Trane TCD330B, TCD360B, TCD420B, TCD480B, TCD600B Installation And Maintenance Manual

...
0 (0)
Installation, Operation, and Maintenance
Voyager™ Commercial
27.5 to 50 Ton 60 Hz
Model Numbers
“B” and later design sequence TC*, TE*, YC*330B, 360B, 420B, 480B, 600B (60 Hz/3 phase) TC*, TE*, YC*275B, 305B, 350B, 400B, 500B (50 Hz/3 phase)
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.
August 2012 RT-SVX34F-EN
SAFETY WARNING
Warnings, Cautions and Notices
Warnings, Cautions and Notices. Note that warnings,
cautions and notices appear at appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in personal injury or death. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.
Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.
ATT EN TI ON : Warnings, Cautions and Notices appear at
appropriate sections throughout this literature. Read these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.
Indicates a situation that could result in equipment or property-damage only
Personal Protective Equipment (PPE) Required!
Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.
Before installing/servicing this unit, technicians MUST put on all Personal Protective Equipment (PPE) recommended for the work being undertaken. ALWAYS refer to appropriate MSDS sheets and OSHA guidelines for proper PPE.
When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS sheets and OSHA guidelines for information on allowable personal exposure levels, proper respiratory protection and handling recommendations.
If there is a risk of arc or flash, technicians MUST put on all Personal Protective Equipment (PPE) in accordance with NFPA 70E or other country-specific requirements for arc flash protection, PRIOR to servicing the unit.
Failure to follow recommendations could result in death or serious injury.
WARNI NG
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants­including industry replacements for CFCs such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNI NG
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
Overview of Manual
One copy of the appropriate service literature ships inside the control panel of each unit. The procedures discussed in this manual should only be performed by qualified, experienced HVAC technicians.
Note: Do not release refrigerant to the atmosphere! If
adding or removing refrigerant is required, the service technician must comply with all federal, state, and local laws.
This booklet describes the proper installation, startup, operation, and maintenance procedures for TC_, TE_, and YC_22.9 to 50 Ton CV (Constant Volume), VAV (Variable Air Volume), and SZ VAV (Single Zone Variable Air Volume) applications. Refer to the table of contents for a listing of specific topics. Refer to “Diagnostics,” p. 104 for troubleshooting information.
© 2012 Trane All rights reserved RT-SVX34F-EN
By carefully reviewing the information within this manual and following the instructions, the risk of improper operation and/or component damage will be minimized.
It is important that periodic maintenance be performed to help assure trouble free operation. A maintenance schedule is provided at the end of this manual. Should equipment failure occur, contact a qualified service organization with qualified, experienced HVAC technicians to properly diagnose and repair this equipment.
Revision History
RT-SVX34F-EN (10 August 2012)
Motors with Internal Shaft Grounding Ring
Updated Model Number Description, Installation Electrical, Unit Wiring Diagrams
Warnings, Cautions and Notices
60 Hz units with standard options are certified by Underwriters Laboratory.
RT-SVX34F-EN 3
Table of Contents
Model Number Description . . . . . . . . . . . . . . . 7
60 Hz Description . . . . . . . . . . . . . . . . . . . . . . 7
50 Hz Description . . . . . . . . . . . . . . . . . . . . . . 9
General Information . . . . . . . . . . . . . . . . . . . . 11
Commonly Used Acronyms and Abbrevia-
tions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
About the Unit . . . . . . . . . . . . . . . . . . . . . 11
Precautionary Measures . . . . . . . . . . . . . 12
Unit Inspection . . . . . . . . . . . . . . . . . . . . . 12
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Unit Dimensions and Weights . . . . . . . . . . . 13
Recommended Clearances . . . . . . . . . . . . . 13
Roof Curb and Ductwork . . . . . . . . . . . . . . . 13
Horizontal Ductwork . . . . . . . . . . . . . . . . . 13
Unit Rigging and Placement . . . . . . . . . . . 19
Installation General Requirements . . . . . . . 21
Condensate Drain Connection . . . . . . . . . . 21
O/A Sensor & Tubing Installation . . . . . . . 21
Units with Statitrac™ . . . . . . . . . . . . . . . . . 21
Installation Electrical . . . . . . . . . . . . . . . . . . . . 23
Disconnect Switch External Handle (Factory Mounted Option)
. . . . . . . . . . . . . . . . . . . . . 23
Main Power Wiring . . . . . . . . . . . . . . . . . . . 23
Through-the-Base Electrical (Optional Acces-
sory) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Electrical Wire Sizing and Protection Device Equations
Low Voltage Wiring . . . . . . . . . . . . . . . . . 28
Control Power Transformer . . . . . . . . . . . 28
Field Installed AC Control Wiring . . . . . . 28
Field Installed DC Control Wiring . . . . . . 29
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Remote Panels and Sensors . . . . . . . . . . . 32
Constant Volume and Single Zone VAV Con-
trol Options . . . . . . . . . . . . . . . . . . . . . . . . 32
Variable Air Volume (non-SZ VAV) Control
Options . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installation Piping . . . . . . . . . . . . . . . . . . . . . . 36
General Requirements . . . . . . . . . . . . . . . . 36
Connecting the Gas Supply Line to the Fur-
nace Gas Train . . . . . . . . . . . . . . . . . . . . . 36
Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Unit Control Modules . . . . . . . . . . . . . . . . . .38
RTRM - ReliaTel Refrigeration Module . . .38
ECA - Economizer Actuator (Optional) . . .38
PEA - Power Exhaust Actuator (Optional) 38
RTAM - ReliaTel Air Handler Module (Stan-
dard with Traditional VAV) . . . . . . . . . . . .38
Conventional Thermostat Connections
(Available Only with CV) . . . . . . . . . . . . . .39
TCI - Trane Communication Interface (Option-
al) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
LCI - LonTalk® Communication Interface (Op-
tional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
BCI - BACnet® Communication Interface (Op-
tional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Manual Motor Protectors (380V Through
575V Only) . . . . . . . . . . . . . . . . . . . . . . . . .40
System Operation . . . . . . . . . . . . . . . . . . . . .40
Economizer Operation with a Conventional
Thermostat (CV Only) . . . . . . . . . . . . . . . .40
Microelectronic Control Features . . . . . . .40
Economizer Operation with CV Controls .41
Modulating Power Exhaust . . . . . . . . . . . .41
Mechanical Cooling without an Economizer
(CV and SZ VAV) . . . . . . . . . . . . . . . . . . . . 42
Zone Temperature - Occupied Cooling (CV
and SZ VAV) . . . . . . . . . . . . . . . . . . . . . . . .42
Zone Temperature - Occupied Heating (CV
and SZ VAV) . . . . . . . . . . . . . . . . . . . . . . . .42
Supply Fan (CV and SZ VAV) . . . . . . . . . .42
Supply Air Tempering (CV and SZ VAV) .42
Variable Air Volume Applications (Single Zone VAV)
Supply Fan Output Control . . . . . . . . . . . .43
Minimum Supply Fan Output . . . . . . . . . .43
Supply Fan Mode Operation . . . . . . . . . . .43
Setpoint Arbitration . . . . . . . . . . . . . . . . . .44
Ventilation Control . . . . . . . . . . . . . . . . . . .44
Space Pressure Control . . . . . . . . . . . . . . .46
Supply Air Temperature Control - Heating
and Cooling . . . . . . . . . . . . . . . . . . . . . . . . 46
. . . . . . . . . . . . . . . . . . . . . . . . . . . .43
4 RT-SVX34F-EN
Table of Contents
Variable Air Volume Applications (Traditional VAV)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Supply Air Temperature Control - Occupied
Cooling and Heating . . . . . . . . . . . . . . . . 47
Supply Air Temperature Control with an
Economizer . . . . . . . . . . . . . . . . . . . . . . . . 47
VHR Relay Output . . . . . . . . . . . . . . . . . . . 47
Zone Temperature Control without a Night Setback Panel or ICS - Unoccupied
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Zone Temperature Control without a Night Setback Panel or ICS - Unoccupied
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Morning Warm-up (MWU) Control . . . . . 47
Daytime Warm-up (DWU) Control . . . . . 47
Supply Duct Static Pressure Control . . . 48
Supply Air Temperature Reset . . . . . . . . 48
VAV Supply Air Tempering (Only Available
with Modulating Gas Heat) . . . . . . . . . . . 48
Constant Volume or Variable Air Volume Ap­plications (Single Zone or Traditional)
Off Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Zone Temperature - Unoccupied Cooling (CV
or SZ VAV Only) . . . . . . . . . . . . . . . . . . . . 49
Zone Temperature - Unoccupied Heating 49
Mechanical Cooling with an Economizer 49
Gas Heat Control . . . . . . . . . . . . . . . . . . . 49
Electric Heat Control . . . . . . . . . . . . . . . . 50
Clogged Filter Option . . . . . . . . . . . . . . . . 50
Ventilation Override . . . . . . . . . . . . . . . . . 50
Emergency Stop . . . . . . . . . . . . . . . . . . . . 50
Phase Monitor . . . . . . . . . . . . . . . . . . . . . 50
Low Pressure Control . . . . . . . . . . . . . . . . 51
Dehumidification Low Pressure Control . 51
High Pressure Cutout and Temperature Dis-
charge Limit . . . . . . . . . . . . . . . . . . . . . . . 51
Power Exhaust Control (Standard) . . . . . 51
Space Pressure Control - Statitrac . . . . . 51
Power Exhaust Control (Tracking) . . . . . 52
Lead/Lag Control . . . . . . . . . . . . . . . . . . . 52
Coil Frost Protection . . . . . . . . . . . . . . . . . 52
Dehumidification Frost Protection . . . . . 52
VFD Programming Parameters . . . . . . . . 52
. . . 49
Condenser Fan Sequencing Control . . . . .52
Preparing the Unit for Operation . . . . . . . .53
Electrical Phasing . . . . . . . . . . . . . . . . . . . .54
Voltage Supply and Voltage Imbalance . .54
Starting the Unit . . . . . . . . . . . . . . . . . . . . . . .55
Test Modes . . . . . . . . . . . . . . . . . . . . . . . . .55
Verifying Proper Fan Rotation . . . . . . . . . .59
Verifying Proper Air Flow (CFM) -
CV or VFD's . . . . . . . . . . . . . . . . . . . . . . . . .59
Exhaust Fan Operation . . . . . . . . . . . . . . .72
Economizer Damper Adjustment . . . . . . . .74
Economizer (O/A) Dampers . . . . . . . . . . . .74
Manual Fresh Air Damper . . . . . . . . . . . . .75
Starting the Compressor . . . . . . . . . . . . . . .76
Starting 27.5 to 35 Ton Units . . . . . . . . . . 76
Starting 40 to 50 Ton Units . . . . . . . . . . . . 76
Compressor Oil . . . . . . . . . . . . . . . . . . . . .77
Scroll Compressor Operational Noises . .85
Compressor Crankcase Heaters . . . . . . . .85
Charging by Subcooling . . . . . . . . . . . . . .85
Measuring Subcooling . . . . . . . . . . . . . . .85
Gas Heat Units . . . . . . . . . . . . . . . . . . . . . . . . 85
Electric Heat Units . . . . . . . . . . . . . . . . . . . . .86
Final Unit Checkout . . . . . . . . . . . . . . . . . . . .86
For Constant Volume Units . . . . . . . . . . . .86
For Variable Air Volume Units . . . . . . . . .86
For Single Zone Variable Air Volume
Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .87
Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . .88
General Unit Requirements . . . . . . . . . . . . .88
Downflow/Upflow Models: . . . . . . . . . . . .88
All Units: . . . . . . . . . . . . . . . . . . . . . . . . . . .88
Electrical Requirements . . . . . . . . . . . . . . . .88
Field Installed Control Wiring . . . . . . . . . . 88
Gas Heat Requirements . . . . . . . . . . . . . . . .88
Sequence of Operation . . . . . . . . . . . . . . . . . . .89
Mechanical Cooling Sequence Of Operation
Units Without an Economizer . . . . . . . . . .89
Economizer Operation Based on Dry Bulb 89
. . . . . . . . . . . . . . . . . . . . . . . . . .89
RT-SVX34F-EN 5
Table of Contents
Economizer Operation Based on Reference
Enthalpy . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Economizer Operation Based on Compara-
tive Enthalpy . . . . . . . . . . . . . . . . . . . . . . . 90
Dehumidification (Modulating Hot Gas Re­heat) Sequence of Operation
. . . . . . . . . . . 90
Gas Heat Sequence Of Operation . . . . . . . 91
Constant Volume (CV) Unit Fan Operation 91
Variable Air Volume (VAV) Unit Fan Opera­tion (2 Stage and Modulating Gas Heat) 91
Variable Air Volume (VAV) Unit Fan Opera-
tion (Modulating Gas Heat Only) . . . . . . 92
Ignition Control Module . . . . . . . . . . . . . . 92
High Temperature Limit Operation and Loca-
tion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Electric Heat Sequence Of Operation . . . . 92
Constant Volume (CV) . . . . . . . . . . . . . . . 92
Variable Air Volume (VAV) . . . . . . . . . . . 92
Variable Air Volume Applications (Single Zone VAV) Sequence of Operation
Occupied Cooling Operation . . . . . . . . . . 92
Occupied Heating Operation . . . . . . . . . . 93
Unoccupied Cooling and
Heating Operation . . . . . . . . . . . . . . . . . . 94
Dehumidification Operation . . . . . . . . . . 94
Failure and Overriding Conditions . . . . . 95
. . . . . . 92
Low Pressure Control (LPC) Sequence of Op­eration (ReliaTel Control)
. . . . . . . . . . . . . . 95
High Pressure Control and Temperature Dis­charge Limit (ReliaTel Control)
. . . . . . . . . 95
Electrical Phasing . . . . . . . . . . . . . . . . . . .102
Precision Suction Restrictor . . . . . . . . . .102
Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . .104
System Status/Diagnostics . . . . . . . . . . . .104
Terminal locations . . . . . . . . . . . . . . . . . . 104
System Status / Diagnostics checkout proce-
dure (DC volt meter required) . . . . . . . . . 104
Diagnostics (CV and SZ VAV Units Only) 105
Diagnostics (VAV only) . . . . . . . . . . . . . .105
Resetting Cooling and Ignition Lockouts 106
Zone Temperature Sensor (ZSM) Service In-
dicator . . . . . . . . . . . . . . . . . . . . . . . . . . . .106
RTRM Zone Sensor Module (ZSM) Tests 107
Programmable & Digital Zone Sensor
Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
ReliaTel Refrigeration Module (RTRM) .108
Economizer Actuator (ECA)
Test Procedures . . . . . . . . . . . . . . . . . . . .108
ReliaTel Air Module (RTAM) Tests . . . . .109
ReliaTel Air Module (RTOM) Tests . . . . .110
Compressor—Blink Codes . . . . . . . . . . . .110
Troubleshooting . . . . . . . . . . . . . . . . . . . . . .111
TR-200 VFD Programming Parameters . .116
Unit Wiring Diagram Numbers . . . . . . . . . . .118
Warranty and Liability Clause . . . . . . . . . . . .122
COMMERCIAL EQUIPMENT - 20 TONS AND LARGER AND RELATED ACCESSORIES
.122
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Fan Belt Adjustment . . . . . . . . . . . . . . . . . . 96
Monthly Maintenance . . . . . . . . . . . . . . . . . 98
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Cooling Season . . . . . . . . . . . . . . . . . . . . 98
Heating Season . . . . . . . . . . . . . . . . . . . . 99
Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . 100
Fall Restraint . . . . . . . . . . . . . . . . . . . . . . . . 100
Refrigeration System . . . . . . . . . . . . . . . . . 101
Refrigerant Evacuation and Charging . 101
Charge Storage . . . . . . . . . . . . . . . . . . . . 101
Compressor Oil . . . . . . . . . . . . . . . . . . . . 101
Compressor Replacements . . . . . . . . . . . 102
6 RT-SVX34F-EN
Model Number Description
YCD 330 B E L A 0 A1
123 456 7 8 9 10 11 1213
60 Hz Description
Digit 1, 2 — Unit Function
TC = DX Cooling, No Heat TE = DX Cooling, Electric Heat YC = DX Cooling, Natural Gas Heat
Digit 3 — Unit Airflow Design
D = Downflow Supply and Return H = Horizontal Supply and Return F = Horizontal Supply and Upflow
Return
R = Downflow Supply and Horizontal
Return
Digit 4, 5, 6 — Nominal Cooling Capacity
330 = 27½ Tons 360 = 30 Tons 420 = 35 Tons 480 = 40 Tons 600 = 50 Tons
Digit 7 — Major Development Sequence
B = R-410A Refrigerant
Digit 8 — Power Supply
E = 208/60/3 F = 230/60/3 4 = 460/60/3 5 = 575/60/3
Digit 9 — Heating Capacity
0 = No Heat (TC only)
Note: The following digits apply to YC
units only.
L = Low Heat (YC only) H = High Heat (YC only) J = Low Heat-Stainless Steel Gas
Heat Exchanger (YC only)
K = High Heat-Stainless Steel Gas
Heat Exchangers (YC only)
M = Low Heat-Stainless Steel Gas
Heat Exchanger w/ Modulating control (27.5-35 ton YC only)
P = High Heat-Stainless Steel Gas
Heat Exchangers w/ Modulating control (27.5-35 ton YC only)
R = Low Heat-Stainless Steel Gas
Heat Exchanger w/ Modulating control (40-50 ton YC only)
T = High Heat-Stainless Steel Gas
Heat Exchangers w/ Modulating control (40-50 ton YC only)
1
4
Note: The following digits apply to TE
A = 36 kW (27 kW for 208v) B = 54 kW (41 kW for 208v) C = 72 kW D = 90 kW E = 108 kW
units only.
Digit 10 — Design Sequence
A = First
Digit 11 — Exhaust
0= None 1 = Barometric Relief (Available
w/ Economizer only)
2 = 100% Power Exhaust Fan
(Available w/ Economizer only)
3 = 50% Power Exhaust Fan
(Available w/ Economizer only)
4 = 100% Fresh Air Tracking Power
Exhaust Fan (Available w/ Economizer only)
5 = 50% Fresh Air Tracking Power
Exhaust Fan (Available w/ Economizer only)
6 = 100% Power Exhaust w/
Statitrac™
6
Digit 12 — Filter
A = 2” MERV 4, Std Eff, Throwaway
B = 2” MERV 8, High Eff, Throwaway
C = 4” MERV 8, High Eff, Throwaway
D = 4” MERV 14, High Eff, Throwaway
Filters
Filters
Filters
Filters
Digit 13 — Supply Fan Motor, HP
1= 7.5 Hp 2=10 Hp 3= 15 Hp 4 = 20 Hp
Digit 14 — Supply Air Fan Drive
3
Selections
A = 550 RPM H = 500 RPM B = 600 RPM J = 525 RPM C = 650 RPM K = 575 RPM D = 700 RPM L = 625 RPM E = 750 RPM M = 675 RPM F = 790 RPM N = 725 RPM G = 800 RPM
Digit 15 — Fresh Air Selection
A= No Fresh Air B = 0-25% Manual Damper C = 0-100% Economizer, Dry Bulb
Control
D = 0-100% Economizer,
Reference Enthalpy Control
E = 0-100% Economizer,
Differential Enthalpy Control
F = “C” Option and Low Leak
Fresh Air Damper
G = “D” Option and Low Leak
Fresh Air Damper
H = “E” Option and Low Leak
Fresh Air Damper
Digit 16 — System Control
1 = Constant Volume w/Zone
Temperature Control
2 = Constant Volume w/ Discharge Air
Control
4 = VAV Supply Air Temperature
Control w/Variable Frequency Drive w/o Bypass
5 = VAV Supply Air Temperature
Control w/Variable Frequency Drive and Bypass
6 = Single Zone VAV w/VFD w/o
Bypass
7 = Single Zone VAV w/VFD w/
Bypass
A = VAV Supply Air Temperature
Control w/VFD w/o Bypass w/ Motor Shaft Grounding Ring
B = VAV Supply Air Temperature
Control w/VFD w/Bypass w/Motor Shaft Grounding Ring
C = Single Zone VAV w/VFD w/o
Bypass w/ Motor Shaft Grounding Ring
D = Single Zone VAV w/VFD w/
Bypass w/Motor Shaft Grounding Ring
Note: Zone sensors are not included
with option and must be ordered as a separate accessory.
Miscellaneous Options 
Digit 17
A = Service Valves
2
Digit 18
B = Through the Base Electrical
Provision
Digit 19
C = Non-Fused Disconnect Switch
w/External Handle
RT-SVX34F-EN 7
Model Number Description
Digit 20
D = Factory-Powered 15A GFI
Convenience Outlet and Non-Fused Disconnect Switch w/External Handle
Digit 21
E = Field-Powered 15A GFI
Convenience Outlet
Digit 22
F = Trane Communication
Interface (TCI)
Digit 23
G = Ventilation Override
Digit 24
H = Hinged Service Access
Digit 25
H = Tool-less Condenser Hail Guards J = Condenser Coil Guards
Digit 26
K = LCI (LonTalk) B = BACnet Communications
Interface (BCI)
Digit 27
*=Unused Digit
Digit 28
M = Stainless Steel Drain Pans
Digit 29 — Condenser Coil Options
0 = Standard Efficiency
Condenser Coil
J = Corrosion Protected Condenser
Coil
Digit 30-31 — Miscellaneous Options
P = Discharge Temperature
Sensor
R = Clogged Filter Switch
Digit 32 — Dehumidification Option
T = Modulating Hot Gas Reheat
Model Number Notes
1. All voltages are across the line
starting only.
2. Option includes Liquid, Discharge,
Suction Valves.
3. Supply air fan drives A thru G are
used with 27½-35 ton units only and drives H thru N are used with 40 & 50 ton units only.
4. Electric Heat KW ratings are based
upon voltage ratings of 208/240/480/ 600 V. For a 240 V heater derated to 208 V, the resulting kW rating decreases from 36 kW to 27 kW, and from 54 kW to 41 kW. Voltage
offerings are as follows: (see Tab l e 17,
p. 46 for additional information):
Electric
Heater
Rated
Tons
Voltage
27½
to 35
40
and
50
5. The service digit for each model number contains 32 digits; all 32 digits must be referenced.
6. Ventilation override exhaust mode is not available for the exhaust fan with fresh air tracking power exhaust. VOM is available for the exhaust fan without fresh air tracking power exhaust.
27/3641/
208 x x
240 x x
480 xxxx
600 x x x
208 x
240 x
480 x x x x
600 x x x x
KW
54 72 90 108
8 RT-SVX34F-EN
Model Number Description
YCD 275 B C L A 0 A1
123 456 7 8 9 10 11 1213
50 Hz Description
Digits 1, 2 – Unit Function
TC = DX Cooling, No Heat TE = DX Cooling, Electric Heat YC = DX Cooling, Natural Gas Heat
Digit 3 – Unit Airflow Design
D = Downflow Supply and Return H = Horizontal Supply and Return F = Horizontal Supply and Upflow
Return
R = Downflow Supply and Horizontal
Return
Digits 4, 5, 6 – Nominal Cooling Capacity
275 = 22.9 Tons (82 kW) 305 = 25.4 Tons (89 kW) 350 = 29.2 Tons (105 kW) 400 = 33.3 Tons (120 kW) 500 = 41.7 Tons (148 kW)
Digit 7 – Major Development Sequence
B = R-410A Refrigerant
Digit 8 – Power Supply
C = 380/50/3 D = 415/50/3
Digit 9 – Heating Capacity
0 = No Heat (TC only) L = Low Heat (YC only) H = High Heat (YC only)
Note: When second digit is “E” for
Electric Heat, the following values apply in the ninth digit.
380V / 415V
A = 23 kW / 27 kW B = 34 kW / 40 kW C = 45 kW / 54 kW D = 56 kW / 67 kW E = 68 kW / 81 kW
Digit 10 – Design Sequence
A= First
Digit 11 – Exhaust6
0= None 1 = Barometric Relief (Available
w/Economizer only)
2 = 100% Power Exhaust Fan
(Available w/ Economizer only)
3 = 50% Power Exhaust Fan
(Available w/ Economizer only)
4 = 100% Fresh Air Tracking Power
Exhaust Fan (Available w/Economizer only)
5 = 50% Fresh Air Tracking Power
Exhaust Fan (Available w/ Economizer only)
6 = 100% Power Exhaust w/
Statitrac™
1
4
Digit 12 – Filter
A = 2” (51 MM) MERV 4, Std Eff,
B = 2” (51 MM) MERV 8, High Eff,
C = 4” (102 MM) MERV 8, High Eff,
D = 4” (102 MM) MERV 14, High Eff,
Throwaway Filters
Throwaway Filters
Throwaway Filters
Throwaway Filters
Digit 13 – Supply Fan Motor, HP
1 = 7.5 Hp (5.6 kW) 2 = 10 Hp (7.5 kW) 3=15 Hp (10 kW) 4 = 20 Hp (15 kW)
Digit 14 – Supply Air Fan Drive Selections
A = 458 RPM H = 417 RPM B = 500 RPM J = 437 RPM C = 541 RPM K = 479 RPM D = 583 RPM L = 521 RPM E = 625 RPM M = 562 RPM F = 658 RPM N = 604 RPM G = 664 RPM
3
Digit 15 – Fresh Air Selection
A= No Fresh Air B = 0-25% Manual Damper C = 0-100% Economizer, Dry Bulb
D = 0-100% Economizer,
E = 0-100% Economizer,
F = “C” Option and Low Leak
G = “D” Option and Low Leak
H = “E” Option and Low Leak
Control
Reference Enthalpy Control
Differential Enthalpy Control
Fresh Air Damper
Fresh Air Damper
Fresh Air Damper
Digit 16 – System Control
1 = Constant Volume w/ Zone
2 = Constant Volume w/ Discharge Air
4 = VAV Supply Air Temperature
5 = VAV Supply Air Temperature
6 = Single Zone VAV w/VFD w/o
7 = Single Zone VAV w/VFD w/
A = VAV Supply Air Temperature
B = VAV Supply Air Temperature
Temperature Control
Control
Control w/Variable Frequency Drive w/o Bypass
Control w/Variable Frequency Drive and Bypass
Bypass
Bypass
Control w/VFD w/o Bypass w/ Motor Shaft Grounding Ring
Control w/VFD w/Bypass w/Motor Shaft Grounding Ring
C = Single Zone VAV w/VFD w/o
Bypass w/ Motor Shaft Grounding Ring
D = Single Zone VAV w/VFD w/
Bypass w/Motor Shaft Grounding Ring
Note: Zone sensors are not included
with option and must be ordered as a separate accessory.
Miscellaneous Options Digit 17
A = Service Valves
2
Digit 18
B = Through the Base Electrical
Provision
Digit 19
C = Non-Fused Disconnect Switch
with External Handle
Digit 20
D= Factory-Powered 15A GFI
Convenience Outlet and Non-Fused Disconnect Switch with External Handle
Digit 21
E = Field-Powered 15A GFI
Convenience Outlet
Digit 22
F = Trane Communication
Interface (TCI)
Digit 23
G = Ventilation Override
Digit 24
H = Hinged Service Access
Digit 25
H = Tool-less Condenser Hail Guards J = Condenser Coil Guards
Digit 26
K = LCI (LonTalk) B = BACnet Communications
Interface (BCI)
Digit 27
* = Unused Digit
Digit 28
M = Stainless Steel Drain Pans
Digit 29 — Condenser Coil Options
0 = Standard Efficiency
Condenser Coil
J = Corrosion Protected Condenser
Coil
RT-SVX34F-EN 9
Model Number Description
Digit 30-31 — Miscellaneous Options
P = Discharge Temperature Sensor R = Clogged Filter Switch
Digit 32 — Dehumidification Option
T = Modulating Hot Gas Reheat
Model Number Notes
1. All voltages are across-the-line starting only.
2. Option includes Liquid, Discharge, Suction Valves.
3. Supply air fan drives A thru G are used with 22.9-29.2 ton (82-105 kW) units only and drives H through N are used with 33.3 and 41.7 ton (120-148 kW) units only.
4. Electric Heat kW ratings are based upon voltage ratings of 380/415 V. Heaters A, B, C, D are used with 22.9-
29.2 ton (82-105 kW) units only and heaters B, C, D, E are used with 33.3-
41.7 ton (120-148 kW) units only.
5. The service digit for each model number contains 32 digits; all 32 digits must be referenced.
6. Ventilation override exhaust mode is not available for the exhaust fan with fresh air tracking power exhaust. VOM is available for the exhaust fan without fresh air tracking power exhaust.
10 RT-SVX34F-EN
General Information
Commonly Used Acronyms and Abbreviations
BAS = Building Automation System PGA = Power Exhaust Actuator
CFM = Cubic Feet per Minute PSIG = Pounds Per Square Inch Gauge pressure
CLV = Cooling Valve (Reheat only) PHM = Phase monitor
COMM = Module Designation for TCI/LCI R/A = Return Air
CV = Constant Volume RAH = Return Air Humidity
CW = Clockwise RAT = Return Air Temperature sensor
CCW = Counterclockwise RH = Right Hand
DSP = Direct Space Pressure control RHP = Reheat Pumpout Solenoid
DTS = Discharge Air Sensor RHV = Reheat Valve
DWU = Daytime Warm-up RLP = Reheat Low Pressure Cutout
E/A = Exhaust Air RPM = Revolutions Per Minute
ECA = Economizer Actuator RTAM = ReliaTel Air Handler Module
EET = Entering Evaporator Temperature Sensor RTDM = ReliaTel Dehumidification Module
F/A = Fresh Air RTVM = ReliaTel Ventilation Module
FFS = Fan Failure Switch RTOM = ReliaTel Options Module
ICS = Integrated Comfort System (See BAS) RTRM = ReliaTel Refrigeration Module
IDM = Indoor Fan Motor S/A = Supply Air
I/O = Input/Output SPC = Space Pressure Calibration Solenoid
IOM =
LCI = LonTalk® Communication Interface SPT = Static Pressure Transducer
LCI-R = LonTalk Communication Interface with ReliaTel SZVAV = Single Zone Variable Air Volume
LH = Left Hand TCI = Trane Communication Interface
MAS = Mixed Air Sensor TCO = Temperature Cutout
MAT = Mixed Air Temperature TDL = Temperature Discharge Limit
MCHE Microchannel VAV = Variable Air Volume
MWU = Morning Warm Up VFD = Variable Frequency Drive
NSB = Night Setback (programmable ZSM BAYSENS119*) VHR = Ventilation Heat Relay (VAV box relay)
O/A = Outside Air W.C. = Water Column
OAH = Outside Air Humidity XFSP = Exhaust Fan Setpoint
OAT = Outside Air Temperature ZSM = Sensor, Zone Sensor, Zone Sensor Module, Zone Panel
Installation, Operation and Maintenance manual (Ships with each unit)
SPP = Space Pressure Transducer
About the Unit
Overall unit dimensional data is illustrated in Figure 1,
p. 13 to Figure 9, p. 17. Each package rooftop unit ships
fully assembled and charged with the proper refrigerant quantity from the factory. They are controlled by a microelectronic unit control processor. Several solid state modules are grouped to form the “Control System”. The number of modules within any given control system will be dependent upon the options and accessories ordered with the unit. Acronyms are used extensively throughout this manual when referring to the “Control System”.
RT-SVX34F-EN 11
Basic unit components include:
Scroll compressors
One (1) Intertwined Evaporator Coil
One (1) Supply Fan
Three (3) to Four (4) Condenser Fans
One (1) Microchannel Condenser Coil
Filters (type is dependent on option selection)
General Information
Precautionary Measures
WARN ING
Fiberglass Wool!
Product contains fiberglass wool. Disturbing the insulation in this product during installation, maintenance or repair will expose you to airborne particles of glass wool fibers and ceramic fibers known to the state of California to cause cancer through inhalation. You MUST wear all necessary Personal Protective Equipment (PPE) including gloves, eye protection, mask, long sleeves and pants when working with products containing fiberglass wool. Exposition to glass wool fibers without all necessary PPE equipment could result in cancer, respiratory, skin or eye irritation, which could result in death or serious injury.
- Avoid breathing fiberglass dust.
- Use a NIOSH approved dust/mist respirator.
- Avoid contact with the skin or eyes. Wear long-sleeved,
loose-fitting clothing, gloves, and eye protection.
- Wash clothes separately from other clothing: rinse
washer thoroughly.
- Operations such as sawing, blowing, tear-out, and
spraying may generate fiber concentrations requiring additional respiratory protection. Use the appropriate NIOSH approved respiration in these situations.
First Aid Measures
Eye Contact - Flush eyes with water to remove dust. If symptoms persist, seek medical attention.
Skin Contact - Wash affected areas gently with soap and warm water after handling.
An optional roof curb, specifically designed for the Voyager commercial rooftop units is available from Trane. The roof curb kit must be field assembled and installed according to the latest edition of the curb installation guide.
Unit Inspection
As soon as the unit arrives at the job site:
Verify that the nameplate data corresponds to the sales order and bill of lading (including electrical data).
Visually inspect the exterior of the unit, including the roof, for physical signs of shipping damage.
Check for material shortages. Figure 11 , p. 18 illustrates where “ship with” items are placed inside the unit.
If the job site inspection reveals damage or material shortages, file a claim with the carrier immediately. Specify the type and extent of the damage on the “bill of lading” before signing. Do not install a damaged unit without the Appropriate Trane sales representative's approval!
Visually check the internal components for shipping damage as soon as possible after delivery and before it is stored. Do not walk on the sheet metal base pans.
WARNI NG
No Step Surface!
Do not walk on the sheet metal drain pan. Walking on the drain pan could cause the supporting metal to collapse, resulting in the operator/technician to fall. Failure to follow this recommendation could result in death or serious injury.
Bridging between the unit's main supports may consist of multiple 2 by 12 boards or sheet metal grating.
If concealed damage is discovered, notify the carrier's terminal office immediately by phone and by mail. Concealed damage must be reported within 15 days.
Request an immediate joint inspection of the damage by the carrier and the consignee. Do not remove the damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Storage
Take precautions to prevent condensate formation inside the unit electrical components and motors when:
a. The unit is stored before it is installed; or,
b. The unit is set on the roof curb and temporary
auxiliary heat is provided in the building.
Isolate all side panel service entrances and base pan openings (e.g., conduit holes, S/A and R/A openings, and flue openings) to minimize ambient air from entering the unit until it is ready for startup.
Do not use the unit heater as temporary heat without completing the startup procedures detailed under
“Startup,” p. 38.
Trane will not assume responsibility for equipment damage resulting from accumulation of condensate on the unit electrical components.
12 RT-SVX34F-EN
Unit Dimensions and Weights
Recommended Clearances
Adequate clearance around and above each Voyager Commercial unit is required to ensure proper operation and to allow sufficient access for servicing.
If the unit installation is higher than the typical curb elevation, a field constructed catwalk around the unit is recommended to provide safe, easy access for maintenance and servicing. Table 1, p. 19 lists the recommended clearances for single and multiple unit installation. These clearances are necessary to assure adequate serviceability, cataloged capacities, and peak operating efficiency.
If the clearances available on the job site appear to be inadequate, review them with your Trane sales representative.
Roof Curb and Ductwork
The curbs for the 27.5 to 50 Ton commercial rooftop units enclose the entire unit base area. They are referred to as “full perimeter” type curbs.
Step-by-step instructions for the curb assembly and installation with curb dimensions and curb configuration for “A”, “B”, and “C” cabinets ship with each Trane accessory roof curb kit. (See the latest edition of the curb installation guide) Follow the instructions carefully to assure proper fit when the unit is set into place.
The S/A and R/A ductwork adjoining the roof curb must be fabricated and installed by the installing contractor before the unit is set into place. Trane curbs include flanges around the openings to accommodate duct attachment.
Ductwork installation recommendations are included in the instruction booklet that ships with each Trane accessory roof curb kit.
Note: For sound consideration, cut only the holes in the
roof deck for the supply and return duct penetration. Do Not remove the roof decking from the inside perimeter of the curb.
the unit into the ductwork. Refer to figures beginning on page 13 for the S/A and R/A opening dimensions.
All outdoor ductwork between the unit and the structure should be weather proofed after installation is completed.
If optional power exhaust is selected, an access door must be field-installed on the horizontal return ductwork to provide access to exhaust fan motors.
Figure 1. 60 Hz 27½-35, 50 Hz 23-29 Tons (TCD, TED,
YCD l ow heat)
If a Trane curb accessory kit is not used:
a. The ductwork can be attached directly to the S/A
and R/A openings. Be sure to use a flexible duct connector at the unit.
b. For “built-up” curbs supplied by others, gaskets
must be installed around the curb perimeter flange, Supply Air opening, and Return Air openings.
c. Insulation must be installed on the bottom of the
condenser section of the unit.
Horizontal Ductwork
When attaching the ductwork to a horizontal supply or horizontal return unit, provide a water tight flexible connector at the unit to prevent noise transmission from
RT-SVX34F-EN 13
Unit Dimensions and Weights
1 1/4 (32)
3 1/4 (81)
NOTES:
1. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION.
179 3/4"
4565.65mm
42"
1066.8mm
83 13/16"
2128.8mm
90 1/16"
2287.5mm
180 5/16"
4579.9mm
90 3/8"
2295.5mm
5 3/8"
136.5mm
7 9/16"
192.1mm
3.25 [82.55mm] TO TOP OF FAN GRILLE
70 7/16"
1789.1mm
40 3/16"
1020.7mm
6 7/8"
174.6mm
1 1/4" [31.7mm] FEMALE
PVC PIPE
3/4" [19.0mm] NPT GAS INLET
SEE NOTE 2
CUSTOMER CONNECTION POINT
Figure 2. Rear view showing duct openings for horizontal supply and return, 60 Hz 27½-35, 50 Hz 23-29 Tons (TCH,
TEH, YCH low heat)
Notes:
For combination of horizontal and downflow openings
On horizontal units, the VFD is located between the
supply and return ductwork, which makes access limited.
Figure 3. 60 Hz 27½-35, 50 Hz 23-29 Tons (TC, TE, YC low heat)
(digit 3 = F or R) see Figure 1, p. 13 for appropriate downflow/upflow dimensions and Figure 2, p. 14 for appropriate horizontal dimensions.
Note: Dimensions in ( ) are mm, 1”= 25.4 mm.
14 RT-SVX34F-EN
Figure 4. 60 Hz 27½-35, 50 Hz 23-29 Tons (YD high heat)
1 1/4 (32)
3 1/4 (81)
191
Figure 5. Duct openings, 60 Hz 27½-35, 50 Hz 23-29 Tons (YH high heat)
Unit Dimensions and Weights
Notes:
On horizontal units, the VFD is located between the
supply and return ductwork, which makes access limited.
For combination of horizontal and downflow openings (digit 3 = F or R) see Figure 4, p. 15 for appropriate downflow/upflow dimensions and Figure 5, p. 15 for appropriate horizontal dimensions.
RT-SVX34F-EN 15
Unit Dimensions and Weights
5270.5mm
207 1/2"
42"
5 3/8"
83 13/16"
2128.8mm
7 9/16"
208 1/16"
5284.7mm
90 5/8"
2301.8mm
90 1/16"
70 7/16"
40 3/16"
6 15/16"
PVC PIPE FEMALE
1" [25.4MM] NPT GAS INLET
NOTES:
1. SEE ROOFCURB DRAWING FOR DETAILS ON FIELD DUCT FITUP AND CONNECTIONS
2. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION.
SEE NOTE 2
CUSTOMER CONNECTION POINT
1066.8mm
2287.5mm
136.5m
192.1m
3.25 [82.55mm] TO TOP OF FAN GRILLE
1789.1mm
1020.7mm
174.6mm
1 1/4" [31.7mm]
Figure 6. 60 Hz 27½-35, 50 Hz 23-29 Tons (YC high heat)
Note: Dimensions in ( ) are mm, 1”= 25.4 mm.
Figure 7. 60 Hz 40-50, 50 Hz 33-42 Tons (TD, TD, YD low and high heat)
16 RT-SVX34F-EN
Unit Dimensions and Weights
1 1/4 (32)
3 1/4 (81)
7 9/16"
232 3/8"
5902.3mm
232 3/4"
5911.8mm
90 5/8"
49 9/16"
1258.8mm
93 3/8"
2371.7mm
5 5/16"
90 1/16"
77"
1955.8mm
46 15/16"
1192.2mm
4 3/4"
120.6mm
NOTES:
1. SEE ROOFCURB DRAWING FOR DETAILS ON FIELD DUCT FITUP AND CONNECTIONS
2. SEE DETAIL HOOD DRAWING FOR HORIZONTAL / DOWNFLOW UNITS FOR ADDITIONAL DIMENSION AND LOCATION.
SEE NOTE 2
CUSTOMER CONNECTION POINT
2301.8mm
PVC PIPE FEMALE
1" [25.4MM] NPT HIGH HEAT GAS INLET
2287.5mm
136.5m
192.1m
3.25 [82.55mm] TO TOP OF FAN GRILLE
1 1/4" [31.7mm]
3/4" [19MM] NPT LOW HEAT GAS INLET
Figure 8. Duct openings, 60 Hz 40-50, 50 Hz 33-42 Tons (TH, TH, YH low and high heat)
Notes:
On horizontal units, the VFD is located between the
supply and return ductwork, which makes access limited.
For combination of horizontal and downflow openings (digit 3 = F or R) see Figure 7, p. 16 for appropriate downflow/upflow dimensions and Figure 8, p. 17 for appropriate horizontal dimensions.
Figure 9. 60 Hz 40-50, 50 Hz 33-42 Tons (TC, TE, YC low and high heat)
Note: Dimensions in ( ) are mm, 1”= 25.4 mm.
RT-SVX34F-EN 17
Unit Dimensions and Weights
Figure 10. Fresh air and power exhaust dimensions for TC*, TE*, and YC* units
Figure 11. Location of “Ship With” items for TC*, TE*, and YC* units
18 RT-SVX34F-EN
Unit Dimensions and Weights
Unit Rigging and Placement
WARN ING
Heavy Objects!
Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury.
Use spreader bars as shown in the diagram. Refer to the Installation manual or nameplate for unit weight. Refer to the Installation instructions located inside the control panel for further rigging information.
1. Verify that the roof curb has the proper gaskets installed and is level and square to assure an adequate curb-to-unit seal.
The units must be as level as possible in order to assure proper condensate flow out of the unit. The maximum side-to-side and end-to-end slope allowable in any application is listed in Table 2, p. 19.
Table 1. Minimum operating clearances installation
(horizontal, downflow, and mixed airflow configurations)
Recommended Clearances
Condenser
(a)
Coil
Single Unit
TC*, TE*, YC*
27.5 to 50 Tons
Multiple Unit
TC*, TE*, YC*
27.5 to 50 Tons
(a) Condenser coil is located at the end and side of the unit.
Economizer/ Exhaust End
6 Feet 8 Feet 4 Feet
Distance Between Units
Economizer/ Exhaust End End/Side
12 Feet 16 Feet 8 Feet
Orientation
End/Side
Service Side
Access
Service Side
Access
Table 2. Maximum slope
Cabinet
“A” (27.5 - 35 Ton Low Heat) 3 1/2 1 5/8
“B” (27.5 - 35 Ton High Heat) 4 1 5/8
“C” (All 40 and 50 Ton Units) 4 1/2 1 5/8
Note: Do not exceed these allowances. Correct the improper slope by
building up the curb base. The material used to raise the base must be adequate to support both the curb and the unit weight.
End to End
(inches)
Side to Side
(inches)
Figure 12. Unit rigging
Figure 13. Center of gravity
Y
Z (see note 2)
X
Table 3. Center of gravity
Center-of-Gravity (inches)
YC Low Heat
Dimension
Unit Model
***330/275* 41 76 33 41 84 33 42 76 33
***360/305* 43 77 33 43 85 33 44 77 33
***420/350* 42 78 33 42 86 33 43 78 33
***480/400* 42 111 35 42 111 35 42 111 35
***600/500* 43 108 35 43 108 35 43 108 35
Note: Center-of-gravity dimensions are approximate, and are based on the
unit equipped with: standard efficiency coils, standard efficiency motors, economizer, and throwaway filters.
Note: Z dimension is upward from the base of the unit.
Example: Locating the center-of-gravity for a YC-360 MBH High Heat unit with 100%
exhaust. X = 43 inches inward from the control panel side Y = 85 inches inward from the compressor end Z = 33 inches upward from the base
XY ZXY ZXY Z
YC High Heat
Dimension
TC/TE
Dimension
RT-SVX34F-EN 19
Unit Dimensions and Weights
DE F
TOP VIEW OF UNIT
COMPRS
CBA
Table 4. Approximate units operating weights — lbs./
Unit
Model
**D330/275 3750 1701 4130 1873 3620 1642 3640 1651
**H330/275 3790 1719 4220 1914 3660 1660 3680 1669
**D360/305 3845 1744 4225 1916 3715 1685 3735 1694
**H360/305 3885 1762 4315 1957 3755 1703 3775 1712
**D420/350 3970 1801 4350 1973 3840 1742 3860 1751
**H420/350 4010 1819 4440 2014 3880 1760 3900 1769
**D480/400 4764 2161 4884 2215 4539 2059 4564 2070
**H480/400 4859 2204 4984 2261 4599 2091 4634 2102
**D600/500 5174 2347 5294 2401 4949 2245 4974 2256
**D600/500 5269 2390 5394 2447 5019 2277 5044 2288
Notes:
1. Basic unit weight includes minimum horsepower supply fan
motor.
1
kg
Basic Unit Weights
1
YC
Low HeatYCHigh Heat TC TE
Table 5. Point loading average weight
1,2
— lbs./kg
Model A B C D E F
**D330/275 846 384 688 313 743 337 745 338 604 275 503 228
**H330/275 867 393 707 321 767 348 753 342 613 279 513 233
**D360/305 836 379 680 309 779 353 741 336 621 285 568 258
**H360/305 897 407 696 316 766 348 729 330 590 268 636 288
**D420/350 892 405 692 314 779 353 765 347 633 288 590 268
**H420/350 867 393 869 395 690 313 758 344 601 273 654 297
**D480/400 820 372 856 388 937 425 742 336 762 346 769 349
**H480/400 841 381 876 397 957 434 754 342 775 352 782 355
**D600/500 894 406 955 428 970 440 756 343 862 391 866 393
**H600/500 915 415 966 438 990 449 768 348 875 397 879 399
Notes:
1. Point Loading is identified with corner A being the corner with the compressors. As you move clockwise around the unit as viewed from the top, mid-point B, corner C, corner D, mid-point E and corner F.
2. Point load calculations provided are based on the unit weight for YC high heat gas models.
Table 6. Approximate operating weights1— optional components — lbs./kg
Unit
Model
**D330/275 110/50 165/74 50/23 260/117 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**H330/300 145/65 200/90 50/23 285/128 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**D360/305 110/50 165/74 50/23 260/117 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**H330/305 145/65 200/90 50/23 285/128 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**D420/350 110/50 165/74 50/23 260/117 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**H420/350 145/65 200/90 50/23 285/128 85/39 115/52 18/8 6/3 30/14 85/38 310/141 330/150
**D480/400 110/50 165/74 50/23 290/131 115/52 150/68 18/8 6/3 30/14 85/38 365/169 365/169
**H480/400 145/65 200/90 50/23 300/135 115/52 150/68 18/8 6/3 30/14 85/38 365/169 365/169
**D600/500 110/50 165/74 50/23 290/131 115/52 150/68 18/8 6/3 30/14 85/38 365/169 365/169
**H600/500 145/65 200/90 50/23 300/135 115/52 150/68 18/8 6/3 30/14 85/38 365/169 365/169
Note:
1. Basic unit weight includes minimum horsepower supply fan motor.
Baro.
Relief
Power
Exhaust
0-25%
Man
Damper Econ.
20 RT-SVX34F-EN
Var. Freq.
Drives (VFD’s)
Bypass Lo Hi
Valves
Serv
Through-
the base Elec.
Non-
Fused
Discon.
Switch
Factory.
GFI with
Discon.
Switch
Roof CurbW/O With
Installation General Requirements
Condensate Drain Connection
Each commercial rooftop unit is equipped with one (1) 1­1/4 inch Female PVC condensate drain connection.
Refer to Figure 11, p. 18 for the location of the connector. A condensate trap must be installed due to the drain connection being on the “negative pressure” side of the fan. Install a P-Trap at the unit using the guidelines in
Figure 14, p. 21.
Pitch the drain line at least 1/2 inch for every 10 feet of horizontal run to assure proper condensate flow.
Ensure that all condensate drain line installations comply with applicable building and waste disposal codes.
Figure 14. Condensate trap installation
4. Remove the dust cap from the tubing connector located below the sensor in the vertical support.
5. Attach one end of the 50' x 3/16” O.D. factory provided pneumatic tubing to the sensor's top port, and the other end of the tubing to the connector in the vertical support. Discard any excess tubing.
Units with Statitrac™
1. Open the filter access door, and locate the Statitrac Transducer Assembly illustrated in Figure 16, p. 22. There are two tube connectors mounted on the left of the solenoid and transducers. Connect one end of the field provided 1/4” (length 50-100 ft.) or 3/8” (length greater than 100 ft.) O.D. pneumatic tubing for the space pressurization control to the fitting indicated in the illustration.
2. Route the opposite end of the tubing to a suitable location inside the building. This location should be the largest open area that will not be affected by sudden static pressure changes.
Figure 15. Pressure tubing
O/A Sensor & Tubing Installation
An Outside Air Pressure Sensor is shipped with all units designed to operate on traditional variable air volume applications (non-SZ VAV) and units with Statitrac™.
A duct pressure transducer and the outside air sensor is used to control the discharge duct static pressure to within a customer-specified controlband. Refer to the illustration in Figure 15, p. 21 and the following steps to install the sensor and the pneumatic tubing.
1. Remove the O/A pressure sensor kit located inside the fan section. The kit contains the following items;
an O/A static pressure sensor
a sensor mounting bracket
50’ of 3/16” O.D. pneumatic tubing
mounting hardware
2. Using two #10-32 x 1-3/4” screws provided, install the sensor's mounting bracket to the factory provided bracket (near the fan section).
3. Using the #10-32 x 1/2” screws provided, install the O/ A static pressure sensor vertically to the sensor bracket.
RT-SVX34F-EN 21
Installation General Requirements
Static Reference Tubing Connects Here (O/A Sensor)
Space Pressure Sensing Tube Connects Here
Space Pressure Calibration Solenoid
Space Pressure Transducer
LO
HI
CNO
NC
Sensing Tube to Outside Air Reference
Space Pressure Transducer
Sensing Tube to Space Pressure
Figure 16. Statitrac transducer assembly
22 RT-SVX34F-EN
Installation Electrical
Disconnect Switch External Handle (Factory Mounted Option)
Units ordered with the factory mounted disconnect switch come equipped with an externally mounted handle. This allows the operator to disconnect power from the unit without having to open the control panel door. The handle location and its three positions are shown below;
ON - Indicates that the disconnect switch is closed, allowing the main power supply to be applied at the unit.
OFF - Indicates that the disconnect switch is open, interrupting the main power supply at the unit.
OPEN COVER/RESET - Turning the handle to this position releases the handle from the disconnect switch, allowing the control panel door to be opened.
WARNI NG
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
Once the door has been opened, it can be closed with the handle in any one of the three positions outlined above, provided it matches the disconnect switch position. The handle can be locked in the “OFF” position. While holding the handle in the “OFF” position, push the spring loaded thumb key, attached to the handle, into the base slot. Place the lock shackle between the handle and the thumb key. This will prevent it from springing out of position.
Figure 17. Disconnect switch
An overall layout of the field required power wiring is illustrated in Figure 18, p. 24. To insure that the unit supply power wiring is properly sized and installed, follow the guidelines outlined below.
Note: All field installed wiring must conform to NEC
guidelines as well as State and Local codes.
Verify that the power supply available is compatible with the unit's name plate ratings for all components. The available power supply must be within 10% of the rated voltage stamped on the nameplate. Use only copper conductors to connect the 3-phase power supply to the unit.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
Main Power Wiring
WARNI NG
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
1. Table 7, p. 25 and Ta b le 10 , p . 2 6 list the electrical service sizing data. The electrical service must be protected from over current and short circuit conditions in accordance with NEC requirements. Protection devices must be sized according to the electrical data on the nameplate. Refer to “Electrical
Wire Sizing and Protection Device Equations” on page 27 for determining:
a. The appropriate electrical service wire size based
on “Minimum Circuit Ampacity” (MCA),
b. The “Maximum Over current Protection” (MOP)
device.
c. The “Recommended Dual Element fuse size” (RDE).
2. If the unit is not equipped with an optional factory installed Nonfused disconnect switch, a field supplied disconnect switch must be installed at or near the unit in accordance with the National Electrical Code (NEC latest edition). Refer to DSS calculations
Wire Sizing and Protection Device Equations” on page 27 for determining correct size.
Location for the electrical service entrance is shown in the unit dimensional drawings beginning with
Figure 1, p. 13. Complete the unit's power wiring
connections onto either the main terminal block HTB1,
“Electrical
RT-SVX34F-EN 23
Installation Electrical
or the factory mounted nonfused disconnect switch inside the unit control panel.
Note: When the factory installed through-the-base
option is not used, the installing contractor is required to seal any holes made in the base of the unit to prevent water from leaking into the building.
3. Provide proper grounding for the unit in accordance with local and national codes.
Figure 18. Typical field power wiring
Through-the-Base Electrical (Optional Accessory)
Liquid-tight conduit couplings are secured to the base of the unit for both power and control wiring. Liquid-tight conduit must be field installed between the couplings and the unit control box to prevent water leaks into the building.
Note: If the unit is set on the roof curb and temporary
auxiliary heat is provided in the building, it is recommended that the electrical and control wiring conduit opening in the control box be temporarily sealed to provide a vapor barrier.
24 RT-SVX34F-EN
Installation Electrical
Table 7. 27½-50 ton electrical service sizing data—60Hz
1
Fan Motors
Model
TC/TE/
YC*330
TC/TE/
YC*360
TC/TE/
YC*420
TC/TE/
YC*480
TC/TE/
YC*600
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. 100% Power Exhaust is with or without Statitrac™.
Characteristics
208/60/3 187-229
230/60/3 207-253
460/60/3 414-506
575/60/3 517-633
208/60/3 187-229 2/13 50.5 315/315
230/60/3 207-253 2/13 50.5 315/315
460/60/3 414-506 2/13 23.0 158/158
575/60/3 517-633 2/13 19.0 136/136
208/60/3 187-229
230/60/3 207-253
460/60/3 414-506
575/60/3 517-633
208/60/3 187-229
230/60/3 207-253
460/60/3 414-506
575/60/3 517-633
208/60/3 187-229
230/60/3 207-253
460/60/3 414-506
575/60/3 517-633
Electrical
Voltage
Range
No/Ton RLA (Ea.) LRA (Ea.) HP FLA No HP
1/12,1/
1/12,1/
1/12,1/
1/12,1/
1/13,1/
1/13,1/
1/13,1/
1/13,1/
1/13,1/
1/13,1/
1/13,1/
1/13,1/
2/13,1/
2/13,1/
2/13,1/
2/13,1/
Allowable
Compressor Supply Condenser Exhaust
7.5
44.0/50.5 304/315
13
44.0/50.5 304/315
13
21.0/23.0 147/158
13
17.5/19.0 122/136
13
50.5/56.0 315/351
15
50.5/56.0 315/351
15
15
23.0/27.5 158/197
15
19.0/23.0 136/146
50.5/83.9 315/485
20
50.5/83.9 315/485
20
23.0/34.0 158/215
20
19.0/27.3 136/175
20
50.5/56.0 315/351
15
50.5/56.0 315/351
15
23.0/27.5 158/197
15
19.0/23.0 136/146
15
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
7.5
10.0
15.0
7.5
10.0
15.0
7.5
10.0
15.0
7.5
10.0
15.0
10.0
15.0
10.0
15.0
10.0
15.0
10.0
15.0
10.0
15.0
20.0
10.0
15.0
20.0
10.0
15.0
20.0
10.0
15.0
20.0
22.2 3 1.1 7.0 1 2 1.0 4.1
29.5
18.8 3 1.1 7.0 1 2 1.0 4.1
25.2
9.4 3 1.1 3.5 1 2 1.0 1.8
12.6
7.8 3 1.1 2.8 1 2 1.0 1.4
10.1
22.2 3 1.1 7.0 1 2 1.0 4.1
29.5
18.8 3 1.1 7.0 1 2 1.0 4.1
25.2
9.4 3 1.1 3.5 1 2 1.0 1.8
12.6
7.8 3 1.1 2.8 1 2 1.0 1.4
10.1
22.2
29.5
3 1.1 7.0 1 2 1.0 4.1
40.7
18.8
25.2
3 1.1 7.0 1 2 1.0 4.1
35.4
9.4
12.6
3 1.1 3.5 1 2 1.0 1.8
17.7
7.8
10.1
3 1.1 2.8 1 2 1.0 1.4
15.1
29.5 4 1.1 7.0 1 2 1.5 5.4
40.7
25.2 4 1.1 7.0 1 2 1.5 5.4
35.4
12.6 4 1.1 3.5 1 2 1.5 2.7
17.7
10.1 4 1.1 2.8 1 2 1.5 2.2
15.1
29.5
40.7
4 1.1 7.0 1 2 1.5 5.4
56.1
25.2
35.4
4 1.1 7.0 1 2 1.5 5.4
49.4
12.6
17.7
4 1.1 3.5 1 2 1.5 2.7
24.7
10.1
15.1
4 1.1 2.8 1 2 1.5 2.2
19.6
FLA
(Ea.)
50% 100%
HP
FLA
(Ea.)No.
RT-SVX34F-EN 25
Installation Electrical
Table 8. Electrical service sizing data — electric heat
module (electric heat only) — 60 Hz
Models: TE(D,H,F,R) 330—600 Electric Heat FLA
KW Heater
Nominal
Unit Size
(Tons)
27½-35
40- 50
Note: All FLA in this table are based on heater operating at 208, 240, 480,
and 600 volts.
Nominal
36 54 72 90 108
Unit
Voltage
208 74.9 112.4
230 86.6 129.9
460 43.3 65.0 86.6 108.3
575 52.0 69.3 86.6
208 112.4
230 129.9
460 65.0 86.6 108.3 129.9
575 52.0 69.3 86.6 103.9
FLA FLA FLA FLA FLA
Table 9. Electrical service sizing data — crankcase
heaters (heating mode only) — 60Hz
Nominal
Unit Size (Tons)
27½ - 35 1111
40, 50 2211
FLA Add Unit Voltage
200 230 460 575
Table 10. Electrical service sizing data — 50Hz
Fan Motors
Compressor
Model
TC/TE/YC*275 380-415/50/3 1/10, 1/11 21.0/23.0 147/ 158 7.5 (5.6)
TC/TE/YC*305 380-415/50/3 2/11 23.0 158 7.5 (5.6)
TC/TE/YC*350 380-415/50/3 1/11, 1/12 23.0/27.5 158/ 197 7.5 (5.6)
TC/TE/YC*400 380-415/50/3 1/11, 1/17 23.0/34.0 158/ 215 10 (6.8)
TC/TE/YC*500 380-415/50/3 2/11, 1/12 23.0/27.5 158/ 197 10 (6.8)
Notes:
1. All condenser fan motors are single phase.
2. All customer wiring and devices must be installed in accordance with local and national electrical codes.
3. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
4. 100% Power Exhaust is with or without Statitrac.
Characteristics
No/Ton
Electrical
RLA
(Ea.)
LRA
(Ea.) HP(kW) FLA No. HP(kW)
Supply Condenser
10 (6.8)
10 (6.8)
10 (6.8)
15 (10.5)
15 (10.5)
15 (10.5)
20 (12.8)
13.6/
16.0/
13.6/
16.0/
13.6/
16.0/
24.0/
16.0/
24.0/
16.0/
24.0/
29.0/
3 .75 (.56) 4.4 1 2
14.1
15.5
3
14.1
15.5
3
14.1
15.5
26.0
4
15.5
26.0
4
15.5
26.0
28.0
0.75
(0.56)
0.75
(0.56)
0.75
(0.56)
0.75
(0.56)
1
50% 100%
FLA
(Ea.)
4.4 1 2
4.4 1 2
4.4 1 2
4.4 1 2
Exhaust
4
(kW)
(0.56)
(0.56)
(0.56)
(0.75)
(0.75)
HP
0.75
0.75
0.75
1.0
1.0
FLA
(Ea.)No.
1.7
1.7
1.7
2.5
2.5
26 RT-SVX34F-EN
Table 11. Electrical service sizing data – electric heat
module (electric heat units only)—50Hz
Models: TE(D,H,F,R) 275 through 500 Electric Heat FLA
Nominal
Unit Size
(Tons)
23-29
33, 42
Note: All FLA in this table are based on heater operating at 380 or 415 volts
as shown above.
Nominal
Unit
Voltage
380 34.5 51.1 68.9 85.5
415 37.6 55.6
380 51.1 68.9 85.5 103.4
415 55.6 75.1 93.2 112.7
KW Heater (380/415V)
23/27 34/40 45/54 56/67 68/81
Table 12. Electrical service sizing data — crankcase
heaters (heating mode only) — 50Hz
FLA Add
Nominal Unit Size
(Tons)
23 - 29 1 1
33 - 42 1 1
Unit Voltage
380 415
Electrical Wire Sizing and Protection Device Equations
To correctly size the main power wiring based on MCA (Minimum Circuit Ampacity), use the appropriate equation listed below. Read the definitions that follow and then use Calculation #1 for determining MCA (Minimum Circuit Ampacity), MOP (Maximum Over current Protection), and RDE (Recommended Dual Element fuse size) for TC (Cooling Only) units and YC (Cooling with Gas Heat) units. Use Calculation #2 for TE (Cooling with Electric Heat) units.
Load Definitions:
LOAD 1 = CURRENT OF THE LARGEST MOTOR (Compressor or Fan Motor)
LOAD 2 = SUM OF THE CURRENTS OF ALL REMAINING MOTORS
LOAD 3 = FLA (Full Load Amps) OF THE ELECTRIC HEATER
LOAD 4 = ANY OTHER LOAD RATED AT 1 AMP OR MORE
CRANKCASE HEATERS FOR HEATING MODE ONLY:
208/230 VOLT
– 27.5 - 35 Ton Units, Add 1 Amp
– 40 - 50 Ton Units, Add 2 Amps
460/575 VOLT
– 27.5 - 35 Tons Units, Add 1 Amp
– 40 - 50 Ton Units, Add 1 Amp
Installation Electrical
Calculation #1 - TC*, YC*-27.5 to 50 Ton Units
MCA = (1.25 x Load 1) + Load 2 + Load 4
MOP = (2.25 x Load 1) + Load 2 + Load 4 (See Note 1)
RDE = (1.5 x Load 1) + Load 2 + Load 4 (See Note 2)
Calculation # 2 - TE*-27.5 to 50 Ton Units
A. Single Source Power (all voltages)
To calculate the correct MCA (Minimum Circuit Ampacity), MOP (Maximum Over current Protection), and RDE (Recommended Dual Element fuse size), two (2) sets of calculations must be performed;
1. Calculate the MCA, MOP and/or RDE values using the above equation as if the unit is operating in the cooling mode.
2. Calculate the MCA, MOP and/or RDE values as if the unit is operating in the heating mode, as follows:
Note: When determining loads, the compressors and
condenser fan motors do not operate during the heating cycle.
Units with less than 50 KW Heaters
MCA = 1.25 x (Load 1 + Load 2 + Load 4) + (1.25 x Load 3)
Units with 50 KW or Larger Heaters
MCA = 1.25 x (Load 1 + Load 2 + Load 4) + Load 3
The MCA value stamped on the nameplate is the largest of the two calculated values.
MOP = (2.25 x Load 1) + Load 2 + Load 3 + Load 4 (See Note
1)
The MOP value stamped on the nameplate is the largest of the two calculated values.
RDE = (1.5 x Load 1) + Load 2 + Load 3 + Load 4 (See Note 2)
Note: Select an over current protection device equal to
the MOP value. If the calculated MOP value does not equal a standard size protection device listed in NEC 240-6, select the next lower over current protection device. If the calculated MOP value is less than the MCA value, select the lowest over current protection device which is equal to or larger than the MCA, providing the selected over current device does not exceed 800 amps.
Note: Select a Dual Element Fuse equal to the RDE value.
If the calculated RDE value does not equal a standard dual element fuse size listed in NEC 240­6, select the next higher fuse size. If the calculated RDE value is greater than the MOP value, select a Dual Element fuse equal to the calculated MOP (Maximum Over current Protection) value
RT-SVX34F-EN 27
Installation Electrical
Disconnect Switch Sizing (DSS)
Calculation A. - YC*, TC*, and TE* Units:
DSS = 1.15 X (LOAD1 + LOAD2 + LOAD4)
For TE* units, use calculations A and B.
Calculation B. - TE* Units:
DSS = 1.15 X (LOAD3 + Supply Fan FLA + Exhaust
Fan FLA).
Use the larger value of calculations A or B to size the electrical disconnect switch.
Low Voltage Wiring
An overall layout of the various control options available for a Constant Volume application is illustrated in
Figure 19, p. 30 and Figure 20, p. 31 illustrates the various
control options for a Variable Air Volume application. The required number of conductors for each control device are listed in the illustration.
A typical field connection diagram for the sensors and other options are shown in the following section “Remote Panels and Sensors”. These diagrams are representative of standard applications and are provided for general reference only. Always refer to the wiring diagram that shipped with the unit for specific electrical schematic and connection information.
Note: All field wiring must conform to NEC guidelines as
well as state and local codes.
Control Power Transformer
WARN ING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/ tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
The 24 volt control power transformers are equipped with internal circuit breakers. They are to be used only with the accessories called out in this manual. If a circuit breaker trips, be sure to turn off all power to the unit before attempting to reset it.
On units equipped with the VFD option, an additional control power transformer is used. The secondary is protected with fuses. Should the fuse blow, be sure to turn off all power to the unit before attempting to replace it.
Field Installed AC Control Wiring
WARNI NG
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
Before installing any connecting wiring, refer to Tab l e 13 ,
p. 28 for conductor sizing guidelines and;
Use copper conductors unless otherwise specified.
Ensure that the AC control voltage wiring between
the controls and the unit's termination point does not exceed three (3) ohms/conductor for the length of the run.
Note: Resistance in excess of 3 ohms per conductor may
cause component failure due to insufficient AC voltage supply.
Refer to dimensional information beginning with
Figure 1, p. 13 for the electrical access locations
provided on the unit.
Do not run the AC low voltage wiring in the same
conduit with the high voltage power supply wiring.
Be sure to check all loads and conductors for grounds, shorts, and miswiring. After correcting any discrepancies, reset the circuit breakers by pressing the black button located on the left side of the transformer.
Table 13. AC conductors
Distance from unit to control Recommended wire size
000-460 feet 18 gauge
461-732 feet 16 gauge
733-1000 feet 14 gauge
28 RT-SVX34F-EN
Installation Electrical
Field Installed DC Control Wiring
WARN ING
Proper Field Wiring and Grounding Required!
All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.
NOTICE:
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors could result in equipment damage.
Before installing the connecting wiring between the components utilizing a DC analog output/input signal and the unit, refer to Table 14, p. 29 for conductor sizing guidelines and;
Use standard copper conductor thermostat wire unless otherwise specified.
Ensure that the wiring between the controls and the unit's termination point does not exceed two and a half (2-1/2) ohms/conductor for the length of the run.
Note: Resistance in excess of 21/2 ohms per conductor
can cause deviations in the accuracy of the controls.
Refer to dimensional drawings beginning with
Figure 1, p. 13 for the electrical access locations
provided on the unit.
Do not run the electrical wires transporting DC signals in or around conduit housing high voltage wires.
Must not pass between buildings.
Table 14. DC conductors
Distance from unit to control Recommended wire size
000-150 feet 22 gauge
151-240 feet 20 gauge
241-385 feet 18 gauge
386-610 feet 16 gauge
611-970 feet 14 gauge
Units equipped with the Trane Communication Interface (TCI) option, which utilizes a serial communication link;
Must be 18 AWG shielded twisted pair cable Belden 8760 or equivalent).
Must not exceed 5,000 feet maximum for each link.
RT-SVX34F-EN 29
Installation Electrical
LT B6
Space
Humidity
Sensor
Space
Humidistat
RTRM J7 Thermostat Inputs N/A for SZ VAV
Figure 19. Typical field wiring requirements for CV and SZ VAV control options
30 RT-SVX34F-EN
Loading...
+ 92 hidden pages