Mitsubishi MSC-A07YV-E1, MSC-A09YV-E1, MSC-A12YV-E1 Service Manual

0 (0)

SPLIT-TYPE, AIR CONDITIONERS

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

No. OB329

HFC

utilized

SERVICE MANUAL R410A

Wireless type Models

MSC-A07YV MSC-A09YV MSC-A12YV

-E1 (WH)

-E1 (WH)

-E1 (WH)

CONTENTS

Indication of model name

MSC-A07YV - E1

MSC-A09YV - E1

MSC-A12YV - E1

1.TECHNICAL CHANGES ················

2.PART NAMES AND FUNCTIONS············

3.SPECIFICATION····················

4.NOISE CRITERIA CURVES ···············

5.OUTLINES AND DIMENSIONS ·············

6.WIRING DIAGRAM ··················

7.REFRIGERANT SYSTEM DIAGRAM ···········

8.MICROPROCESSOR CONTROL ············

9.SERVICE FUNCTIONS ·················

10.TROUBLESHOOTING·················

11.DISASSEMBLY INSTRUCTIONS·············

12.PARTS LIST······················

NOTE:

•This manual describes technical data of indoor units.

•As for outdoor units MU-A07/A09/A12YV - E1 , refer to the service manual OB330. •As for outdoor units MUH-A07/A09/A12YV - E1 , refer to the service manual OB331.

•As for outdoor units MUX-A10/A19/A20/A25/A26WV - E1 , refer to the service manual OB307 REVISED EDITION-A.

•As for outdoor units MUX-A22WV - E1 , refer to the service manual OB318.

•As for outdoor units MXZ-A18/A26/A32WV - E1 , refer to the service manual OB319.

1 TECHNICAL CHANGES

MSC-A07WV- E1 MSC-A07YV- E1

MSC-A09WV- E1 MSC-A09YV- E1

MSC-A12WV- E1 MSC-A12YV- E1

1.Design of front panel has changed.

2.Air filter has changed to the catechin air filter.

2 PART NAMES AND FUNCTIONS

MSC-A07YV - E1

MSC-A09YV - E1

MSC-A12YV - E1

INDOOR UNIT

Air cleaning filter (white bellows type)

Panel

Catechin air filter (With deodorizer)

Air outlet

Vertical vanes

Fan

Horizontal vane

Operation section

(When the front panel is opened)

Emergency operation switch

Front panel

Air inlet

to Breaker

Power supply cord

Remote control receiving section

Remote controller

Display section

Operation indicator lamp

Remote control receiving section

3

MSC-A07YV- E1

MSC-A09YV- E1

MSC-A12YV- E1

ACCESSORIES

<Indoor unit>

1

Installation plate

1

 

 

 

2

Installation plate fixing screw 4 o 25 mm

5

 

 

 

3

Remote controller holder

1

 

 

 

4

Fixing screw for 3 3.5 o 16 mm

2

 

 

 

5

Battery (AAA) for remote controller

2

 

 

 

6

Wireless remote controller

1

 

 

 

7

Felt tape (Used for left or left-rear piping)

1

 

 

 

8

Air cleaning filter

1

 

 

 

REMOTE CONTROLLER

Signal transmitting section

Operation display section

OPERATE /STOP (ON /OFF)button

 

 

PM

 

 

AM

ON/OFF

TOO

TOO

 

WARM

COOL

TEMPERATURE buttons

Open the front lid.

FAN SPEED CONTROL button

OPERATION SELECT button ECONO COOL button

RESET button

AM

ON/OFF

TOO

TOO

 

WARM

COOL

 

FAN

STOP

I FEEL COOL

 

 

HEAT DRY

VANE

START

 

 

/FAN

 

 

/

 

HR.

MODE

 

ECONO COOL

 

MIN.

 

RESET CLOCK

 

Indication of remote controller model is on back.

OFF-TIMER button ON-TIMER button

HR. button MIN. button (TIME SET button)

CLOCK SET button

VANE CONTROL button

4

3 SPECIFICATION

Indoor model

Function

Indoor unit power supply

Capacity Air flow(High/Med.w/Loww)

Power outlet

Electrical

data

Running current

 

 

 

 

Power input

 

 

Power factor

 

 

Fan motor current

Fan

motor

Model

Winding

 

 

 

 

resistance(at 20:)

 

 

Dimensions WOHOD

 

 

Weight

 

 

Air direction

 

remarks

Sound level(High/Med.w/Loww)

Special

Fan speed(High/Med.w/Loww)

Thermistor RT11(at 25:)

 

 

Fan speed regulator

 

 

Thermistor RT12(at 25:)

 

 

Remote controller model

 

MSC-A07YV - E1

MSC-A09YV - E1

MSC-A12YV - E1

 

Cooling

Heating

Cooling

Heating

Cooling

Heating

 

Single phase

Single phase

Single phase

 

230V,50Hz

230V,50Hz

230V,50Hz

K /h

474/372w/276w 510/420w/342w

474/384 w/306w 588/456w/342w

582/444 w/324w 606/498w/396w

A

 

10

10

 

 

10

A

0.17

0.17

 

0.19

W

 

35

35

 

 

40

%

 

90

90

 

 

92

A

0.17

0.17

 

0.19

 

RC4V19-LA

RC4V19-LA

RC4V19-KA

"

WHT-BLK 413

WHT-BLK 413

WHT-BLK 316

BLK-RED 334

BLK-RED 334

BLK-RED 299

 

mm

815O278O244

815O278O244

815O278O244

kg

 

9

9

 

 

10

 

 

5

5

 

 

5

dB

36/31w/25 w

36/31w/25 w

36/31w/25w

39/32w/25 w

40/33w/26w

39/33w/26w

rpm

900/750w/600w 950/820w/700w

900/770w/650w 1,050/870w/700w

930/760w/600w 960/830w/700w

 

 

3

3

 

 

3

k"

 

10

10

 

 

10

k"

 

10

10

 

 

10

 

KP1A or KG3A

KP1A or KG3A

KP1A or KG3A

NOTE: 1. Test conditions are based on ISO 5151.

 

Cooling : Indoor

DB27°C WB19°C

Heating : Indoor DB20°C

Outdoor DB35°C WB24°C

 

OutdoorDB 7°C/WB 6°C

Indoor-Outdoor piping length 5m

2.Remote controller model KP1A and KG3A are the same in terms of specification. W Reference value

5

Mitsubishi MSC-A07YV-E1, MSC-A09YV-E1, MSC-A12YV-E1 Service Manual

4 NOISE CRITERIA CURVES

MSC-A07YV-

E1

FAN SPEED FUNCTION

SPL(dB(A))

LINE

 

 

 

 

 

 

 

 

 

 

High

 

COOL

36

 

 

 

 

 

 

 

HEAT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test conditions,

 

 

 

 

 

 

 

 

Cooling : DB27:

WB19:

 

90

 

 

 

 

Heating : DB20:

WB -:

 

 

 

 

 

 

 

 

 

MICRO BAR

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

dB re 0.0002

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-70

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

 

 

 

 

 

 

 

 

 

BAND SOUND

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

30

 

 

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

 

 

 

 

 

 

 

 

 

 

20

APPROXIMATE

 

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

MSC-A12YV-

E1

FAN SPEED FUNCTION

SPL(dB(A))

LINE

 

 

 

 

 

 

 

 

 

 

High

 

COOL

40

 

 

 

 

 

 

 

HEAT

39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test conditions,

 

 

 

90

 

 

 

 

Cooling : DB27:

WB19:

 

 

 

 

 

 

 

 

 

MICRO BAR

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

dB re 0.0002

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-70

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

 

 

 

 

 

 

 

 

 

BAND SOUND

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

30

 

 

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

 

 

 

 

 

 

 

 

 

 

20

APPROXIMATE

 

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

MSC-A09YV-

E1

FAN SPEED FUNCTION

SPL(dB(A))

LINE

 

 

COOL

36

 

 

 

 

 

 

High

 

HEAT

39

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test conditions.

 

 

 

 

 

 

 

 

Cooling : DB27:

WB19:

 

90

 

 

 

 

Heating : DB20:

WB -:

 

 

 

 

 

 

 

 

 

MICRO BAR

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

dB re 0.0002

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-70

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

 

 

 

 

 

 

 

 

 

BAND SOUND

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

30

 

 

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

 

 

 

 

 

 

 

 

 

 

20

APPROXIMATE

 

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

INDOORUNIT

WALL

1m

0.8m

MICROPHONE

6

5 OUTLINES AND DIMENSIONS

MSC-A07YV - E1

81.5

MSC-A09YV - E1

INDOOR UNIT

Installation plate

 

Indoor unit

 

783

133.5

231.5

Unit: mm

271 4.5

41

 

 

2.5

42

81.5

326

326

81.5

Wall hole [65

815

278

60

606

58

19

162

 

Wireless remote controller

 

Air in

more

 

7 or

 

 

149

 

30

 

 

Air out

Power supply cord Lead to right 1.0m Lead to left 0.3m

2425 Installation plate

{Liquid line [6.35-0.5m Gas line [9.52-0.43m Insulation [37 O.D

[21 I.D

 

90

Drain hose [16

 

110

 

(Connected part O,D)

 

 

244

 

Insulation [28

 

 

MSC-A12YV - E1

161.5

INDOOR UNIT

Installation plate

 

 

Indoor unit

 

783

161.5

17.5

218.5

258

278

 

 

41

 

 

 

 

2.5

42

 

 

81.5

326

 

326

 

81.5

 

 

 

 

 

 

 

 

Wall hole [65

 

815

 

 

242

5

Installation plate

 

 

 

more

 

 

 

Liquid line [6.35-0.5m

 

 

 

 

 

 

Gas line [9.52-0.43m

 

 

Air in

or

 

 

{ Insulation [37 O.D

 

 

 

 

 

 

[21 I.D

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

60

606

149

30

 

90

 

Drain hose [16

 

110

 

 

 

 

 

 

 

 

 

(Connected part O,D)

58

19

 

 

 

 

 

 

Air out

244

 

 

Insulation [28

 

 

Power supply cord

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lead to right 1.0m

 

 

 

 

 

 

162

 

Lead to left 0.3m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wireless remote controller

7

6

WIRING DIAGRAM

 

 

 

 

 

 

 

 

 

 

MSC-A07YV - E1

MSC-A09YV - E1

MSC-A12YV - E1

 

 

 

 

 

 

 

 

INDOOR UNIT

 

 

MODELS WIRING DIAGRAM

 

 

 

 

 

 

 

 

TO OUTDOOR

TB

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

BRN

 

 

 

TAB12

 

 

 

CN

 

RT12

 

 

CONNECTING

L

 

 

 

 

 

 

 

 

 

BRN

 

 

 

 

 

 

 

 

112

 

 

 

 

 

FOR

 

 

 

 

CN201

 

 

 

CN

 

RT11

 

 

3

RED

 

 

 

 

 

 

 

 

 

MUH OR

 

 

 

T11

 

 

111

 

 

 

 

 

 

3

 

 

 

 

 

MXZ TYPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

 

 

 

 

2

 

 

 

 

 

BLK

1

 

 

12V

BLU

 

 

 

 

NR11

 

 

3

 

 

 

 

 

 

 

CN

GRY

 

 

 

 

 

1

 

 

2

 

 

FOR

BLU

 

 

 

 

 

 

 

121

 

YLW

 

 

 

 

 

 

CN202

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

MF

 

MU OR

2

WHT

 

 

 

 

C11

1

 

BRN

 

MUX TYPE

 

 

 

 

 

2

 

 

WHT

4

 

 

1

 

 

 

 

1

F11

SR141

 

3

 

5

 

 

12V

BLK

 

 

 

 

 

 

 

5

 

RED

6

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

CN

 

CN

 

 

CN211

 

 

 

 

 

 

 

LD103

151

 

101

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

ELECTRONIC CONTROL P.C. BOARD

 

 

 

 

 

CORD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~/N 230V

 

GRN

 

 

5

5

 

 

 

 

 

 

 

 

 

50Hz

 

 

 

POWER MONITOR,

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRN/YLW

 

MV

 

RECEIVER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P.C.BOARD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT BREAKER

 

 

 

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

CONTROLLER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SYMBOL

NAME

 

SYMBOL

 

NAME

 

SYMBOL

 

 

 

NAME

 

 

C11

INDOOR FAN CAPACITOR

NR11

VARISTOR

 

TB

 

TERMINAL BLOCK

 

 

F11

FUSE(3.15A)

 

RT11

ROOM TEMPERATURE THERMISTOR

T11

 

TRANSFORMER

 

 

MF

INDOOR FAN MOTOR (INNER FUSE)

RT12

INDOOR COIL THERMISTOR

MV

VANE MOTOR

SR141

SOLID STATE RELAY

NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.

2.Use copper conductors only. (For field wiring)

3.Symbols below indicate.

/: Terminal block, : Connector

7

 

 

REFRIGERANT SYSTEM DIAGRAM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSC-A07YV - E1

MSC-A09YV - E1

MSC-A12YV - E1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit:mm

 

 

 

 

 

 

 

Refrigerant pipe [9.52

 

 

 

 

 

 

 

 

 

 

Refrigerant pipe [12.7

 

INDOOR UNIT

 

 

INDOOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(with heat insulator)

 

 

 

 

 

 

 

 

 

 

(with heat insulator)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

Indoor coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat

 

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exchanger

 

 

 

 

RT12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exchanger

 

 

 

 

 

 

 

 

Flared connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flared connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Room temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Room temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flared connection

Flared connection

Refrigerant flow

Refrigerant pipe [6.35

 

 

Refrigerant flow

Refrigerant pipe [6.35

 

 

in cooling

(with heat insulator)

 

 

in cooling

(with heat insulator)

 

 

8

 

 

Fan speed

8 MICROPROCESSOR CONTROL

MSC-A07YV - E1

MSC-A09YV - E1

MSC-A12YV - E1

Once the operation mode are set, the same operation mode can be repeated by simply turning the OPERATE/STOP (ON/OFF) button ON. Indoor unit receives the signal with a beep tone.

When the system turns off, 3-minute time delay will operate to protect system from overload and compressor will not restart for 3 minutes.

WIRELESS REMOTE CONTROLLER

INDOOR UNIT DISPLAY SECTION

Signal transmitting section

Operation Indicator lamp

The operation indicator at the right side of the indoor unit indicates the operation state.

Operation display section

 

 

PM

OPERATE /STOP

 

 

AM

 

 

 

(ON /OFF)button

ON/OFF

TOO

TOO

 

 

WARM

COOL

TEMPERATURE buttons

Open the front lid.

AM

ON/OFF TOO TOO WARM COOL

FAN SPEED CONTROL button

FAN

STOP

OFF-TIMER button

I FEEL COOL

 

HEAT

VANE

START

ON-TIMER button

DRY

 

/

 

/FAN

 

 

MODE

HR.

HR. button

OPERATION SELECT button

 

 

ECONO COOL

MIN.

MIN. button

ECONO COOL button

RESET CLOCK

 

(TIME SET button)

RESET button

 

 

CLOCK SET button

 

 

 

VANE CONTROL button

8-1. COOL ( ) OPERATION

The following indication does not depend on the shape of lamp.

Operation Indicator

lighted

not lighted

Difference between target

Indication Operation state temperature and room temperature

This shows that the air conditioner is operating to reach

the target temperature.

Approx. 2 :

Please wait until the target temperature is obtained.

or more

This shows that the

 

room temperature is

Approx. 2 :

approaching the

or less

target temperature.

 

(1)Press OPERATE/STOP(ON/OFF) button. OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.

(2)Select COOL mode with the OPERATION SELECT button.

(3)Press TEMPERATURE buttons (TOO WARM or TOO COOL button)to select the desired temperature. The setting range is 16 ~ 31°C

 

 

Difference between room

1. Thermostat control

 

temperature and set tem-

 

perature during operation

Thermostat is ON or OFF by difference between room temperature and set temperature

 

 

 

 

 

 

Initial temperature difference

Thermostat

Set temperature

Room temperature minus set temperature : 0.3 : or more················································ON

 

 

 

 

 

 

 

 

 

 

 

 

 

Room temperature minus set temperature : less than -0.3 :············································OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.Indoor fan speed control

Indoor fan operates continuously at the set speed by FAN SPEED CONTROL button regardless of thermostat’s OFF-ON.

In Auto the fan speed is as follows.

Initial temperature difference

Room temperature minus set temperature : 1.7 degrees or more·······························High Room temperature minus set temperature : Between 1 and 1.7 degrees···················Med. Room temperature minus set temperature : less than 1 degree··································Low

-0.3 : 0.3 :

Difference between room temperature and set temperature during operation

3 deg.

1 deg. 1.7 deg.

9

Difference between room temperature and set temperature during operation

3. Coil frost prevention

Temperature control

When the indoor coil thermistor RT12 reads 4°C or below(MSC-A07/A09YV) / 0°C or below(MSC-A12YV) for 5 minutes, the coil frost prevention mode starts.

The indoor fan operates at the set speed and the compressor stops for 5 minutes.

After that, if RT12 still reads below 4°C (MSC-A07/A09YV) / 0°C (MSC-A12YV), this mode is prolonged until the RT12 reads over 4°C (MSC-A07/A09YV) / 0°C (MSC-A12YV).

Time control

When the three conditions as follows have been satisfied for 1 hour and 45 minutes, the compressor stops for 3 minutes. The indoor fan operates at the set speed.

a.Compressor has been continuously operating.

b.Indoor fan speed is Low or Med.

c.Room temperature is below 26°C.

When compressor stops, the accumulated time is cancelled. When compressor restarts, time counting starts from the beginning.

Time counting also stops temporarily when the indoor fan speed becomes High or the room temperature exceeds 26°C. However, when two of the above conditions (b.and c.) are satisfied again, time accumulation is resumed.

Operation chart

 

 

 

 

 

Example

 

ON

 

ON

 

 

 

 

 

 

OFF

 

Compressor

OFF

 

 

 

Outdoor fan

 

 

 

 

 

ON ( continuously at set speed)

 

 

Indoor fan

 

 

 

 

 

 

 

 

8-2. DRY ( ) OPERATION

(1)Press OPERATE/STOP(ON/OFF) button.

OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.

(2)Select DRY mode with the OPERATION SELECT button.

(3)The microprocessor reads the room temperature and determines the set temperature. Set temperature is as shown on the right chart.

DRY operation will not function when the room temperature is 13°C or below.

(4)When DRY operation functions the fan speed is lower than COOL operation except at (fan speed) Low.

The system for dry operation uses the same refrigerant circuit as the cooling circuit.

The compressor and the indoor fan are controlled by the room temperature.

 

Set temperature and

 

 

 

35: initial room temperature in dry mode

 

30

 

 

 

 

 

temperature

25

 

 

 

 

 

20

 

 

 

 

 

Set

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

10

 

 

 

 

35 :

 

10

15

20

25

30

Initial room temperature

1.Thermostat control

Thermostat is ON or OFF by difference between room temperature and set temperature.

Initial temperature difference Thermostat Room temperature minus set temperature : 0.3 : or more················································ON Room temperature minus set temperature : less than -0.3 :············································OFF

2.Indoor fan speed control

Indoor fan operates at the set speed by FAN SPEED CONTROL button. In Auto fan speed becomes Low.

3.The operation of the compressor and indoor / outdoor fan <MU-A07/A09/A12YV, MUH-A07/A09/A12YV, MUX-A10/A19/A20/A22/A25/A26WV>

Compressor operates by room temperature control and time control. Indoor fan and outdoor fan operate in the same cycle as the compressor.

When the room temperature is 23°C or over:

When the thermostat is ON, the compressor repeats 8 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.

When the room temperature is under 23°C.

When the thermostat is ON, the compressor repeats 2 minutes ON and 3 minutes OFF. When the thermostat is OFF, the compressor repeats 4 minutes OFF and 1 minute ON.

Set temperature

-0.3 : 0.3 :

10

Loading...