Trane OA1D, OA2D, OA3D Installation and Maintenance Manual

0 (0)

Installation, Operation,

and Maintenance

Horizon™ Outdoor Air Unit

Indirect Gas-Fired/Electric Heat

Models: OA1D, OA2D, OA3D

Important: Proper execution of the tasks outlined in this Installation, Operation, and Maintenance manual require and assume the technician has been certified as a start up technician for the Horizon Outdoor Air unit. This includes working knowledge of the Tracer TU program.

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

April 2014

OAU-SVX01E-EN

Introduction

Read this manual thoroughly before operating or servicing this unit.

Warnings, Cautions, and Notices

Safety advisories appear throughout this manual as required. Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

The three types of advisories are defined as follows:

WARNING

CAUTIONs

NOTICE:

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Important Responsible Refrigerant Practices

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING

Proper Field Wiring and Grounding

Required!

Failure to follow code could result in death or serious injury. All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes.

WARNING

Personal Protective Equipment (PPE)

Required!

Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.

Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.

When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.

If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

Failure to follow instructions could result in death or serious injury.

© 2014 Trane All rights reserved

OAU-SVX01E-EN

Introduction

WARNING

Contains Refrigerant!

System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.

Failure to follow proper procedures or the use of nonapproved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage.

WARNING

Hazard of Explosion and Deadly Gases!

Never solder, braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present. Always remove refrigerant by following the guidelines established by the EPA Federal Clean Air Act or other state or local codes as appropriate. After refrigerant removal, use dry nitrogen to bring system back to atmospheric pressure before opening system for repairs. Mixtures of refrigerants and air under pressure may become combustible in the presence of an ignition source leading to an explosion. Excessive heat from soldering, brazing or welding with refrigerant vapors present can form highly toxic gases and extremely corrosive acids. Failure to follow all proper safe refrigerant handling practices could result in death or serious injury.

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission. Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

OAU-SVX01E-EN (17 Apr 2014)

Model number updates

OAU-SVX01E-EN

3

Sequence of Operation

Table of Contents

 

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . 2

Warnings, Cautions, and Notices . . . . .

. . . 2

Important Environmental Concerns . . . . . 2

Important Responsible Refrigerant Practices

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . 2

Model Number Descriptions . . . . . . . . . . .

. . . 6

Horizon Outdoor Air Unit . . . . . . . . . . . .

. . . 6

General Information . . . . . . . . . . . . . . . . . .

. . . 9

Overview of Manual . . . . . . . . . . . . . . .

. . . 9

Model Number Description . . . . . . . . .

. . . 9

Unit Nameplate . . . . . . . . . . . . . . . . . .

. . . 9

Compressor Nameplate . . . . . . . . . . . . .

. . 9

Unit Description . . . . . . . . . . . . . . . . . . .

. . 9

Indoor Fan Failure Input . . . . . . . . . . . .

. . 9

Low Pressure Control ReliaTel Control

. . 9

Refrigerant Circuits . . . . . . . . . . . . . . . .

. . 9

High Pressure Control ReliaTel Control

. . 9

Space Temperature / RH Sensor (Optional)

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 10

High Temperature Sensor . . . . . . . . . . .

. 10

Outdoor Air Temperature and Relative Hu-

midity Sensor . . . . . . . . . . . . . . . . . . . . .

. 10

Control Input (Occupied / Unoccupied)

. 10

Hot Gas Reheat . . . . . . . . . . . . . . . . . . . .

. 10

100 Percent Outdoor Air Hood with Damper

and Filters . . . . . . . . . . . . . . . . . . . . . . . .

. 10

Modulating Indirect Gas-Fired Burner

. . 10

Through the Base Electrical with Disconnect

Switch . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 10

Through the Base Gas Piping . . . . . . . .

. 10

Hinged Access Doors . . . . . . . . . . . . . . .

. 10

Modulating Electric Heat . . . . . . . . . . . .

. 10

Unit Inspection . . . . . . . . . . . . . . . . . . . . . .

. 11

First Aid Measures . . . . . . . . . . . . . . . . .

. 11

Storage . . . . . . . . . . . . . . . . . . . . . . . . . .

. 11

Unit Clearances . . . . . . . . . . . . . . . . . . .

. 11

Unit Clearances, Curb Dimensions, and Dimen-

sional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. 12

OA1 Units . . . . . . . . . . . . . . . . . . . . . . . . . .

. 12

Unit Clearances . . . . . . . . . . . . . . . . . . .

. 12

Curb Dimensions . . . . . . . . . . . . . . . . . . . .12

Dimensional Data . . . . . . . . . . . . . . . . . . . .13

OA2 Units . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

Unit Clearances . . . . . . . . . . . . . . . . . . . . .14

Curb Dimensions . . . . . . . . . . . . . . . . . . . .15

Dimensional Data . . . . . . . . . . . . . . . . . . . .15

OA3 Units . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

Unit Clearances . . . . . . . . . . . . . . . . . . . . .16

Curb Dimensions . . . . . . . . . . . . . . . . . . . .17

Dimensional Data . . . . . . . . . . . . . . . . . . . .17

Unit Weight and Rigging . . . . . . . . . . . . . . . . .18

Unit Weight . . . . . . . . . . . . . . . . . . . . . . . . .18

Corner Weight . . . . . . . . . . . . . . . . . . . . . .19

Rigging . . . . . . . . . . . . . . . . . . . . . . . . . . . .20

. . . . . . . . . . . . . . . . . . .21

Space Control with Indirect Gas-Fired or Electric Heat and Modulating HGRH, ERV, and Powered Ex. . . . . . . . . . . . . . . . . . . . . . . . . . .21

Sequence of Operation—”Occupied” . . .21

Sequence of Operation—”Unoccupied” .22

Discharge Air Control with Indirect Gas-Fired or Electric Heat and Modulating HGRH, ERV, and Powered Ex. . . . . . . . . . . . . . . . . . . . . . .23

Sequence of Operation—”Occupied” . . .23

Sequence of Operation—”Unoccupied” .24

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . .25

General Unit Requirements . . . . . . . . . . . .25

Main Electrical Power Requirements . . . .26

Condensate Drain Configuration . . . . . . .26

Filter Installation . . . . . . . . . . . . . . . . . . . . .26

Field Installed Power Wiring . . . . . . . . . . .26

Main Unit Power . . . . . . . . . . . . . . . . . . . . . .28

Standard Wiring . . . . . . . . . . . . . . . . . . . . .28

Voltage Imbalance . . . . . . . . . . . . . . . . . . .28

Electrical Phasing (Three-Phase Motors) .29

Compressor Crankcase Heaters . . . . . . . .29

Main Unit Display and ReliaTel Controls .30

Field-Installed Control Wiring . . . . . . . . . .30

Control Power Transformer . . . . . . . . . . .30

4

OAU-SVX01E-EN

Controls Using 24 Vac . . . . . . . . . . . . . . . 30

Controls Using DC Analog Input/Output

(Standard Low Voltage Multiconductor Wire)

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

DC Conductors . . . . . . . . . . . . . . . . . . . . . . . 31

System Configuration and Pre-Start . . . . . . 33

Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Indirect Gas-Fired Heating Start-Up . . . . . 36

Start-Up Procedure . . . . . . . . . . . . . . . . . 36

Safety Controls . . . . . . . . . . . . . . . . . . . . . 39

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Monthly Maintenance . . . . . . . . . . . . . . . . . 40

Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Supply/Return Air Smoke Detector Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

Cooling Season . . . . . . . . . . . . . . . . . . . . 40

Heating Season . . . . . . . . . . . . . . . . . . . . 40

Condenser Coil Cleaning . . . . . . . . . . . . . 40

Final Process . . . . . . . . . . . . . . . . . . . . . . . . . 41

Performance Data . . . . . . . . . . . . . . . . . . . . . . 42

Superheat and Refrigeration Circuit Data 48

Alarms and Troubleshooting . . . . . . . . . . . . 52

Microprocessor Control . . . . . . . . . . . . . . 52

System Alarms . . . . . . . . . . . . . . . . . . . . . 52

Sensor Failure Alarm Display . . . . . . . . . 52

RTRM Failure Modes . . . . . . . . . . . . . . . . 54

Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

OAU Filter Guide . . . . . . . . . . . . . . . . . . . . . 55

OAU-SVX01E-EN

5

Model Number Descriptions

O A 2 D 3 0 0 A 4 - D 1 A 1 A 0 G M - G 1 K B 0 A C 3 C J - A 4 1 B 1 0 2 A 0

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39

Horizon Outdoor Air

Unit

Digit 1, 2 — Unit Type

OA = Outdoor Air

Digit 3 — Cabinet Size

1= 625 cfm–4,000 cfm

2= 1,500 cfm–9,000 cfm

3= 3,750 cfm–13,500 cfm

Digit 4 — Major Design

Sequence

C= Revision 4

D= Revision 5

E= Heat Pump

Digit 5, 6, 7 — Normal Gross Cooling Capacity (MBh)

000= No Cooling

060 = 5 Tons High Efficiency

072 = 6 Tons High Efficiency

084 = 7 Tons High Efficiency

096 = 8 Tons High Efficiency

120 = 10 Tons High Efficiency

144 = 12 Tons High Efficiency

180 = 15 Tons High Efficiency

210 = 17 Tons High Efficiency

240 = 20 Tons High Efficiency

264 = 22 Tons High Efficiency

300 = 25 Tons High Efficiency

360 = 30 Tons High Efficiency

420 = 35 Tons High Efficiency

480 = 40 Tons High Efficiency

540 = 45 Tons High Efficiency

600 = 50 Tons High Efficiency

648 = 54 Tons High Efficiency

Digit 8 — Minor Design

Sequence

A

B

Digit 9 — Voltage Selection

1

=

115/60/1

2

=

208-230/60/1

3

=

208-230/60/3

4

=

460/60/3

5

=

575/60/3

Digit 10 — Reserved for Future Use

Digit 11 — Evaporator Type

0 = No Cooling

A= DX 3-Row

B= DX 4-Row

C= DX 4-Row Interlaced

D= DX 6-Row Interlaced

E= DX 8-Row

F= Glycol/Chilled Water Coil

G= DX 4-Row with

MSP® Technology

Digit 12 — Hot Gas Reheat

0= No HGRH

1= Fin and Tube Modulating

2= Fin and Tube On/Off

3= Microchannel Modulating

4= Microchannel On/Off

Digit 13 — Compressor

0 = No Compressors

A= Scroll Compressors

B= Digital Scroll (1st Circuit Only)

C= Digital Scroll (1st and 2nd Circuit)

D= Variable Speed Scroll (1st Circuit Only)

E= Variable Speed Scroll (1st and

2nd Circuit)

Digit 14 — Condenser

0= No Condenser

1= Air-Cooled Fin and Tube

2= Air-Cooled Fin and Tube w/Head Pressure On/Off Control

3= Water-Cooled DX Condenser Copper/Steel

4= Air-Cooled Fin and Tube

w/Head Pressure Variable Speed

5= Air-Cooled Microchannel

6= Air-Cooled Microchannel w/Head Pressure On/Off Control

7= Air-Cooled Microchannel Variable Speed

8= Water-Cooled DX Condenser Copper/Nickel

Digit 15 — Refrigerant Capacity

Control

0 = No RCC Valve

A= RCC Valve on 1st Circuit

B= RCC Valve on 1st and 2nd Circuit

C= ERCC Valve on 1st Circuit

D= ERCC Valve on 1st and 2nd Circuit

E= HGBP Valve on 1st Circuit

F= HGBP Valve on 1st and

2nd Circuit

Digit 16 — Indoor Fan Motor (IFM)

0= Direct Drive w/VFD

1= Direct Drive (VFD by Others)

2= Belt Drive

3= Belt Drive w/VFD

4= Direct Drive w/Shaft Grounding Ring w/VFD

5= Special Motor Option

Digit 17 — Indoor Fan Wheel

A

=

122

B

=

122.6

C

=

150

D

=

150.6

E

=

165

F

=

165.6

G

=

182

H

=

182.6

J

=

200

K

=

200.6

L= 182 X 2

M= 182.6 X 2

Digit 18 — Indoor Fan Motor

Power (hp)

A= 1/2 hp—1800 rpm

B= 1/2 hp—3600 rpm

C= 3/4 hp—1800 rpm

D= 3/4 hp—3600 rpm

E= 1 hp—1800 rpm

F= 1 hp—3600 rpm

G= 1.5 hp—1800 rpm

H= 1.5 hp—3600 rpm

J= 2 hp—1800 rpm

K= 2 hp—3600 rpm

L= 3 hp—1800 rpm

M= 3 hp—3600 rpm

N= 5 hp—1800 rpm

P = 5 hp—3600 rpm

R= 7.5 hp—1800 rpm

S= 7.5 hp—3600 rpm

T= 10 hp—1800 rpm

U= 10 hp—3600 rpm

V= 15 hp—1800 rpm

W= 15 hp—3600 rpm

Digit 19 — Reserved for Future Use

Digit 20 — Heat Type (PRI/SEC)

0 = No Heat

A= Indirect-Fired (IF)

B= Direct-Fired (DF)

C = Electric—4-Stage

D= Electric—SCR Modulating

E= Dual Fuel (PRI-IF/SEC-DF)

F= Dual Fuel (PRI-ELEC/SEC-DF)

G= Dual Fuel (PRI-IF/SEC-ELEC)

H= Dual Fuel (PRI-ELEC/SEC-ELEC)

J= Hot Water

K= Steam

Digit 21 — Primary Fuel Type

0= No Heat

1= Natural Gas

2 = Propane

3= Electric—Open Coil

4= Electric—Sheathed Coil

5= Hot Water

6= Steam

6

OAU-SVX01E-EN

Model Number Descriptions

Digit 22 — Heat Capacity

(Primary Heat Source)

Digit

IF

ELEC

0

No Heat

No Heat

A

50 MBh

10 kW

B

75 MBh

20 kW

C

100 MBh

24 kW

D

125 MBh

28 kW

E

150 MBh

32 kW

F

200 MBh

40 kW

G

250 MBh

48 kW

H

300 MBh

60 kW

J

350 MBh

68 kW

K

400 MBh

79 kW

L

500 MBh

99 kW

M

600 MBh

111 kW

N

700 MBh

119 kW

P

800 MBh

139 kW

R

1000 MBh

159 kW

S179 kW

T199 kW

U215 kW

XSpecial Heater Option

Digit 23 — Heat Capacity

(Secondary Heat Source)

Digit

IF

ELEC

DF

0

No Heat/No Secondary Heat

A

50 MBh

10 kW

300 MBh

B

75 MBh

20 kW

600 MBh

C

100 MBh

24 kW

900 MBh

D

125 MBh

28 kW

1200 MBh

E

150 MBh

32 kW

 

F

200 MBh

40 kW

 

G

250 MBh

48 kW

 

H

300 MBh

60 kW

 

J

350 MBh

68 kW

 

K

400 MBh

79 kW

 

L

500 MBh

99 kW

 

M

600 MBh

111 kW

 

N

700 MBh

119 kW

 

P

800 MBh

139 kW

 

R

1000 MBh

159 kW

 

S179 kW

T199 kW

U215 kW

Digit 24 — Corrosive

Environment Package

0= No Corrosive Package

1= S/S Cabinet, Basepan, Eco-Coated Coils

2= S/S Cabinet, Basepan

3= S/S Basepan, Eco-Coated Coils

4= S/S Coil Casing

5= S/S Interior Casing

6= Eco-Coated Coils

7= S/S Coil Casing with

Eco-Coated Coils

8= Copper/Copper Condenser, Evap, HGRH Coils

Digit 25, 26 — Unit Controls

00 = Non-DDC—Electromechanical

AA= Trane—Discharge Air Control w/LON Read-Write w/Display

AB = Trane—Space Control w/LON Read-Write w/Display

AC = Trane—Discharge Air Control w/BACnet® (No Display)

AD = Trane—Space Control w/BACnet (No Display)

AF = Trane—Discharge Air Control w/BACnet w/Display

AG = Trane—Space Control w/BACnet w/Display

AH = Trane—Discharge Air Control w/BACnet w/Display

AI = Trane—Discharge Air Control w/LON Read-Write (No Display)

AJ = Trane—Space Control

w/LON Read-Write (No Display) AK = Trane—Multi-Zone VAV Control

w/LON Read-Write w/Display AL = Trane—Multi-Zone VAV Control

w/BACnet w/Display

AM = Trane—Multi-Zone VAV Control w/LON Read-Write (No Display)

AN = Trane—Multi-Zone VAV Control w/BACnet (No Display)

AO = Trane—Single-Zone VAV Control w/LON Read-Write w/Display

AP = Trane—Single-Zone VAV Control w/BACnet w/Display

AQ = Trane—Single-Zone VAV Control w/LON Read-Write (No Display)

AR = Trane—Single-Zone VAV Control w/BACnet (No Display)

Digit 27 — Powered Exhaust Fan

Motor (PFM) and Exhaust

Dampers

0= No Powered Exhaust

1= Direct Drive w/VFD and Gravity Dampers

2= Direct Drive (VFD by Others)

3= Belt Drive

4= Belt Drive w/VFD

5= Special Motor Option

6= Direct Drive w/VFD and Barometric Relief Damper

7= Direct Drive w/VFD and Isolation Dampers w/End Switch

8= Barometric Relief Dampers

(NO PFM)

Digit 28 — Powered Exhaust Fan

Wheel

0

=

No Powered Exhaust

A

=

122

B

=

122.6

C

=

150

D

=

150.6

E

=

165

F

=

165.6

G

=

182

H

=

182.6

J

=

200

K

=

200.6

L= 182 X 2

M= 182.6 X 2

Digit 29 — Powered Exhaust Fan

Motor Power

0 = No Powered Exhaust

A= 1/2 hp—1800 rpm

B= 1/2 hp—3600 rpm

C= 3/4 hp—1800 rpm

D= 3/4 hp—3600 rpm

E= 1 hp—1800 rpm

F= 1 hp—3600 rpm

G= 1.5 hp—1800 rpm

H= 1.5 hp—3600 rpm

J= 2 hp—1800 rpm

K= 2 hp—3600 rpm

L= 3 hp—1800 rpm

M= 3 hp—3600 rpm

N= 5 hp—1800 rpm

P = 5 hp—3600 rpm

R= 7.5 hp—1800 rpm

S= 7.5 hp—3600 rpm

T= 10 hp—1800 rpm

U= 10 hp—3600 rpm

V= 15 hp—1800 rpm

W= 15 hp—3600 rpm

Digit 30 — Reserved for Future Use

Digit 31 — ERV (Requires

Powered Exhaust)

0 = No ERV

A= ERV-Composite Construction

B= ERV—Composite Construction with Frost Protection w/VFD

C= ERV—Composite Construction with Bypass

D= ERV—Composite Construction with Frost Protection and Bypass

E= ERV—Aluminum Construction

F= ERV—Aluminum Construction with Frost Protection w/VFD

G= ERV—Aluminum Construction with Bypass

H= ERV—Aluminum Construction with Frost Protection and Bypass

Digit 32 — ERV Size

0

=

No ERV

1

=

3014

2

=

3622

3

=

4136

4

=

4634

5

=

5856

6

=

6488

7

=

6876

8

=

74122

Digit 33 — Damper Options

0= 100% OA 2-Position Damper

1= 100% OA 2-Position Damper w/RA 2-Position Damper

2= Modulating OA and RA Dampers w/Economizer

OAU-SVX01E-EN

7

Model Number Descriptions

Digit 34 — Filtration Options

A= Aluminum Mesh Intake Filters (ALM)

B= MERV-8,30%, and ALM

C= MERV-13, 80%, and ALM

D= MERV-14, 95%, and ALM

E= MERV-8 30%, MERV-13 80%, and ALM

F= MERV-8 30%, MERV-14 95%, and ALM

G= MERV-8, 30%, and ALM, with UVC

H= MERV-13, 80%, and ALM, with

UVC

J= MERV-14, 95%, and ALM, with UVC

K= MERV-8 30%, MERV-13 80%, ALM, and UVC

L= MERV-8 30%, MERV-14 95%, ALM, and UVC

M= MERV-8 30%, ALM, and TCACS

N= MERV-13 80%, ALM, and TCACS

P= MERV-14 95%, ALM, and TCACS

Q= MERV-8 30%, MERV-13 80%, ALM, and TCACS

R= MERV-8 30%, MERV-14 95%, ALM, and TCACS

X = Special Filter Options

Digit 35 — Smoke Detector (Factory-Installed)

0= No Smoke Detector

1= Supply Smoke Detector

2= Return Smoke Detector

3= Supply and Return Smoke Detector

Digit 36 — Electrical Options

0 = Non-Fused Disconnect

A= Fused Disconnect Switch

B= Non-Fused Disconnect w/Convenience Outlet

C= Fused Disconnect Switch w/Convenience Outlet

D= Dual Point Power w/Convenience Outlet

F= 65 SCCR Electrical Rating w/Non-Fused Disconnect

G= 65 SCCR Electrical Rating w/Fused Disconnect

H= 65 KAIC Electrical Rating w/Non-Fused Disconnect

J= 65 KAIC Electrical Rating w/Fused Disconnect

Digit 37 — Air Flow Monitoring

0= No Airflow Monitoring

1= Airflow Monitoring—IFM Piezo Ring

2= Airflow Monitoring—PE Piezo Ring

3= Airflow Monitoring—Outdoor Air with Display and IFM

w/Piezo Ring

4= Airflow Monitoring—IFM

Piezo Ring and PE Piezo Ring

5= Airflow Monitoring—Outdoor Air Monitoring w/Display Supply Air and Exhaust Air

w/Piezo Rings

Digit 38 — Accessories

0

=

No Options

A

=

Hailguards

B= LED Service Light and

C= Hailguards and LED Service Light

Digit 39 — Altitude

0= Sea Level to 1,000 Feet

1= 1,001 to 2,000 Feet

2= 2,001 to 3,000 Feet

3= 3,001 to 4,000 Feet

4= 4,001 to 5,000 Feet

5= 5,001 to 6,000 Feet

6= 6,001 to 7,000 Feet

7= Above 7,000 Feet

8

OAU-SVX01E-EN

General Information

Overview of Manual

Note: One copy of this document ships inside the control panel of each unit and is customer property. It must be retained by the unit’s maintenance personnel.

This booklet describes proper installation, operation, and maintenance procedures for air cooled systems. By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.

It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.

Model Number Description

All products are identified by a multiple-character model number that precisely identifies a particular type of unit. An explanation of the alphanumeric identification code is provided (see “Model Number Descriptions,” p. 6). Its use will enable the owner/operator, installing contractors, and service engineers to define the operation, specific components, and other options for any specific unit.

When ordering replacement parts or requesting service, be sure to refer to the specific model number and serial number printed on the unit nameplate.

Unit Nameplate

A Mylar® unit nameplate is located on the unit’s corner support next to the control box. It includes the unit model number, serial number, electrical characteristics, refrigerant charge, as well as other pertinent unit data.

Compressor Nameplate

The nameplate for the compressors are located on the side of the compressor.

Unit Description

Before shipment, each unit is leak tested, dehydrated, charged with refrigerant and compressor oil, and run tested for proper control operation.

The condenser coils are aluminum fin, mechanically bonded to copper tubing.

Direct-drive, vertical discharge condenser fans are provided with built-in thermal overload protection.

The Outdoor Air Unit Main Unit Display and ReliaTel™ Control Module (RTRM) are microelectronic control systems. The acronym RTRM is extensively throughout this document when referring to the control system network.

The Main Unit Display and the RTRM are mounted in the Main Control Panel. The Main Unit Display and RTRM

receive information from sensors and customer binary contacts to satisfy the applicable request for ventilation, cooling, dehumidification and heating.

Indoor Fan Failure Input

The Indoor Fan Failure Switch (IFFS) is connected to verify indoor fan operation.

When there is a call for the indoor fan to be energized, the differential pressure switch, connected to the Main Unit Display, must prove airflow within 30 seconds or the Main Unit Display will shut off all mechanical operations, lock the system out and send a diagnostic alarm to the Unit Display. The system will remain locked out until a reset is initiated through the MCM via the Alarm Reset Function on the Unit Display.

Low Pressure Control ReliaTel Control

This input incorporates the compressor low pressure control (CLP 1/2) of each refrigeration circuit and can be activated by opening a field supplied contact installed on the OAUTS.

If this circuit is open before the compressor is started, the ReliaTel™ control will not allow the affected compressor to operate. Anytime this circuit is opened for 1 continuous second during compressor operation, the compressor for that circuit is immediately turned “Off.” The compressor will not be allowed to restart for a minimum of 3 minutes should the contacts close.

If four consecutive open conditions occur during the first three minutes of operation, the compressor for that circuit will be locked out, and a manual reset will be required to restart the compressor.

Refrigerant Circuits

For 5–7 ton units, one refrigerant circuit shall incorporate a standard 6-row coil. For 8–54 ton units, two independent refrigerant circuits shall incorporate an interlaced coil. All circuits shall have thermal expansion valves (TXVs), service pressure ports and refrigerant line filter driers as standard. An area will be provided for replacement suction line driers. Refrigerant circuit one (1st Stage) is equipped with a factory installed and preset refrigerant capacity control (RCC) to prevent evaporator coil temperatures below approximately 38°F (114 lb suction). The refrigerant capacity device is not installed when the unit is equipped with a digital scroll.

High Pressure Control ReliaTel Control

The compressor high pressure controls (CHP 1/2/3/4) are wired in series between the compressor outputs on RTRM1 (CHP 1/2) and RTRM2 (CHP 3/4) and the compressor contactor coils. If one of the high pressure control switches opens, the respective RTRM senses a lack of current while calling for cooling and locks the compressor out.

OAU-SVX01E-EN

9

General Information

On dual circuit units, if the high pressure control opens, the compressor on the affected circuit is locked out. A manual reset for the affected circuit is required.

Space Temperature / RH Sensor (Optional)

Field installed, wall mounted temperature sensor (BAYSENS036A) and humidity to control space cooling, heating and dew point. Refer to “Space Control with Indirect Gas-Fired or Electric Heat and Modulating HGRH, ERV, and Powered Ex.,” p. 21 for specific details.

High Temperature Sensor

The Discharge Air Temperature Sensor (DTC) supplies a continuous signal to the MCM. Factory setting for Discharge Air Temperature (DTC) Discharge Air Temperature Setpoint (MDTS) is 90°F (adj 70–100°F), the unit will be shut down, and require a manual restart if Discharge Air Temperature exceeds MDTS for 10 minutes (adj 10–25 minutes). If DAT exceeds Discharge Air High Temperature Cutoff (DHCS) of 125°F for 10 minutes, the unit will shut down and require manual restart.

Outdoor Air Temperature and Relative

Humidity Sensor

This factory installed combination outdoor air sensor located in the outdoor air hood is designed to sense both outdoor air temperature and relative humidity for use by the microprocessor controller to make required ventilation, cooling, dehumidification and heating decisions. Refer to “Sequence of Operation,” p. 21 for detailed unit control and operational modes.

Control Input (Occupied / Unoccupied)

Terminals are provided on the terminal strip labeled OAUTS for a field installed dry contact or switch closure to put the unit in the Occupied or Unoccupied modes.

Hot Gas Reheat

This option shall consist of a hot-gas reheat coil located on the leaving air side of the evaporator. Refer to the “Sequence of Operation,” p. 21 for detailed unit control and operational modes.

100 Percent Outdoor Air Hood with Damper and Filters

Factory-installed and -integrated 100 percent outdoor air hood with damper controlled by a direct coupled actuator and 2 in. (50.80 mm) permanent and washable aluminum mesh filters (mist eliminators) removable through a hinged access panel. The unit is factory equipped with provisions to accept an optional field installed 100 percent return air damper controlled by a direct coupled actuator that is electrically interlocked with the outdoor air damper.

Modulating Indirect Gas-Fired Burner

The unit will have fully modulating, high turndown, indirect gas-fired heat. The heating section will include

high turn-down burners and a stainless steel tubular heat exchanger. The heat exchanger will be constructed of type 439 stainless steel and be a tubular design capable of draining internal condensate. External flue to be constructed of type 430 stainless steel.

Units will be suitable for use with natural gas or Liquid Propane (LP) gas.

Through the Base Electrical with Disconnect Switch

Factory installed 3-pole, molded case disconnect switch with provisions for through the base electrical connections will be included. The disconnect switch, with integral overcurrent circuit breaker, will be installed in the unit in a water tight enclosure with access through a hinged door. Factory wiring will be provided from the switch to the unit high voltage terminal block. The switch will be UL/CSA agency recognized.

Through the Base Gas Piping

The unit will include provisions for installing through the base gas piping. The factory installed option will have all piping necessary including an external shutoff piping yoke with pre-assembled, manual gas shut-off valve, elbows, and union. The manual shut-off valve will include an 1/8 in. (3.17 mm) NPT pressure tap. This assembly will require minor field labor to install.

Hinged Access Doors

Hinged access doors with hold open brackets will be factory-installed.

Modulating Electric Heat

The unit may have fully modulating, SCR, or Verniercontrolled, electric heat. The primary heating section will include open coil heating elements, automatic and manual cut-outs, low voltage controls, air proving switch, maximum 48 amps per circuit and fusing for heaters over 48 amps. For ductwork installation, refer to “Ductwork,” p. 25.

10

OAU-SVX01E-EN

General Information

Unit Inspection

WARNING

Fiberglass Wool!

Product may contain fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. Glass wool fibers may also cause respiratory, skin or eye irritation.

As soon as the unit arrives at the job site:

Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).

Verify that the power supply complies with the unit nameplate specifications.

Visually inspect the exterior of the unit, including the roof, for signs of shipping damage.

Visually inspect the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.

If concealed damage is discovered, notify the carrier’s terminal of damage immediately by phone and by mail. Concealed damage must be reported within 15 days.

Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.

Notify the appropriate sales representative before installing or repairing a damaged unit.

Avoid breathing fiberglass dust.

Use a NIOSH approved dust/mist respirator.

Avoid contact with the skin or eyes. Wear long-sleeved, loose-fitting clothing, gloves, and eye protection.

Wash clothes separately from other clothing: rinse washer thoroughly.

Operations such as sawing, blowing, tear-out, and spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.

First Aid Measures

Eye Contact

Flush eyes with water to remove dust. If symptoms persist, seek medical attention.

Skin Contact

Wash affected areas gently with soap and warm water after handling.

Storage

Take precautions to prevent condensate from forming inside the unit’s electrical compartments and motors if:

the unit is stored before it is installed; or,

the unit is set on the roof curb, and temporary heat is provided in the building. Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) from the ambient air until the unit is ready for start-up.

Note: Do not use the unit’s heater for temporary heat without first completing the start-up procedure detailed in “Start-Up,” p. 36.

The manufacturer will not assume any responsibility for equipment damage resulting from condensate accumulation on the unit’s electrical and/or mechanical components.

Unit Clearances

“Unit Clearances, Curb Dimensions, and Dimensional Data,” p. 12 contains figures that illustrate the minimum operating and service clearances for either a single or multiple unit installation: Figure 1, p. 12 and Figure 2, p. 12 for OA1 units,Figure 7, p. 14 through Figure 10, p. 15 for OA2 units, and Figure 15, p. 16 through Figure 18, p. 17 for OA3 units. These clearances are the minimum distances necessary to assure adequate serviceability, cataloged unit capacity, and peak operating efficiency.

Providing less than the recommended clearances may result in condenser coil starvation, “short-circuiting” of exhaust or recirculation of hot condenser air.

OAU-SVX01E-EN

11

Unit Clearances, Curb Dimensions, and Dimensional

Data

WARNING

Combustible Materials!

Maintain proper clearance between the unit heat exchanger, vent surfaces and combustible materials. Refer to unit nameplate and installation instructions for proper clearances. Improper clearances could result in a fire hazard. Failure to maintain proper clearances could result in death or serious injury or property damage.

OA1 Units

Unit Clearances

Figure 1. Typical installation clearances for OA1 unit

CLEARANCE FROM

TOP OF UNIT 72"

CLEARANCE 48"

CLEARANCE 36"

CLEARANCE 36"

CLEARANCE 60"

Figure 2. Typical installation clearances for OA1 unit with auxiliary cabinet

6'0"

7'0"

3'0"

4'0"

3'0"

3'0"

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

Curb Dimensions

Figure 3. Unit curb data for OA1 5–15 tons

3'-0"

4'-0"

 

8 õļ

7 öļ

3'-0"

2 öļ

3'-0"

1 õļ

öļ

4 ôļ

49ļ

õļ

19ļ

1 ôļ

RETU

RN

SUPPLY

1.00 TYP.

12

OAU-SVX01E-EN

Unit Clearances, Curb Dimensions, and Dimensional Data

Figure 4. Unit curb data for OA1 5–15 tons with auxiliary cabinet

öļ

1 õļ

Ɍļ

12 ɍļ

õļ

8 õļ

19"

7 öļ

1 ôļ

28öļ

 

 

S

 

U

 

P

 

PL

 

Y

1.00

TYP.

40" 3 ôļ

RETU

RN

GUTTER

 

GUTTER DETAIL

4 ôļ

Ɍļ

49"

 

 

ôļ

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

Dimensional Data

Figure 5. Unit dimensional data for OA1 5–15 tons (in.)

87.33

59.23

36.71

29.63

87.18

53.00

59.45

87.12

Figure 6. Unit dimensional data for OA1 5–15 tons with auxiliary cabinet (in.)

87.33

59.23 35.24

131.26

53.00

59.45

87.12

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

OAU-SVX01E-EN

13

Unit Clearances, Curb Dimensions, and Dimensional Data

OA2 Units

Unit Clearances

Figure 7. Typical installation clearances for OA2 unit

CLEARANCE FROM

TOP OF UNIT 72"

CLEARANCE 36"

CLEARANCE 48"

CLEARANCE 60"

CLEARANCE 36"

3'0"

4'0"

3'0"

3'0"

Figure 8. Typical installation clearances for OA2 unit with auxiliary cabinet

CLEARANCE FROM

TOP OF UNIT 72"

CLEARANCE 36"

CLEARANCE 48"

CLEARANCE 60"

CLEARANCE 36"

3'0"

4'0"

3'0"

3'0"

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

Figure 9. Typical installation clearances for OA2 unit

6'0"

7'0"

14

OAU-SVX01E-EN

Unit Clearances, Curb Dimensions, and Dimensional Data

Dimensional Data

Figure 10. Typical installation clearances for OA2 unit

with auxiliary cabinet

Figure 13. Unit dimensional data for OA2 12–30 tons

106.45

6'0"

7'0"

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

Curb Dimensions

Figure 11. Unit curb data for OA2 12–30 tons (in.)

 

 

2 õļ

ļ

29ļ

 

9 ôļ

 

 

 

R

 

 

ETUR

30ļ

 

N

 

 

1 õļ

 

 

SU

TYP.

öļ

PPL

 

 

 

Y

5 ôļ

 

 

56ļ

 

 

Figure 12. Unit curb data for OA2 12–30 tons with auxiliary cabinet (in.)

 

 

 

Ɍļ

58ļ

 

 

 

5 ôļ

16 Ɍļ

 

 

 

 

 

 

õļ

 

ļ

29ļ

 

 

9 Ɏļ

R

 

 

 

 

 

 

 

 

ET

 

 

 

 

U

 

 

 

 

R

30ļ

 

 

 

N

 

 

 

 

1 õļ

 

 

GUTTER

 

S

 

TYP.

 

 

U

 

 

öļ

 

P

PLY

 

 

 

 

 

GUTTER DETAIL

 

 

 

 

Ɍļ

5 ôļ

 

 

 

ôļ

56ļ

 

 

 

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

 

43.02

80.57

BASE TO BOTTOM

OF AIR INLET

106.00

60.00

135.52

66.83

94.21

Figure 14. Unit dimensional data for OA2 12–30 tons with auxiliary cabinet

62.51

106.10

43.02

BASE TO BOTTOM

OF AIR INLET

80.57

62.11

106.00

200.99

60.00

66.83

94.21

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

OAU-SVX01E-EN

15

Unit Clearances, Curb Dimensions, and Dimensional Data

OA3 Units

Unit Clearances

Figure 15. Typical installation clearances for OA3 unit

CLEARANCE FROM

TOP OF UNIT 72"

CLEARANCE 36"

CLEARANCE 48"

CLEARANCE 60"

CLEARANCE 36"

Figure 16. Typical installation clearances for OA3 unit with auxiliary cabinet

CLEARANCE FROM

TOP OF UNIT 72"

CLEARANCE 36"

CLEARANCE 48"

CLEARANCE 60"

CLEARANCE 36"

3'0"

3'0"

 

4'0"

 

 

3'0"

 

4'0"

3'0"

 

3'0"

 

3'0"

Note: Certain options require auxiliary cabinet. Refer to

project-specific unit submittals.

 

 

Figure 17.

Typical installation clearances for OA3 unit

6'0"

7'0"

16

OAU-SVX01E-EN

Trane OA1D, OA2D, OA3D Installation and Maintenance Manual

Unit Clearances, Curb Dimensions, and Dimensional Data

Dimensional Data

Figure 18. Typical installation clearances for OA3 unit

with auxiliary cabinet

Figure 21. Unit dimensional data for OA3 30–54 tons

6'0"

7'0"

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

Curb Dimensions

Figure 19. Unit curb data for OA3 30–54 tons

 

 

 

 

 

2 õļ

 

140ļ

 

5 ɏļ

RET

 

13 ôļ

 

 

 

 

 

 

 

 

 

 

U

 

 

 

 

 

R

 

 

 

 

 

N

 

33ļ

 

 

 

 

2 ɍļ

 

S

 

 

 

 

 

TYP.

 

 

U

 

 

 

 

 

P

 

 

 

 

 

PL

 

öļ

 

 

 

Y

 

 

 

 

 

 

5 ôļ

 

 

 

 

 

63ļ

 

 

 

 

 

Figure 20. Unit curb data for OA3 30–54 tons with auxiliary cabinet

Ɍļ 5 ɏļ5 ɍļ

202ļ 2 õļ

140ļ

13 ôļ

33ļ

2 ɍļ öļ

5 ôļ

63ļ

5 ɏļ

SUPPLY

RETU

RN

GUTTER

1ļ TYP.

GUTTER DETAIL

Ɍļ

ôļ

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

144.17

92.07

48.62

42.00

144.00

67.00

74.63

98.49

Figure 22. Unit dimensional data for OA3 30–54 tons with auxiliary cabinet

144.17

92.07

35.84

 

 

62.00

144.00

67.00

74.63

98.49

Note: Certain options require auxiliary cabinet. Refer to project-specific unit submittals.

OAU-SVX01E-EN

17

Loading...
+ 39 hidden pages