Mitsubishi MUX-19TV-E1, MUX-20TV-E1, MUX-25TV-E1 Service Manual

0 (0)

SPLIT-TYPE,AIR CONDITIONERS

No. OB284

SERVICE MANUAL

Multi system type

Models

MUX-19TV - E1

MUX-20TV - E1

MUX-25TV - E1

MUX-19TV - E1 MUX-20TV - E1 MUX-25TV - E1

CONTENTS

1.TECHNICAL CHANGES ················

2.PART NAMES AND FUNCTIONS············

3.INDOOR/OUTDOOR

CORRESPONDENCE TABLE ··············

4.SPECIFICATION····················

5.NOISE CRITERIA CURVES ···············

6.OUTLINES AND DIMENSIONS ·············

7.WIRING DIAGRAM ··················

8.REFRIGERANT SYSTEM DIAGRAM ···········

9.PERFORMANCE CURVES ···············

10.TROUBLESHOOTING·················

11.DISASSEMBLY INSTRUCTIONS············

12.PARTS LIST······················

13.OPTIONAL PARTS···················

This manual describes technical data of outdoor unit.

For indoor unit refer to the service manuals No.OB227 REVISED EDITION-B and OB252 REVISED EDITION-A of corresponding models.

1 TECHNICAL CHANGES

MUX-19TV - E1

MUX-20TV - E1

MUX-25TV - E1

New models

2 PART NAMES AND FUNCTIONS

OUTDOOR UNIT

MUX-19TV - E1

MUX-20TV - E1

MUX-25TV - E1

Air inlet (Back and side)

Piping

Drainage hose

Air outlet

2

3 INDOOR / OUTDOOR CORRESPONDENCE TABLE

Combination of the connectable indoor units

OUTDOOR UNIT

MUX-19TV- E1

MUX-20TV- E1

MUX-25TV- E1

A:07,

B:12

A:09,

B:09,

C:09

A:12,

B:12

 

 

 

 

 

 

 

There is no combination other than this table.

4 SPECIFICATION

Outdoor model

Outdoor unit power supply

Indoor unit No.

Capacity

Outdoor air flow

 

K /h

 

Capacity

kW

 

Dehumidification

R/h

 

Power outlet

A

 

 

Running current

A

 

Electrical data

Power input

W

Auxiliary heater

A(kW)

 

 

Power factor

%

 

Starting current

A

 

 

Compressor motor current

A

 

 

Fan motor current

A

 

Coefficient of performance(C.O.P)

Compressor

Model

"

Output

 

W

 

Winding

 

 

 

resistance(at20:)

 

Fan motor

Model

 

Winding

"

 

 

 

resistance(at20:)

 

 

 

 

 

Dimensions WOHOD

mm

 

Weight

kg

 

Sound level

dB

Special remarks

Fan speed

rpm

Fan speed regulator

kg

 

 

 

 

Refrigerant filling

 

 

 

capacity(R22)

 

 

 

Refrigerating oil (Model)

cc

NOTE: Test conditions are based on ISO 5151.

Cooling : Indoor

DB27°C

/ WB19°C

Outdoor

DB35°C

/ WB(24°C)

MUX-19TV - E1

Single phase 230V, 50Hz

Opetate 1 unit

Opetate 1 unit

Opetate 2 unit

A

B

A+B

3.5

2.2

3.5+2.2

1.6

0.8

1.6+0.8

 

Hi:2,460 / Lo:1,920

 

 

15

 

6.01

3.33

8.94

1,280

745

2,005

 

 

92.6

97.3

97.5

 

45.6

 

5.68

3.00

8.37

0.33

0.33

0.57

2.65

2.82

2.74

RH220VHAT (Room A) / RH135VHAT (Room B)

1,050 / 650

C-R 2.13/4.18

C-S 3.91/5.76

RA6V60-DA

WHT-BLK 90 BKL-YLW 54

BLK-RED 146

840 640 330

63

52

High:730 / Low:580

2

Room A : 0.87

Room B :1.0

520(MS56) / 300(MS56)

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor model

 

 

 

 

 

 

MUX-20TV - E1

 

 

 

 

 

Outdoor unit power supply

 

 

 

 

Single phase

 

 

 

 

 

 

 

 

 

 

 

 

230V, 50Hz

 

 

 

 

 

Indoor unit No.

 

 

Opetate 1 unit

Opetate 1 unit

Opetate 2 unit

Opetate 2 unit

Opetate 3 unit

 

 

 

 

 

A

B or C

B+C

A+B or A+C

A+B+C

 

 

 

 

 

 

Capacity

Outdoor air flow

 

K /h

 

2.5

High: 2,460 / Low: 1,920

2.4+1.75 2

 

 

 

Capacity

 

kW

 

2.7

1.75 2

2.4+2.7

 

 

 

Dehumidification

 

R/h

 

1.1

1.2

0.3 2

0.9+1.2

0.9+0.3 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power outlet

 

A

 

 

 

 

15

 

 

 

 

 

Running current

 

A

 

 

3.43

4.23

4.36

7.56

7.79

Electrical data

 

Power input

 

W

 

775

965

1,000

1,740

1,785

 

Auxiliary heater

 

A(kW)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power factor

 

%

 

98.2

99.2

99.7

99.9

99.6

 

 

 

Starting current

 

A

 

 

 

 

40

 

 

 

 

 

Compressor motor current

A

 

 

3.10

3.90

4.03

6.99

7.22

 

 

 

Fan motor current

 

A

 

 

0.33

0.33

0.33

0.57

0.57

Coefficient of performance(C.O.P)

 

3.09

2.70

3.27

2.82

3.12

Compressor

Model

 

 

 

 

 

RH140VHAT (Room A) / RH174VHAT (Room B,C)

 

 

 

 

 

 

 

 

 

 

Output

 

"

 

 

 

700/800

 

 

 

 

 

 

W

 

 

 

 

 

 

 

 

Winding

 

 

 

 

 

 

C-R 4.03/3.30

 

 

 

 

 

resistance(at20:)

 

 

 

 

 

C-S 5.71/5.80

 

 

Fan motor

 

Model

 

 

 

 

 

RA6V60-DA

 

 

 

Winding

 

"

 

 

 

WHT-BLK 90 BLK-YLW 54

 

 

 

 

 

 

 

 

 

 

 

resistance(at20:)

 

 

 

 

 

BLK-RED 146

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions WOHOD

 

mm

 

 

 

840 640 330

 

 

 

 

 

Weight

 

kg

 

 

 

62

 

 

 

 

 

Sound level

 

dB

 

 

 

52

 

 

 

 

 

Fan speed

 

rpm

 

 

High: 730 / Low: 580

 

Special remarks

 

 

Fan speed regulator

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant filling

 

kg

 

 

 

Room A : 0.8

 

 

 

 

 

capacity(R22)

 

 

 

 

 

 

Room B,C : 0.96

 

 

 

 

 

Refrigerating oil (Model)

cc

 

 

300(MS56) / 300(MS56)

 

NOTE: Test conditions are based on ISO 5151.

 

 

 

 

 

 

 

 

Cooling : Indoor

DB27°C / WB19°C

 

 

 

 

 

 

 

 

Outdoor

DB35°C / WB(24°C)

 

 

 

 

4

Outdoor model

Outdoor unit power supply

Indoor unit No.

Capacity

Outdoor air flow

 

K /h

 

Capacity

kW

 

Dehumidification

R/h

 

Power outlet

A

 

 

Running current

A

 

Electrical data

Power input

W

Auxiliary heater

A(kW)

 

 

Power factor

%

 

Starting current

A

 

 

Compressor motor current

A

 

 

Fan motor current

A

 

Coefficient of performance(C.O.P)

Compressor

Model

"

Output

 

W

 

Winding

 

 

 

resistance(at20:)

 

Fan motor

Model

 

Winding

"

 

 

 

resistance(at20:)

 

 

 

 

 

Dimensions WOHOD

mm

 

Weight

kg

 

Sound level

dB

Special remarks

Fan speed

rpm

Fan speed regulator

kg

 

 

 

 

Refrigerant filling

 

 

 

capacity(R22)

 

 

 

Refrigerating oil (Model)

cc

NOTE: Test conditions are based on ISO 5151.

Cooling : Indoor

DB27°C

/ WB19°C

Outdoor

DB35°C

/ WB(24°C)

MUX-25TV - E1

Single phase 230V, 50Hz

Opetate 1 unit

Opetate 2 unit

A or B

A+B

3.5

3.5 2

1.6

1.6 2

High:2,760 / Low:1,920

 

25

6.11

12.42

1,350

2,760

 

96.1

96.6

 

56

5.79

11.81

0.32

0.61

2.52

2.46

RH231VHAT 2

1,100 2

C-R 2.13

C-S 3.91

RA6V60-EA

WHT-BLK 67 BLK-YLW 75

BLK-RED 73

840 640 330

65

54

High: 810 / Low: 580

2

Room A: 0.9

Room B: 0.9

520(MS56) / 520(MS56)

5

5 NOISE CRITERIA CURVES

MUX-19TV - E1

 

 

SPEED

SPL(dB(A))

LINE

 

 

 

 

 

 

MUX-20TV - E1

 

 

 

High

52

 

 

 

 

 

 

 

 

 

 

 

 

Test conditions.

 

 

90

 

 

 

 

Cooling :DB35: WB24:

 

 

 

 

 

 

 

 

 

MICRO BAR

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

dB re 0.002

 

 

 

 

 

 

 

 

NC-70

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

 

 

 

 

 

 

 

 

 

BAND SOUND

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

30

 

 

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

 

 

 

 

 

 

 

 

 

 

20

APPROXIMATE

 

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

MUX-25TV - E1

 

 

SPEED

SPL(dB(A))

LINE

 

 

 

 

 

 

 

 

 

 

 

 

 

High

54

 

 

 

 

 

 

Test conditions.

 

 

 

90

 

 

 

 

Cooling :DB35: WB24:

 

 

 

 

 

 

 

 

 

MICRO BAR

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

dB re 0.002

 

 

 

 

 

 

 

 

NC-70

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

 

 

 

 

 

 

 

 

 

BAND SOUND

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

30

 

 

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

 

 

 

 

 

 

 

 

 

 

20

APPROXIMATE

 

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

6

Mitsubishi MUX-19TV-E1, MUX-20TV-E1, MUX-25TV-E1 Service Manual

6 OUTLINES AND DIMENSIONS

OUTDOOR UNIT

Unit: mm

 

MUX-19TV- E1

 

 

 

 

500

Drainage

272.9

438.4

3hoies {33

 

Air in

 

 

 

125.6

34

 

 

Air in

 

100.3

40

 

 

Air out

 

840

 

121.3

319.8

OUTDOOR UNIT

MUX-20TV- E1

 

 

 

500

Drainage

272.9

438.4

3hoies {33

 

Air in

 

 

 

125.6

34

 

 

Air in

 

100.3

40

 

 

Air out

 

840

 

121.3

319.8

Open as a rule 500mm or more if the front and both sides are open

100mm or more 100mm or more 200mm or more if

there are obstacles to both sides

330

360.6

Open as a rule

 

 

 

 

 

 

 

 

500mm or more if the back,

 

350mm or more

 

 

both sides and top are open

 

 

 

 

 

61.7

 

Service panel

 

 

 

 

Liquid refrigerant

 

 

pipe joint

 

 

 

Refrigerant pipe

 

 

(flared) {6.35

640

 

°

 

Gas refrigerant

 

°

10

 

pipe joint

 

10

 

 

} B UNIT

5050

Refrigerant pipe

 

 

 

 

(flared) {9.52

 

 

} A UNIT

50

 

66.2

 

 

 

Gas refrigerant

80.7

 

264.2

75.8

 

pipe joint

 

 

 

 

 

Refrigerant pipe

(flared) {12.7

Unit: mm

330

360.6

61.7

 

 

°

640

°

10

10

 

 

 

Open as a rule 500mm or more if the front and both sides are open

100mm or more 100mm or more 200mm or more if

there are obstacles to both sides

Open as a rule

500mm or more if the back, 350mm or more both sides and top are open

Service panel Liquid refrigerant pipe joint Refrigerant pipe (flared) {6.35

} C UNIT 50

} A UNIT

50

505050

} B UNIT

 

66.2

75.8

Gas refrigerant

pipe joint

264.2

Refrigerant pipe (flared) {9.52

7

OUTDOOR UNIT

Unit: mm

 

MUX-25TV- E1

 

 

 

 

500

 

Drainage

272.9

438.4

 

3hoies {33

 

Air in

 

 

 

 

 

125.6

34

 

 

330

 

Air in

 

 

 

 

100.3

 

 

40

 

 

 

 

 

 

 

Air out

 

 

 

 

840

61.7

 

 

 

121.3

 

640

319.8

80.7

100mm or more

360.6

Open as a rule

500mm or more if the back, both sides and top are open

Open as a rule 500mm or more if the front and both sides are open

100mm or more 200mm or more if there are obstacles to both sides

350mm or more

 

 

Service panel

 

 

Liquid refrigerant

 

 

pipe joint

 

°

Refrigerant pipe

 

(flared) {6.35

°

10

 

 

10

 

} A UNIT 505050

 

 

 

} B UNIT

 

 

 

75.8

Gas refrigerant

 

264.2

pipe joint

 

 

Refrigerant pipe (flared) {12.7

8

7

WIRING DIAGRAM

 

 

 

MUX-19TV - E1

MUX-25TV - E1

 

 

 

 

 

 

OUTDOOR UNIT MODELS WIRING DIAGRAM

POWER SUPPLY

L

TB1

BRN

2 TB4

 

 

 

 

~/N

 

 

 

 

 

 

 

 

 

 

230V

 

N

 

BLU

1

 

 

 

 

 

50Hz

 

 

 

 

 

 

 

 

 

 

PE

GRN/YLW

BLU

BRN

 

 

BRN

CIRCUIT BREAKER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 2 1

CN90 OUTDOOR CONTROL PC BOARD

TO INDOOR

 

2

TB2

BLU

3

CN71

F61

(3.15A)

 

 

UNIT A

 

 

 

 

 

 

 

 

 

 

1

 

 

2

 

 

 

 

 

CONNECTING

 

YLW

 

 

 

 

 

12V

 

 

 

1

 

 

 

 

 

 

2

 

 

 

 

 

 

 

TO INDOOR

 

 

BLU

3

CN73

 

NR61

 

 

UNIT B

 

 

 

 

 

 

 

 

1

 

 

2

 

 

 

 

CONNECTING

 

ORN

 

 

 

 

T61

12V

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

SR861

SR862

 

 

 

 

 

 

 

 

CN91 1 2 3 4 5 6

LD2

LD1

 

 

 

 

 

 

 

WHT YLW

BLK RED

RED

RED

 

 

 

 

 

 

 

 

 

 

C61

 

 

 

 

 

 

 

 

MF61

 

 

BLU

BRN

 

BLU

 

X521

 

X522

3

4

3

4

 

X522

X521

 

C1 RED

S

BLK R MC1 C

WHT

C2 RED

S

BLK R MC2 C

WHT

SYMBOL

NAME

SYMBOL

NAME

SYMBOL

NAME

C1

COMPRESSOR CAPACITOR (MC1)

MC2

COMPRESSOR (INNER PROTECTOR)

TB1

TERMINAL BLOCK

C2

COMPRESSOR CAPACITOR (MC2)

MF61

FAN MOTOR (INNER PROTECTOR)

TB2~TB4

TERMINAL BLOCK

C61

FAN MOTOR CAPACITOR

NR61

SURGE ABSORBER

T61

TRANSFORMER

F61

FUSE (3.15A)

SR861

FAN MOTOR RELAY

X521

COMPRESSOR CONTACTOR (MC1)

MC1

COMPRESSOR (INNER PROTECTOR)

SR862

FAN MOTOR RELAY

X522

COMPRESSOR CONTACTOR (MC2)

NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.

 

VG79B082H01

2.Use copper conductors only. (For field wiring)

3.Symbols below indicate.

/: Terminal block, : Connector

MUX-20TV - E1

OUTDOOR UNIT MODEL WIRING DIAGRAM

POWER SUPPLY

L

TB1

BRN 2 TB4

 

 

 

 

 

 

 

~/N

 

 

 

 

 

 

 

 

 

 

 

 

230V

N

 

BLU 1

 

 

 

 

 

 

 

 

 

50Hz

 

 

BLU

BRN

 

 

 

 

 

BRN

 

 

PE

GRN/YLW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT BREAKER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 2 1

CN90 OUTDOOR CONTROL PC BOARD

CONNECTING

2

TB2

YLW

2

CN71

F61

(3.15A)

 

 

 

 

 

1

 

 

 

 

 

 

TO INDOOR

 

 

BLU

3

 

 

 

 

 

 

 

 

UNIT A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12V

2

 

 

1

 

 

 

 

 

 

 

 

TO INDOOR

 

BLU

3

CN73

 

NR61

 

 

 

 

1

 

 

 

 

T61

 

CONNECTING

 

ORN

2

 

 

 

 

 

 

UNIT B

 

 

 

 

 

 

 

 

 

 

 

 

12V

 

 

 

1

 

SR861

SR862

 

 

 

 

SR863

TO INDOOR

2

TB3

BLU

2

CN74

 

 

 

 

CONNECTING

1

 

WHT

 

 

 

 

CN81

UNIT C

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12V

 

 

 

1

CN91 1 2 3 4 5 6

LD2

LD1

1 2 3

 

 

 

 

 

 

WHT YLW

BLK

RED

RED

RED

BLU

BLU

 

 

 

 

 

 

 

 

 

 

C61

 

21RB

 

 

 

 

 

 

 

MF61

 

 

 

 

BLU

 

BRN

 

BLU

 

 

X521

X522

3

4

3

4

 

 

X522

X521

 

SR866

SR865

CN85

CN86

1 2 3

1 2 3

BLU

BLU

BLU

BLU

21R3

21R4

C1 RED

S

BLK R MC1 C

WHT

C2 RED

S

BLK R MC2 C

WHT

 

SYMBOL

NAME

SYMBOL

NAME

SYMBOL

NAME

 

C1

COMPRESSOR CAPACITOR (MC1)

NR61

SURGE ABSORBER

TB2~TB4

TERMINAL BLOCK

 

C2

COMPRESSOR CAPACITOR (MC2)

SR861

FAN MOTOR RELAY

T61

TRANSFORMER

 

C61

FAN MOTOR CAPACITOR

SR862

FAN MOTOR RELAY

X521

COMPRESSOR CONTACTOR (MC1)

 

 

 

 

 

 

 

 

F61

FUSE (3.15A)

SR863

RELAY (21RB)

X522

COMPRESSOR CONTACTOR (MC2)

 

MC1

COMPRESSOR (INNER PROTECTOR)

SR865

RELAY (C) (21R4)

21RB

SOLENOID COIL

 

 

 

 

 

 

 

 

MC2

COMPRESSOR (INNER PROTECTOR)

SR866

RELAY (B) (21R3)

21R3

SOLENOID COIL (B)

 

MF61

FAN MOTOR (INNER PROTECTOR)

TB1

TERMINAL BLOCK

21R4

SOLENOID COIL (C)

NOTE:1. About the outdoor side electric wiring refer to the outdoor unit electric wiring diagram for servicing.

 

VG79B081H01

2.Use copper conductors only. (For field wiring)

3.Symbols below indicate.

/: Terminal block, : Connector

9

 

8

 

REFRIGERANT SYSTEM DIAGRAM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSC-07RV- E3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUX-19TV- E1

Unit: mm

MSC-12RV- E3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTDOOR UNIT

 

 

 

 

 

 

 

 

 

Room

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

 

Refrigerant pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

{12.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(With insulation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop valve

 

 

 

 

 

 

 

 

 

 

 

UNIT A

 

heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with service port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSC-12RV

 

E3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flared connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop valve

Compressor(MC1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capillary tube

 

 

 

 

 

 

Outdoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

{6.35

 

 

 

 

 

 

 

 

 

 

 

 

{3.0 {1.6 660

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(With insulation)

 

 

 

 

 

 

 

 

 

 

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Room

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

Refrigerant pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

{9.52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT11

 

 

 

 

 

 

(With insulation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop valve

 

 

 

 

 

 

 

 

 

 

 

UNIT B

 

heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

with service port

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MSC-07RV

 

E3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flared connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop valve

Compressor(MC2)

 

 

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RT12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capillary tube

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

{3.0 {1.4 810

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

{6.35

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(With insulation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX. REFRIGERANT PIPING LENGTH & MAX. HEIGHT DIFFERENCE

Indoor unit B

MSC-07RV E3

Indoor unit A

MSC-12RV E3

 

 

 

 

 

 

 

L

 

H

 

 

L

 

 

H

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MUX-19TV

E1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional piping max. length 15m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT No.

 

 

 

 

Pipe length

 

 

 

 

Height difference (H)

 

 

No. of bends

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max. limits

 

A , B

 

L

 

15m

 

 

 

 

 

10m

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ADDITIONAL REFRIGERANT CHARGE (R22:g)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

Refrigerant piping length (one way)

 

 

 

 

 

 

 

 

precharged (g)

 

 

7m

8m

 

9m

10m

 

11m

 

 

12m

 

13m

14m

 

15m

A

UNIT

870

 

 

0

15

 

30

45

 

 

60

75

 

90

 

105

 

120

B

UNIT

1,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPING PREPARATION

1 Table below shows the specifications of pipes commercially available.

 

 

 

UNIT No.

Pipe

Outside diameter

Insulation

Insulation material

 

 

 

mm

thickness

 

 

 

 

 

 

 

 

 

 

 

and

 

UNIT

For liquid

6.35

8 mm

 

A

B

Heat resisting foam plastic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

For gas

9.52

8 mm

 

 

 

B

 

0.045 specific gravity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT

For gas

12.7

8 mm

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

2 Ensure that the 2 refrigerant pipes are well insulated to prevent condensation. 3 Refrigerant bending radius must be 10cm or more.

10

Unit: mm

MSC-09RV- E3

INDOOR UNIT

MUX-20TV- E1

OUTDOOR UNIT

UNIT A

MSC-09RV E3

UNIT B

MSC-09RV E3

UNIT C

MSC-09RV E3

Room

temperature

Refrigerant pipe

thermistor

{9.52

RT11

(With insulation)

Indoor

 

 

Stop valve

 

 

heat

 

 

with service port

 

 

exchanger

 

 

 

 

 

 

Flared connection

 

 

 

 

Indoor coil

 

Stop valve

Compressor(MC1)

 

thermistor

 

 

 

 

 

 

 

 

RT12

 

 

 

 

 

 

Refrigerant pipe

 

Capillary tube

 

Room

{6.35

 

{3.0 {1.4 450

Outdoor

(With insulation)

 

 

 

heat

temperature

 

 

 

 

 

 

 

 

exchanger

thermistor

Refrigerant pipe

Stop valve

 

Solenoid valve

 

 

RT11

{9.52

with service port

 

21RB

 

 

(With insulation)

 

 

 

Indoor

 

 

 

Capillary tube

 

heat

 

 

 

{3.0 {1.6 1,000

 

exchanger

Flared connection

 

 

 

 

 

 

 

 

 

 

 

Stop valve

Solenoid valve

 

 

 

 

21R3

 

 

 

 

 

 

 

Indoor coil

 

 

 

Compressor(MC2)

 

 

 

 

 

 

thermistor

Refrigerant pipe

 

Capillary tube

 

 

RT12

 

 

 

{6.35

 

{3.0 {1.6 900

 

 

Room

 

 

 

(With insulation)

 

 

Capillary tube

 

temperature

 

 

 

 

 

 

 

{3.0 {1.8 450

 

thermistor

Refrigerant pipe

 

 

 

RT11

 

 

 

 

 

{9.52

 

 

 

 

Indoor

 

Stop valve

 

 

 

heat

 

 

 

 

 

with service port

 

 

exchanger

Flared connection

 

 

Refrigerant

flow

 

 

 

 

 

 

 

Solenoid valve

 

 

21R4

Indoor coil

 

 

thermistor

Stop valve

Capillary tube

RT12

Refrigerant pipe

{3.0 {1.6 900

 

{6.35

(With insulation)

11

MUX-20TV- E1

MAX.REFRIGERANT PIPING LENGTH & MAX. HEIGHT DIFFERENCE

Indoor unit C

 

Indoor unit B

 

Indoor unit A

MSC-09RV - E3

 

MSC-09RV - E3

 

MSC-09RV - E3

 

 

 

 

 

LC

H

LB

H

LA

H

Outdoor unit

MUX-20TV - E1

 

UNIT No.

 

Pipe length

 

Height difference (H)

No. of bends

 

 

 

 

 

 

 

 

 

Max.

A

LA

 

15m

 

10m

 

10

 

 

 

 

 

 

 

 

B

LB

15m

LB

Total

10m

10

Total

limits

 

 

+

 

 

 

 

LC

15m

30m

10m

10

15

 

C

LC

 

 

 

 

 

 

 

 

 

 

 

 

Note: The length of piping to individual units (A,B,C) should not exceed 10 meters.

If units B and C are linked, the maximum combined length of piping should not exceed 15 meters.

ADDITIONAL REFRIGERANT CHARGE (R22:g)

 

Outdoor unit

 

 

 

 

 

 

 

 

 

Refrigerant piping length (one way)

 

 

 

 

 

 

A unit

precharged (g)

 

7m

 

 

8m

 

 

9m

10m

 

 

11m

 

12m

 

13m

14m

 

15m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

800

 

0

 

 

15

 

 

30

 

45

 

 

60

 

75

90

 

105

 

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

Refrigerant piping length (one way, 2 unit total)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B unit + C unit

precharged (g)

10m

11m

12m

13m

14m

15m

16m

17m

18m

19m

20m

21m

22m

23m

24m

25m

26m

27m

28m

29m

30m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

960

0

 

10

20

30

40

50

60

70

 

80

90

 

100

110

120

130

140

150

160

170

180

190

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPING PREPARATION

1Table below shows the specifications of pipes commercially available.

UNIT No.

Pipe

Outside diameter

Insulation

Insulation material

 

mm

thickness

 

 

 

 

 

 

 

 

 

 

 

 

A , B and

For liquid

6.35

8mm

Heat resisting foam plastic

C unit

For gas

9.52

8mm

0.045 specific gravity

 

2Ensure that the 2 refrigerant pipes are well insulated to prevent condensation. 3Refrigerant bending radius must be 10cm or more.

12

Loading...
+ 28 hidden pages