© KROHNE 09/2003
Supplementary
Installation and
Operating Instructions
HART Communicator 275
Asset Management Solutions (AMS)
Process Device Manager (PDM)
IFC 110
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg |
1/15 |
Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de |
|
Supplementary Installation and Operating Instructions IFC110 HART
HC275, AMS, PDM
1 |
General Information |
3 |
|
2 |
IDs and Revision numbers |
5 |
|
3 |
Implementation Peculiarities |
6 |
|
4 |
HART Communicator 275 (HC275) |
6 |
|
|
4.1 |
Installation |
6 |
|
4.2 |
Operating |
6 |
5 |
Asset Management Solutions (AMS) |
6 |
|
|
5.1 |
Installation |
6 |
|
5.2 |
Operating |
6 |
6 |
Process Device Manager (PDM) |
7 |
|
|
6.1 |
Installation |
7 |
|
6.2 |
Operating |
7 |
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg |
2/15 |
Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de |
|
Supplementary Installation and Operating Instructions IFC110 HART
HC275, AMS, PDM
1 General Information
The IFC110 is a "four-wire" transmitter with 4...20mA current output and HARTâ capability. It is available with active current output or active/passive current output.
General characteristics of the IFC110 HARTâ interface:
·Multidrop Mode is supported
·Burst Mode is not supported
Electrical connection: Refer to sections 2.1, 2.2, 2.6 of the “Installation and Operating Instructions Electromagnetic flowmeters ALTOFLUX IFC 110 F” (KROHNE).
There are two ways of using the HARTâ communication:
a) As a point-to-point connection between the IFC110 and the HARTâ master equipment.
Point-to-Point Analog/Digital Mode
Primary Master
Terminal I
Terminal I
HART |
|
Analog |
|
Modem |
|
||
|
|
|
|
|
HART |
4 mA |
20 |
|
|
|
³ 250 O
4...20 mA
IFC110
Addr. 0
Secondary Master
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg |
3/15 |
Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de |
|
Supplementary Installation and Operating Instructions IFC110 HART
HC275, AMS, PDM
b) As a multipoint connection (multidrop) with up to 15 devices (IFC110 or other HARTâ equipment).
Multidrop Mode
Primary Master
HART
Modem
|
HART |
|
|
Power |
³ 250 O |
|
|
|
|
|
|
Supply |
|
|
|
|
|
|
Terminal I |
|
4 mA |
4 mA |
Terminal I |
|
|
. . . |
|
|
Secondary Master |
Up to 15 |
|
|
|
Slaves |
|
|
|
. . . |
|
|
IFC110 |
|
IFC110 |
|
Addr. > 0 |
|
Addr. > 0 |
|
(passive Current Output) |
|
(passive Current Output) |
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg |
4/15 |
Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de |
|
Supplementary Installation and Operating Instructions IFC110 HART
HC275, AMS, PDM
If the IFC110 is equipped with a continously active current output a 'third wire' is needed to properly connect it together with two-wire loop powered devices in the same network.
Multidrop Mode (‘three-wire’)
(Connecting two-wire and four-wire devices in the same network)
Primary Master
|
HART |
|
|
|
4 mA |
|
4 mA |
HART |
|
two-wire |
|
Modem |
|
loop powered |
|
|
|
devices |
|
|
|
. . . |
|
|
Addr. > 0 |
|
Addr. > 0 |
Power |
HART |
|
Terminal I |
Supply |
|
||
|
|
||
|
4 mA |
4 mA |
Terminal I |
|
|
||
|
|
four-wire |
|
|
|
active source |
|
|
³ 250 O |
devices |
|
|
|
|
|
Secondary Master |
|
. . . |
|
|
IFC110 |
IFC110 |
|
|
|
||
|
Addr. > 0 |
|
|
|
|
Addr. > 0 |
|
|
|
|
2 IDs and Revision Numbers
The HART Device Descriptions described in this document have the following IDs and revision numbers:
Manufacturer ID: |
69 (0x45) |
Device Type: |
243 (0xF3) |
Device Revision: |
2 |
DD Revision: |
1 |
HART Universal Revision: |
5 |
HC 275 OS Revision: |
³ 4.9 |
AMS Version: |
³ 5.0 |
PDM Version: |
³ 5.1 |
For information about Transmitter Revisions and related Device Descriptions refer to the KROHNE HART Device List.
KROHNE Messtechnik GmbH & Co. KG · Ludwig-Krohne-Str. 5 D-47058 Duisburg |
5/15 |
Tel.: 0203-301 0 Fax: 0203-301 389 · e-mail: krohne@krohne.de |
|