Mitsubishi MSH-18NV- E4, MUH-18NV- E4 Service Manual

0 (0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Revision:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

●Information for connecting MSH-18NV- E4 with

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

MXZ-32RV- E1 was described.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

●TROUBLESHOOTING has been modified.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No. OB229

REVISED EDITION-A

SERVICE MANUAL

Wireless type

Model

MSH-18NV - E4 (WH) · MUH-18NV - E4

CONTENTS

1.TECHNICAL CHANGES ····································2

2.PART NAMES AND FUNCTIONS······················2

3.SPECIFICATION·················································4

4.OUTLINES AND DIMENSIONS ························ 5

5.WIRING DIAGRAM ············································6

6.REFRIGERANT SYSTEM DIAGRAM ················7

MSH-18NV - E4

7. PERFORMANCE CURVES ································8

8. MICROPROCESSOR CONTROL ····················10

9. SERVICE FUNCTIONS ····································19

10. TROUBLESHOOTING······································21

11. DISASSEMBLY INSTRUCTIONS·····················30

12.PARTS LIST··················································· ···34

13.OPTIONAL PARTS···········································37

•Refer to the Service Manual OB185 REVISED EDITION C when MSH-18NV- E4 is connected with MXZ-32NV- E1 or MXZ-32NV- E2 as multi system units.

•Refer to the Service Manual OB227 REVISED EDITION-B when MSH-18NV- E4 is connected with MXZ-32RV- E1 as multi system units.

1 TECHNICAL CHANGES

MSH-18NV- E4 became possible the connection to MXZ-32RV- E1 as multi system units.

2 PART NAMES AND FUNCTIONS

INDOOR UNIT

MSH-18NV - E4

Front panel

(When the grille is open)

2

OUTDOOR UNIT

MUH-18NV - E4

REMOTE CONTROLLER

MSH-18NV - E4

Signal transmitting section

Operation display section

OPERATE/STOP

(ON/OFF)button

OPERATION SELECT button

FAN SPEED CONTROL button

SLEEP button

ON-TIMER button

CLOCK SET button

HR. button MIN. button (TIMER SET button)

Air inlet (back and side)

Piping

Drainage hose

Air outlet

Drain outlet

TEMPERATURE buttons

VANE CONTROL button SWING button OFF-TIMER button RESET button

3

3

 

 

SPECIFICATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wRefer to the Service Manual OB185 REVISED EDITION C when MSH-18NV- E4

is connected with

 

MXZ-32NV- E1

or MXZ-32NV- E2

as multi system units.

 

 

 

 

 

 

 

 

 

wRefer to the Service Manual OB227 REVISED EDITION-B when MSH-18NV- E4

is connected with

 

MXZ-32RV- E1

as multi system units.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

 

 

 

 

MSH-18NV - E4

 

WMSH-18NV-

 

 

 

(INDOOR UNIT)

 

 

 

 

 

 

 

 

 

 

E4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

 

 

Cooling

 

Heating

Cooling

 

 

Heating

 

 

 

 

 

Power supply

 

 

Single phase,220-240V,50Hz

Single phase,220-240V,50Hz

 

 

 

 

 

Capacity

 

 

 

kW

5.1

 

5.4

 

 

 

 

Capacity

 

Dehumidification

 

 

 

R/h

2.5

 

 

 

 

 

 

 

 

 

Air flow(Hi)

 

 

 

K /h

INDOOR 756 OUTDOOR 2142-2244

756

 

 

 

 

 

 

 

Power outlet

 

 

 

A

 

15

 

10

 

 

 

 

 

 

 

Running current

 

 

 

A

9.4-9.2

 

9.2-9.0

0.28

 

 

 

 

 

 

 

Power input

 

 

 

W

2,030-2,120

 

1,980-2,070

60

 

 

 

 

 

 

 

Auxiliary heater

 

 

 

A(kW)

 

 

 

 

Electrical data

 

Power factor

 

 

 

%

98-96

 

98-96

97-89

 

 

 

 

 

 

Starting current

 

 

 

A

52-58

 

 

 

 

 

 

 

 

Compressor motor current

 

A

8.76-8.56

 

8.56-8.36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan motor current

 

A

INDOOR 0.25 OUTDOOR 0.39

0.25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Coefficient of performance(C.O.P)

 

 

 

 

2.51-2.41

 

2.73-2.61

 

 

 

 

 

 

 

Model

 

 

 

 

PH-36VPET

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

 

 

W

1600

 

 

 

 

 

 

 

 

Winding resistance(at20:)

 

"

C-R1.03 C-S2.04

 

 

 

 

 

Indoor

 

Model

 

 

 

 

RA4V27-EA or EF

 

RA4V27-EA or EF

 

fan motor

 

Winding resistance(at20:)

 

"

WHT-BLK183.8 BLK-RED250.5

WHT-BLK183.8 BLK-RED250.5

 

Outdoor

 

Model

 

 

 

 

RA6V50-OF or OG

 

 

 

fan motor

 

Winding resistance(at20:)

 

"

WHT-BLK116.4 BLK-RED111.0

 

 

 

 

 

 

 

 

 

Width

 

mm

1,015

 

1,015

 

 

 

 

 

 

Indoor unit

 

Height

 

mm

320

 

320

 

 

Dimensions

 

 

 

Depth

 

mm

190

 

190

 

 

 

 

 

Width

 

mm

850

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

Height

 

mm

605

 

 

 

 

 

 

 

 

 

 

Depth

 

mm

290

 

 

 

 

 

Weight

 

Indoor unit

 

 

 

kg

 

14

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

kg

 

54

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air direction

 

 

 

 

 

5

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound level

 

Indoor unit

 

dB

 

42

 

42

 

 

 

 

 

 

 

(Hi)

 

Outdoor unit

dB

 

52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan speed

 

Indoor unit

 

rpm

1,180

 

1,180

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Hi)

 

Outdoor unit

rpm

810-845

 

 

 

Special remarks

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan speed

 

Indoor unit

 

 

 

4

 

4

 

 

 

 

 

 

 

regulator

 

Outdoor unit

 

 

1

 

 

 

 

 

 

 

 

Refrigerant filling capacity(R-22)

 

kg

1.65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerating oil

(Model)

 

cc

900 (MS32N1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT11(at25:)

k"

 

10

 

10

 

 

 

 

 

 

 

Thermistor

 

RT12(at25:)

k"

 

10

 

10

 

 

 

 

 

 

 

 

 

RT61(at0:)

k"

33.18

 

 

 

NOTE:Test conditions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling : Indoor DB27°C / WB19°C

Heating : Indoor DB20°C /WB15.5°C

 

 

 

 

 

 

 

 

Outdoor DB35°C / WB24°C

 

Outdoor DB7°C / WB6°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

Mitsubishi MSH-18NV- E4, MUH-18NV- E4 Service Manual

4 OUTLINES AND DIMENSIONS

MSH-18NV - E4

INDOOR UNIT

995

1015

320

 

 

 

 

50

775

 

 

 

56

17.5

 

 

 

 

 

160

 

MUH-18NV - E4

 

 

OUTDOOR UNIT

 

 

Drainage

355

20

 

350

 

hole [16.2

 

 

 

Air in

 

 

35

 

 

 

 

248

90

 

 

 

Air in

 

 

 

Drainage

Air out

 

3holes [33

 

605

292

 

20

183

 

500

 

850

Unit: mm

 

 

4holes 11 20

Indoor unit

 

 

150

648

217

 

60

40

 

 

20

 

 

450

254

297

 

 

 

 

 

 

450

 

 

3

438 352

Installation plate

190

Air in

190

Air out

 

Wall hole [75

5

Installation plate

Liquid line [8-0.5m {Gas line [12-0.43m Insulation [50 O.D

[28 I.D

Drain hose [16

Insulation [28

Power supply cord

Lead to right 2m

Lead to left 1m

 

 

 

 

 

 

 

 

 

 

 

sides

 

 

 

 

 

 

or

right/left

 

only

 

 

 

 

front

 

top

has

.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unobstructed

 

 

 

vacant,

If

the

 

 

the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are

 

 

10cm

 

 

 

 

 

 

to

be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

290

310

345

50

30

157

100

If the right/left sides or back side is vacant, the front has only to be 50cm unobstructed.

Service panel

Liquid refrigerant pipe joint

Refregerant pipe (flared) [6.35

-

-

30

35

 

Gas refregerant pipe joint

161 Refregerant pipe (flared) [15.88

74

5

5 WIRING DIAGRAM

MSH-18NV - E4 MODEL WIRING DIAGRAM

INDOOR UNIT TO OUTDOOR

LTB BRN

 

 

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

CN

 

RT12

CONNECTING

 

BRN

 

 

 

 

 

 

HIC1

IC141

112

 

12VDC

3

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F12

 

 

 

 

 

 

 

 

3

 

 

 

 

BLU

 

 

 

 

 

NR11 C11

CN

BRN

 

N

 

2

BLU

1

4

TRANS

 

BLU

 

4

 

WHT MF

220-240V~2

 

WHT

BLU

 

 

CN201

52C

 

121

 

YLW

 

 

 

 

1

 

 

3

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

CN211

 

GRY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLU

BRN

 

 

 

 

 

F11

 

2

 

RED

 

 

 

 

 

 

 

 

 

BLK

POWER

 

 

 

GRN/YLW

LD1

 

 

 

 

 

1

 

 

 

DSAR

 

 

 

 

 

 

 

SUPPLY

 

 

CN

CN

 

CN

 

 

 

CN

 

RT11

CORD

 

 

 

 

101

102

 

151 ELECTRONIC CONTROL P.C BOARD

111

 

~/N 220-240V

 

 

 

 

 

 

5

 

 

 

 

 

 

50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3

 

 

 

 

 

 

 

 

 

 

GRN/YLW

MV

 

 

 

 

 

 

CIRCUIT BREAKER

 

RECEIVER

 

DISPLAY

 

 

 

 

 

 

 

P.C.BOARD

 

P.C.BOARD

 

 

 

 

 

 

FOR MULTI SYSTEM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

12VDC 3

 

 

 

 

 

 

 

 

 

 

 

 

TO OUTDOOR

 

2

 

REMOTE

 

 

 

 

 

 

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

N

 

CONTROLLER

 

 

 

 

 

 

 

 

CONNECTING

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYMBOL

NAME

SYMBOL

NAME

SYMBOL

NAME

C11

INDOOR FAN CAPACITOR

HIC1

DC/DC CONVERTER

RT12

INDOOR COIL THERMISTOR

DSAR

SURGE ABSORBER

MF

INDOOR FAN MOTOR(INNER FUSE)

TB

TERMINAL BLOCK

F11

FUSE(3.15A)

MV

VANE MOTOR

52C

CONTACTOR

F12

THERMAL FUSE(93:)

NR11

VARISTOR

 

 

IC141

HYBRID IC

RT11

ROOM TEMPERATURE THERMISTOR

 

 

NOTE:1. For the outdoor electric wiring refer to the outdoor unit electric wiring diagram for servicing.

2.Use copper conductors only.(For field wiring)

3.Symbols below indicate.

:Terminal block, : Connector

MUH-18NV - E4

MODEL WIRING DIAGRAM

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR UNIT

 

 

 

 

 

 

 

21S4

 

52C

 

 

 

 

 

 

 

 

 

 

 

RT61

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

BLK

 

VLT

VLT

 

 

 

 

 

 

 

 

TB

 

 

 

 

 

 

 

 

MF

 

 

 

 

 

CN730 CN661

 

 

 

 

 

 

 

 

 

 

 

12VDC

3

 

RED

CN721

 

CN720

 

 

 

 

 

 

 

 

 

 

 

1

F61

 

X62

 

 

 

 

 

 

 

 

 

 

FROM INDOOR UNIT CONNECTING

220-240V~2

 

WHT

 

 

 

SR61

C65

1

RED

1

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT

TAB21

IC881

 

NR61

 

 

2

WHT 2 ORN

 

 

 

N

 

 

 

 

 

 

 

3

 

3 WHT

 

 

 

BLU

 

TRANS

 

 

 

 

4

BLK 4 BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X62 CN711

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DSAR

TAB20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEICER P.C.BOARD

 

 

 

 

 

 

 

 

 

GRN/YLW

 

WHT NO 52C COM

 

WHT

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

C1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLU

 

 

RED

 

MC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

BLK

 

S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYMBOL

 

NAME

 

SYMBOL

 

NAME

 

 

SYMBOL

 

 

 

NAME

C1

COMPRESSOR CAPACITOR

 

MC

COMPRESSOR(INNER THERMOSTAT)

TB

 

TERMINAL BLOCK

C65

OUTDOOR FAN CAPACITOR

MF

OUTDOOR FAN MOTOR(INNER THERMOSTAT)

X62

REVERSING VALVE COIL RELAY

DSAR

SURGE ABSORBER

NR61

VARISTOR

21S4

REVERSING VALVE COIL

F61

FUSE(2A)

 

RT61

DEFROST THERMISTOR

52C

CONTACTOR

IC881

DC/DC CONVERTER

SR61

SOLID STATE RELAY

 

 

 

 

NOTE: 1. Use copper conductors only (For field wiring).

 

 

 

 

 

 

2. Symbols below indicate.

 

 

 

 

 

 

Sleeve

 

: Terminal block,

 

 

 

 

: Connector

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.Slide the sleeve.

3. “ ”show the terminals with a lock mechanism, so they cannot be removed when you pull

 

 

 

Locking lever

 

 

2.Pull the wire while

the lead wire.

 

 

 

 

 

 

 

 

 

 

pushing the locking

 

 

 

 

 

 

Be sure to pull the wire by pushing the locking lever (projected part) of the terminal with a finger.

 

 

 

 

 

 

lever.

 

 

 

 

 

 

 

 

 

 

 

 

6

6 REFRIGERANT SYSTEM DIAGRAM

MSH-18NV - E4

 

MUH-18NV - E4

 

 

 

 

 

 

 

OUTDOOR UNIT

INDOOR UNIT

Refrigerant pipe [15.88

Reversing valve

 

 

 

 

 

(Option)

(4- way valve)

 

(with heat insulator)

Indoor

Indoor coil

thermistor

heat

RT12

exchanger

Distributor

Flared connection

Muffler

 

 

Stop valve

Strainer

Outdoor

 

(with service port)

 

Defrost

heat

 

exchanger

 

thermistor

 

 

 

RT61

 

Room temperature

 

thermistor

 

RT11

Accumulator

 

Flared connection

Strainer

Stop valve

Refrigerant pipe[ 6.35 (Option)

(with heat insulator)

MAX. REFRIGERANT PIPING LENGTH

Compressor

Capillary tube [3.0o[2.0o500

Capillary tube [3.0o[1.6o750 (2 pcs)

Check valve

Reversing valve coil (4-way valve coil) Heating ON Cooling OFF

Refrigerant flow in cooling

Refrigerant flow in heating

 

Refrigerant piping

Piping size O.D : mm

Length of connecting pipe : m

Model

Max. length : m

 

 

 

 

 

A

Gas

Liquid

Indoor unit

Outdoor unit

MSH-18NV - E4

15

15.88

6.35

Gas 0.43

Gas 0

Liquid 0.5

Liquid 0

 

 

 

 

 

 

 

 

 

 

MAX. HEIGHT DIFFERENCE

Indoor unit

wMax. Height

Refrigerant Piping

difference: 5m

Max. Length

 

A

Outdoor unit

wHeight difference should be within 5m

regardless of which unit, indoor or outdoor position is high.

ADDITIONAL REFRIGERANT CHARGE(R-22 : g)

Model

Outdoor unit precharged

 

Refrigerant piping length (one way)

 

(up to 7m)

7m

 

10m

 

15m

 

 

 

MSH-18NV - E4

1650

0

 

150

 

400

Calculation : Xg=50g/m (A-7)m

7

7 PERFORMANCE CURVES

MSH-18NV - E4

The standard data contained in these specifications apply only to the operation of the air conditioner under normal conditions, since operating conditions vary according to the areas where these units are installed. The following information has been provided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.

(1) GUARANTEED VOLTAGE

Rated voltage : ±10% (198 ~ 264V), 50Hz

 

 

 

(2) AIR FLOW

 

 

 

Air flow should be set at MAX.

 

 

 

(3) MAIN READINGS

 

}

 

(1)

Indoor intake air wet-bulb temperature :

°CWB

 

(2)

Indoor outlet air wet-bulb temperature :

°CWB

Cooling

 

(3)

Outdoor intake air dry-bulb temperature :

°CDB

 

 

 

(4)

Total input:

W

}

 

(5)

Indoor intake air dry-bulb temperature :

°CDB

 

(6)

Outdoor intake air wet-bulb temperature :

°CWB

Heating

(7)

Total input :

W

 

Indoor air wet/dry-bulb temperature difference on the left side of the chart on this page and next page shows the difference between the indoor intake air wet/dry-bulb temperature and the indoor outlet air wet/dry-bulb temperature for your reference at service.

How to measure the indoor air wet-bulb/dry-bulb temperature difference

1.Attach at least 2 sets of wet-and dry-bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of wet-and dry-bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed is high.

2.Attach at least 2 sets of wet-and dry-bulb thermometers to the outdoor air intake. Cover the thermometers to prevent direct rays of the sun.

3.Check that the air filter is cleaned.

4.Open windows and doors of room.

5.Press the EMERGENCY OPERATION switch once(twice) to start the EMERGENCY COOL(HEAT) MODE.

6.When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.

7.10 minutes later, measure temperature again and check that the temperature does not change.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR UNIT

 

 

INDOOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wet-and dry-bulb thermometers

Wet-and dry-bulb thermometers

12.2

11.2

10.1

9.1

8.2

7.2

MSH-18NV - E4

8

28.0

25.9

23.7

21.6

19.4

17.2

15.1

12.9

MSH-18NV - E4

NOTE:The above curves are for the heating operation without any frost.

OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT COOL operation

1 Both indoor and outdoor unit are under the same temperature/humidity condition.

Dry-bulb temperature

Relative humidity(%)

 

 

20

50

 

 

25

60

 

 

30

70

 

 

2 Air flow should be set at MAX.

3The unit of pressure has been changed to MPa on the international system of units(SI unit system). The conversion factor is : 1(MPa • G) =10.2(kgf/f • G)

(kgf/F•G)(MPa•G) MUH-18NV - E4

low pressure

7

 

0.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220V/240V

 

 

 

 

 

 

 

 

 

 

 

 

5

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

4

0.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

0.3

 

 

 

 

 

 

 

 

 

 

18 20

 

 

30 32 35(:)

 

15

25

 

 

 

 

 

 

 

50

60

70(%)

 

Ambient temperature(˚C)

Ambient humidity(%)

HEAT operation

Condition indoor:Dry bulb temperature 20.0°C Wet bulb temperature 14.5°C

Outdoor:Dry bulb temperature 7,15,20°C

Wet bulb temperature 6,12,14.5°C

Outdoor unit current (A)

Outdoor unit current (A)

MUH-18NV - E4

11

10

220V/240V

9

8

7

6

15 18 20

25

30 32 35(:)

50

60

70(%)

Ambient temperature(˚C)

Ambient humidity(%)

MUH-18NV - E4

11

10

220V/240V

9

8

7

 

20 21 25(:)

5 7 10

15

Ambient temperature(˚C)

9

8 MICROPROCESSOR CONTROL

WIRELESS REMOTE CONTROLLER

MSH-18NV - E4

 

 

Once the operation mode are set, the same operation mode

 

can be repeated by simply turning the OPERATE/STOP

 

(ON/OFF) button ON.

 

 

Indoor unit receives the signal with a beep tone.

 

When the system turns off, 3-minute time delay will operate to

 

protect system from overload and compressor will not restart

 

for 3 minutes.

 

 

8-1. “I FEEL CONTROL” (

) OPERATION

 

(1) Press OPERATE/STOP (ON/OFF) button on the remote

 

controller. Operation Indicator lamp of the indoor unit

 

turns on with a beep tone.

 

 

(2) Press OPERATION SELECT button to set “I FEEL

 

CONTROL”( ). Then a beep tone is heard.

 

(3) The operation mode is determined by the room

 

temperature at start-up of the operation.

 

Initial room temperature

Mode

 

25: or more

COOL mode of

 

"I FEEL CONTROL"

 

 

 

23:to 25:

DRY mode of

 

"I FEEL CONTROL"

 

 

 

less than 23:

HEAT mode of

 

"I FEEL CONTROL"

 

 

• Once the mode is fixed, the mode does not change by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

room temperature afterwards.

 

 

 

 

 

 

 

 

 

 

 

INDOOR UNIT DISPLAY SECTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Under the ON-TIMER (

) operation, mode is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Indicator lamp

 

 

 

 

 

 

 

determined according to the room temperature as the

 

 

 

 

 

 

 

operation starts.

 

 

 

 

 

 

 

 

 

 

The operation indicator at the right side of the indoor

 

 

 

 

 

 

 

 

 

 

 

 

• When the system is stopped with the OPERATE/STOP

unit indicates the operation state.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(ON/OFF) button on the remote controller, and restarted

 

 

 

 

 

 

 

 

 

 

 

 

 

 

within 2 hours in “I FEEL CONTROL”

 

 

 

) mode, the

 

 

Operation Indicator

 

 

 

lighting

 

(

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system operates in previous mode automatically

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

regardless of the room temperature.

 

 

 

 

 

 

 

not lighting

 

Example

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Previous operation

 

 

Restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL mode of

 

 

COOL mode of

 

 

 

 

 

 

 

 

Difference

 

 

 

 

“I FEEL CONTROL”

 

 

“I FEEL CONTROL”

 

 

 

 

 

 

 

 

betweeen set

 

 

 

 

or COOL mode

 

 

 

 

 

 

 

 

 

 

 

Indication

Operation state

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and room

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This shows that the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

air conditioner is

 

 

 

 

 

 

 

When the system is restarted after 2 hours and more, the

 

 

 

operating to reach

 

Approx. 2 :

 

 

 

 

 

 

the target temperature.

 

 

 

operation mode is determined by the room temperature

 

 

 

 

or more

 

 

 

 

 

 

 

Please wait unit the

 

 

 

 

 

at start-up of the operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

target temperature is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

obtained.

 

 

 

 

 

 

Example

 

 

 

Restart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOL or DRY or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This shows that the

 

 

 

 

 

 

Previous operation

 

 

 

HEAT mode of “I FEEL

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL” that

 

 

 

room temperature is

 

Approx. 2 : COOL mode of

 

 

 

 

 

 

 

 

 

 

determined by room

 

 

 

approaching the

 

or less

“I FEEL CONTROL”

 

 

 

 

 

 

 

 

 

 

temperature at start-up

 

 

 

target temperature.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or COOL mode

 

 

 

of the operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

1deg. 1.7deg.
Difference between room temperature and set temperature during operation.

(4) The initial set temperature is decided by the initial room temperature.

Model

Initial room temperature

Initial set temperature

 

 

 

 

COOL mode of

26: or more

24:

1

"I FEEL CONTROL"

 

 

25: to 26:

Initial room temperature

 

 

 

minus 2:

 

 

 

 

DRY mode of

23: to 25:

Initial room temperature

"I FEEL CONTROL"

minus 2:

 

HEAT mode of

less than 23:

26:

 

"I FEEL CONTROL"

 

 

 

 

 

 

 

 

1 When the system is restarted with the remote controller, the system operates with the previous set temperature regardless of room temperature at restart.

The set temperature is calculated by the previous set temperature.

(5)TEMPERATURES buttons

In “I FEEL CONTROL” ( ) mode, set temperature is decided by the microprocessor based on the room temperature. In addition, set temperature can be controlled by TOO WARM or TOO COOL buttons when you feel too cool or too warm. Each time the TOO WARM or TOO COOL button is pressed,the indoor unit receives the signal and emits a beep tone.

Fuzzy control

When the TOO COOL or TOO WARM button is pressed, the microprocessor changes the set temperature, considering the room temperature, the frequency of pressing TOO COOL or TOO WARM button and the user’s preference to heat or cool. So this is called “Fuzzy control”, and works only in “I FEEL CONTROL” mode.

In DRY mode of “I FEEL CONTROL”, the set temperature doesn’t change.

TOO

 

COOL

To raise the set temperature 1~2 degrees(°C)

TOO

 

WARM

To lower the set temperature 1~2 degrees(°C)

— COOL mode of “I FEEL CONTROL” —

1. Indoor fan speed control

Indoor fan operates at the set speed by FAN SPEED CONTROL button. In AUTO the fan speed is as follows.

Initial temperature difference Fan Speed

Room temperature minus set temperature : 2 degrees or more····························Hi

Room temperature minus set temperature : Between 1 and 2 degrees·················Me

2deg. 4deg.

Room temperature minus set temperature : less than 1 degree····························Lo

2.Coil frost prevention

Temperature control

When the indoor coil thermistor RT12 reads 3°C or below, the coil frost prevention mode starts immediately. However, the coil frost prevention doesn’t work for 5 minutes since the compressor has started.

The indoor fan operates at the set speed and the compressor stops for 5 minutes.

After that, if RT12 still reads below 3°C this mode prolonged until the RT12 reads over 3°C.

11

Time control

When the three conditions as follows have been satisfied for 1 hour and 45 minutes, compressor stops for 3 minutes.

a.Compressor has been continuously operating.

b.Indoor fan speed is Lo or Me.

c.Room temperature is below 26°C.

When compressor stops, the accumulated time is cancelled and when compressor restarts, time counting starts from the beginning.

Time counting also stops temporarily when the indoor fan speed becomes Hi or the room temperature exceeds 26°C.However, when two of the above conditions (b.and c.) are satisfied again.Time accumulation is resumed.

Operation chart

 

ON

 

ON

Example

 

 

 

 

 

 

 

 

 

 

OFF

 

Compressor

OFF

 

 

 

Outdoor fan

 

 

 

 

 

ON (continuously at set speed)

 

 

Indoor fan

 

 

 

 

 

 

 

 

—DRY mode of “I FEEL CONTROL”—

The system for dry operation uses the same refrigerant circuit as the cooling circuit. The compressor and the indoor fan are controlled by the room temperature.

By such controls, indoor flow amounts will be reduced in order to lower humidity without much room temperature decrease.

1.Indoor fan speed control

Indoor fan operates at the set speed by FAN SPEED CONTROL button. However, in AUTO fan operation, fan speed becomes Lo.

2.The operation of the compressor and indoor/ outdoor fan

Compressor operates by room temperature control and time control. Set temperature is controlled to fall 2°C from initial room temperature.

Indoor fan and outdoor fan operate in the same cycle as the compressor. •When the room temperature is 23°C or over:

When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.

When the room temperature is under 23°C.

When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.

Operation time chart

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example

 

 

ON

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermostat

OFF

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

ON

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor fan

OFF

 

 

OFF

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

ON

ON

 

 

Outdoor fan OFF

 

 

OFF

 

 

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8 min.

 

3 min.

4 min. 1 min.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.Coil frost prevention

The operation is as same as coil frost prevention during COOL mode of “I FEEL CONTROL”.

Indoor fan operates at the set speed and the compressor stops for 5 minutes, because protection(Coil frost prevention) has the priority.

However, when coil frost prevention works while the compressor is not operating, it’s speed becomes Lo.

12

Loading...
+ 26 hidden pages