I/O Unit

CS1 Series, C200HX/HG/HE, C200HS, C200H

Position Control Unit

C200HW-NC113, C200HW-NC213, and C200HW-NC413

One-axis, Two-axis, and Four-axis Postion Control Units Capable of Memory Operation or Direct Operation

The C200HW-NC113, C200HW-NC213, and C200HW-NC413 are one-axis, two-axis, and four-axis Position Control Units for the CS1-Series, C200HX/HG/HE, C200HS, and C200H PCs. These Units receive instructions from the CPU Unit and output pulses to various motor drivers for positioning.

 

 

 

 

 

 

 

 

 

Memory operation

 

 

 

 

 

 

 

 

 

 

 

Position control

 

 

 

 

Direct operation

Position

 

 

 

 

 

 

 

 

Interrupt feeding

 

 

 

 

 

 

 

 

 

Control

 

 

 

 

 

 

 

 

 

Unit

 

 

Speed control

 

 

 

 

operations

 

 

 

 

 

Origin search

 

 

 

 

 

 

 

 

 

 

 

 

Other operations

 

 

 

 

Jogging

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Teaching

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Override

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Present position change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Backlash compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zone setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Deceleration stop

 

 

 

 

 

 

 

 

 

Features

Memory Operation and Direct Operation

Operation can be controlled through memory operation, where data for positioning is transferred to the Position Control Unit and then specified for position control, or through direct operation, where target positions and speeds are set each time from the CPU Unit. Combining these methods is also possible, allowing a Position Control Unit to perform flexible positioning operations ranging from easy to complicated.

C200HW-

NC113/NC213/NC413

Independent

System

Automatic Configuration

Example

Continuous

Servo Relay Unit

Input

Pulse Input

Servodriver

Servomotor

Various Basis Functions

The C200HW-NC113, C200HW-MC213, and C200HW-413 support various basic functions, such as origin searches, interrupt feeding, speed controls, jogging, teaching, overrides (speed coefficients), backlash compensation, present position changes, zone settings, and deceleration stops.

Memory Operation Position Control Unit

CPU Unit

Data transfer bits

Position data

Speed data Start sequence No. specification

Direct Operation

Position Control Unit

CPU Unit

Data transfer bits

Position data Speed data Direct start command

Enhanced Functions

The C200HW-NC113, C200HW-MC213, and C200HW-413 support the following functions that the previous models (C200HNC211 and C200H-NC112) do not support.

Direct operation is possible.

S-curve acceleration/declaration is possible in addition to trapezoidal acceleration/declaration.

Speed control is possible.

Backlash compensation speed can be specified.

Forced intervention is possible (specified position data can be forcibly executed).

Flash memory operation is possible.

ªProgrammable Controllerº is abbreviated as ªPCº in theseSpecification Sheets.

1

Position Control Unit

Product Specifications

 

 

Compact Size

The single-axis, two-axis, and four-axis models are all one compact size.

Special Support Software for CS1-Series and C200HX/HG/HE PCs)

Special Support Software, the SYSMAC-NCT, which runs on Windows 95, allows the user to easily create various data for the Position Control Unit. It can also be used for writing data to the PCU, reading data from the PCU, saving data, and printing data.

Easy Data Transfer

Position data used for memory operation can be transferred to the Position Control Unit by using the NC Support Software (for CS1-Series and C200HX/HG/HE PCs only), data transfer bits, and the Intelligent I/O Write (IOWR) and Intelligent I/O Read (IORD) instructions (for CS1-Series and C200HX/HG/HE PCs only).

ROM Operation by Flash Memory

Position data used for memory operation can be stored in the flash memory in the Position Control Unit. It is retained even when the power is turned OFF. So, there is no need for battery maintenance.

Models

Applicable PCs

Unit classification

Number of control axes

Controlled driver

Model number

 

 

 

 

 

CS1, C200HX/HG/HE,

C200H Special I/O Unit

1 axis

Pulse-train input driver or

C200HW-NC113

C200HS, and C200H

 

 

stepping motor driver

 

 

2 axes

C200HW-NC213

PCs

 

 

 

 

 

 

 

4 axes

 

C200HW-NC413

 

 

 

Support Software (Sold Separately)

Name

System requirements

Applicable PCs

Specifications

Model

 

 

 

 

 

 

SYSMAC-NCT

Personal computer: IBM AT or

CS1-Series and

Creating

WS01-NCTF1-E

 

 

compatible

C200HX/HG/HE

positioning data

 

 

 

Operating system: Windows 95

PCs only

and parameter

 

 

 

(Cannot be used

data, transferring

 

 

 

Minimum memory: 16 MB

 

 

 

with C200H or

data to the Unit,

 

 

 

Available disk space: 10 MB min.

C200HS PCs.)

writing data to

 

 

 

 

the flash

 

 

 

 

 

 

 

 

 

 

memory, and

 

 

 

 

 

printing Unit

 

 

 

 

 

status monitor

 

 

 

 

 

data, positioning

 

 

 

 

 

data, and

 

 

 

 

 

parameter data

 

 

 

 

 

 

 

 

Connecting

For connecting the RS-232C port on

2.0 m, 5.0 m

 

XW2Z-

 

Cable

the CPU Unit

 

 

(For details, refer

 

 

 

 

 

 

 

 

 

 

to optional

 

 

 

 

 

parts.)

Specifications

Item

 

Specifications

 

 

 

 

 

 

 

 

 

 

C200HW-NC113

C200HW-NC213

C200HW-NC413

 

 

 

 

 

 

Applicable PCs

 

CS1-Series, C200HX/HG/HE, C200HS, C200H

 

 

 

 

 

 

Unit classification

C200H Special I/O Unit

 

 

 

 

 

Mounting location

CPU Rack, C200H Expansion I/O Rack, CS1 Expansion Rack, SYSMAC BUS Remote I/O Slave Unit

 

 

 

 

Maximum number of Units

16 or 10 Units depending on the CPU Unit model (refer to

8 or 5 Units depending on the

that can be mounted

Connectable CPU Unit Models).

 

CPU Unit model (refer to

 

 

 

 

 

Connectable CPU Unit Models).

 

 

 

 

 

Unit numbers

 

0 to F or 0 to 9 depending on the CPU Unit model (refer to

0 to 8, or 0 to 8 and A to E

 

 

 

Connectable CPU Unit Models).

 

depending on the CPU Unit

 

 

 

 

 

model (refer to Connectable

 

 

 

 

 

CPU Unit Models).

 

 

 

 

 

 

Data

 

Words

5 words/Unit

10 words/Unit

20 words/Unit

exchange

 

allocated in

 

 

 

 

CPU Unit → Position Control Unit: Operating commands (sequence numbers, start, origin search, etc.)

area with

 

the Special

 

Position Control Unit → CPU Unit: Status (positioning completed, present position, etc.)

CPU Unit

 

I/O Unit Area

 

 

 

 

 

 

 

 

DM area

100 words/Unit

 

 

 

 

words

 

 

 

 

 

allocated to

CPU Unit → Position Control Unit: Common parameters and axis parameters (I/O selection, operation

 

 

Special I/O

mode selection, start speed, origin search speed, acceleration/deceleration time, etc.)

 

 

Units

 

 

 

Controlled driver

Pulse-train input type Servodriver or stepping motor driver

 

 

 

 

Control

 

Control

Open-loop control by pulse train output (automatic trapezoidal or S-curve acceleration/deceleration)

 

 

system

 

 

 

 

 

 

 

 

 

 

 

Number of

1 axis

2 axes

4 axes

 

 

control axes

 

 

 

 

 

 

 

 

 

Control unit

 

Pulse

 

 

2

 

Product Specifications

 

Position Control Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

Specifications

 

 

 

 

 

 

 

 

 

 

C200HW-NC113

C200HW-NC213

C200HW-NC413

 

 

 

 

 

 

 

 

Positioning operations

Two types: Memory operation and direct operation

 

 

 

 

Memory operation: Transfers sequence data such as position data and speed data to the Position

 

 

 

Control Unit beforehand, and executes positioning in ascending order of sequence numbers by

 

 

 

specifying the start sequence number from the CPU Unit.

 

 

 

 

Completion code of each sequence for memory operation: Independent, automatic, continuous, bank

 

 

 

end, speed control (continuous output), or interrupt feeding (continuos output with positioning) can be

 

 

 

specified.

 

 

 

 

 

Direct operation: Writes position data and speed data to the specified area in the CPU Unit and

 

 

 

executes positioning by outputting the data to the Position Control Unit through I/O refresh.

 

Speed control and interrupt feeding are also possible.

 

Independent

1 axis

2 independent axes

4 independent axes

 

 

 

 

 

 

Linear

±

2 axes max.

4 axes max.

 

interpolation

 

 

 

 

 

 

 

 

 

Speed control

1 axis

2 independent axes

4 independent axes

 

 

 

 

 

 

Interrupt

1 axis

2 independent axes

4 independent axes

 

feeding

 

 

 

 

 

 

 

 

Positions

Range

±9,999,999 to 9,999,999 pulses

 

 

 

Data items

100/axis

 

 

 

 

 

 

 

Speeds

Range

1 pps to 500 Kpps

 

 

 

 

 

 

 

 

Data items

100/axis

 

 

 

 

 

 

Acceleration

Range

0 to 250 s, until maximum speed is reached.

 

and

 

 

 

 

deceleration

Data items

9/axis for acceleration and deceleration each.

 

times

 

 

 

 

 

 

 

 

 

 

3

 

Position Control Unit

 

 

 

Product Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

Specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C200HW-NC113

 

C200HW-NC213

 

C200HW-NC413

 

 

 

 

 

 

 

 

 

 

 

 

Functions

 

Origin search

Origin proximity input signal: selectable (absent, N.O. or N.C. contact).

 

 

 

 

 

 

Origin input signal: selectable (N.O. or N.C. contact)

 

 

 

 

 

 

Origin compensation: ±9,999,999 to 9,999,999 pulses

 

 

 

 

 

 

Origin search speed: High-speed or proximity-speed can be set.

 

 

 

 

 

 

Origin search method: May be set to stop upon origin input signal after proximity input signal has turned

 

 

 

 

 

ON, to stop upon origin input signal after proximity input signal has turned OFF, to stop upon origin input

 

 

 

 

 

signal without using proximity input signal, or to stop upon origin input signal after limit input signal has

 

 

 

 

 

turned OFF.

 

 

 

 

 

 

 

 

 

N.O. = Normally open

 

 

 

 

 

 

 

 

 

N.C. = Normally closed

 

 

 

 

 

 

 

Origin search

0

 

Stepping motors are used and external sensor signals are used as origin input signals. In

 

 

 

 

operation

(Mode 0)

this case, error counter reset output and origin-adjustment command output can be used

 

 

 

 

mode

 

 

as general-purpose outputs.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Servodrivers are used and encoder phase-Z signals are used as origin input signals. The

 

 

 

 

 

(Mode 1)

Servodriver's positioning completed signals are not used.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

Servodrivers are used and encoder phase-Z signals are used as origin input signals. The

 

 

 

 

 

(Mode 2)

Servodriver's positioning completed signals are used.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Servodrivers such as OMRON H-Series and M-Series are used. The Servodriver's

 

 

 

 

 

(Mode 3)

origin-adjustment command is used to complete origin search. The Servodriver's

 

 

 

 

 

 

 

positioning completed signals are used.

 

 

 

 

 

 

 

 

 

 

 

 

 

Jogging

Jogging can be executed at a specified speed.

 

 

 

 

 

 

 

 

 

 

 

 

Dwell times

19/axis can be set from 0 to 9.99 s (unit: 0.01 s).

 

 

 

 

 

 

 

 

 

 

 

 

Acceleration/

Trapezoidal or S-curve (Can be set separately for each axis.)

 

 

 

 

 

deceleration

 

 

 

 

 

 

 

 

 

 

 

curves

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Zones

Zone Flag turns ON when present position is within a specified zone. Three zones can be set for each

 

 

 

 

 

axis.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Software limit

Can be set within a range of ±9,999,999 to 9,999,999 pulses.

 

 

 

 

 

 

 

 

 

 

 

 

Backlash

0 to 9,999 pulses. Compensation speed can also be set.

 

 

 

 

 

compensation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Teaching

With a command from the CPU Unit, the present position can be taken as the position data.

 

 

 

 

 

 

 

 

 

 

Forced

Stops the active sequence and executes the specified sequence No. (Valid during memory operation

 

 

 

 

intervention

only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Deceleration

The STOP command causes positioning to decelerate to a stop according to the specified deceleration

 

 

 

 

stop

time.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Present

The PRESENT POSITION CHANGE command can be used to change the present position to a

 

 

 

 

position

specified value.

 

 

 

 

 

 

 

change

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Override

When the override enabling command is executed during positioning, the target speed is changed by

 

 

 

 

 

applying the override coefficient.

 

 

 

 

 

 

 

 

 

 

 

 

 

Pulse output

Prohibits pulse output when emergency stop, CW limit, CCW limit, or CW/CCW software limit input

 

 

 

 

prohibited

turns ON.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data transfer

Various data can be transferred to the memory in the Position Control Unit, using either of the following

 

 

 

 

(data

methods:

 

 

 

 

 

 

 

 

 

 

read/write)

1) Data transfer bits

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2) Intelligent I/O Write (IOWR) and Intelligent I/O Read (IORD) instructions (for CS1-Series and

 

 

 

 

 

C200HX/HG/HE PCs only)

 

 

 

 

 

 

 

 

3) SYSMAC-NCT Support Software (for CS1 Series and C200HX/HG/HE PCs only)

 

 

 

 

 

 

 

 

 

 

 

Data saving

Various data can be saved in the internal flash memory.

 

 

 

 

 

 

If data is saved, the Position Control Unit can be operated using the saved data when it is turned ON or

 

 

 

 

 

restarted. There is no need to transfer data to the Unit each time.

 

 

 

 

 

 

Note: Flash memory life expectancy: 100,000 times (reads/writes)

 

 

4