Air Outlet Guide (to change air blowing direction) |
PAC-SH96SG-E |
|||
Figure |
|
Descriptions |
||
|
|
A part to change air direction from outdoor unit. Can also be |
||
|
|
used to prevent short cycles. |
||
|
|
Applicable Models |
||
|
|
PUHZ-ZRP100/125/140KA |
||
|
|
PUHZ-RP200/250KA |
|
|
|
|
|
2 pieces required |
|
|
|
Specifications |
||
|
|
|
Color (Munsell) |
Ivory (3.0Y 7.8/1.1) |
|
Air outlet guide |
Exterior |
Material |
Air outlet grille: Alloy hot-dip zinc- |
|
|
coated carbon steel sheet |
||
|
|
|
||
|
|
Weight |
|
7kg |
|
|
Air outlet direction |
Changeable between up, down or sideways |
|
|
|
Accessory name x Qty. |
Washer faced screw (M5x15) x 12 (Iron |
|
|
|
<Material/Surface treatment> wire (SWCH18A)/Zinc nickel plated) |
||
|
|
|
|
Washer x 12, Spring washer x 12 |
Dimensions
Unit : mm
Air outlet grile
598
625 |
6×85 (=510) |
85
Support
150
285
626
285
45°
638
PARTS |
OPTIONAL |
CAUTION
*Air Guide prevents reverse rotation of outdoor unit fan when it enters low speed rotation mode with fan controller being operated. It is also used for protection of fan when strong winds, such as a typhoon, wind blowing through tall
buildings, etc., directly strike the air outlet. In addition, installation of this product is necessary when cooling opetation is to be performed in outdoor tempreture of -5 or lower (down to -15 ).
Note the followings when installing this guide:
1)Be sure not to use "upward discharge" in a place where snowing is possible. Snow may accumulate in the guard, which could damage the fan, etc.
2)Attaching this unit will decrease the performance (by 2-3%) and increase noise from outdoor unit (by approx. 1-2 dB).
3)Do not use "upward discharge" when there are any obstacles at the back and on both sides of outdoor unit (air is taken in from top of unit): This could cause a short cycle.
4)To eliminate the influence of external wind, be sure to install the unit with its back facing to wall.
5)Do not install this unit in a place where wind directly blows to the back of the unit.
E-204