Trane Stealth Air-Cooled Chiller Model RTAE Installation and Maintenance Manual

0 (0)

Installation, Operation,

and Maintenance

Stealth™ Air-Cooled Chiller Model RTAE

150 to 300 Nominal Tons

SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and airconditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

October 2014

RTAE-SVX001B-EN

Warnings, Cautions and Notices

Warnings, Cautions and Notices. Note that warnings, cautions and notices appear at appropriate intervals throughout this manual. Warnings are provided to alert installing contractors to potential hazards that could result in death or personal injury. Cautions are designed to alert personnel to hazardous situations that could result in personal injury, while notices indicate a situation that could result in equipment or property-damage-only accidents.

Your personal safety and the proper operation of this machine depend upon the strict observance of these precautions.

Read this manual thoroughly before operating or servicing this unit.

ATTENTION: Warnings, Cautions and Notices appear at appropriate sections throughout this literature. Read these carefully:

WARNING

CAUTIONs

NOTICE:

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It could also be used to alert against unsafe practices.

Indicates a situation that could result in equipment or property-damage only

Important

Environmental Concerns!

Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment.Trane advocates the responsible handling of all refrigerants-including industry replacements for CFCs such as HCFCs and HFCs.

Responsible Refrigerant Practices!

Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified.The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that

must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.

WARNING

Refrigerant under High Pressure!

System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives. Failure to recover refrigerant to relieve pressure or the use of nonapproved refrigerants, refrigerant substitutes, or refrigerant additives could result in an explosion which could result in death or serious injury or equipment damage.

WARNING

Personal Protective Equipment (PPE)

Required!

Installing/servicing this unit could result in exposure to electrical, mechanical and chemical hazards.

Before installing/servicing this unit, technicians MUST put on all PPE required for the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves, safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash clothing). ALWAYS refer to appropriate Material Safety Data Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA guidelines for proper PPE.

When working with or around hazardous chemicals, ALWAYS refer to the appropriate MSDS/SDS and OSHA/GHS (Global Harmonized System of Classification and Labelling of Chemicals) guidelines for information on allowable personal exposure levels, proper respiratory protection and handling instructions.

If there is a risk of energized electrical contact, arc, or flash, technicians MUST put on all PPE in accordance

with OSHA, NFPA 70E, or other country-specific requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.

Failure to follow instructions could result in death or serious injury.

© 2014Trane All rights reserved

RTAE-SVX001B-EN

Warnings, Cautions and Notices

WARNING

Proper Field Wiring and Grounding

Required!

All field wiring MUST be performed by qualified personnel. Improperly installed and grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST follow requirements for field wiring installation and grounding as described in NEC and your local/state electrical codes. Failure to follow code could result in death or serious injury.

Factory Warranty Information

Compliance with the following is required to preserve the factory warranty:

All Unit Installations

Startup MUST be performed byTrane, or an authorized agent ofTrane, to VALIDATE this WARRANTY. Contractor must provide a two-week startup notification toTrane (or an agent ofTrane specifically authorized to perform startup).

Copyright

This document and the information in it are the property of Trane, and may not be used or reproduced in whole or in part without written permission.Trane reserves the right to revise this publication at any time, and to make changes to its content without obligation to notify any person of such revision or change.

Trademarks

All trademarks referenced in this document are the trademarks of their respective owners.

Revision History

RTAE-SVX001B-EN (29 Oct 2014)

Added transformer option.

Added harmonic filter option.

Added 150T and 165T single circuit units.

Added extreme low ambient option.

Added seismic isolation option.

Added CE/PED option.

Updated unit weights and isolator information.

Updated drive cooling fluid volumes.

Modified oil sump check procedure.

RTAE-SVX001A-EN (24 Sep 2013)

New release.

RTAE-SVX001B-EN

3

Table of Contents

 

Warnings, Cautions and Notices . . . . . . . . . .

2

Factory Warranty Information . . . . . . . . . . .

3

Copyright . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Revision History . . . . . . . . . . . . . . . . . . . . . . .

3

Model Number Description . . . . . . . . . . . . . . .

6

Outdoor Unit Nameplate . . . . . . . . . . . . . . .

6

Compressor Nameplate . . . . . . . . . . . . . . . .

6

Model Number Descriptions . . . . . . . . . . . . . .

7

Unit Model Number . . . . . . . . . . . . . . . . . . . .

7

Compressor Model Number . . . . . . . . . . . .

8

Compressor Serial Number . . . . . . . . . . . . .

8

General Information . . . . . . . . . . . . . . . . . . . . .

9

Unit Description . . . . . . . . . . . . . . . . . . . . . . .

9

Accessory/Option Information . . . . . . . . . . .

9

General Data . . . . . . . . . . . . . . . . . . . . . . . . . . .

10

Drive Cooling System . . . . . . . . . . . . . . . . .

11

Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . .

12

Unit Inspection . . . . . . . . . . . . . . . . . . . . .

12

Inspection . . . . . . . . . . . . . . . . . . . . . . . . .

12

Storage . . . . . . . . . . . . . . . . . . . . . . . . . . .

12

Installation Requirements . . . . . . . . . . . . . .

13

Dimensions and Weights . . . . . . . . . . . . . . . .

14

Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14

Unit Dimensions . . . . . . . . . . . . . . . . . . . . . .

14

Service Clearances . . . . . . . . . . . . . . . . . . . .

14

Installation Mechanical . . . . . . . . . . . . . . . . . .

15

Location Requirements . . . . . . . . . . . . . . . .

15

Sound Considerations . . . . . . . . . . . . . . .

15

Foundation . . . . . . . . . . . . . . . . . . . . . . . .

15

Clearances . . . . . . . . . . . . . . . . . . . . . . . . .

15

Center of Gravity . . . . . . . . . . . . . . . . . . . . .

20

Isolation and Sound Emission . . . . . . . . . .

20

Unit Isolation and Leveling . . . . . . . . . . .

20

Compressor Shipping Bolt Removal . . . .

23

Units with InvisiSound™ Ultimate Option

 

(Model Number Digit 12 = 3) . . . . . . . . . .

23

Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . .

23

Evaporator Piping Components . . . . . . .

25

Pressure Relief Valves . . . . . . . . . . . . . . . . . .26

Evaporator Waterside Pressure Drop

Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27

Freeze Protection . . . . . . . . . . . . . . . . . . . . . .29

Low Evaporator Refrigerant Cutout,

Glycol Requirements . . . . . . . . . . . . . . . . . . .30

Installation Electrical . . . . . . . . . . . . . . . . . . . . .31

General Recommendations . . . . . . . . . . . . .31

Adaptive Frequency™ Drive (AFD3)

Capacitor Discharge . . . . . . . . . . . . . . . . . .32

Units with Nitrogen Charge Option . . . . .32

Installer-Supplied Components . . . . . . . . . .32

Power Supply Wiring . . . . . . . . . . . . . . . . .33

Control Power Supply . . . . . . . . . . . . . . . .34

Service Power Connection . . . . . . . . . . . .34

Heater Power Supply . . . . . . . . . . . . . . . . .34

Interconnecting Wiring . . . . . . . . . . . . . . . . .35

Chilled Water Pump Control . . . . . . . . . . .35

Programmable Relays . . . . . . . . . . . . . . . . . .35

Relay Assignments Using Tracer™ TU . . .36

Low Voltage Wiring . . . . . . . . . . . . . . . . . . . .36

Emergency Stop . . . . . . . . . . . . . . . . . . . . .36

External Auto/Stop . . . . . . . . . . . . . . . . . . .36

External Circuit Lockout –

Circuit #1 and #2 . . . . . . . . . . . . . . . . . . . . .36

Ice Building Option . . . . . . . . . . . . . . . . . .37

External Chilled Water Setpoint (ECWS)

Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37

External Demand Limit Setpoint (EDLS)

Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37

Chilled Water Reset (CWR) . . . . . . . . . . . .38

Transformer Power Rating . . . . . . . . . . . . . .39

Communications Interface . . . . . . . . . . . . . .39

LonTalk Interface (LCI-C) . . . . . . . . . . . . . .39

BACnet Interface (BCI-C) . . . . . . . . . . . . . .39

Modbus Remote Terminal Unit Interface .39

Operating Principals . . . . . . . . . . . . . . . . . . . . .40

Refrigeration Circuits . . . . . . . . . . . . . . . . . .40

Refrigeration Cycle . . . . . . . . . . . . . . . . . . . .40

Refrigerant R-134a . . . . . . . . . . . . . . . . . . . . .40

4

RTAE-SVX001B-EN

Compressor and Lube Oil System .

. . . . . 40

Condenser and Fans . . . . . . . . . . . . .

. . . . . 40

Evaporator . . . . . . . . . . . . . . . . . . . . . .

. . . . . 41

Drive Cooling System . . . . . . . . . . . .

. . . . . 41

Controls . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . 42

UC800 Specifications . . . . . . . . . . . . .

. . . . . 42

Wiring and Port Descriptions . . . .

. . . . . 42

Communication Interfaces . . . . . . .

. . . . . 43

Rotary Switches . . . . . . . . . . . . . . .

. . . . . 43

LED Description and Operation . . .

. . . . . 43

Tracer AdaptiView TD7 Display . . . .

. . . . . 43

Operator Interface . . . . . . . . . . . . .

. . . . . 43

Main Display Area/Home Screen .

. . . . . 44

Viewing Chiller Operating Modes

. . . . . 44

Alarms . . . . . . . . . . . . . . . . . . . . . .

. . . . . 46

Reports . . . . . . . . . . . . . . . . . . . . . .

. . . . . 47

Equipment Settings . . . . . . . . . . . .

. . . . . 49

Display Settings . . . . . . . . . . . . . . .

. . . . . 51

Viewing the Settings Screen . . . .

. . . . . 51

Cleaning the Display . . . . . . . . . . .

. . . . . 52

Security Settings . . . . . . . . . . . . . .

. . . . . 52

Disabling/Enabling Security . . . . .

. . . . . 52

InvisiSound Ultimate - Noise Reduction

Mode . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . 54

Tracer™ TU . . . . . . . . . . . . . . . . . . . . .

. . . . . 55

Pre-Start . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . . . 56

Start-Up and Shutdown . . . . . . . . . . . .

. . . . . 57

Unit Start-Up . . . . . . . . . . . . . . . . . . . .

. . . . . 57

Temporary Shutdown And Restart .

. . . . . 57

Extended Shutdown Procedure . . . .

. . . . . 57

Seasonal Unit Start-Up Procedure .

. . . . . 58

System Restart After Extended Shutdown 58

Sequence of Operation . . . . . . . . . . .

. . . . . 59

Software Operation Overview . . . .

. . . . . 59

Timelines . . . . . . . . . . . . . . . . . . . . .

. . . . . 59

Power Up Diagram . . . . . . . . . . . . .

. . . . . 60

Power Up to Starting . . . . . . . . . . .

. . . . . 61

Stopped to Starting . . . . . . . . . . . .

. . . . . 62

Running (Lead Compressor/Circuit Start

and Run) . . . . . . . . . . . . . . . . . . . . .

. . . . . 63

Running (Lag Compressor/Circuit

Start and Run) . . . . . . . . . . . . . . . . . . . . . .63

Satisfied Setpoint . . . . . . . . . . . . . . . . . . . .64

Normal Shutdown to Stopped or

Run Inhibit . . . . . . . . . . . . . . . . . . . . . . . . .65

Immediate Shutdown to Stopped or

Run Inhibit . . . . . . . . . . . . . . . . . . . . . . . . .65

Ice Making (Running to Ice Making to Running) . . . . . . . . . . . . . . . . . . . . . . . . . . .66

Ice Making (Auto to Ice Making to Ice Making Complete) . . . . . . . . . . . . . . . . . . .67

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . .68

Recommended Maintenance . . . . . . . . . . . .69

Weekly . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69

Monthly . . . . . . . . . . . . . . . . . . . . . . . . . . . .69

Annual . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69

Refrigerant and Oil Charge Management .69

Lubrication System . . . . . . . . . . . . . . . . . . . .69

Oil Sump Level Check . . . . . . . . . . . . . . . .69

Drive Cooling System . . . . . . . . . . . . . . . . . .71

Service Intervals . . . . . . . . . . . . . . . . . . . . .71

Unit Diagnostics . . . . . . . . . . . . . . . . . . . . .71

pH Test . . . . . . . . . . . . . . . . . . . . . . . . . . . .71

Pressure Relief Cap . . . . . . . . . . . . . . . . . .71

Drive Cooling Expansion Tank . . . . . . . . .71

Condenser Coils — Cleaning and

Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . .72

Coil Cleaning and Inspection Interval . . . .72

Cleaning Air Side of RTAE Coils . . . . . . . .72

Cleaning Coated Coils . . . . . . . . . . . . . . . .72

Coil Corrosion Protection Inspection . . . .72

Reinstallation of Compressor Shipping

Bolts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72

Servicing Chiller Roof . . . . . . . . . . . . . . . .72

Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73

AFD Diagnostics . . . . . . . . . . . . . . . . . . . . . . .73

Main Processor Diagnostics . . . . . . . . . . . . .76

Communication Diagnostics . . . . . . . . . . . .85

Operator Display Diagnostics and

Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . .88

Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . .89

Log and Check Sheet . . . . . . . . . . . . . . . . . . . .90

RTAE-SVX001B-EN

5

Trane Stealth Air-Cooled Chiller Model RTAE Installation and Maintenance Manual

Model Number Description

Nameplates

The Stealth™ outdoor unit nameplates are applied to the exterior of the Control Panel. A compressor nameplate is located on each compressor. When the unit arrives, compare all nameplate data with ordering, submittal, and shipping information.

Outdoor Unit Nameplate

See Figure 1 for a typical unit nameplate.The outdoor unit nameplate provides the following information:

Unit model and size description.

Unit serial number.

Identifies unit electrical requirements.

Lists correct operating charges of R-134a and refrigerant oil (Trane OIL00311).

Lists unit test pressures.

Identifies installation, operation and maintenance and service data literature.

Lists drawing numbers for unit wiring diagrams.

of typical unit model number and the coding system for each.

Each position, or group of positions, in the model number is used to represent a feature. For example, in the first table, position 08 of the unit model number, Unit Voltage, contains the number “4”.A 4 in this position means that the unit voltage is 460/60/3.

Unit Model Number. An example of a typical unit model number (M/N) is:

RTAE 200F UA01 AA1F N1X1 A1A0 0CB0 X02X AA03 000

Model number digits are selected and assigned in accordance with the definitions as listed in “Unit Model Number,” p. 7.

Compressor Nameplate

The compressor nameplate provides the following information:

Compressor model number. See “Compressor Model Number,” p. 8.

Compressor serial number. See “Compressor Serial Number,” p. 8.

Model Number Coding System

The model numbers for the unit and the compressor are composed of numbers and letters that represent features of the equipment. Shown in the following table is a sample

Compressor electrical characteristics.

Utilization range.

Recommended refrigerant.

Figure 1.

Typical unit nameplate

6

RTAE-SVX001B-EN

Model Number Descriptions

Unit Model Number

Digits 1,2 — Unit Model

RT = Rotary Chiller

Digits 3— Unit Type

A = Air-cooled

Digits 4 — Development

Sequence

E = Development Sequence

Digits 5-7 — Nominal Capacity

149 = 150 NominalTons Single Circuit

164 = 165 NominalTons Single Circuit

150 = 150 NominalTons

165 = 165 NominalTons

180 = 180 NominalTons

200 = 200 NominalTons

225 = 225 NominalTons

250 = 250 NominalTons

275 = 275 NominalTons

300 = 300 NominalTons

Digit 8— Unit Voltage

A

=

200/60/3

B

=

230/60/3

C

=

380/50/3

D

=

380/60/3

E

=

400/50/3

F

=

460/60/3

G

=

575/60/3

H

=

400/60/3

Digit 9 — Manufacturing

Location

U = Trane Commercial Systems,

Pueblo, CO USA

Digits 10, 11— Design Sequence

** = Factory assigned

Digit 12 — Unit Sound Package

1= InvisiSound™ Standard Unit

2= InvisiSound Superior

(Line Wraps, Reduced Fan

Speed)

3= InvisiSound Ultimate

(Compressor Sound Attenuation, Line Wraps, Reduced Fan Speed)

Digit 13 — Agency Listing

0

=

No Agency Listing

A

=

UL/CUL Listing

C

=

CE European Safety Standard

Digit 14 — Pressure Vessel Code

A

=

ASME Pressure Vessel Code

D

=

Australia Pressure Vessel Code

C= CRN or Canada Equivalent Pressure Vessel Code

L = Chinese Pressure Vessel Code

P= PED European Pressure Vessel

Code

Digit 15 — Factory Charge

1= Refrigerant Charge HFC-134a

2= Nitrogen Charge

Digit 16 — Evaporator

Application

F = Standard Cooling

(40 to 68°F/5.5 to 20°C)

G= LowTemp Process (<40°F LeavingTemp)

C= Ice-making (20 to 68°F/-7 to 20°C) w/ Hardwired Interface

Digit 17 — Evaporator

Configuration

N

=

2 Pass Evaporator

P

=

3 Pass Evaporator

Digit 18 — Evaporator Fluid

Type

1 = Water

2= Calcium Chloride

3= Ethylene Glycol

4= Propylene Glycol

5= Methanol

Digit 19 — Water Connection

X

=

Grooved Pipe

F

=

Grooved Pipe + Flange

Digit 20 — Flow Switch

1= Factory Installed - Other Fluid (15 cm/s)

2= Factory Installed - Water 2 (35 cm/s)

3= Factory Installed - Water 3 (45 cm/s)

Digit 21 — Insulation

A= Factory Insulation - All Cold Parts 0.75”

B= Evaporator-Only Insulation - High Humidity/Low EvapTemp 1.25”

Digit 22 — Unit Application

1

=

Standard Ambient

 

 

(32 to 105°F/0 to 40.6°C)

2

=

Low Ambient

 

 

(0 to 105°F/-17.7 to 40.6°C)

3

=

Extreme Low Ambient

 

 

(-20 to 105°F/-28.9 to 40.6°C)

4

=

High Ambient

 

 

(32 to 125°F/0 to 52°C)

5

=

Wide Ambient

 

 

(0 to 125°F/-17.7 to 52°C)

Digit 23 — Condenser Fin Options

A = Aluminum Fins with Slits

D= CompleteCoat™ Epoxy Coated Fins

Digits 24, 25 — Not Used

Digit 26 — Power Line

Connection Type

A = Terminal Block

C= Circuit Breaker

D= Circuit Breaker w/ High Fault Rated Control Panel

Digit 27 — Short Circuit Current

Rating

A= Default A Short Circuit Rating

B= High A Short Circuit Rating

Digit 28 — Transformer

0

=

NoTransformer

1

=

Factory InstalledTransformer

Digit 29 — Line Voltage

Harmonic Mitigation

X

=

Line Reactors (~30%TDD)

1

=

Filter circuit (IEEE519 Compliant)

Digit 30 — Electrical

Accessories

0 = No Convenience Outlet

C= 15A 115V convenience Outlet (Type B)

Digit 31 — Remote

Communication Options

0= No Remote Digital Communication

1= LonTalk® Interface LCI-C (Tracer™ Compatible)

2= BACnet® MS/TP Interface (Tracer compatible)

3= ModBus™ Interface

Digit 32 — Hard Wire

Communication

X = None

A= Hard Wired Bundle - All

B= Remote Leaving WaterTemp Setpoint

C= Remote Leaving temp and Demand Limit Setpoints

D= Programmable Relay

E= Programmable Relay and Leaving Water and Demand

Limit

Setpoint

F= Percent Capacity

G= Percent Capacity and Leaving Water and Demand Limit

Setpoint

H= Percent Capacity and Programmable Relay

Digit 33 — Not Used

RTAE-SVX001B-EN

7

Model Number Descriptions

Digit 34 — Structural Options

A= Standard Unit Structure

B= Seismic to International Building Code (IBC)

C= California Office of Statewide Health Planning and Development (OSHPD) Certification

D= Wind Load for Florida Hurricane 175 MPH

E= Seismic (IBC) and Wind Load

F= OSHPD and Wind Load

Digit 35 — Appearance Options

0

=

No Appearance Options

A

=

Architectural Louvered Panels

Digit 36 — Unit Isolation

0= No Isolation

1= Elastomeric Isolators

3 = Seismic Rated Isopads

Digit 37 — Not Used

0 = Not Used

Digit 38 — Not Used

0 = Not Used

Digit 39 — Special

0

=

None

S

=

Special

Compressor Model

Number

Digits 1-4 — Compressor Type

CHHS= Positive displacement, helical rotary (twin screw) hermetic compressor

Digit 5 — Frame Size

R= R Frame: 70 - 100 tons

S= S Frame: 112 - 165 tons

Digit 6— Motor Length

B= 145 mm

C= 170 mm

E= 165 mm

F= 190 mm

Digit 7 — Motor Winding

Characteristics

*= Factory assigned

Digit 8 — Volume Ratio

B = High Volume Ratio

Digit 9 — Refrigerant

1 = R-134a

Digits 10-11— Design Sequence

** = Factory assigned

Compressor Serial

Number

Digits 1-2 —Year

YY= Last two digits of year of manufacture

Digit 3— Week

WW= Week of build, from 00 to 52

Digit 5 — Day

1

=

Monday

2

=

Tuesday

3

=

Wednesday

4

=

Thursday

5

=

Friday

6

=

Saturday

7

=

sunday

Digits 6-8 — Coded Time Stamp

TTT = Used to ensure uniqueness of serial number

Digit 9 — Assembly Line

Assembly line compressor was built on. Varies with facility

Digit 10— Build Location

A = Monterrey

8

RTAE-SVX001B-EN

General Information

Unit Description

The 150-300 ton Stealth™ units are helical-rotary type, aircooled liquid chillers designed for installation outdoors. The compressor circuits are completely assembled, hermetic packages that are factory-piped, wired, leaktested, dehydrated, and tested for proper control operation before shipment.

Chilled water inlet and outlet openings are covered for shipment.The Stealth featuresTrane’s exclusive Adaptive Control ™ logic, which monitors the control variables that govern the operation of the chiller unit. Adaptive Control logic can adjust capacity variables to avoid chiller shutdown when necessary, and keep producing chilled water. All unit sizes are available with two independent refrigerant circuits. A single refrigeration circuit option is available for 150 and 165T units. Each compressor is controlled by a variable speed Adaptive Frequency™ Drive Generation 3 (AFD3). Each refrigerant circuit is provided with filter, sight glass, electronic expansion valve, and charging valves.The shell-and-tube type evaporator is manufactured in accordance with ASME standards or other international codes. Each evaporator is fully insulated and is equipped with water drain and vent connection. As an option, a convenience outlet can be supplied.

Units are shipped with full oil charge and can be ordered with either a factory refrigerant charge, or optional nitrogen charge.

Figure 2. Typical Stealth RTAE

Accessory/Option Information

Check all the accessories and loose parts which are shipped with the unit against the shipping list. Included in these items will be water vessel drain plugs, electrical diagrams, and service literature, which are placed inside the control panel for shipment.

If optional elastomeric isolators are ordered with unit (model number digit 36 = 1), they are shipped mounted on diagonal supports on the end of the unit opposite control panel. See Figure 3 and Figure 4.

If optional seismic isopads are selected (model number digit 36= 2), they will be shipped inside the unit control panel.

Figure 3. Elastomeric isolator shipping location

Elastomeric Isolator

Shipping Locations

(not all isolators shown -

quantity varies with unit configuration)

Figure 4. Elastomeric isolators attached for shipping

RTAE-SVX001B-EN

9

General Data

General Data

Table 1. General data table

Unit Size (tons)

 

150

165

180

200

225

250

275

300

 

150SC

165SC

Compressor Model

 

CHHSR

CHHSR

CHHSR

CHHSR

CHHSS

CHHSS

CHHSS

CHHSS

 

CHHSS

CHHSS

Quantity

#

2

2

2

2

2

2

2

2

 

1

1

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator

 

 

 

 

 

 

 

 

 

 

 

 

Water Storage

(gal)

17.5

18.7

21.9

23.9

26.6

28.7

33.0

36.0

 

17.3

17.3

 

(L)

66.1

70.9

82.8

90.5

100.6

108.8

125.0

136.1

 

65.6

65.6

 

 

 

 

2 Pass arrangement

 

 

 

 

 

 

Minimum Flow

(gpm)

171

187

202

228

261

288

318

354

 

169

169

 

 

(l/s)

10.8

11.8

12.7

14.4

16.5

18.2

20.1

22.3

 

10.7

10.7

Maximum Flow

(gpm)

626

684

742

835

957

1055

1165

1299

 

620

620

 

(l/s)

39.5

43.1

46.8

52.7

60.4

66.5

73.5

81.9

 

39.1

39.1

 

 

 

 

3 Pass arrangement

 

 

 

 

 

 

Minimum Flow

(gpm)

114

124

135

152

174

192

212

236

113

113

 

(l/s)

7.2

7.8

8.5

9.6

11.0

12.1

13.4

14.9

7.1

7.1

Maximum Flow

(gpm)

417

456

495

557

638

703

777

866

414

414

 

(l/s)

26.3

28.8

31.2

35.1

40.2

44.3

49.0

54.6

26.1

26.1

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser

 

 

 

 

 

 

 

 

 

 

 

 

Qty of Coils

 

8

10

10

12

12

12

14

16

8

10

Coil Length

(in)

78.74

78.74

78.74

78.74

78.74

78.74

78.74

78.74

78.74

78.74

 

(mm)

2000

2000

2000

2000

2000

2000

2000

2000

2000

2000

Coil Height

(in)

50

50

50

50

50

50

50

50

50

50

 

(mm)

1270

1270

1270

1270

1270

1270

1270

1270

1270

1270

Fins/Ft

 

192

192

192

192

192

192

192

192

192

192

Rows

 

3

3

3

3

3

3

3

3

3

3

 

 

 

 

 

 

 

 

 

 

 

 

 

Condenser Fans

 

 

 

 

 

 

 

 

 

 

 

 

Quantity

#

8

10

10

12

12

12

14

16

8

10

Diameter

(in)

37.5

37.5

37.5

37.5

37.5

37.5

37.5

37.5

37.5

37.5

 

(mm)

953

953

953

953

953

953

953

953

953

953

Total Airflow

(cfm)

107,392

134,240

134,240

161,088

161,088

161,088

187,936

214,784

107,392

132,240

 

(m3/hr)

182,460

228,075

228,075

273,690

273,690

273,690

319,305

364,920

182,460

228,075

Tip Speed (ft/min)

8700

8700

8700

8700

8700

8700

8700

8700

8700

8700

 

(M/S)

44.2

44.2

44.2

44.2

44.2

44.2

44.2

44.2

44.2

44.2

Ambient Temperature Range

 

 

 

 

 

 

 

 

 

 

Standard Ambient

°F (°C)

 

 

 

 

32 to 105 (0 to 40.6)

 

 

 

 

Low Ambient

°F (°C)

 

 

 

 

0 to 105 (-17.7 to 40.6)

 

 

 

 

Extreme Low Ambient

°F (°C)

 

 

 

 

-20 to 105 (-28.9 to 40.6)

 

 

 

 

High Ambient

°F (°C)

 

 

 

 

32 to 125 (0 to 52)

 

 

 

 

Wide Ambient

°F (°C)

 

 

 

 

0 to 125 (-17.7 to 52)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

General Unit

 

 

 

 

 

 

 

 

 

 

 

Refrigerant

 

 

 

 

HFC-134a

 

 

 

HFC-134a

Refrigerant Ckts

#

 

 

 

 

2

 

 

 

 

1

Minimum Load

%

20

18

17

15

20

18

16

15

30

27

Refrigerant Charge/ckt

(lbs)

172

181

210

218

265

261

318

325

322

346

 

(kg)

78

82

95

99

120

118

144

148

146

157

Oil

 

 

Trane OIL00311 (bulk)/OIL00315 (1 gal)/OIL00317 (5 gal)

 

 

 

Oil Charge/ckt

(gal)

3.0

3.0

3.0

3.0

4.0

4.0

4.0

4.0

4.0

4.0

 

(L)

11.4

11.4

11.4

11.4

15.1

15.1

15.1

15.1

15.1

15.1

 

 

 

 

 

 

 

 

 

 

 

 

10

RTAE-SVX001B-EN

General Data

Drive Cooling System

Drive cooling fluid volumes are dependent on unit configuration.

Use Table 2 for units that meet the following criteria:

Model number digits 10, 11 = AA

Use Table 2 for units that meet the following criteria:

Model number digits 10, 11 = AB

AND Digits 28, 29 = 0X

Table 2. Drive cooling with load inductor

Use Table 2 for units that meet the following criteria:

Model number digits 10, 11 = AC

AND Digits 3-7 = 225, 250, 275 or 300

AND Digit 22 = 1 or 2

AND Digits 28, 29 = 0X

Use Table 3 for all other unit configurations.

 

 

 

 

Unit Size (tons)

 

 

 

 

 

 

 

 

Standard Length Unit

 

 

 

 

 

 

150

 

 

225-250

 

275-300

 

 

165-200

 

 

 

gal

l

gal

l

 

gal

l

 

gal

l

 

 

 

 

 

 

 

 

 

Fluid Type

 

 

Trane Heat Transfer Fluid CHM01023

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluid Volume

 

 

 

 

 

 

 

 

 

 

Ckt 1

1.74

6.58

1.83

6.92

 

2.00

7.58

 

2.09

7.92

Ckt2

1.93

7.30

2.27

8.59

 

2.44

9.24

 

2.58

9.78

Total

3.67

13.88

4.10

15.51

 

4.44

16.82

 

4.67

17.69

 

 

 

 

 

 

 

 

 

 

 

Table 3. Drive cooling without load inductor

 

 

 

 

 

 

 

 

Unit Size (tons)

 

 

 

 

 

 

 

 

 

 

Standard Length Unit

 

 

 

 

Extended Length Units(a)

 

 

 

 

 

 

 

 

 

 

 

 

150S - 165S

 

150

165-250

275-300

150S - 165S

150

165-250

275-300

 

gal

l

 

gal

l

gal

l

gal

l

gal

l

gal

l

gal

l

gal

l

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fluid Type

 

 

 

 

 

 

Trane Heat Transfer Fluid CHM01023

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FluidVolume

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ckt 1

1.28

4.86

 

1.14

4.30

1.23

4.64

1.32

4.98

1.37

5.20

1.30

4.93

1.32

4.98

1.41

5.33

Ckt2

n/a

n/a

 

1.32

5.01

1.67

6.31

1.81

6.84

n/a

n/a

1.67

6.31

1.81

6.84

1.95

7.38

Total

1.28

4.86

 

2.46

9.31

2.89

10.95

3.12

11.83

1.37

5.20

2.97

11.23

3.12

11.83

3.36

12.71

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(a) Units are extended length if either of the following are selected: Transformer (model number digit 28 = 1)

Harmonic Filtration Option (model number digit 29 = 1)

Units without Harmonic Filtration Option or Transformer (digits 28, 29 = 0X) are standard length.

NOTICE:

Equipment Damage!

Use only Trane Heat Transfer Fluid P/N CHM01023. This fluid is a direct use concentration and is not to be diluted. Do not top off with water or any other fluid. Use of unapproved fluids, or dilution of approved fluid could result in catastrophic equipment damage.

Non-Trane approved chemicals could react with system components and result in failure. Contact a qualified service technician and your localTrane Parts Center.

Note: The use of incorrect compounds in the drive cooling system may result in scaling, erosion, corrosion or freezing.TheTrane Company warranty specifically excludes liability for corrosion, erosion, freezing or deterioration of Trane equipment.

Proper fluid level is important to the operation of the unit. See “Drive Cooling ExpansionTank,” p. 71 for fluid level check instructions.The circuit capacities are shown in tables above.

If the level is below the recommended minimum levels, contact your localTrane office.

Note: Drive cooling fluid service life is 5 years. See “Drive Cooling System,” p. 71.

RTAE-SVX001B-EN

11

Pre-Installation

Unit Inspection

When unit is delivered, verify it is the correct unit and is properly equipped. Compare information on the unit nameplate with ordering and submittal information. Inspect all exterior components for visible damage. Report any apparent damage or material shortage to carrier and make a “unit damage” notation on carrier’s delivery receipt. Specify extent and type of damage found and notifyTrane Sales Office. Do not proceed with installation of a damaged unit without sales office approval.

Inspection

To protect against loss due to damage in transit, complete the following steps upon receipt of unit.

Inspect the individual pieces of the shipment before accepting the unit. Check for obvious damage to the unit or packing material.

Inspect the unit for concealed damage as soon as possible after delivery and before it is stored. Concealed damage must be reported within 15 days.

If concealed damage is discovered, stop unpacking the shipment. Do not remove damaged material from the receiving location.Take photos of the damage, if possible.The owner must provide reasonable evidence that the damage did not occur after delivery.

Notify the carrier’s terminal of the damage immediately, by phone and by mail. Request an immediate, joint inspection of the damage with the carrier and the consignee.

NotifyTrane sales representative and arrange for repair. Do not repair unit until damage is inspected by the carrier’s representative.

Storage

Extended storage of outdoor unit prior to installation requires these precautionary measures:

Store the outdoor unit in a secure area.

For units that have been charged with refrigerant, verify the following valves are closed on each circuit:

Suction service valve (butterfly valve)

Liquid line angle valve or EXV (EXV is driven closed whenever circuit is powered)

Oil line shutoff valves to brazed plate heat exchangers

Note: Units with factory refrigerant charge (model number digit 15 = 1) are shipped with suction, liquid and oil line shutoff valves closed, isolating most of refrigerant charge in the evaporator. If unit goes directly into long term storage, it is recommended that these valve positions be confirmed.

For units with nitrogen charge option (model number digit 15 = 2), units are shipped with valves open. If unit goes directly into storage prior to refrigerant charge, confirm all service valves are open.

N2

At least every three months (quarterly), check the pressure in the refrigerant circuits to verify that the refrigerant charge is intact. If it is not, contact a

qualified service organization and the appropriate Trane sales office.

12

RTAE-SVX001B-EN

Pre-Installation

Installation Requirements

A list of the contractor responsibilities typically associated with the unit installation process is provided in Table 4.

Table 4. Installation requirements

 

Trane Supplied

Trane Supplied

Field Supplied

Type

Trane Installed

Field Installed

Field Installed

 

 

 

 

Foundation

 

 

• Meet foundation requirements

 

 

 

 

 

 

 

• Safety chains

Rigging

 

 

• Clevis connectors

 

 

• Lifting beam

 

 

 

 

 

 

• Spreader bar

 

 

 

 

 

• Trane, or an agent

 

 

 

of Trane specifically

 

 

Disassembly/Reassembly

authorized to perform

 

 

start-up of Trane®

 

 

(as required)(a)

 

 

products (contact

 

 

 

your local Trane

 

 

 

office for pricing)

 

 

 

 

 

 

Isolation

 

• Elastomeric isolators

• Elastomeric isolators (optional)

 

(optional)

 

 

 

 

 

 

 

 

 

 

• Circuit breakers (optional)

 

 

 

• Electrical connections to unit mounted starter

 

 

 

• Wiring sizes per submittal and NEC

 

• Circuit breakers

 

• Terminal lugs

Electrical

(optional)

 

• Ground connection(s)

 

• Unit mounted starter

 

• BAS wiring (optional)

 

 

 

• Control voltage wiring

 

 

 

• Chilled water pump contactor and wiring

 

 

 

• Option relays and wiring

 

 

 

 

 

 

 

• Taps for thermometers and gauges

 

 

 

• Thermometers

 

 

 

• Water flow pressure gauges

Water piping

• Flow switch

 

• Isolation and balancing valves in water piping

 

 

 

• Vents and drain

 

 

 

• Waterside pressure relief valves

 

 

 

• Water strainer

 

 

 

 

Insulation

• Insulation

 

• Insulation

 

 

 

 

Water Piping Connection Components

• Grooved pipe

• Flange kit (optional)

 

 

 

 

 

Other Materials

• R-134a refrigerant

 

 

• Dry nitrogen

 

 

 

(optional)

 

 

 

 

 

 

“Stealth™ RTAE Installation

 

 

 

Completion Check Sheet and Request

 

 

 

for Trane Service”

 

 

 

(RLC-ADF002-EN,

 

 

 

see “Log and Check Sheet,” p. 90)

 

 

 

 

 

 

 

 

• Trane, or an agent of

 

 

Chiller Start-up Commissioning(b)

Trane specifically

 

 

authorized to perform

 

 

 

start-up of Trane®

 

 

 

products

 

 

 

 

 

 

(a)Trane, or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products, will perform or have direct on-site supervision of the disassembly and reassembly work.

(b)Start-up must be performed by Trane or an agent of Trane specifically authorized to perform start-up and warranty of Trane® products. Contractor shall provide Trane (or an agent of Trane specifically authorized to perform start-up) with notice of the scheduled start-up at least two weeks prior to the scheduled start-up.

RTAE-SVX001B-EN

13

Dimensions and Weights

Weights

Table 5. Weights

 

 

Standard Length Unit

 

 

Extended Length Unit(a)

 

Unit Size

Shipping

Operating

Shipping

Operating

(tons)

lbs

kg

lbs

kg

lbs

kg

lbs

kg

 

 

 

 

 

 

 

 

 

 

InvisiSound™ Standard or Superior(b)

 

 

150S

9436

4280

9596

4353

11013

4995

11173

5068

165S

10451

4741

10611

4813

12011

5448

12171

5521

 

 

 

 

 

 

 

 

 

150

11333

5141

11479

5207

13492

6120

13638

6186

165

12377

5614

12533

5685

14532

6592

14688

6662

180

12698

5760

12880

5843

14853

6737

15035

6820

200

13808

6263

14007

6354

15991

7254

16213

7354

 

 

 

 

 

 

 

 

 

225

15244

6915

15466

7015

17427

7905

17649

8005

250

15622

7086

15861

7195

17805

8076

18044

8185

275

16820

7630

17095

7754

18975

8607

19250

8732

300

17965

8149

18265

8285

20121

9127

20421

9263

 

 

 

 

 

 

 

 

 

 

 

 

 

InvisiSound

Ultimate(c)

 

 

 

150S

10236

4643

10396

4716

11813

5358

11973

5431

165S

11251

5103

11411

5176

12811

5811

12971

5884

 

 

 

 

 

 

 

 

 

150

12133

5504

12279

5570

14292

6483

14438

6549

165

13177

5977

13333

6048

15332

6955

15488

7025

180

13498

6123

13680

6205

15653

7100

15835

7183

200

14608

6626

14807

6716

16791

7616

17013

7717

 

 

 

 

 

 

 

 

 

225

16044

7278

16266

7378

18227

8268

18449

8368

250

16422

7449

16661

7557

18605

8439

18844

8548

275

17620

7992

17895

8117

19775

8970

20050

9095

300

18765

8512

19065

8648

20921

9490

21221

9626

 

 

 

 

 

 

 

 

 

(a) Units are extended length if either of the following are selected: Transformer (model number digit 28 = 1)

Harmonic Filtration Option (model number digit 29 = 1)

Units without Harmonic Filtration Option or Transformer (digits 28, 29 = 0X) are standard length. (b)Model number digit 12 = 1 or 2

(c) Model number digit 12 = 3

Unit Dimensions

See unit submittals for specific unit dimensions and water connection locations.

Service Clearances

Figure 5. RTAE service clearances - top view

NO OBSTRUCTIONS ABOVE UNIT

Control

 

Panel

85” (2160mm)

 

See note 2

40”

 

(1016

24”

mm)

(600.1mm)

 

See

 

note 1

 

 

36” (914.4mm)

14

 

NOTES:

1.A full 40” clearance is required in front of the control panel. Must be measured from front of panel, not end of unit base.

2.Clearance of 85” on the side of the

unit is required for coil replacement. Preferred side for coil replacement is shown (left side of unit, as facing control

panel), however either side is acceptable.

RTAE-SVX001B-EN

Installation Mechanical

Location Requirements

Sound Considerations

Refer toTrane Engineering Bulletin Chiller Sound Ratings and Installation Guide RLC-PRB035-EN for sound consideration applications.

Locate the unit away from sound-sensitive areas.

Install the optional elastomeric isolators under the unit. See “Isolation and Sound Emission,” p. 20.

Chilled water piping should not be supported by chiller frame.

Install rubber vibration isolators in all water piping.

Use flexible electrical conduit.

Seal all wall penetrations.

Note: Consult an acoustical engineer for critical applications.

Foundation

Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the applicable operating weight (i.e., including completed piping, and full operating charges of refrigerant, oil and water). See Table 5, p. 14 for unit operating weights. Once in place, the unit must be level within 1/4” (6.4 mm) across the length and width of the unit.TheTrane Company is not responsible for equipment problems resulting from an improperly designed or constructed foundation.

Clearances

Provide enough space around the unit to allow the installation and maintenance personnel unrestricted access to all service points. See submittal drawings for the unit dimensions, to provide sufficient clearance for the opening of control panel doors and unit service. See Figure 5, p. 14 for minimum clearances. In all cases, local codes which require additional clearances will take precedence over these recommendations.

For close spacing information, see RLC-PRB037-EN.

Rigging

WARNING

Improper Unit Lift!

Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in unit dropping and possibly crushing operator/technician which could result in death or serious injury and possible equipment or property-only damage.

WARNING

Heavy Objects!

Ensure that all the lifting equipment used is properly rated for the weight of the unit being lifted. Each of the cables (chains or slings), hooks, and shackles used to lift the unit must be capable of supporting the entire weight of the unit. Lifting cables (chains or slings) may not be of the same length. Adjust as necessary for even unit lift. Other lifting arrangements could cause equipment or property damage. Failure to follow instructions above or properly lift unit could result in unit dropping and possibly crushing operator/ technician which could result in death or serious injury.

WARNING

Proper Lifting Configuration Required!

Use only lift locations designated with label shown in Figure 6. Do NOT use locations marked with label shown in Figure 7. Use unit lifting configurations as shown in Table 6 and Figure 8, p. 16 thru Figure 10,

p. 17. Other lifting arrangements could result in death, serious injury or equipment damage.

Figure 6. Label - lift location

X39003897001A

Figure 7. Label - do not lift

X39003894001A

Important:

Do not fork lift unit.

See unit nameplate and/or unit submittal for total shipping weight.

See Table 6 and Figure 8 thru Figure 10 for unit lifting configuration.

See Table 7, p. 18 and Table 8, p. 19 for lift weights and dimensions at each lifting point locations.

See Table 9, p. 20 for center of gravity information.

RTAE-SVX001B-EN

15

Installation Mechanical

Table 6.

Lifting configuration selection

 

 

 

 

 

 

 

 

 

 

Tons

Unit Length(a)

Lift Configuration

See

 

 

150S, 165S, 150

Standard and Extended

4-point

Figure 8, p. 16

165, 180, 200, 225, 250

Standard

 

 

 

 

 

 

 

165, 180, 200, 225, 250

Extended

6-point

Figure 9, p. 17

 

 

275

Standard

 

 

 

 

 

 

 

 

 

 

 

 

275

Extended

8-point

Figure 10, p. 17

 

 

300

Standard and Extended

 

 

 

 

(a) Units are extended length if either of the following are selected: Transformer (model number digit 28 = 1)

Harmonic Filtration Option (model number digit 29 = 1)

Units without Harmonic Filtration Option or Transformer (digits 28, 29 = 0X) are standard length.

Figure 8. 4-point lift configuration

96” (2438mm) Spreader Bar

Lifting Location 2

(Lifting location 3

located on other side of unit)

Control Panel

Lifting Location 1

(Lifting location 4

located on other side of unit)

16

RTAE-SVX001B-EN

Installation Mechanical

Figure 9. 6-point lift configuration

96” (2438mm) Spreader Bar

96”

(2438mm) Spreader Bar

Control Panel

Lifting Location 3 (Lifting location 4 located on other side of unit)

Lifting Location 2 (Lifting location 5

located on other side of unit)

Lifting Location 1 (Lifting location 6

located on other side of unit)

Figure 10. 8-point lift configuration

96” (2438mm) Spreader Bar

Qty 2

Lifting Location 4 (Lifting location 5 located on other side of unit)

Lifting Location 3 (Lifting location 6

located on other side of unit)

Lifting Location 2 (Lifting location 5

located on other side of unit)

Control Panel

Lifting Location 1 (Lifting location 8 located on other side of unit)

RTAE-SVX001B-EN

17

Installation Mechanical

Table 7.

Lift weights by location

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Location

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

 

 

 

 

 

 

 

 

 

 

Tons

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Length Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150S

2540

1152

2451

1112

2164

981

2281

1034

-

-

-

-

-

-

-

-

 

165S

2656

1205

2352

1067

2730

1238

2713

1230

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

3426

1554

2638

1197

2234

1014

3035

1377

-

-

-

-

-

-

-

-

165

3452

1566

2876

1304

2810

1275

3239

1469

-

-

-

-

-

-

-

-

180

3528

1600

2941

1334

2896

1314

3333

1512

-

-

-

-

-

-

-

-

200

3586

1627

3325

1508

3316

1504

3581

1624

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

4003

1816

3551

1611

3617

1641

4073

1847

-

-

-

-

-

-

-

-

250

4098

1859

3637

1650

3711

1683

4176

1894

-

-

-

-

-

-

-

-

275

2484

1127

1943

881

3683

1671

3829

1737

2255

1023

2625

1191

-

-

-

-

300

2061

935

2289

1038

2515

1141

1682

763

2729

1238

3008

1364

1737

788

1943

881

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Extended Length Unit(a)

 

 

 

 

 

 

 

150S

2698

1224

2597

1178

2837

1287

2881

1307

-

-

-

-

-

-

-

-

 

165S

2988

1356

2841

1289

3135

1422

3047

1382

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

3825

1735

3363

1525

2920

1324

3384

1535

-

-

-

-

-

-

-

-

165

2653

1203

2629

1192

2570

1166

1959

889

2046

928

2675

1213

-

-

-

-

180

2685

1218

2674

1213

2641

1198

1946

883

2100

953

2807

1273

-

-

-

-

200

2919

1324

2640

1198

2797

1269

2846

1291

2274

1032

2514

1141

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

3065

1391

2705

1227

3237

1468

3144

1426

2406

1091

2870

1302

-

-

-

-

250

3117

1414

2749

1247

3322

1507

3229

1465

2458

1115

2930

1329

-

-

-

-

275

2145

973

2668

1210

3279

1487

1513

686

2412

1094

2482

1126

1644

746

2831

1284

300

2056

933

2440

1107

3452

1566

2241

1017

3089

1401

2993

1358

1460

662

2389

1084

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(a) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)

Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.

18

RTAE-SVX001B-EN

Installation Mechanical

Table 8.

Lifting locations (from control panel end of frame)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Location

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

3

 

4

 

 

5

 

 

6

 

 

7

 

 

8

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

Tons

 

in

mm

in

mm

in

mm

in

mm

 

in

mm

 

in

mm

 

in

mm

 

in

mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Length Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150S

 

45.5

1156

45.5

1156

153.9

3909

153.9

3909

 

-

-

 

-

-

 

-

-

 

-

-

 

165S

 

23.5

596

23.5

596

189.7

4818

189.7

4818

 

-

-

 

-

-

 

-

-

 

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

 

39.6

1006

39.6

1006

171.4

4353

171.4

4353

 

-

-

-

-

-

-

-

-

165

 

60.4

1534

60.4

1534

224.6

5705

224.6

5705

 

-

-

-

-

-

-

-

-

180

 

60.4

1534

60.4

1534

224.6

5705

224.6

5705

 

-

-

-

-

-

-

-

-

200

 

53.3

1355

53.3

1355

258.7

6570

258.7

6570

 

 

-

 

-

-

 

-

-

 

-

-

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

 

53.3

1355

53.3

1355

258.7

6570

258.7

6570

 

-

-

-

-

-

-

-

-

250

 

53.3

1355

53.3

1355

258.7

6570

258.7

6570

 

-

-

-

-

-

-

-

-

275

 

75.8

1926

75.8

1926

190.7

4845

190.7

4845

 

311.9

7922

311.9

7922

-

-

-

-

300

 

47.6

1210

47.6

1210

171.3

4350

171.3

4350

 

242.8

6168

242.8

6168

365.1

9274

365.1

9274

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Extended Length Unit(a)

 

 

 

 

 

 

 

 

 

 

150S

 

23.5

596

23.5

596

207.1

5261

207.1

5261

 

-

-

 

-

-

 

-

-

 

-

-

 

165S

 

23.5

596

23.5

596

242.9

6170

242.9

6170

 

-

-

 

-

-

 

-

-

 

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

 

44.7

1136

44.7

1136

224.6

5705

224.6

5705

 

-

-

 

-

-

 

-

-

 

-

-

165

 

61.1

1552

61.1

1552

171.3

4350

171.3

4350

 

277.8

7057

277.8

7057

-

-

-

-

180

 

61.1

1552

61.1

1552

171.3

4350

171.3

4350

 

277.8

7057

277.8

7057

-

-

-

-

200

 

47.6

1210

47.6

1210

190.7

4845

190.7

4845

 

311.9

7922

311.9

7922

 

-

 

-

-

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

 

47.6

1210

47.6

1210

190.7

4845

190.7

4845

 

311.9

7922

311.9

7922

-

-

-

-

250

 

47.6

1210

47.6

1210

190.7

4845

190.7

4845

 

311.9

7922

311.9

7922

-

-

-

-

275

 

75.8

1926

75.8

1926

182.0

4623

182.0

4623

 

258.5

6565

258.5

6565

365.1

9274

365.1

9274

300

 

47.6

1210

47.6

1210

168.5

4280

168.5

4280

 

296.1

7520

296.1

7520

418.3

10626

418.3

10626

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(a) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)

Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.

RTAE-SVX001B-EN

19

Installation Mechanical

Center of Gravity

Figure 11. Center of gravity

CG

X

SIDE VIEW

CG

Z

Y

END VIEW

(Non-Control Panel End)

Table 9.

Centers of gravity

 

 

 

 

 

 

 

 

 

 

 

 

 

CGx

 

 

CGy

 

CGz

 

Tons

in

mm

in

mm

in

mm

 

 

 

 

 

 

 

 

 

 

Standard Length Unit

 

 

 

 

 

 

 

 

 

 

 

150S

96.6

2454

43.8

1112

40.4

1025

 

165S

110.0

2793

45.2

1149

42.8

1087

 

 

 

 

 

 

 

 

150

105.5

2679

43.9

1115

37.5

953

165

142.4

3617

43.9

1115

39.7

1008

180

142.8

3628

43.9

1115

39.4

1002

200

155.5

3951

43.9

1115

41.2

1047

 

 

 

 

 

 

 

 

225

156.1

3964

43.9

1115

39.8

1011

250

156.4

3973

43.9

1115

39.7

1008

275

194.1

4930

43.9

1115

41.1

1043

300

207.1

5260

43.9

1115

42.4

1076

 

 

 

 

 

 

 

 

 

 

Extended Length Unit(a)

 

 

 

150S

118.8

3017

44.1

1121

37.2

944

 

165S

136.4

3464

44.7

1137

39.4

1002

 

 

 

 

 

 

 

 

150

134.7

3421

43.9

1115

33.3

846

165

169.1

4295

43.9

1115

35.4

898

180

169.9

4314

43.9

1115

35.2

894

200

181.6

4613

43.9

1115

36.9

937

 

 

 

 

 

 

 

 

225

183.6

4665

43.9

1115

36.0

915

250

184.2

4680

43.9

1115

36.0

913

275

220.2

5594

43.9

1115

37.4

950

300

232.3

5900

43.9

1115

38.7

984

 

 

 

 

 

 

 

 

(a) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)

UnitswithoutLowHarmonicDistortionOptionorAutotransformer(digits 28, 29 = X0) are standard length.

Isolation and Sound Emission

The most effective form of isolation is to locate the unit away from any sound sensitive area. Structurally transmitted sound can be reduced by elastomeric vibration eliminators. Spring isolators are not recommended. Consult an acoustical engineer in critical sound applications.

For maximum isolation effect, isolate water lines and electrical conduit. Wall sleeves and rubber isolated piping hangers can be used to reduce the sound transmitted through water piping.To reduce the sound transmitted through electrical conduit, use flexible electrical conduit.

State and local codes on sound emissions should always be considered. Since the environment in which a sound source is located affects sound pressure, unit placement must be carefully evaluated. Sound power levels for Stealth chillers are available on request.

Unit Isolation and Leveling

For additional reduction of sound and vibration, install the optional elastomeric isolators.

Construct an isolated concrete pad for the unit or provide concrete footings at the unit mounting points. Mount the unit directly to the concrete pads or footings.

Level the unit using the base rail as a reference.The unit must be level within 1/4-in (6 mm) over the entire length and width. Use shims as necessary to level the unit.

Elastomeric Isolators

(Optional for units without seismic rating)

Note: See unit submittal, or Table 11, p. 21 thru Table 13, p. 23 for point weights, isolator location and isolator selections.

1.Secure the isolators to the mounting surface using the mounting slots in the isolator base plate. Do not fully tighten the isolator mounting bolts at this time.

2.Align the mounting holes in the base of the unit with the threaded positioning pins on the top of the isolators.

3.Lower the unit onto the isolators and secure the isolator to the unit with a nut.

4.Level the unit carefully. Fully tighten the isolator mounting bolts.

20

RTAE-SVX001B-EN

5.

Figure 12. Elastomeric isolator

5.0 in

1/2 - 13NC - 2B

4.63 in

0.56 in

0.50 in

1.60 ± .25 in

Mounting molded in neoprene

3.0 in

2.75 in

0.38 in

Max Load

 

Maximum

 

(lbs)

Color

Deflection (in)

Type

 

 

 

 

2250

RED

0.50

RDP-4

3000

GREEN

0.50

RDP-4

 

 

 

 

Installation Mechanical

Elastomeric Isolation Pads for Seismic Option

Elastomeric pads ship inside the unit control panel.They are provided with an isolation washer and 3/4” free hole in the center of the plate.

Figure 13. Seismic isolation pad — installed

Table 10. Seismically rated elastomeric isolation pad

 

 

Dimension (in)

 

Model

Max Load

Length

Width

Height

 

 

 

 

 

B-36

2520

6

6

.625

 

 

 

 

 

Figure 14. Mounting point locations(a)

2

4

6

8

10

Control panel

 

 

 

 

1

3

5

7

9

(a)Quantity of isolators varies with unit. Shorter units will not use locations 5 and 6. See submittal for actual number required for specific unit.

Table 11. Point weights

 

 

 

 

 

 

 

 

 

 

Location

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

Tons

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

 

lb

kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150S

1731

785

1664

755

1834

832

1773

804

1219

553

1375

624

-

-

-

-

-

-

 

-

-

165S

1666

756

1559

707

1886

855

1870

848

1914

868

1716

778

-

-

-

-

-

-

 

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

1452

659

1543

700

1326

602

1446

656

1464

664

1350

612

1490

676

1262

572

-

-

 

-

-

165

1539

698

1341

608

1622

736

1553

704

1657

752

1607

729

1522

690

1536

697

-

-

 

-

-

180

1536

697

1338

607

1676

760

1620

735

1709

775

1659

753

1579

716

1581

717

-

-

 

-

-

200

1442

654

1764

800

1696

769

1810

821

1836

833

1694

768

1986

901

1580

717

-

-

 

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

1430

649

1792

813

1999

907

2058

933

2111

958

1994

905

2139

970

1721

781

-

-

 

-

-

250

1426

647

1803

818

2064

936

2144

973

2182

990

2055

932

2195

996

1753

795

-

-

 

-

-

275

1624

737

1627

738

1802

817

1746

792

1795

814

1530

694

1653

750

1831

830

1577

715

 

1634

741

300

1634

741

1850

839

1871

849

1925

873

1898

861

1938

879

1887

856

1695

769

1752

795

 

1515

687

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RTAE-SVX001B-EN

21

Installation Mechanical

Table 11.

Point weights (continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Location

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tons

lb

 

kg

lb

kg

 

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

lb

kg

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Extended Length Unit(a)

 

 

 

 

 

 

 

 

 

150S

1553

704

1795

814

 

1974

895

1959

889

2088

947

1804

818

-

-

-

-

-

-

-

-

 

165S

1344

610

1236

561

 

1537

697

1494

678

1686

765

1668

757

1636

742

1570

712

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

1563

709

1621

735

 

1705

773

1875

850

1952

885

1575

714

1601

726

1601

726

-

-

-

-

165

1776

806

1827

829

 

1956

887

1925

873

2058

933

1958

888

1517

688

1515

687

-

-

-

-

180

1774

805

1822

827

 

1990

903

1975

896

2128

965

2030

921

1577

715

1557

706

-

-

-

-

200

1706

774

1524

691

 

1662

754

1294

587

1938

879

1738

788

1267

575

1753

795

1457

661

1652

749

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

1857

842

1669

757

 

1844

836

1412

640

2156

978

1860

844

1378

625

1985

900

1501

681

1766

801

250

1852

840

1664

755

 

1885

855

1439

653

2219

1006

1936

878

1438

652

2046

928

1530

694

1795

814

275

1874

850

1860

844

 

1626

737

1700

771

2204

1000

2101

953

2017

915

2131

967

1820

826

1642

745

300

1946

883

1826

828

 

1854

841

1795

814

2143

972

2106

955

2408

1092

2338

1060

1808

820

1898

861

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(a) Units are extended length if either of the following are selected:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Low Harmonic Distortion Option (model number digit 29 = 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

Autotransformer (model number digit 28 = 1 or 2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.

 

 

 

 

 

 

Table 12.

Isolator locations(a)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Location

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

5

 

6

 

7

 

8

 

9

 

10

 

Tons

in

 

mm

in

mm

 

in

mm

in

mm

in

mm

in

mm

in

mm

in

mm

in

mm

in

mm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150S

23.6

600

27.6

700

 

102.4

2600

94.5

2400

187.0

4750

187.0

4750

-

-

-

-

-

-

-

-

 

165S

15.7

400

23.0

585

 

98.4

2500

102.2

2595

196.9

5000

204.7

5200

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

24.4

620

11.8

300

 

47.2

1200

82.7

2100

100.4

2550

153.5

3900

188.2

4780

188.2

4780

-

-

-

-

165

17.7

450

23.0

585

 

98.6

2505

102.2

2595

155.5

3950

190.6

4840

242.1

6150

242.9

6170

-

-

-

-

180

17.7

450

23.0

585

 

98.6

2505

102.2

2595

155.5

3950

190.6

4840

242.1

6150

242.9

6170

-

-

-

-

200

23.6

600

23.6

600

 

102.4

2600

137.8

3500

155.5

3950

198.8

5050

255.9

6500

263.8

6700

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

23.6

600

23.6

600

 

102.4

2600

137.8

3500

155.5

3950

198.8

5050

255.9

6500

263.8

6700

-

-

-

-

250

23.6

600

23.6

600

 

102.4

2600

137.8

3500

155.5

3950

198.8

5050

255.9

6500

263.8

6700

-

-

-

-

275

21.7

550

18.9

480

 

141.3

3590

125.2

3180

196.1

4980

236.2

6000

236.2

6000

259.8

6598

328.0

8330

324.4

8240

300

19.7

500

27.6

700

 

143.1

3634

143.1

3634

202.4

5142

235.6

5984

257.9

6551

296.6

7534

347.8

8834

339.5

8624

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Extended Length Unit(b)

 

 

 

 

 

 

 

 

 

150S

19.7

500

15.7

400

 

102.4

2600

133.9

3400

204.7

5200

208.7

5300

-

-

-

-

-

-

-

-

 

165S

23.6

600

23.6

600

 

86.6

2200

78.7

2000

149.6

3800

157.5

4000

259.8

6600

259.8

6600

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

25.0

635

23.6

600

 

84.6

2150

98.4

2500

147.6

3750

190.9

4850

240.2

6100

240.2

6100

-

-

-

-

165

19.7

500

19.7

500

 

129.9

3300

129.9

3300

204.7

5200

234.3

5950

293.3

7450

299.2

7600

-

-

-

-

180

19.7

500

19.7

500

 

129.9

3300

129.9

3300

204.7

5200

234.3

5950

293.3

7450

299.2

7600

-

-

-

-

200

25.6

650

19.7

500

 

118.1

3000

98.4

2500

208.7

5300

196.9

5000

255.9

6500

255.9

6500

315.0

8000

315.0

8000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

25.6

650

19.7

500

 

118.1

3000

98.4

2500

208.7

5300

196.9

5000

255.9

6500

255.9

6500

315.0

8000

315.0

8000

250

25.6

650

19.7

500

 

118.1

3000

98.4

2500

208.7

5300

196.9

5000

255.9

6500

255.9

6500

315.0

8000

315.0

8000

275

6.3

 

160

9.8

250

 

177.2

4500

139.8

3550

198.8

5050

242.1

6150

309.1

7850

313.0

7950

354.3

9000

370.1

9400

300

9.8

 

250

9.8

250

 

177.2

4500

139.8

3550

206.7

5250

242.1

6150

311.8

7920

313.4

7960

393.7 10000

393.7 10000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(a) Dimensions are referenced from end of frame on the control panel side. (b)Units are extended length if either of the following are selected:

Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)

Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.

22

RTAE-SVX001B-EN

Installation Mechanical

Table 13.

Isolator selections

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Location

 

 

 

 

 

 

 

 

 

Tons

 

1

 

 

3

 

4

 

5

 

6

 

7

 

8

 

9

 

10

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard Length Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150S

 

Red 62

Red 62

 

Red 62

 

Red 62

 

Red 62

 

Red 62

 

-

-

 

-

-

 

165S

 

Red 62

Red 62

 

Red 62

 

Red 62

 

Red 62

 

Red 62

 

-

-

 

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

-

-

165

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

-

-

180

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

-

-

 

200

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

-

-

 

225

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

-

-

250

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

275

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

300

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

 

 

 

 

 

 

 

Extended Length Unit(a)

 

 

 

 

 

 

 

 

 

150S

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

-

-

 

-

-

 

165S

 

Red 62

Red 62

 

Red 62

 

Red 62

 

Red 62

 

Red 62

 

Red 62

 

Red 62

 

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

150

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

-

-

165

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

-

-

180

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

-

-

 

200

 

Red 62

Red 62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

225

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

250

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

275

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

300

 

Red 62

Red 62

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Green 63

 

Red 62

 

Red 62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(a) Units are extended length if either of the following are selected: Low Harmonic Distortion Option (model number digit 29 = 1) Autotransformer (model number digit 28 = 1 or 2)

Units without Low Harmonic Distortion Option or Autotransformer (digits 28, 29 = X0) are standard length.

Compressor Shipping Bolt Removal

Units with InvisiSound™ Ultimate Option (Model Number Digit 12 = 3)

For chillers built with InvisiSound Ultimate option, compressor shipping bolts must be removed to assure minimum noise during operation. Use a 24mm socket to remove the (3) M15 x 75mm shipping bolts for each compressor.They are located under compressor mounting feet. See Figure 15.

Important:

DO NOT DISCARD SHIPPING BOLTS. Store bolts in the control panel for future use.

All shipping bolts MUST be reinstalled prior to compressor removal or unit move.

NOTICE:

Equipment Damage!

Do not remove compressor or move unit without reattaching compressor shipping bolts. Failure to reinstall bolts could cause shifting of parts and result in equipment damage.

Figure 15. Compressor shipping bolt removal

Isolator

 

 

Compressor

Compressor

 

Mounting

 

Foot

Shipping Bolt

 

Drainage

Locate the unit near a large capacity drain for water vessel drain-down during shutdown or repair. Evaporators are provided with drain connections. A vent on top of evaporator waterbox prevents vacuum by allowing air into evaporator for complete drainage. All local and national codes apply.

RTAE-SVX001B-EN

23

Installation Mechanical

Evaporator Piping

RTAE units are available with 2 or 3 pass configurations. See Figure 16.

Figure 16. Evaporator pass configurations

2-Pass Evaporators

Control Panel End

Top View (Condenser removed for clarity)

Inlet Water

Connection

Outlet Water

Outlet

Inlet

Connection

 

End View

 

 

(Non-control panel end)

3-Pass Evaporators

Outlet Waterbox

Control Panel End

Inlet Waterbox (Outlet waterbox opposite end)

Top View

 

End View

Inlet Waterbox

(Non-control panel end)

(Condenser removed for clarity)

 

 

NOTICE:

Proper Water Treatment!

The use of untreated or improperly treated water could result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required. Trane assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water.

NOTICE:

Evaporator Damage!

The chilled water connections to the evaporator are to be “victaulic” type connections. Do not attempt to weld these connections, as the heat generated from welding can cause microscopic and macroscopic fractures on the cast iron waterboxes that can lead to premature failure of the waterbox. To prevent damage to chilled water components, do not allow evaporator pressure (maximum working pressure) to exceed 150 psig (10.5 bar).

Evaporator water connections are grooved.

Thoroughly flush all water piping to the unit before making the final piping connections to the unit.

Components and layout will vary slightly, depending on the location of connections and the water source.

A vent is provided on the top of the evaporator at the chilled water inlet. Be sure to provide additional vents at high points in the piping to bleed air from the chilled water system. Install necessary pressure gauges to monitor the entering and leaving chilled water pressures.

Provide shutoff valves in lines to the gauges to isolate them from the system when they are not in use. Use rubber vibration eliminators to prevent vibration transmission through the water lines.

If desired, install thermometers in the lines to monitor entering and leaving water temperatures. Install a balancing valve in the leaving water line to control water flow balance. Install shutoff valves on both the entering and leaving water lines so that the evaporator can be isolated for service

24

RTAE-SVX001B-EN

 

 

 

 

 

 

 

Installation Mechanical

Evaporator Piping Components

 

 

operating safety. SeeThese components and their general

Piping components include all devices and controls used

locations are given below.

 

 

to provide proper water system operation and unit

 

 

Figure 17. Typical Stealth™ water piping

 

 

 

 

 

6

4

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

8

 

B

 

7

3

2

 

 

 

 

 

 

A

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

A

 

 

 

2

8

C

 

2

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

Table 14. Water piping components

 

 

 

 

 

Item

Description

 

 

 

Item

Description

 

1

Bypass Valve

 

 

 

Pi

Pressure Gauge

 

2

Isolation Valve

 

 

 

FT

Water Flow Switch

 

3

Vibration Eliminator

 

 

 

T1

Evap Water Inlet Temp Sensor

4

Evaporator - End View (2-pass)

 

 

T2

Evap Water Outlet Temp Sensor

5

Evaporator Waterbox (2-pass)

 

 

 

 

NOTES

6

Vent

 

 

 

A

Isolate unit for initial water loop cleaning

7

Strainer

 

 

 

B

Vent must be installed at the high point of the line

8

Drain

 

 

 

C

Drain must be installed at the low point of the line

Entering Chilled Water Piping

Air vents (to bleed air from system).

Water pressure gauges with shutoff valves.

Vibration eliminators.

Shutoff (isolation) valves.Thermometers (if desired).

Clean-out tees.

Pipe strainer.

Leaving Chilled Water Piping

Air vents (to bleed air from system).

Water pressure gauges with shutoff valves.

Vibration eliminators.

Shutoff (isolation) valves.

Thermometers.

Clean-out tees.

Balancing valve.

Drains

A 1/2” drain connection is located under outlet end of evaporator waterbox for drainage during unit servicing. A shutoff valve must be installed on drain line.

Pressure Gauges

Install field-supplied pressure components as shown in Figure 17, p. 25. Locate pressure gauges or taps in a straight run of pipe; avoid placement near elbows, etc. Be sure to install the gauges at the same elevation on each shell if the shells have opposite-end water connections.

To read manifolded pressure gauges, open one valve and close the other (depending upon the reading desired).This eliminates errors resulting from differently calibrated gauges installed at unmatched elevations.

RTAE-SVX001B-EN

25

Installation Mechanical

Pressure Relief Valves

NOTICE:

Evaporator Damage!

To prevent shell damage, install pressure relief valves in the evaporator water system.

Indexing Flow Switch

To properly index the flow switch, the following requirements must be met:

The dot must be at a position no greater than 90° off Index.

The torque must be between 22 ft-lb minimum and 74 ft-lb maximum.

Install a water pressure relief valve in the evaporator inlet piping between the evaporator and the inlet shutoff valve, as shown in Figure 17, p. 25. Water vessels with closecoupled shutoff valves have a high potential for hydrostatic pressure buildup on a water temperature increase. Refer to applicable codes for relief valve installation guidelines.

Evaporator Flow Switch

NOTICE:

Equipment Damage!

Flow switch is on a 24V circuit. Do NOT apply 120V to the flow switch. Incorrect voltage application could cause damage to the flow switch.

The flow switch is factory-installed and programmed based on the operating conditions submitted with the order.The leaving evaporator temperature, fluid type and fluid concentration affect the selected flow switch. If the operating conditions on the job site change, the flow switch may need to be replaced. Contact your localTrane Sales office for more information.

The sensor head includes 3 LEDs, two yellow and one green.Wait 15 seconds after power is applied to the sensor before evaluating LEDs for flow status. When wired correctly and flow is established, only the green LED should be lit. Following are the LED indicators:

A minimum distance of 5x pipe diameter must be maintained between flow switch and any bends, valves, changes in cross sections, etc.

Figure 18. Proper flow switch indexing

Top View

Flow

Index

The flow switch must have the dot

in the shaded area to the left of this line for proper indexing (±90° off Index)

Green ON, both yellow OFF — Flow

Green and outside yellow ON — No Flow

Center yellow ON continuously — Miswire

Factory installed jumper wire W11 must be removed if using auxiliary contacts and/or additional proof of flow. See schematics in RTAE-SVE01*-EN for more details.

NOTICE:

Equipment Damage!

Incorrect wiring of auxiliary contacts could cause equipment damage.

If using auxiliary flow sensing, both yellow LEDs come on initially when flow is stopped.The center yellow LED will turn off after approximately 7 seconds.The LED indicators are otherwise the same as indicated above.

26

RTAE-SVX001B-EN

Installation Mechanical

Evaporator Waterside Pressure Drop Curves

Figure 19. Evaporator waterside pressure drop curve — 2-pass

 

50

300T

 

 

 

 

 

 

 

47.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

45

275T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42.5

250T

 

 

 

 

 

 

 

40

225T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

37.5

200T

 

 

 

 

 

 

 

35

 

 

 

 

 

 

H2O)

 

 

 

 

 

 

 

32.5

185T

 

 

 

 

 

 

 

 

 

 

 

 

 

30

165T

 

 

 

 

 

 

(ft.

 

 

 

 

 

 

27.5

 

 

 

 

 

 

 

Drop

150T

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

Pressure

150S,

 

 

 

 

 

 

22.5

 

 

 

 

 

 

165S

 

 

 

 

 

 

20

 

 

 

 

 

 

 

17.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

12.5

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

7.5

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

2.5

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

0

200

400

600

800

1000

1200

1400

Water Flow (GPM)

RTAE-SVX001B-EN

27

Installation Mechanical

Figure 20. Evaporator waterside pressure drop curve — 3-pass

 

 

 

 

 

 

75

300T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

275T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

250T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

225T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

200T

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H2O)

50

185T

 

 

 

 

 

 

 

 

 

45

165T

 

 

 

 

 

 

 

 

 

(ft.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drop

40

150T

 

 

 

 

 

 

 

 

 

 

150S,

 

 

 

 

 

 

 

 

 

Pressure

35

 

 

 

 

 

 

 

 

 

 

165S

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

0

100

200

300

400

500

600

700

800

900

1000

Water Flow (GPM)

28

RTAE-SVX001B-EN

Installation Mechanical

Freeze Protection

One or more of the ambient freeze avoidance methods in Table 15 must be used to protect the Stealth chiller from ambient freeze damage.

Table 15. RTAC freeze avoidance methods

 

Protects to

 

Method

ambient

 

temperature

Notes

 

 

 

 

 

Heaters alone will provide low ambient protection down to -20°F (-29°C), but will NOT

 

 

protect the evaporator from freezing as a result of charge migration. Therefore, it is

 

 

required that water pump control be used in conjunction with heaters.

 

 

• Heaters are factory-installed on the evaporator and water piping and will protect them from freezing

 

 

• Install heat tape on all water piping, pumps, and other components that may be damaged if exposed

 

 

to freezing temperatures. Heat tape must be designed for low ambient temperature applications. Heat

 

 

tape selection should be based on the lowest expected ambient temperature.

 

 

• Tracer™ UC800 controller can start the pump when freezing conditions are detected. For this option

 

 

the pump must to be controlled by the Stealth unit and this function must be validated.

 

 

• Water circuit valves need to stay open at all times.

 

 

• Water pump control and heater combination will protect the evaporator down to any

Water Pump Control

Down to -20°F

ambient temperature provided power is available to the pump and the controller. This

AND Heaters

option will NOT protect the evaporator in the event of a power failure to the chiller unless

 

 

backup power is supplied to the necessary components.

 

 

• When no chiller operation is possible and the pump is already off, UC800 pump control for freeze

 

 

protection will command the pump to turn:

 

 

ON if average of the evaporator entering water temperature, the evaporator leaving water

 

 

temperature, and the evaporator refrigerant pool temperature is less than Low Evaporator Refrigerant

 

 

Temperature Cutout (LERTC) + 4°F for a period of time.

 

 

OFF again if the evaporator refrigerant pool temperature rises above the LERTC + 6°F for a period

 

 

of time.

 

 

Note: Time period referenced for ON and Off conditions above is dependent on past running conditions

 

 

and present temperatures measured.

 

 

ON if entering OR leaving water temperature< LWTC for 30°F-sec (17°C-sec)

 

 

OFF again if water temperature > LWTC for 30 min

 

 

 

 

Varies.

• Freeze protection can be accomplished by adding sufficient glycol to protect against freezing below

 

See “Low

the lowest ambient expected.

 

Evaporator

• Use of glycol type antifreeze reduces the cooling capacity of the unit and must be

Freeze Inhibitor

Refrigerant Cutout,

considered in the design of the system specifications.

 

Glycol

 

 

Requirements,”

 

 

p. 30

 

 

 

 

 

 

• Shut off the power supply to the unit and to all heaters.

Drain Water Circuit

Below -20°F

• Purge the water circuit.

 

 

• Blow out the evaporator to ensure no liquid is left in the evaporator.

 

 

 

NOTICE:

Evaporator Damage!

If insufficient concentration or no glycol is used, the evaporator water flow must be controlled by the UC800 AND heaters must be used to avoid catastrophic damage to the evaporator due to freezing. It is the responsibility of the installing contractor and/or the customer to ensure that a pump will start when called upon by the chiller controls. Refer to RLC-PRB012-EN. Even with water pump control, a power loss of as little as 15 minutes under freezing conditions can damage the evaporator. Only the proper addition of freeze inhibitor or complete drainage of the water circuit can ensure no evaporator damage in the event of a power failure.

RTAE-SVX001B-EN

29

Loading...
+ 67 hidden pages