Sintesis chillers are part of the Ingersoll Rand EcoWise™ portfolio
of products that are designed to lower their environmental
impact with next-generation, low global warming potential
(GWP) refrigerants and high effi ciency operation.
These instructions are given as a guide to good practice in
the installation, start-up, operation, and maintenance by
the user, of Trane RTAF chillers, manufactured in France. A
separate manual is available for the use and maintenance
of the unit’s control, Tracer™ UC800. They do not contain full
service procedures necessary for the continued successful
operation of this equipment. The services of a qualified
technician should be employed through the medium of a
maintenance contract with a reputable service company.
Read this manual thoroughly before unit start-up.
Units are assembled, pressure tested, dehydrated, charged
and tested in accordance with factory standard before
shipment.
Warnings and Cautions
Warnings and Cautions appear at appropriate sections
throughout this manual. Your personal safety and the
proper operation of this machine require that you follow
them carefully. The constructor assumes no liability
for installations or servicing performed by unqualified
personnel.
WARNING: Indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation
which, if not avoided, may result in minor or moderate
injury. It may also be used to alert against unsafe practices
or for equipment or property-damage-only accidents.
Safety Recommendations
To avoid death, injury, equipment or property damage, the
following recommendations should be observed during
maintenance and service visits:
1. The maximum allowable pressures for system leak testing
on low and high pressure side are given in the chapter
“Installation”. Insure to do not exceed test pressure by using
appropriate device.
2. Disconnect all power supplies before any servicing on
the unit.
3. Service work on the refrigeration system and the
electrical system should be carried out only by qualified and
experienced personnel.
4. To avoid any risk, it is recommended to place the unit on
an area with limited access.
Reception
On arrival, inspect the unit before signing the delivery note.
Specify any visible damage on the delivery note, and send
a registered letter of protest to the last carrier of the goods
within 7 days of delivery.
Notify the local TRANE sales office at the same time.
The delivery note must be clearly signed and countersigned
by the driver.
Any concealed damage shall be notified by a registered
letter of protest to the last carrier of the goods within
7 days of delivery. Notify the local TRANE sales office
at the same time.
Important notice: No shipping claims will be accepted by
TRANE if the above mentioned procedure is not respected.
For more information, refer to the general sales conditions
of your local TRANE sales office.
Note: Unit inspection in France. Delay to send registered
letter in case of visible and concealed damage is only
72 hours.
Loose Parts Inventory
Check all the accessories and loose parts that are shipped
with the unit against the shipping list. Included in these
items will be the water vessel drain plugs, rigging and
electrical diagrams, service literature, which are placed
inside the control panel and/or starter panel for shipment.
If optional elastomeric isolators are ordered with the unit
(model number digit 42 =1) they are shipped mounted on
the horizontal support frame of the chiller. The isolators’
location and distribution weight diagram is placed with
the service literature inside the starter/control panel.
Warranty
Warranty is based on the general terms and conditions of
the manufacturer. The warranty is void if the equipment is
repaired or modified without the written approval of the
manufacturer, if the operating limits are exceeded or if the
control system or the electrical wiring is modified. Damage
due to misuse, lack of maintenance or failure to comply
with the manufacturer’s instructions or recommendations
is not covered by the warranty obligation. If the user does
not conform to the rules of this manual, it may entail
cancellation of warranty and liabilities by the manufacturer.
Startup MUST be performed by Trane, or an authorized
agent of Trane, to VALIDATE this WARRANTY. Contractor
must provide a two-week startup notification to Trane (or an
agent of Trane specifically authorized to perform startup).
Unit Description
The Sintesis RTAF units are helical-rotary type, air-cooled
chillers designed for outdoor installation. The refrigerant
circuits are factory-piped, leak tested and dehydrated. Every
unit is electrically tested for proper control operation before
shipment.
Chilled water inlet and outlet openings are covered for
shipment. The Sintesis RTAF features Trane’s exclusive
Adaptive Control™ logic, which monitors the control
variables that govern the operation of the chiller unit.
Adaptive control logic can adjust capacity variables to avoid
chiller shutdown when necessary, and keep producing
chilled water. The units feature two independent refrigerant
circuits. On the HSE HSS version, 1 compressor per circuit
is controlled by a dedicated variable speed Adaptive
Frequency Drive. Each refrigerant circuit is provided
with filter, sight glass, electronic expansion valve, and
charging valves. The shell-and-tube CHIL™ (Compact-High
performance-Integrated design-Low charge) evaporator is
manufactured in accordance with the Pressure Equipment
Directive (PED) code. Each evaporator is fully insulated and
equipped with water drain and vent connection.
Units are shipped with full oil charge and can be ordered
with either a factory refrigerant charge or optional
refrigerant pre-charge.
4
RLC-SVX19G-GB
Inspection
When the unit is delivered, verify that it is the correct
unit and that it is properly equipped.
Inspect all exterior components for visible damage.
Report any apparent damage or material shortage to
the carrier and make a “unit damage” notation on the
carrier’s delivery receipt. Specify the extent and type of
damage found and notify the appropriate Trane Sales
Office.
Do not proceed with installation of a damaged unit
without sales office approval.
Inspection Checklist
To protect against loss due to damage incurred in transit,
complete the following checklist upon receipt of the unit.
• Inspect the individual pieces of the shipment before
accepting the unit. Check for obvious damage to the
unit or packing material.
• Inspect the unit for concealed damage as soon as
possible after delivery and before it is stored.
Concealed damage must be reported within 10 days
after receipt.
• If concealed damage is discovered, stop unpacking
the shipment. Do not remove damaged material from
the receiving location. Take photos of the damage, if
possible. The owner must provide reasonable evidence
that the damage did not occur after delivery.
• Notify the carrier’s terminal of the damage
immediately, by phone and by mail. Request an
immediate, joint inspection of the damage with the
carrier and the consignee.
• Notify the Trane sales representative and arrange for
repair. Do not repair the unit, however, until damage is
inspected by the transportation representative.
Pre-Installation
Storage
Extended storage of the unit prior to the installation
requires the following precautions:
Store the unit in a secured area, to avoid intentional
damages.
Close the suction, discharge and liquid-line isolation
valves.
At least every three months (quarterly), check the
pressure in the refrigerant circuits to verify that the
refrigerant charge is intact. If it is not, contact a qualified
service organization and the appropriate Trane sales
office.
Note: If the unit is stored before servicing near a
construction site it is highly recommended to protect
micro-channel coils from any concrete dust. Failure to do
so may considerably reduce reliability of the unit.
RLC-SVX19G-GB
5
Pre-Installation
Installation Requirements
A list of the contractor responsibilities typically associated with the unit installation process is provided in Table 1.
Table 1 – Installation requirements
Type
Foundation• Meet foundation requirements
Rigging
Isolation
Electrical
Water piping• Flow switch
Insulation• Insulation• Insulation
Water Piping Connection Components• Grooved pipe
Other Materials
“Sintesis Model RTAF Installation
Completion Check Sheet and Request
for Trane Service”
Chiller Start-up Commissioning
(a)
Trane Supplied
Trane Installed
• Circuit breakers
(optional)
• Unit mounted
starter
• R-134a, R-513A
or R1234ze
refrigerant
• Full factory
charge or preload charge
• Dry nitrogen
(optional)
• Trane, or an
agent of Trane
specically
authorized to
perform startup of Trane®
products
Trane Supplied
Field Installed
• Elastomeric
isolators
(optional)
Field Supplied
Field Installed
• Safety chains
• Clevis connectors
• Lifting beam
• Spreader bar
• Elastomeric isolators (optional)
• Circuit breakers (optional)
• Electrical connections to unit mounted starter
• Wiring sizes per submittal and NEC
• Terminal lugs
• Ground connection(s)
• BAS wiring (optional)
• Control voltage wiring
• Chilled water pump contactor and wiring
• Option relays and wiring
• Taps for thermometers and gauges
• Thermometers
• Water ow pressure gauges
• Isolation and balancing valves in water piping
• Vents and drain
• Waterside pressure relief valves
• Water strainer
• Glycol for Glycol free conguration
(a)
Start-up must be performed by Trane or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products. Contractor
shall provide Trane (or an agent of Trane specifically authorized to perform start-up) with notice of the scheduled start-up at least two weeks prior to the
scheduled start-up.
D = 400V/50Hz/3ph
4 = 460V/60Hz/3ph
J = 380V/60Hz/3ph
Digit 9 – Manufacturing Location
E = Europe
Digit 10, 11 – Design sequence
A0 = Factory assigned
RLC-SVX19G-GB
Digit 12 - Efficiency
N = Standard Efficiency
H = High Efficiency
A = Extra Efficiency
U = High Seasonal Short (HSS)
V = High Seasonal Efficiency
Digit 13 – Agency listing
C = CE Marking
Digit 14 – Pressure vessel code
2 = PED (Pressure equipment directive)
D = Australian code
Digit 15 – Acoustic level
X = Standard noise (SN)
L = Low noise (LN)
A = AC Extra Low Noise
Q = Low Noise with Night Noise SetBack (NNSB)
E = Extra Low Noise (XLN)
Digit 16 – Operating map : airside
X = Standard ambient
L = Low ambient
H = High ambient
Digit 17 – Relief valve option
L = Single Relief Valve High Pressure side
D = Dual Relief Valve with 3 way valve High Pressure side
Digit 18 – Water connection
X = Grooved pipe connection
W = Grooved pipe with coupling and pipe stub
Digit 19 – Operating map water side
N = Comfort cooling (above 4.4°C)
P = Process cooling (below 4.4°C) (Brine application)
C = Ice Making (-7°C to 20°C)
Digit 20 – Evaporator Configurations
2 = Standard pass evaporator
T = Standard Pass Evaporator + Turbulators
Digit 21 – Thermal Insulation
N = Standard
H = High performance
X = None
Digit 22 – Condenser Coating
N = Aluminum Micro Channel
C = E-Coated Micro Channel (Free Cooling excluded)
Digit 23 - Heat Recovery
X = No Heat Recovery
P = Partial Heat Recovery
Q = Partial Heat Recovery with on site fan control (PHR +)
T = Total Heat Recovery (full equipment)
V = Total Heat Recovery (no piping connection)
Digit 24 – Hydraulic module
X = Pump signal On/Off
1 = Dual pump standard pressure
3 = Dual pump high pressure
Digit 25 - Free Cooling
X = No Free Cooling
F = Total Free-Cooling Direct
G = Partial Free-cooling Direct
H = Total Free Cooling Glycol Free
J = Partial Free Cooling Glycol Free
7
Unit Model Number Description
Digit 26 – Disconnect switch
F = With Fuse
B = With circuit breaker
Digit 27 – Under/Over Voltage
X = None
1 = Included
2 = Included with ground fault protection
Digit 28 – Human Interface language
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
M = Swedish
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
2 = Romanian
6 = Hungarian
8 = Turkish
Digit 29 – Smart com protocol
X = None
B = Bacnet interface
M = Modbus interface
L = LonTalk interface
Digit 30 – Communication customer
X = None
A = External set point & capacity outputs
Digit 31 – Flow switch
X = None
F = Field installed flow switch
Digit 32 – Electrical Panel Protection
X = Enclosure with deadfront protection
1 = Enclosure with IP 20 internal protection
Digit 33 – Master Slave
X = Open for Future Use
Digit 34 – Unit User Interface
L = Standard, Local UI supplied (TD7)
Digit 35 – Energy meter
X = No energy meter
M = Energy meter installed
Digit 36 – Open for future use = X
Digit 37 – Variable Primary Flow
X = None
F = Constant Speed Pump -AFD Adjustment
P = Variable Speed Pump - Constant delta P
T = Variable Speed Pump - Constant delta T
Digit 38 – Open for future use = X
Digit 39 – Open for future use = X
Digit 40 – Power socket
X = None
P = Included (230V - 100W)
Digit 41 – Factory tests
X = No final performances test
B = Visual inspection with customer
E = Performance test w/o customer
Digit 42 – Installation accessory
X = None
1 = Neoprene Isolators
4 = Neoprene pads
Digit 43 – Literature language
B = Bulgarian
C = Spanish
D = German
E = English
F = French
H = Dutch
I = Italian
K = Finnish
L = Danish
M = Swedish
N = Norvegian
P = Polish
R = Russian
T = Czech
U = Greek
V = Portuguese
Z = Slovenian
2 = Romanian
3 = Serbian
4 = Slovak
5 = Croatian
6 = Hungarian
8 = Turkish
Digit 44 – Shipping package
X = Standard protection
A = Containerization package
Digit 45 – Refrigerant
0 = R134a Factory pre-charge
1 = R134a Factory full refrigerant charge
2 = R513A Factory pre-charge
3 = R513A Factory full refrigerant charge
L = Factory Nitrogen Charge for R1234ze unit
M = Factory Nitrogen Charge for R513A unit
N = Factory Nitrogen Charge for R134a unit
Y = R1234ze Factory pre-charge
Z = R1234ze Factory full refrigerant charge
Digit 46 – Open for future use = X
Digit 47 – Open for future use = X
Digit 48 – Design special
X = none
S = special
8
RLC-SVX19G-GB
General Data
Table 2a – General Data RTAF 090-245 Standard Efficiency - Standard and Low Noise (SN&LN) - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Size 245 not avalaible in R513A.
10
RLC-SVX19G-GB
General Data
Table 2b – General Data RTAF 090-185 Standard Efficiency - Standard and Low Noise (SN&LN) - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)325357387419450502544602
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)162176190201212242269273
Unit rated amps (Max compressor+fan+control)(A)272295318339360409450458
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.870.870.870.880.850.860.870.87
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150/150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN SE SN LN
12
RLC-SVX19G-GB
General Data
Table 3a – General Data RTAF 90-245 Standard Efficiency - Extra Low Noise (XLN) - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Size 245 not avalaible in R513A.
14
RLC-SVX19G-GB
General Data
Table 3b – General Data RTAF 090-185 Standard Efficiency - Extra Low Noise (XLN) - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)325357388419450502544603
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)163177191202213243270274
Unit rated amps (Max compressor+fan+control)(A)264287310331352399440446
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.890.890.890.880.870.880.890.89
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142119/142119/163119/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE XLNSE XLNSE XLNSE XLNSE XLNSE XLNSE XLNSE XLN
16
RLC-SVX19G-GB
General Data
Table 4a – General Data RTAF 090-245 Standard Efficiency - AC Extra Low Noise - R134a - R513A
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Size 245 not avalaible in R513A.
18
RLC-SVX19G-GB
General Data
Table 4b – General Data RTAF 090-185 Standard Efficiency - AC Extra Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)328359389420451503545606
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)158.5172.5186.5197.5208.5238.4265.4268.3
Unit rated amps (Max compressor+fan+control)(A)263.7286.7309.7330.7351.7398.6439.5445.3
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.870.870.870.870.870.870.870.87
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150/150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN
20
RLC-SVX19G-GB
General Data
Table 5a – General Data RTAF 090-245 High Efficiency - Standard and Low Noise - R134a - R513A
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090105125145155175190205245 (10)
HE SN LN HE SN LNHE SN LN HE SN LNHE SN LN HE SN LN HE SN LNHE SN LN HE SN LN
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) Size 245 not avalaible in R513A.
(kg)43/4142/4045/4148/4650/4460/4662/5666/6266/62
22
RLC-SVX19G-GB
General Data
Table 5b – General Data RTAF 090-185 High Efficiency - Standard and Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)331365397430463512557614
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)165179193204215246273277
Unit rated amps (Max compressor+fan+control)(A)280303326347368417458466
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.860.860.860.860.850.860.870.86
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150/150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN SE AC XLN
24
RLC-SVX19G-GB
General Data
Table 6a – General Data RTAF 090-205 High Efficiency- AC Extra Low Noise - R134a - R513A
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090105125145155175190205
Cooling Capacity (1)(kW)330381450529572627683744
Unit electrical data (2) (3) (5)
Maximum Power input in cooling (kW)136157185216239262287310
Unit rated amps (Max compr +Fan+Control)(A)226264314370405444485524
Unit start up amps (Starting Amps of the largest compr+RLA
of 2nd compr+RLA of all fans+ control)
Displacement Power Factor (DPF) 0.880.860.860.850.860.850.860.86
Max power cable cross section(mm2)1x2401x2401x2402x3002x3002x3002x3002x300
Disconnect switch size(A)400400500630630800800800
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4550/5070/5070/7085/70100/70100/85100/100
Max Compr Power input Circuit 1/Circuit 2kW60/6071/7199/7199/99121/99144/99144/121144/144
Max Amps Circuit 1 / Circuit 2 (3) (5)(A)97/97116/116166/116166/166201/166240/166240/201240/240
Start up Amps Circuit 1 / Circuit 2 (3) (5)(A)144/144180/180291/180291/291354/291354/291354/354354/354
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN
26
RLC-SVX19G-GB
General Data
Table 6b – General Data RTAF 090-185 High Efficiency- AC Extra Low Noise - R1234 ze
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090100110120130145155185
Cooling Capacity (1)(kW)328360392424457506549607
Unit electrical data (2) (3) (4)
Maximum Power input in cooling(kW)161175189200211241268271
Unit rated amps (Max compressor+fan+control)(A)269292315336357404445451
Unit start up amps starting Amps of the larges compr+RLA
of 2nd compr+RLA of all fans+control)
Displacement Power Factor (DPF)0.870.870.870.860.860.870.870.87
Max power cable cross section mm
Disconnect switch size(A)400400500500500630630630
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4555/4555/5565/5565/6578/6578/7878/78
Max Compr Power input (Circuit 1 / Circuit 2)kW73/7387/7387/8798/8798/98125/98125/125125/125
Max Amps Circuit1 / Circuit 2 (3) (5)(A)119/119142/119142/142163/142163/163204/163204/204204/204
Start up Amps Circuit1 / Circuit 2 (3)(5)(A)217/217259/217259/259291/259 291/291354/291354/354354/354
Motor RPM(rpm)30003000300030003000300030003000
Oil sump heater Circuit1 / Circuit 2(W)150/150
Evaporator
Quantity#11111111
TypeFlooded shell and tube heat exchanger
Evaporator model115B115A115A165C165B200C200C200B
Evaporator Water Content volume(l)5158586474898999
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19 = p). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
(10) OIL0066E or OIL0067E may have been used on early orders and there is no restriction to continue to use them but preferable oil is OIL00315 or
OIL00317.
HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN HE AC XLN
28
RLC-SVX19G-GB
General Data
Table 7a – General Data RTAF 090-205 Extra Efficiency - Standard and Low Noise - R134a - R513A
RTAFRTAFRTAFRTAFRTAFRTAFRTAFRTAF
090105125145155175190205
XE SN LNXE SN LN XE SN LNXE SN LN XE SN LNXE SN LN XE SN LNXE SN LN
Cooling Capacity (1)(kW)326380447526569633690752
Unit electrical data (2) (3) (5)
Maximum Power input in cooling(kW)141.1162.3190.5222.6245.0267.9294.2317.1
Unit rated amps (Max compr +Fan+Control) (A)227265315371406445486525
Unit start up amps (Starting Amps of the largest
compr+RLA of 2nd compr+RLA of all fans+ control)
Unit Power factor0.900.890.880.870.870.870.880.87
Max power cable cross section (mm²)2402402402*3002*3002*3002*3002*300
Disconnect switch size(A)400400500630630630800800
Compressor
Quantity#22222222
TypeScrewScrewScrewScrewScrewScrewScrewScrew
Model (9)45/4550/5070/5070/7085/70100/70100/85100/100
Max Compr Power input Circuit 1/Circuit 2kW60/6071/7199/7199/99121/99144/99144/121144/144
Max Amps Circuit 1 / Circuit 2 (3) (5)(A)97/97116/116166/116166/166201/166240/166240/201240/240
Start up Amps Circuit 1 / Circuit 2 (3) (5)(A)144/144180/180291/180291/291354/291354/291354/354354/354
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser air temperature 35°C - for detailed performances consult
Order Write Up.
(2) Under 400V/3/50Hz.
(3) Rated Condition without Pump Package.
(4) Percent minimum load may be adjusted around 15%-20% according to operating conditions by local sales office.
(5) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(6) Not applicable for Glycol application - see tables with Minimum Flow with Glycol.
(7) Max speed - range is 60% to 100% of max speed.
(8) Refrigerant charge may vary according to option - for instance +20% for process (digit 19=P). For real value refer to unit nameplate.
(9) Data containing information on two circuits shown as follows: ckt1/ckt2.
30